950 BR Megohm

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

MEGOHMMETERS An array of

Megohmmeters
For all of your Insulation Testing needs... to choose from
AEMC® offers a full line of
­megohmmeters with test
­voltages from 10V to 15kV,
(model dependent), capable
of measuring i­nsulation
resistances from 1000Ω
to 29TΩ . These rugged,
weather ­resistant meters are
­accurate, ­reliable and built to
perform. Battery, AC powered
and hand-cranked models
­are available.

Our products are backed by over 125 years of experience in test and measurement
equipment, and encompass the latest international standards for quality and safety.

Technical Hotline: (800) 343-1391


www.aemc.com
Understanding Insulation Resistance Testing
Why have an insulation testing program?
A regular program of testing i­nsulation resistance is
strongly ­recommended to prevent electrical shocks,
assure personal safety and to reduce or e ­ liminate down
time. It helps to detect deterioration of i­nsulation in order
to schedule repair work such as: vacuum c ­ leaning, steam
­cleaning, drying and rewinding or testing newly installed
conductors. It is also h
­ elpful when ­evaluating the quality of
the repairs before the equipment is put back into operation.

What causes insulation failure?


Some of the more c ­ ommon causes of i­nsulation failure
include: overloading conductors, excessive heat or cold,
moisture, dirt, corrosive vapors, o
­ il, v
­ ibration, aging and
nicked wiring.

What tests are used to detect insulation


­deterioration?
There are numerous maintenance tests for assessing
­insulation ­quality. The three tests primarily used to Model 6555 performing an i­nsulation test.
test motors, generator and transformer insulation are:
polarization index, spot reading and step voltage.

What equipment is n
­ ecessary for conducting insulation r­ esistance tests?
 Megohmmeter with a timed test function
 Temperature indicator

APPLICATIONS
 Humidity meter (not n
­ ecessary if equipment
temperature is above the dew point)

 Motors (AC and DC), transformers, cables,


switchgears and electrical wiring installations
 Test industrial commercial wiring and
motor control centers
Four questions for selecting  Acceptance testing and preventive maintenance
the proper megohmmeter  Domestic and industrial contracting
What is the proper v
­ oltage range?­  Dielectric Absorption Ratio (DAR) and
Typically 2x equipment operating voltage up to 1000V Polarization Index (PI) measurements
and equal to the operating voltages above 1000V  Spot reading tests

What is the desired power source?  High resistance or absorption tests


Battery, AC p
­ owered, hand-cranked  Timed resistance measurements

What is the resistance range of interest?  Low insulation test range for testing old
MΩ, GW, TW or flooded installations
 Drying out conductors
What type of display is preferred?
 Continuity checks
Analog (best for trend analysis), or Digital
(eliminate g
­ uesswork), or gives exact reading  Cable testing (including telecom)
and shows trend  Test transformers
 Heaters, relays, circuit breakers

2 www.aemc.com Technical Assistance (800) 343-1391


Data Analysis & Reporting Software for Megohmmeters

Configure All Functions of: Models 1060,


5060, 5070, 6526, 6532, 6534, 6550 & 6555
• Print reports of all test results
• Select test voltage and run tests from your computer
with a simple click and execute process
• Capture and display data in real-time
• Retrieve data from the instrument’s memory:
• Over 1500 insulation resistance measurements
(model dependent)
• Over 4000 resistance measurements
• Display DAR and PI ratios
• Plot graphs of manual and timed tests
Clear and easy setup from one dialog box for Model 5060.
• Include your analysis comments section with the report
• Store a library of setups for different a
­ pplications
• Certification of results through report generation
• Free updates are available on our website www.aemc.com

Model 5070 includes Step Function which allows programming of Four tabbed dialog boxes allow for clear and easy setup of all
three different test profiles, each containing up to five voltage steps functions of the Model 5070, including setup for variable voltage
between 40 and 5100V and time per step of up to 10 hours. and alarm set points, as well as step voltage tests and
temperature compensation.

