Dsa 00165002
Dsa 00165002
Upgraded Inverters
with Software Customize Function
VVVF Inverter
Two types of rated specifications, H specifications and P specifications, can be selected according to the load
status, for a wider range of standard applicable motors and substantial cost reduction (200 V type STB Series).
1
INDEX
Lineup 3
Function Specifications 4
Standard Specifications 12
Terminal Functions 22
Protection Functions 28
Usage Cautions 33
2
Lineup
0.75
SBT-0.75K/1.5K
1.5
1.5 SHF-1.5K
SBT-1.5K/2.2K
2.2 SPF-2.2K
2.2 SHF-2.2K
SBT-2.2K/3.7K
3.7 SPF-4.0K
3.7 SHF-4.0K
SBT-3.7K/5.5K
5.5 SPF-5.5K
5.5 SHF-5.5K
SBT-5.5K/7.5K
7.5 SPF-7.5K
7.5 SHF-7.5K
SBT-7.5K/11K
11 SPF-11K
11 SHF-11K
SBT-11K/15K
15 SPF-15K
15 SHF-15K
SBT-15K/18.5K
18.5 SPF-18.5K
18.5 SHF-18.5K
SBT-18.5K/22K
22 SPF-22K
22 SHF-22K
SBT-22K/30K
30 SPF-30K
30 SBT-30K SHF-30K
37 SPF-37K
37 SBT-37K SHF-37K
45 SPF-45K
45 SBT-45K SHF-45K
55 SPF-55K
55 SBT-55K SHF-55K
75 SPF-75K
* The SAMCO-SPF Series (90 kW to 315 kW) lineup is offered as 400V type inverters of 90KW or higher.
For details, contact your nearest sales office, which can be found on the back cover.
3
Function Specifications
Lineup
The SAMCO-vm05 Series comes in two types of rated specifications, H characteristic and P
characteristic, that can be selected according to the application, be it general-purpose industrial use or
use for fans, pumps, etc. *Only for 200V class, below SBT-22k/30k.
Specifications
Function
Selection of the ratings is enabled by using the ratings selection function (cd060).
• H characteristic (cd060=1)
Rated specification of 150%/min. load capacity. Suitable for constant torque loads in general-purpose industrial
applications.
Operation
• P characteristic (cd060=2)
Panel
Rated specification of 120%/min. load capacity. Suitable for reduced torque loads such as in fans, and pumps. P
characteristic applicable motors provides the rated current that can drive motors with a capacity one rank higher
than H characteristic applicable motors.
Specifications
Standard
Selection Setting Example
Dimension
characteristic is available by
Diagrams
P characteristic: 2.2 kW
External
selecting to set P characteristic.
Connection
rank lower than that normally required.
Terminal
Diagram
to drive a 2.2kW motor!
Functions
Terminal
• Customized software
Software customized to customer requirements is provided. This marks an industry first that enables switching
Function List
from regular general-purpose inverters to "customer-specific inverters."
Software
• Wide array of software functions
We provide software functions according to customer requirements, specification changes, etc., whenever needed.
Various control algorithms designed for various applications are also provided as standard, for maximum flexibility.
Functions
Protection
• Free transfer software
Using the FMTP dedicated transfer software, it is easy to add software through direct serial connection with a PC.
Options and
RS-232C Communication
Peripheral
Devices
Program transfer
Cautions
Usage
FMTP
D-sub 9pin dedicated
Standard transfer
cable specification software
Control terminal
compatibility
diagram
4
Software Function List
By providing various control algorithms, the SAMCO-vm05 Series allows the use of the following functions.
For further details about these functions, refer to page 26.
RJ45 type
10Base-T LAN cable
can be used
5
Function Specifications
Lineup
Winding control
Specifications
Sanken's original tension control algorithms are based on the winding patterns controlling winders,
Function
feeders, rewinders, and support a wide range of line speeds. No controller for dancer control such as
found in conventional systems is required.
Operation
•Winding speed prediction pattern operation is the basic algorithm.
Panel
•Tension control with superior stability, including during intermediate stops and restarts, is achieved by adding
dancer position correction control.
Specifications
•Automatic calculation of winding start frequency, end frequency, and winding duration as output frequency
Standard
prediction pattern based on winding amount (increase) phenomenon just by inputting settings
•Up to 4 patterns can be set in advance for easier setup during pattern settings, and can be selected with an
external signal.
