38 SDMS-02
38 SDMS-02
REV. 0 (12-07-2018)
6. MARKING ...................................................................................................................................................... 7
9. GUARANTEE .................................................................................................................................................. 9
2
38-SDMS-05 REV.0
1. SCOPE
This specification defines the minimum technical requirements for design, engineering,
manufacturing, testing, inspection and performance of smart OHL fault indicators intended
to be used in medium-voltage overhead line distribution network of Saudi Electricity
Company (SEC) in Saudi Arabia.
4
38-SDMS-05 REV.0
5.2.4 Clamping tightness of the smart OHL fault indicators shall be able to
withstand wind pressure without slipping or falling out of the conductor.
5.2.5 The smart OHL fault indicators shall be equipped with local indications
plus remote signalization. Local indication by ultra-bright blinking
LEDs. Any additional local indicating method may be proposed and
shall be evaluated by SEC.
Local indications shall have a clear 360° visibility from a distance of
100m at daylight and 500m at night-time.
Provision for live line testing the indications should be available.
5.2.6 The smart OHL fault indicators shall be maintenance-free, fully self-
contained without external transformer or connections, and do not
require additional source of supply.
5.2.7 The battery for driving the local indications shall be military-grade,
easily replaceable with or without using common hand tools and shall
have a minimum operating life of 10 years and total continuous
indicating time of 1500 hours or more.
Soldered battery terminal connections are not acceptable.
5.2.8 The smart OHL fault indicators shall be bi-directional and able to detect
all line-to-line and line-to-ground fault conditions with built-in
restraints to prevent false operation due to sudden variations in load-
current, proximity to other circuits, inrush currents due to feeder
switching or auto-recloser operation.
5.2.9 The smart OHL fault indicators shall be equipped with the following
selectable and adjustable local reset options:
Local Automatic Reset: 10 to 30 seconds after recovering the
line voltage (re-energized line) and return of minimum primary
current of 3A.
Local Timed Reset: selectable to 2, 4, and 8 hours.
Local manual reset shall also be provided such as by using magnet
mountable on standard insulated hot-sticks, or proximity local remote-
control, or any other method accessible from the ground level.
Magnet and its adapter to hot-sticks, and/or proximity local remote-
control shall be supplied for every 50 units of smart OHL fault
indicators.
5
38-SDMS-05 REV.0
5.2.10 The smart OHL fault indicators shall be provided with manual pre-
adjusted trip current value of the load currents in steps of up to 500
amperes or better, and load dependent self-adjusted value of trip current.
5.2.11 The smart OHL fault indicators shall have a response time not lower
than 80ms to prevent false indication due to disturbances with tolerance
of ±10ms.
5.3. COMMUNICATION REQUIREMENTS
The smart OHL fault indicators shall be capable of receiving information from
adjacent smart fault indicators and forwarding the information on remote servers
or SMS client.
5.3.1 The (Master) smart OHL fault indicator with integrated RTU shall be
provided with a SIM card slot to accommodate a standard size SIM
card for use in Saudi Arabia GSM network connections to forward
information to remote servers or SMS client. It shall also be equipped
with short distance radio frequency communication to be able to
connect up to 8 (Slave) smart OHL fault indicators. It should be able
to periodically transmit an SMS “heartbeat” to remote servers or SMS
client to verify its status.
5.3.2 The (Slave) smart OHL fault indicator shall be equipped with short-
distance radio frequency communication of up to 70 meters that
would enable it to forward information to adjacent (Master) smart
OHL fault indicators that is capable of forwarding the information on
remote servers or SMS clients.
5.3.3 The Data Terminal Unit (DTU) or gateway shall be designed to
operate continuously and unattended. It should be able to receive,
collect, and process information from remote (Master) smart OHL
fault indicators. It shall be provided with a maintenance-free UPS to
be able to survive short power outages. It should allow (Master) smart
OHL fault indicators to be integrated in SCADA systems with OPC
(OLE for Process Control) or IEC 60870-5-104 communication
protocols. It shall be provided with a SIM card slot to accommodate a
standard size SIM card for use in Saudi Arabia GSM network
connections. It shall be able to be configured or access by authorized
personnel either locally or remotely.
6
38-SDMS-05 REV.0
6. MARKING
Each smart OHL fault indicator shall have a clear and durable nameplate that will remain
visible throughout the lifetime of the device, and shall bear the following information:
a. Manufacturer and Model/Type
b. Smart OHL Fault Indicator Ratings
c. Conformance Standard, i.e. IEEE 495 or equivalent
d. Serial Number
e. Year of Manufacture
f. Origin
g. SEC Issued PO Number
h. Vendor Name
i. Reference SEC Specification
j. SEC Monogram
7
38-SDMS-05 REV.0
SEC reserves the right to request the supplier/manufacturer to repeat the type test
every five (5) years, or as needed should the supplied smart OHL fault indicators
have frequent faults and failures.
7.3. SAMPLE INSPECTION
Samples together with actual CAD drawings, user manual and routine test reports
shall be submitted for inspection/evaluation prior to issuance of approval for mass
production. The following attributes shall be checked:
a. Dimensional verification
b. Markings
c. User Manual
d. Hot-stick adapter
e. Accessories for Manual Reset: magnet + hot-stick attachment or proximity
local remote-control
f. Packaging
g. Functionality
h. SIM Card Slot
9. GUARANTEE
The supplier/manufacturer shall guarantee the products against all defects arising out of
faulty design or manufacturing defects or defective materials for a period of five (5) years
from the date of delivery.
The supplier/manufacturer shall guarantee that the batteries provided in each smart OHL
fault indicators have a minimum operating life of 10 years.
The supplier shall guarantee the uniformity of the products delivered with the approved
samples.
10. SUBMITTALS
10.1. SUBMITTALS REQUIRED WITH TENDER/INQUIRY
10.1.1. Summary in table form with the following information: list of items
offered, manufacturer, origin, catalogue number, and quantity
10.1.2. Clause-by-clause compliance with the latest revision of SEC
specification 38-SDMS-05.
10.1.3. Manufacturer’s Catalogue and User Manual
10.1.4. Certificate stating that the raw material has been sampled, tested and
inspected in accordance with relevant standard specifications.
10.1.5. Product type test reports and certificates carried out from SEC
approved laboratories
10.1.6. Filled-up technical data schedule on each of the items offered
10.1.7. Manufacturer CAD drawings for each of the items offered
10.1.8. USB Flash Drive containing e-copy of all the documents mentioned
above
9
38-SDMS-05 REV.0
10
38-SDMS-05 REV.0
11
38-SDMS-05 REV.0
2.12 Response Time, milliseconds >80
2.13 Inrush Current Restraint Required
2.14 Symmetrical Fault Current 25kA / 160ms
2.15 Accessories -
Hot-stick Mounting Adapter Provided Yes / Not Applicable
Magnet + Hot-stick Adapter Provided Yes / Not Applicable
Proximity Local Remote-Control Provided Yes / Not Applicable
2.16 Communication Requirements -
SIM Card Slot Available Yes
SIM Card Size Standard
Short-Distance Radio Frequency Communication Yes
Maximum Distance from the Master 70m
3 Others -
Product is Type Tested Yes
SEC Approved Laboratory **
Date Tested **
Manufacturer **
Model/Type **
Country of Origin **
Submittals Required with Tender/Inquiry
**
Included or Not?
12
38-SDMS-05 REV.0
Smart OHL Fault Indicators
Manufacturer of
Description Vendor/Supplier
Material/Equipment
Name of Company
13