{
Insulation resistance
­during the test run


Two easy clicks Step voltage during
(Instrument > Run Test) the test run
start test and
graphs results

Test voltage ­selection


Insulation resistance
Test result ­status with temperature
box ­displays ­ compensation
complete test results
in real-time

Run test and display text and graphical results from one dialog box.
Model 5070 also displays step voltage.

Technical Assistance (800) 343-1391 www.aemc.com 3


MEGOHMMETER SELECTION GUIDE
10V & 100V Megohmmeters
Expert tools for testing
AEMC ® offers low voltage insulation testers

10kV & 15kV


designed for both field and shop use. They are well
suited for measuring the qualities of phone cables
data cables and ESD Floor Testing. Measurement
of AC and DC voltage, resistance, continuity, cable
capacitance, cable length and AC c
be performed.
­ urrent can also Digital Megohmmeters
High-end portable instruments for measuring a
variety of electrical insulation resistance values.
500V Megohmmeters
AEMC ® offers a complete line of i­nsulation The Megohmmeter Models
testers designed to test the quality of insulation 6550 and 6555 are the right
on equipment powered from sources up to 240V
tools for testing insulation
using test voltages up to 500V. Both analog and
digital meters are available. AC powered, b ­ attery safely and accurately,
powered and hand-cranked models are available. and are ideal for use on
Measurements can be in the MW, GW and TW rotating equipment and
range. Most m ­ odels offer multi-function c
­ apability, machinery operating at
measuring AC/DC volts, resistance and continuity,
10kV or higher. They
as well as i­nsulation resistance.
are fully automated
10,000V and
1000V Megohmmeters 15,000V graphical
insulation
AEMC ® offers a complete line of i­nsulation testers
designed to test the quality of insulation using testers. They
1000V test voltage (required for testing equipment provide insulation
powered from sources up to 480Vac). Both ­analog measurements
and digital meters are available. AC powered, up to 29,000GW
­battery powered and hand-cranked models are
(29TW, model dependent).
­ odels can measure into the GW
available. Many m
and TW range. Most m ­ odels offer multi-function Test results include DAR,
capability, m
­ easuring AC/DC volts, r­esistance and PI, DD, ∆R, Capacitance,
­continuity, as well as i­nsulation resistance. Both Leakage Current, as well as
hand-held instruments and rugged instruments programmable temperature
built into portable cases are available.
correction of resistance
readings.
5000V Megohmmeters The Models 6550 & 6555
AEMC offers a complete line of i­nsulation testers
® also offer the ability to
designed to test the quality of insulation using program up to three
5000V test voltages required for testing large step voltage profiles (from
motors, generators, transformers, cables and 40 to 10,000 or 15,000V,
large rotating machinery. AC powered and battery
powered models are a ­ vailable. All models can
model dependent), each
measure into the GW and TW ranges. All models containing up to ten steps. IP
53
offer multifunction c
­ apability, measuring AC/ They also include three
DC volts, resistance and continuity, as well as ramp profiles and three programmable test voltages in
insulation resistance. addition to the standard fixed voltages of 500, 1000,
2500, 5000, 10,000 and 15,000V. These units have
a USB interface and a data storage function, which
10kV & 15kV Megohmmeters
permits storage of test results in files specific to the
AEMC ® offers a complete line of safe and accurate
device under test. The included DataView® software
i­nsulation testers that are ideal for use on rotating
equipment and machinery operating at 10kV or configures and runs tests directly from a PC and
higher. They are the only fully automated 10,000V creates data analysis reports.
and 15,000V graphical insulation testers. They
provide insulation measurements up to 29,000GW
(29TW). Test results include DAR, PI, DD, ∆R,
Capacitance, Leakage Current, as well
as programmable temperature correction of
resistance readings.
Note: 1000V, 5000V, 10kV & 15kV megohmmeters offer memory storage and PC connection for report generation (model dependent).