•Settings as output frequency prediction patterns based on the winding amount (decrease) phenomenon can also
be performed, for use for rewinder attending lines and printer paper feed control.
Dimension
Diagrams
External
• Monitor function
•The winding elapsed time can be monitor displayed on the operation panel. The winding elapsed time is saved
during intermediate stops of the inverter and stops caused by alarm protection.
Connection
Terminal
Basic block diagram of wiredrawing machine system
Diagram
Feed control inverter Winding control inverter
Frequency command
Operation command
Dancer displacement
Functions
Terminal
Wiredrawing machine system feedback
Function List
Software
Die
Functions
Protection
Automatic calculation of
winding calculation pattern Winding speed prediction control
Options and
Peripheral
Devices
Frequency
f inv1 K Fs
Fe + ref
Ratio operation
f out
Feeding side inverter −
gain Time Winding side inverter
output frequency
output frequency
command
Winding duration
Cautions
Dancer
position signal PI control
+ −
diagram
Home position
reference value Error e
6
Multiple pump drive control (constant pressure feedwater system control)
By providing an SWS board (option), a constant pressure feedwater system that uses multiple pumps,
such as feedwater pump pressure control and multiple pump rotation operation and parallel operation,
can easily be configured. A periodic switching function designed to extend pump life and a pump
selection function for which maintenance ease has been dramatically improved with a control terminal are
also provided.
• Up to 4 pumps can be controlled according to the water supply status with just one inverter.
• Selection of pump operation switching according to the pressure fluctuations status or at
periodic intervals is possible.
• Settings and status display in pressure units are possible.
System configuration example (Example: Four-unit parallel operation system combining commercial drive and inverter drive)
MC0
Commercial power supply
M1 P1
M2 P2
Pressure test value
MC3
MC4
Internal
M3 P3
SWS
option MC5
MC6
M4 P4
MC7
MC control signals
7
Function Specifications
Lineup
This function allows operation for the set time, regardless of the inching signal input time. Operation that
equals or exceeds the minimum time is secured regardless of the operation signal ON width. This
function is effective as a simple home position hold function for improving the position accuracy for
Specifications
rounded-weaving machines.
Function
• The minimum ON width is secured even if the operation command width is uneven.
• Combined with JOG operation, this function is ideal for fine operation when yarn of
rounded-weaving machines is cut off.
Operation
Panel
Basic conceptual diagram
Specifications
Standard
INV operation ON OFF
JOB terminal ON
Dimension
Diagrams
External
Connection
Terminal
Diagram
Even if the intervals during which the button is pressed are uneven, constant-time operation is
Functions
Terminal
V•f separation function
This function allows independent setting of the inverter output frequency and output voltage. Either a V・f
ratio type or complete separation type can be selected according to load. Since adjustments of output
Function List
voltage commands can be performed at will through analog input from external, this function can be
Software
applicable to wiredrawing machine system driven by torque motor.
Functions
Protection
+100
% 1X
Reference voltage
Voltage command change amount
Voltage
command
Options and
Voltage command
Peripheral
Devices
Voltage
command
+0% 0.5X
Original V•f
voltage command
Cautions
Usage
-100
% 0X
Control terminal
compatibility
0V 5V 10V 0V 5V 10V
diagram
8
Function Specifications
『SB-PG』
Speed
estimation IGBT
calculation PG
SAMCO-vm05
PG pulse
waveform
processing
Environmental measures
Reliability is further improved through the use of a totally enclosed-type IP-20 structure and a moisture-
proofed board. Moreover, harmful harmonic can be suppressed by connecting a DC reactor (option).
DC reactor
Option Improves the inverter's input power factor and reduces the influence of inter-phase power supply
voltage imbalances on the inverter.
9
Operation panel
Section names
Lineup
Displays frequency, output current, speed of
7-segment monitor
rotation, load factor, output voltage, pressure
Specifications
value, no unit display, settings, and alarms,
Function
using high-luminescence LEDs.
Ctrl display
Operation
Operation and setting status Numeric keys
Panel
display Directly input numeric data
Operation mode display
Operation and stop status
display Decimal point key
Specifications
Drive key
Standard
Operation command
Dimension
Diagrams
External
Program key Display change /clear key Step keys
Function code setting Switches and clears unit display Step input of various frequency
setting value
* The operation panel can be detached from the main unit and attached to the control panel.
