0% found this document useful (0 votes)
36 views23 pages

CH 2

The document discusses time response analysis of control systems. It defines different types of time responses including transient and steady state. It also describes standard test signals used for analysis like impulse, step, ramp and parabolic signals. The document then analyzes time responses of first and second order systems to these standard inputs.

Uploaded by

wehabekoda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views23 pages

CH 2

The document discusses time response analysis of control systems. It defines different types of time responses including transient and steady state. It also describes standard test signals used for analysis like impulse, step, ramp and parabolic signals. The document then analyzes time responses of first and second order systems to these standard inputs.

Uploaded by

wehabekoda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

Chapter Two

Time Response Analysis of Control System


• The 1st step in analyzing control system is deriving a mathematical model
of a system and analysis of system performance. There are several methods
used for the analysis of system performance.
• Response of control system to test input signals analyzed both in time
response and frequency response.
– Time domain response examines the amplitude VS time characteristics of
measuring signals.
– Frequency domain response analysis measured signals replaced with group of
sinusoid (wavelength.) amplitude, frequency, and phase are examined.
• If the output of control system for an input w.r.t to time, is called the
time response of the control system. Time response consists of
– Transient response
– Steady state response
•The graph indicate both transient and steady state
responses. mathematically, we can write
the time response as;

•After applying i/p to a control system, o/p


takes time till it reaches to steady state 1
called transient state.
• The transient response will be zero for large value of ‘t’. Ideally,
value of ‘t’ is infinity & practically, it is constant.
Mathematically,
Lets see an example: Find the transient & steady state terms of the
response of the control system 𝑐 𝑡 = 10 + 5e −𝑡 .
– The second term will be zero as ‘t’ denotes infinity, so this is transient
term. And the first term remains same even ‘t’ approaches to infinity.
Standard test signals:
• Standard test signals are used to know the performance of control
system using time response of the output.
Impulse, step, ramp & parabolic signals are test signals.
Unit impulse signal [ð 𝑡 ]: Defined as
𝑡≠0
– δ 𝑡 = {0
∞ 𝑡=0
• So, the unit impulse signal exists at ‘t’ is zero.
2
Unit step signal [𝑢 𝑡 ]: Defined as
𝑢 𝑡 = 1; 𝑡 ≥ 0 and
= 0; 𝑡<0
•Exists for all +𝑣e values of ‘t’ including 0. Unless
its value is 0 for all −𝑣e values.
Unit Ramp signal [𝑟 𝑡 ]: Defined as
– 𝑟 𝑡 = 𝑡; 𝑡 ≥ 0 and
= 0; 𝑡<0
– We can write unit ramp signal, r(t) in terms of unit step
signal, u(t) as 𝑟 𝑡 = 𝑡𝑢(𝑡)
•Exists for all +𝑣e value of ‘t’ including zero, & its value
increases linearly w.r.t to ‘t’ including zero.
Unit Parabolic signal [𝑝 𝑡 ]: Defined as
2
𝑡 𝑡 ≥ 0 and
– 𝑝 𝑡 = ;
2
= 0; 𝑡<0
– We can write unit parabolic signal, p(t) in terms of unit
𝑡2
step signal, u(t) as 𝑟 𝑡 = 𝑢(𝑡).
2
• Exists for all +𝑣e values of ‘t’ including zero. The value
increases non-linearly.
Time response analysis of 1st & 2nd order systems
1
• Consider the following block diagram with transfer function,
𝑠𝑇
connected with unity negative feedback.
– We know the TF of closed loop cs

– Substitute the TF yields;

The power of energy storage element (s) is one in the denominator term.
Hence, based on this, the system said to be first order system.
• The denominator of transfer function is called the characterization function.
• The roots of the denominator of the above transfer function are called the poles
of the transfer unction.
• Meanwhile, the roots of the numerator of the transfer function are called the
zeros of the transfer function.
• We can represent the poles and zeros of transfer function in s-plane (complex
plane to the system dynamics.)
Unit-Impulse response of 1st order system:
• Consider unit impulse signal as an input to the 1st order system.
So, Apply Laplace transform on both sides. R( 𝑠) = 1.
– Consider the equation

• Substitute R(s) in the above equation

• Rearrange the above equation in one of the standard form of Laplace

• Apply inverse Laplace transform on both

sides. for 𝑡 ≥ 0
• The unit impulse response, c 𝑡 is an
exponential decaying signal for +ve values
of ‘t’ & its zero for negative value of ‘t’.
37
Unit-Step response of 1st order system
• Consider the unit step signal as an input to first order system.
1
So, r 𝑡 = 𝑢(𝑡), Apply Laplace transform on both sides. R 𝑠 =
s
1
• Consider the equation, c 𝑠 = 𝑅(𝑠)
𝑠𝑇+1

• Substitute R 𝑠 = 1 in the unit-step response yields;


s
1 1 1
c 𝑠 = =
𝑠𝑇 + 1 𝑠 𝑠(𝑠𝑇 + 1)
• Do partial fraction expansion on the above equation C(s);

• After simplifying and solving A=1 & B=-T, substitution gives

6
The value of c(t) is zero at t=0 and for all –ve value of t. it’s gradually increasing
from zero to one in steady state
7
Unit-Ramp response of 1st order system:
• Consider the unit Ramp signal as an input,
So, r( t ) = 𝑡𝑢(𝑡), Apply Laplace transform on both sides.
1
• Consider the equation, c 𝑠 = 𝑅(𝑠)
𝑠𝑇+1