4 www.aemc.com Technical Assistance (800) 343-1391


Safely & Accurately Models 6550 & 6555
Multiple Voltage Ramp &
MODEL
Test Voltage
6550
500V, 1000V, 2500V, 5000V, 10,000V Step Test Modes
Insulation Range 10kΩ to 25,000GΩ
Other Measurements Auto DAR, PI, DD, ∆R (ppm/V) ratios
Leakage Current 0 to 8mA “Burn-In” Test Mode
Voltage Test 40 to 10kV
Other Ramp and Voltage Test, Capacitance Measurement,
Programmable Current Tests, Ramp & Step Test and Burn Test
Power Source NiMH rechargeable batteries
Display Digital / Analog
Communication DataView software/USB optically-isolated port
®

Dimensions 13.39 x 11.81 x 7.87"


Weight Approx. 13.7lb (6.2kg)
Catalog No. 2130.31

MODEL 6555
Test Voltage 500V, 1000V, 2500V, 5000V, 10,000V, 15,000V
Insulation Range 10kΩ to 29,000GΩ (29TΩ)
Other Measurements Auto DAR, PI, DD, ∆R (ppm/V) ratios
Voltage Step Test Mode
Leakage Current 0 to 8mA
Voltage Test 40 to 15kV
Other Ramp and Voltage Test, Capacitance Measurement,
Programmable Current Tests, Ramp & Step Test and Burn Test
Power Source NiMH rechargeable batteries
Display Digital / Analog
Communication DataView software / USB optically-isolated port
®

Dimensions 13.39 x 11.81 x 7.87"


Weight Approx. 13.7lb (6.2kg)
Catalog No. 2130.32

PRODUCT INCLUDES

Small classic tool bag, set of color-coded (red/blue/black) 9 ft (15kV) Voltage Ramp Test Mode
integral leads and alligator clips (1000V CAT IV), one 15kV jumper lead
(blue), set of two color-coded test probes (red/black-1000V CAT IV), optical
USB cable, 115V US power cord, 9.6V rechargeable NiMH batteries.

USB Stick
Quick start user guide, and USB stick supplied with
DataView software and user manual.
®

Technical Assistance (800) 343-1391 www.aemc.com 5


500V & 1000V Hand-Cranked
1000V Model 1015 Models 6501 & 6503 1000V Digital Model 6527

IP IP
54 51

Test Voltage 500, 1000Vdc MODELS 6501 6503 Test Voltage 250, 500, 1000Vdc
Insulation Range 100kΩ to 1000MΩ Test Voltage 500Vdc 250, 500, Insulation Range 1kΩ to 4000MΩ (4GΩ)
Resistance Range 1000Ω 1000Vdc Resistance Range 400kΩ
Continuity Range ±10Ω Insulation Range 500kΩ to 200MΩ 1 to 5000MΩ Continuity Range 400Ω
Voltage Measurement 600Vac Resistance Range 0 to 500kΩ — Voltage Measurement 600V (AC);1000V (DC)
Power Source Eight 1.5V AA batteries Continuity Range 100Ω — Power Source Six 1.5V AA batteries
Display Analog Voltage Measurement 600Vac Display Digital dual display with backlight
Other Rubber housing Power Source Hand-cranked Other Hold, Test Time & Lock functions
Dimensions 6.6 x 4.2 x 2.2" Display Analog Dimensions 7.9 x 3.6 x 2.0"
Weight 1.45 lbs Test Current 1mA constant current — Weight 1.5 lbs
Catalog No. 1403.01 Other ABS plastic with overmolded protection Catalog No. 2126.53
Dimensions 4.7 x 4.4 x 5.3" with lid
Weight 3.3 lbs
Catalog No. 2126.51 2126.52
For Electrostatic
Discharge Testing 1000V Digital/Analog 5000V Digital/Analog
Model 6536 Models 1050 & 1060 Model 6505