Connection
Terminal
Diagram
Operation panel keys
Functions
Terminal
• Starts forward or reverse run.
Drive key DRIVE
(The direction of rotation is switched by Cd130.)
• Stops operation.
Stop key
Function List
STOP
• Resets the alarm in the alarm stop status.
Software
• In the Status Display mode, changes the display on the 7-segment display.
Display switch/ CLEAR
• In the Function Code Display mode, clears the input numeric data or
clear key DISP
makes the preceding [ENTER] key operation invalid.
Step key
• In the Status Display Mode, decrements the frequency.
Options and
Enter key ENTER • Confirms numeric data indicated on the 7-segment display.
Cautions
Usage
1 2 3 4 5
Numeric keys
• In the Status Display Mode, allows direct frequency setting.
6 7 8 9 0 • Used to enter numeric data into the 7-segment display. Status
Control terminal
10
Operation panel
Data is read for the input function code number and the numeric
ENTER
data input wait status is then entered.
PROG The status display mode is returned to. (Flashing or lit display)
•To perform value input again, press the CLEAR/DISP key to return to the display prior to input.
•To stop function code data input, press the CLEAR/DISP key to return to the Function Code Display mode. (To
stop input after having changed a value, press the CLEAR/DISP key twice without pressing the ENTER key. This
will cause the mode to change back to the Function Code Display mode.)
Display mode
•In the status display mode, frequency, output current, speed of rotation, load factor, output voltage, pressure
value, and no unit display are cycled through by pressing the CLEAR/DISP key.
•Operation mode display displays the "operating" and "stopped" status.
Operation Display
Stopped Light on
11
Standard Specifications
Lineup
Model SBT-0.75K/1.5K SBT-1.5K/2.2K SBT-2.2K/3.7K SBT-3.7K/5.5K SBT-5.5K/7.5K SBT-7.5K/11K SBT-11K/15K SBT-15K/18.5K SBT-18.5K/22K SBT-22K/30K
Load *1 H P H P H P H P H P H P H P H P H P H P
characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic characteristic
Specifications
Applicable motor capacity [kW] 0.75 1.5 1.5 2.2 2.2 3.7 3.7 5.5 5.5 7.5 7.5 11 11 15 15 18.5 18.5 22 22 30
Output
Function
Rated capacity [kVA] *2 1.9 2.7 3.0 3.7 4.3 5.8 6.7 8.5 9.1 11.4 12.8 16.8 17.5 21.7 22.9 25.9 28.6 31.2 33.5 41.9
Rated current [A] 5.1 7.0 8.0 9.6 11.2 15.1 17.6 22.3 24 30 33 44 46 57 60 68 75 82 88 110
Overload current [A] *3 7.6 8.4 12.0 11.5 16.8 18.1 26.4 26.7 36 36 49.5 52.8 69 68.4 90 81.6 112.5 98.4 132 132
Rated output voltage 200V 50/60Hz 220V 60Hz
Operation
Input
Panel
Allowable fluctuation Voltage: ±10%, Frequency: ±5%, Voltage imbalance: 3% max.
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Protective structure Totally enclosed (IP20)
Specifications
Cooling method Self-cooling Forced air cooling
Standard
Gross weight 3kg 4kg 4kg 4.5kg 8kg 8kg 10kg 12kg 15kg 18kg
Control method V/f control or sensorless vector control
High-frequency carrier Sine wave PWM (carrier frequency: 1 to 14 kHz) *4
Output H characteristic 0.05 to 600 Hz (starting frequency: 0.05 to 20 Hz variable) *5
Dimension
frequency
Diagrams
External
Control functions
Frequency
Digital setting ±0.01% of the output frequency (at -10 to +40。C)
Connection
accuracy
Analog setting ±0.2% of the maximum output frequency (at 25。C+-10。C) *6
Terminal
Diagram
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto alarm recovery,
Additional functions
PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only)
Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Functions
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
Terminal
Operational functions
command
setting Analog setting 2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5 kΩ, 0.3 W or more)
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run stop/alarm reset,
Input signals emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only)
[Digital input: 8 channels (arbitrary allocation available)][Analog input: 1 channel for voltage, 1 channel for current and voltage]
Function List
Contact output Alarm batch and multifunctional contact output (1C contact, 250VAC, 0.3 A)
Software
Output
signals
Monitor signal
Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
[Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
LED display Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm
Serial communication I/F RS485,RS232C
Functions
Protection
Function extension Software upgrade by RS232C serial communication supported
External power supply output 24 VDC, 150 mA (control terminal)
Protection functions Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
H characteristic -10 to +50°C (However, remove top ventilation cover at +40°C and higher)
Options and
Ambient
Peripheral
Devices
temperature
Environment
P characteristic -10 to +40°C (However, remove top ventilation cover at +30°C and higher for SBT-3.7K/5.5K and lower)
Storage temperature −20∼+65°C *7
Ambient humidity 90% or less (with no condensation)
Operating environment Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
Cautions
Usage
*1 H characteristic: Constant torque load (for general industry) P characteristic: Dual law decreasing torque load (for fans and pumps)
*2 Rated capacity at the output voltage of 220 V
*3 1 minute every 10 minutes
*4 The maximum carrier frequency varies with the rated characteristics and the operating status.