• Substitute R 𝑠 = s12 in the above equation


1 1 1
c 𝑠 = =
𝑠𝑇 + 1 𝑠2 𝑠2(𝑠𝑇 + 1)
• Do partial fraction expansion of the above equation C(s);
1 𝐴 𝐵 𝐶
c 𝑠 = = + +
𝑠2(𝑠𝑇 + 1) 𝑠 2 𝑠 𝑠𝑇 + 1

1 𝐴 𝑠𝑇 + 1 + 𝐵𝑠 𝑠𝑇 + 1 + 𝐶𝑠 2
=
𝑠2(𝑠𝑇 + 1) 𝑠2(𝑠𝑇 + 1)
• After simplifying and solving A= 1, B= -T and C= T2
8
Substitution gives;

ƒo𝑡 𝑡 ≥ 0

9
Parabolic response of 1st order system
• Consider the unit Ramp signal as an input to first order system. So
𝑢(𝑡), Apply Laplace transform on both sides.
1
• Consider the equation, c 𝑠 = 𝑅(𝑠)
𝑠𝑇+1

• Substitute R 𝑠 = s13 in the above equation


1 1 1
c 𝑠 = =
𝑠𝑇 + 1 𝑠3 𝑠3(𝑠𝑇 + 1)
• Do partial fraction of C(s);
1 𝐴 𝐵 𝐶 𝐷
c 𝑠 = = + + +
𝑠3(𝑠𝑇 + 1) 𝑠3 𝑠2 𝑠 𝑠𝑇 + 1
After simplifying, you will get the values of A=1, B=-T, C=T2 and D=-T3.
substitution

10
11
Response of 2nd order system
• Consider the following block diagram of closed loop control system. An
open loop transfer function is connected with a unity negative feedback.
• We know the TF of the closed
loop control system having unity
negative feedback as

• Substitute, In the above equation.

• The power of energy storage element (s) is two in the denominator term.
Hence, based on this, the system said to be second order system

12
• Different cases of damping are
– No damping case ð = 0
– Critically damped case ð = 1
– Under damped case 0 < ð < 1
– Over damped case ð > 1
• Using this condition unit impulse, unit step, unit ramp and unit
parabolic response can be expresses with same procedure 13
Unit-impulse response of 2nd order system
• Consider unit impulse signal as an input to the 2nd order system.
So, r 𝑡 = δ(𝑡), Laplace transform of unit step signal is. 𝑅(𝑠) = 1
– The TF of second order closed loop control system is

Follow same procedure with 1st order case

14
Unit-step response of 2nd order system
• Consider unit step signal as an input to the 2nd order system.
So, r 𝑡 = u(𝑡), Laplace transform of unit step signal is. 𝑅(𝑠) = 1𝑠
– The TF of second order closed loop control system is
Follow same procedure
Transient response Specification
• The step response of the second order system for the
underdamped case is shown in the following figure.

• The response up to the settling time is known as transient response &


the response after the settling time is known as steady state Response.
• Delay time (𝑡𝑑): it’s the time required for the response to reach
half of its final value from the zero instant.
• Rise time (tr): it is the time required for the response to rise from 0%
to 100% of its final value. Same time this is applicable for the
underdamped conditions.

• Peak time (tp): it’s the time required for the response to reach the
peak value for the first time.

• Peak overshot (Mp): it’s also called maximum overshot, defined as the
deviation of the response at peak time from the final value of
response.
• Settling time (ts): it’s time required for the response to reach the
steady state & stay within the specified tolerance band around the final
value. The tolerance bands are 2% & 5%.
– The settling time for 5% tolerance band is

– The settling time for 2% tolerance band is

17
Steady state errors (e𝑠𝑠).
• The deviation of the output of control system from desired
response during steady state.

• The transfer function of unity negative feedback control system as

18
Where 𝑘𝑝, 𝑘𝑣 and 𝑘𝑎 are position error constant, velocity error
constant and acceleration error constant respectively.
Example: find the steady state error for an input signal r(t) =
of unity negative feedback control system with
– The given input signal is a combination of three signals step, ramp and
parabolic. We can not define steady state error for impulse signal
because it exist only at origin.
• The following table shows the error constants and steady state
error values for these three signals.
20
Example: Find the time domain specification of a control system having
the closed loop transfer function when the unit step signal is
applied as an input to this control system.
• The standard form of the transfer function of 2nd order closed loop
control system as

– By equating the two transfer functions we will get natural


frequency as 𝜔𝑛 = 2𝑟𝑎𝑑/𝑠e𝑐 and damping ratio ð = 0.5.
• The formula to calculate damping frequency 𝜔d as

• To calculate 𝜃 use the relation or cos 𝜃 = ð

• Substitute the above necessary values in the formula of each time


domain specification. 21
22
Assignment Q-2
1. A unity feedback control system is characterized by an open loop transfer
k
function 𝐺 𝑠 = a) Determine the gain k so that the system will have a
𝑠(𝑠+10)
ð of 0.5, b) Determine the settling time, peak overshoot and time to peak
overshoot for a unit step signal.

2𝑠
2. Calculate time domain specification for 𝐺 𝑠 = , 𝐻 𝑠 = 1,
𝑠(𝑠+6)

3. Consider a unity feed back control system with a closed loop transfer function
𝐶(𝑠) k𝑠+𝑏
of = . Determine open loop transfer function 𝐺 𝑠 and show that
𝑅(𝑠) 𝑠 2 +𝑎𝑠+𝑏
𝑎 −k
the steady state error with unit ramp input is given by e𝑠𝑠 =
𝑏

10
4. Find the steady state error for 𝐺 𝑠 = and r(t)= 1 + 2t + 0.5t2
𝑠(𝑠+0.25)
23

You might also like