FET Y
SA

IP IP IP
54
Rated 53 RA
TIN G 53

Test Voltage Adjustable 10 - 100Vdc MODELS 1050 1060 Test Voltage 500, 1000, 2500, 5000Vdc
Insulation Range 20GΩ Test Voltage 50, 100, 250, 500, 1000Vdc Insulation Range 10kΩ to 10TΩ
Resistance Range 1000kΩ Insulation Range 2kΩ to 4000GΩ (4TΩ) Other Measurement DAR, PI, Capacitance
Continuity Range 10Ω, 100Ω Other Measurement DAR, PI, Capacitance Leakage Current 1pA to 3mA
Voltage Measurement 700Vac/dc Resistance Range 0.01Ω to 400kΩ Voltage Measurement 1 to 2500Vac/4000VDC
Power Source Six AA batteries Continuity Range 0.01 to 39.99Ω Power Source 9.6V NiMH battery pack
Display Digital/Analog, bargraph, backlight Voltage Measurement 1000Vac/dc Display Digital/Analog
Other Alarm, ∆REL Memory (Readings) 20 128kb Communication —
Dimensions 8.30 x 4.25 x 2.36" Power Source Eight 1.5V C cell batteries 9.6V NiMH battery pack Dimensions 10.63 x 9.84 x 7.09"
Weight 1.87 lbs Display Digital/Analog, bargraph, backlight Weight 9.5 lbs
Catalog No. 2155.56 Communication —
DataView® software Catalog No. 2130.18
Catalog No. 2155.57 RS-232 to USB adapter
Model 6536 ESD Floor Test Kit Dimensions 9.45 x 7.28 x 4.33"
Weight 7.5 lbs
Catalog No. 2130.01 2130.03
True
6 www.aemc.com Technical Assistance (800) 343-1391
OH
TE

ME
For Testing Motors, For Insulation Measurements Insulation Measurements
Pumps & Transformers on Communication & Data Cables for Electrical Components
Models 6522, 6524 & 6526 Model 6532 Model 6534

IP 6526 IP IP
54
Rated
only 54
Rated
54
Rated

MODELS 6522 6524 6526 Test Voltage 50, 100V Test Voltage 10, 25, 100, 250, 500Vdc
Test Voltage 250, 500, 1000Vdc 50, 100, 250, 500, 1000Vdc Insulation Range 20GΩ Insulation Range 50GΩ
Insulation Range 40GΩ 200GΩ Resistance Range 1000kΩ Resistance Range 1000kΩ
Resistance Range — 1000kΩ Continuity Range 10Ω, 100Ω Continuity Range 10Ω, 100Ω
Continuity Range 10Ω 10Ω, 100Ω Voltage Measurement 700Vac/dc Voltage Measurement 700Vac/dc
Voltage Measurement 700Vac/dc Memory (Measurements) 1300 Memory (Measurements) 1300
Memory (Measurements) 300 1300 Power Source Six AA batteries Power Source Six AA batteries
Power Source Six AA batteries Display Digital/Analog, bargraph Display Digital/Analog, bargraph
Display Digital/Analog, bargraph Other Lead Compensation, Alarms Other ∆REL, Lead Compensation
Other Lead Compensation ∆REL Pass/Fail LED Dimensions 8.30 x 4.25 x 2.36" Dimensions 8.30 x 4.25 x 2.36"
Dimensions 8.30 x 4.25 x 2.36" Weight 1.87 lbs Weight 1.87 lbs
Weight 1.87 lbs Catalog No. 2155.54 Catalog No. 2155.55
Catalog No. 2155.51 2155.52 2155.53