*5 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
*6 The maximum output frequency is at 5 V, 10 V, and 20 mA.
Control terminal
compatibility
* The SBT-7.5K/11K and lower models are equipped with discharge resistors as standard.
12
200V system (SBT model)
DC braking Starting frequency (0.2 Hz to 20 Hz), braking time (0.1 s to 10 s), braking force (1 to 10 steps)
Restart after momentary power break, flying start, multiple speed operation, frequency jump, automatic alarm reset,
Additional functions
PID control, simplified schedule operation, energy-saving operation, torque limiter (only sensorless vector)
Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminal
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), terminal strip step
command
setting Analog setting 2 ch, 0 V to 5 V, 0 V to 10 V, 4 mA to 20 mA, Polium (5 kW, 0.3 W and above)
Operational functions
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run
Input signals stop/alarm reset, emergency stop, jogging selection, step frequency selection, operation signal holding, torque limiter
(only sensorless vector) [Digital input: 8 ch arbitrary allocation] [Analog input: for voltage 1ch, for current/voltage 1 ch]
Contact output Alarm batch and multi-function contact output (1C contact, 250 V AC, 0.3 A)
Output
signals Operation, frequency coincidence, overload prediction, undervoltage, frequency reach
Monitor signal
[Open collector output 3 ch arbitrary allocation, analog output 2 ch]
LED display Frequency, output current, synchronous rotation, load rate, output voltage, pressure, line speed (free unit), operation, alarms
Overvoltage prevention, current limitation during acceleration/deceleration, break resistance overheat warning,
Warning functions
overload warning, cooling fin overheat warning
Ambient temperature -10˚C to +50˚C (remove the top ventilation cover at a temperature of +40˚C or above)
Environment
13
Standard Specifications
Lineup
Model SHF-1.5K SHF-2.2K SHF-4.0K SHF-5.5K SHF-7.5K SHF-11K SHF-15K SHF-18.5K SHF-22K
Applicable motor capacity 1.5kW 2.2kW 4.0kW 5.5kW 7.5kW 11kW 15kW 18.5kW 22kW
Specifications
rated capacity *1 2.8kVA 4.2kVA 6.2kVA 8.7kVA 11.8kVA 17.3kVA 22.2kVA 26.3kVA 31.9kVA
Output
Function
Rated current *2 4A 6A 9A 12.6A 17A 25A 32A 38A 46A
Operation
Input
Panel
Allowable fluctuation Voltage: -15%, +10%, Frequency: ±5%, Voltage imbalance: 3% max.
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Specifications
Cooling method Forced air cooling
Standard
Gross weight 4kg 4kg 4.5kg 6.5kg 6.5kg 7kg 10kg 12kg 15kg
Dimension
Output frequency range 0.05 to 600 Hz (starting frequency: 0.05 to 20 Hz variable) *4
Diagrams
External
Frequeny Digital setting
Control functions
Frequeny Digital setting ±0.01% of the output frequency (at -10 to +40°C)
accuracy
Connection
Analog setting ±0.2% of the maximum output frequency (at 25°C+-10°C) *5
Terminal
Diagram
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump,
Additional functions auto alarm recovery, PID control operation, simple scheduled operation, energy-saving operation,
torque limiter (for sensorless vector control only)
Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Functions
Terminal
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
command
setting Analog setting 2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5 kΩ, 0.3 W or more)
Start/stop setting
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run stop/alarm reset,
Function List
Input signals emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only)
Software
[Digital input: 8 channels (arbitrary allocation available)][Analog input: 1 channel for voltage, 1 channel for current and voltage]
Contact output Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)
Output
Monitor Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
signals
signal [Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
Functions
Protection
LED display Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm
Protection functions Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Ambient temperature -10 to +50°C (However, remove top ventilation cover at +40°C and higher)
Environment
Operating environment Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
*1 Rated capacity at the output voltage of 400 V
*2 Rated current should be reduced according to output power when input voltage is 400 VAC or higher.
