SIMATIC HAWASSA_NET\ID01-CCT- 10/03/2023 10:00:50 AM
BBT\CPU 416-3 DP\...\FC252 - <offline>
FC252 - <offline>
"THRMO_HOR_TNK LVL CONTRL"
Name: Family:
Author: Version: 0.1
Block version: 2
Time stamp Code: 10/03/2023 10:00:37 AM
Interface: 10/02/2017 09:00:49 PM
Lengths (block/logic/data): 00336 00234 00000
Object properties:
S7_language 9(1) English (United States) 04/01/2015 04:48:16 PM
Name Data Type Address Comment
IN 0.0
OUT 0.0
IN_OUT 0.0
TEMP 0.0
RETURN 0.0
RET_VAL 0.0
Block: FC252
Network: 1
THM+M1.0 / transfer valve to horizontal buffer tnk modif/VALVE IS NORMALY close
Q161.6
I45.3 THM+M1.0
THM+M1.Air trans
pump valve
request open cmd
from brew T72 M11.7 to hor tnk
"I45.3" M11.4 S_ODT SR "Q161.6"
# S Q S Q
S5T#3S TV BI
M11.4
R BCD
I45.3
THM+M1.Air
pump
request
from brew T76
"I45.3" M11.5 S_ODT
# S Q R
S5T#3S TV BI
M11.5
R BCD
Seite 1 von 3
SIMATIC HAWASSA_NET\ID01-CCT- 10/03/2023 10:00:50 AM
BBT\CPU 416-3 DP\...\FC252 - <offline>
Network: 2
THM+M1.0 / trans pump control from horizontal buffer tnk to spent/modif
Q44.5
I45.3 THM+M1.0
THM+M1.Air spent
pump yeat pu
request start cmd
from brew T78 "Q44.5"
"I45.3" M11.2 S_ODTS SR
# S Q S Q
S5T#5S TV BI
M11.2
R BCD
I45.3
THM+M1.Air
pump
request
from brew T79
"I45.3" M11.3 S_ODTS
# S Q R
S5T#3S TV BI
M11.3
R BCD
Network: 3 THM+M1.0 continous ait supply for selonoid @ JB001
Q161.7
THM+M1.0
continous
air
supply
for
selonoid
@ JB001
M11.6 "Q161.7"
Network: 4 Horizontal level sensor signal conditioning
// LSM ball and string type sensor
A "I45.0" I45.0 -- THM+M1.0 BUF_TANK LSM
L S5T#3S
SD "used for LSM" T7 -- HORIZONTAL TANKER LEVEL SWITCH
A "used for LSM" T7 -- HORIZONTAL TANKER LEVEL SWITCH
= "BUF_TANK LSM" M45.1 -- THM+M1.0 BUF_TANK LSM
// LSL ball and string type sensor
A "I44.7" I44.7 -- THM+M1.0 BUF_TANK LSL
L S5T#5S
SD "used for LSM" T7 -- HORIZONTAL TANKER LEVEL SWITCH
A "USED FOR LSL" T8 -- HORIZONTAL TANKER LEVEL SWITCH
= "BUF_TANK LSL" M45.2 -- THM+M1.0 BUF_TANK LSH
// LSH string type sensor
A "I45.1" I45.1 -- THM+M1.0 BUF_TANK LSH
L S5T#5S
SD T 9
A T 9
= "BUF_TANK LSH" M45.3
// on tanker level sensor..low low level
A "I162.0" I162.0 -- THM+M1.0 Spare
L S5T#5S
SD T 18
A T 18
= "LSLL" M45.5 -- installed on tanker
// END
Seite 2 von 3
SIMATIC HAWASSA_NET\ID01-CCT- 10/03/2023 10:00:50 AM
BBT\CPU 416-3 DP\...\FC252 - <offline>
Network: 5 Pump control
transfer from horizontal to thermolise tank
DB201.DBX7
561.2 Q44.2
I45.0 I44.7 Feedback THM+M1.0
THM+M1.0 THM+M1.0 on Q Signal
BUF_TANK BUF_TANK "DB_V". 1 Spare
LSM LSL V370002. T6 M45.0 "QSignal1=
"I45.0" "I44.7" _E_1 M45.4 S_ODT SR THM+M1.0"
# S Q S Q
S5T#3S TV BI
M45.4
R BCD
I44.7
THM+M1.0
BUF_TANK
LSL
"I44.7"
R
DB201.DBX7
561.2
Feedback
on
"DB_V".
V370002.
_E_1
M45.5
installed
on tanker
"LSLL"
Seite 3 von 3