5000V Digital/Analog 5000V Digital/Analog 5000V Graphical


Model 5050 Model 5060 Model 5070

FET Y FET Y FET Y


SA SA SA

IP IP IP
RA
TIN G 53 RA
TIN G 53 RA
TIN G 53

Test Voltage 500, 1000, 2500, 5000Vdc Test Voltage 500, 1000, 2500, 5000Vdc Test Voltage 500, 1000, 2500, 5000Vdc
Insulation Range 10kΩ to 10TΩ Insulation Range 10kΩ to 10TΩ Insulation Range 10kΩ to 10TΩ
Other Measurement DAR, PI, DD, Capacitance Other Measurement DAR, PI, DD, Capacitance Other Measurement DAR, PI, DD, Capacitance,
Dielectric Discharge 0.02 to 50.00 Dielectric Discharge 0.02 to 50.00 Step Voltage & Temperature Correction
Leakage Current 3mA Leakage Current 3mA
Dielectric Discharge 0.02 to 50.00
Voltage Measurement 1 to 2500Vac/4000Vdc Voltage Measurement 1 to 2500Vac/4000Vdc Leakage Current 3mA
Memory (Readings) 20 Memory (Readings) 1500
Voltage Measurement 1 to 2500Vac/4000Vdc
Power Source 9.6V NiMH battery pack Power Source 9.6V NiMH battery pack
Memory (Readings) 1500
Display Digital/Analog, bargraph, backlight Display 10Ω, 100Ω backlight
Power Source 9.6V NiMH battery pack
Communication — Communication DataView® software / 128kB Display Graphical 300 x 240 resolution
Dimensions 10.63 x 9.84 x 7.09" memory with RS-232 to USB adapter Communication DataView® software/ 128kB
Dimensions 10.63 x 9.84 x 7.09" memory with RS-232 to USB adapter
Weight 9.5 lbs Dimensions 10.63 x 9.84 x 7.09"
Catalog No. 2130.20 Weight 9.5 lbs
Catalog No. 2130.21 Weight 9.5 lbs
Catalog No. 2130.30

True
Technical Assistance (800) 343-1391 www.aemc.com 7
OH
TE

ME
Since its creation in 1893, Chauvin Arnoux ® has continued to successfully innovate and develop new products in response to
customer needs and applications. Over the years, Chauvin Arnoux ® has developed extensive expertise and knowledge in many
product lines, i­ncluding: c
­ urrent probes, multimeters (the first multimeter patented in 1937!), ground testers, insulation testers,
environmental testers and many others in the portable test instrument realm.
One product line that stands out is Insulation Testers/Megohmmeters.
Our megohmmeter line finds its roots in the early 1900s. Limited technology was available, so a
galvanometer and a decade resistance box combined with a DC power source was used to make one of
the first megohmmeters. Years later, hand-cranked technology, first using a generator, provided the test
voltage. Today, similar technology is used in the Models 6501 and 6w503 hand-cranked magnetizer, but a
regulated alternator p
­ rovides rectified test voltage and a sealed case protects the meter from the ­
environment. Electronics set in the 1950s and 60s gave birth to e ­ lectronic megohmmeters with
electronic amplifiers. Eventually, digital displays came to the scene, though analog meters remained
due to customer habits and preference.
Today, megohmmeters are digital and incorporate many intelligent features.
Timers, alarms and variable test v­ oltages are becoming common. AEMC ®
introduced a unique line of professional megohmmeters (Models 1050,
1060, 5050, 5060, 5070, 6505, 6527, 6522, 6524, 6526, 6532, 6534,
6536,6550 & 6555) with added features, such as: memory;
automated tests and results (internal c ­ alculations of DAR, PI
Model 6555
and other measurements); graphical displays; PC control; and, Introduced in 2012
report compliant s­ oftware. Market feedback has been very
positive and the megohmmeters are setting new industry standards.
First Megohmmeter
All AEMC® manufactured megohmmeters are designed to the latest ­Introduced in 1909
international safety and testing standards, and are CE marked.
AEMC ® Instruments
TEST & MEASUREMENT INSTRUMENTS

Cable Testers
Clamp-On Meters
Current Measurement Probes
Data Loggers
Digital Multimeters
Electrical Test Tools
Volume 21

Environmental Testers
Ground Resistance Testers
Leakage Current Meters & Probes
Megohmmeters
Micro-Ohmmeters

FAMILY of PRODUCTS
Oscilloscopes
Power Quality Analyzers, Meters & Loggers
Test and Measurement (Lab) Instruments
Thermal Imaging Cameras WWW.AEMC.COM
Transformer Ratiometers TECHNICAL HOTLINE: (800) 343-1391

To learn more or contact us visit our website: www.aemc.com


Call the AEMC® Instruments Technical Assistance Hotline for immediate consultation with an applications engineer: (800) 343-1391
AEMC® Instruments • 15 Faraday Dr. • Dover, NH 03820 USA • (800) 343-1391 • Fax (603) 742-2346 • E-mail: [email protected]
Export Department: +1 (603) 749-6434 x520 • Fax +1 (603) 740-7550 • E-mail: [email protected]
950.BR-MEGOHM_0222 • Printed in the USA
© Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments

You might also like