Control terminal
compatibility
*3 The maximum carrier frequency varies depending on the capacity of the inverter and the operating status.
diagram
*4 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and 20 mA.
*6 This temperature is for short periods, such as during transportation.
14
400V system (SHF model)
Allowable fluctuation Voltage: -15%, +10%, Frequency: +-5%, Voltage imbalance: 3% max. *7
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Frequeny Digital setting ±0.01% of the output frequency (at -10 to +40°C)
accuracy
Analog setting ±0.2% of the maximum output frequency (at 25°C+-10°C) (*5)
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto
Additional functions alarm recovery, PID control operation, simple scheduled operation, energy-saving operation, torque
limiter (for sensorless vector control only)
start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
command
setting Analog setting 2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5 kΩ, 0.3 W or more)
Start/stop setting
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run
stop/alarm reset, emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter
Input signals
(sensorless vector control only)
[Digital input: 8 channels (arbitrary allocation available)][Analog input: 1 channel for voltage, 1 channel for current and voltage]
Contact output Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)
Output
signals Monitor Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
signal [Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
LED display Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm
Protection functions Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Ambient temperature -10 to +50°C (However, remove top ventilation cover at +40°C and higher)
Environment
Operating environment Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
*1 Rated capacity at the output voltage of 400 V
*2 Rated current should be reduced according to output power when input voltage is 400 VAC or higher.
*3 The maximum carrier frequency varies depending on the capacity of the inverter and the operating status.
*4 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
*5 The maximum output frequency is at 5 V, 10 V, and 20 mA.
*6 This temperature is for short periods, such as during transportation.
*7 For SHF-37K to SHF-55K, a tap (TAP 1 or TAP2) must be switched according to variable input ranges.
15
Standard Specifications
Lineup
Model SPF-2.2K SPF-4.0K SPF-5.5K SPF-7.5K SPF-11K SPF-15K SPF-18.5K SPF-22K SPF-30K
Applicable motor capacity [kW] 2.2kW 4.0kW 5.5kW 7.5kW 11kW 15kW 18.5kW 22kW 30kW
Specifications
Rated capacity [kVA] *1 3.8kVA 6.2kVA 8.7kVA 11.4kVA 16.6kVA 22.2kVA 26.3kVA 31.2kVA 40.9kVA
Output
Function
Rated current [A] *2 5.5A 8.9A 12.6A 16.4A 24A 32A 38A 45A 59A
Overload current [A] 120% 1 minute
Rated output voltage 3ø 380V 50Hz,400V/50Hz,460V/60Hz
Rated voltage and frequency 3ø 380V∼460V 50/60Hz
Operation
Input
Panel
Allowable fluctuation Voltage: +-10%, +10%, Frequency: +-5%, Voltage imbalance: 3% max.
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Protective structure Totally enclosed (IP20)
Specifications
Cooling method Forced air cooling
Standard
Gross weight 4kg 4kg 4.5kg 6.5kg 6.5kg 7kg 10kg 12kg 15kg
Control method V/f control or sensorless vector control
High-frequency carrier Sine wave PWM (carrier frequency: 1 to 14 kHz) *3
Output frequency range
Dimension
0.05 to 200 Hz (starting frequency: 0.05 to 20 Hz variable) *4
Diagrams
External
Control functions
Frequency
Digital setting ±0.01% of the output frequency (at -10 to +40。C)
accuracy
±0.2% of the maximum output frequency (at 25。C±10。C) *5
Connection
Analog setting
Terminal
Diagram
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto alarm recovery,
Additional functions
PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only)
Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Functions
Terminal
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
command
setting Analog setting
Operational functions
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run stop/alarm reset,
Input signals emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only)
Function List
[Digital input: 8 channels (arbitrary allocation available)][Analog input: 1 channel for voltage, 1 channel for current and voltage]
Software
Contact output Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)
Output
signals Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
Monitor signal
[Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
LED display Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm
Functions
Protection
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Ambient temperature -10 to +40°C (However, remove top ventilation cover at +30°C and higher for the SPF-5.5K and lower.)
Environment
Operating environment Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
16
Standard Specifications
Allowable fluctuation Voltage: +-10%, +10%, Frequency: +-5%, Voltage imbalance: 3% max. *7
Power supply impedance 1% or more (Use the optional reactor if less than 1%)
Protective structure Totally enclosed (IP20)
Cooling method Forced air cooling
Gross weight 20kg 25kg 32kg 33kg
Control method V/f control or sensorless vector control
High-frequency carrier Sine wave PWM (carrier frequency: 1 to 14 kHz) *3
Output frequency range 0.05 to 200 Hz (starting frequency: 0.05 to 20 Hz variable) *4
Control functions
DC braking Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Restart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto alarm recovery,
Additional functions
PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only)
Start/stop setting Operation panel, serial communication (RS485, RS232C), control circuit terminals
Frequency Digital setting Operation panel, serial communication (RS485, RS232C), step setting from terminal board
command
setting Analog setting 2 channels, 0 to 5 V, 0 to 10 V, 4 to 20 mA, variable resistor (5kΩ, 0.3 W or more)
Operational functions
Frequency command, forward run command, reverse run command, acceleration/deceleration time setting, free-run stop/alarm reset,
Input signals emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only)
[Digital input: 8 channels (arbitrary allocation available)][Analog input: 1 channel for voltage, 1 channel for current and voltage]
Contact output Alarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)
Output
signals Operating, frequency matching, overload alarm, undervoltage, overvoltage, frequency approach,
Monitor signal
[Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels]
LED display Frequency, output current, synchronous rotation, load factor, output voltage, pressure, line speed (no units), operating, alarm
Protection functions Current limiting, overcurrent shutoff, motor overload, external thermal alarm, undervoltage, overvoltage, momentary power failure, fin overheat, open phase
Warning functions Overvoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Ambient temperature -10 to +40°C (However, remove top ventilation cover at +30°C and higher for the SPF-5.5K and lower.)
Environment
Operating environment Indoors at 1,000 m or lower altitude (No direct sunlight, corrosive or inflammable gases, oil mist, or dust)
17
External Dimension Diagrams
ラ
イ
Lineup
◆ SBT-0.75K/1.5K ∼ SBT-3.7K/5.5K ン
ナ
ッ
◆ SHF-1.5K ∼ SHF-4.0K プ
◆ SPF-2.2K ∼ SPF-5.5K
Specifications
機
Function
2-φ5 能
仕
様
7 8 9
Operation
DRIVE STOP PROG 1 2 3
Panel
CLEAR
DISP 0 ・ ENTER
(Unit: mm)
238
250
Specifications
Model D
Standard
SBT-0.75K/1.5K 145
SBT-1.5K/2.2K
SBT-2.2K/3.7K 170
SBT-3.7K/5.5K
外
Dimension
Diagrams
SHF-1.5K
External
形
SHF-2.2K 170 寸
SHF-4.0K 法
5
SPF-2.2K 図
128 SPF-4.0K 170
Connection
Terminal
Diagram
140 D SPF-5.5K
Functions
端
Terminal
子
◆ SBT-5.5K/7.5K ∼ SBT-15K/18.5K 機
能
◆ SHF-5.5K ∼ SHF-15K
◆ SPF-7.5K ∼ SPF-18.5K ソ
Function List
フ
Software
ト
ウ
ェ
(Unit: mm) ア
機
能
一
Model H H1 W W1 D 覧
SBT-5.5K/7.5K
2-φ6 Functions
保
Protection
300 280 200 180
SBT-7.5K/11K 護
205 機
7
4
8
5
9
6
SBT-11K/15K 能
340 240 220
Ctrl MPa V % rpm A Hz
SHF-5.5K
205
SHF-11K
SPF-7.5K
6 SPF-15K
compatibility
W1
diagram
18
18
• SBT-18.5K/22K ~ SBT-22K/30K
• SBT-30K ~ SBT-55K
• SHF-18.5K ~ SHF-22K
• SPF-22K ~ SPF-30K
2-φ7
(Unit: mm)
7 8 9
SBT-18.5K/22K 205
390 370 270 248
SBT-22K/30K 230
SBT-30K
H1
H
SBT-45K
650 630 375 353 300
SBT-55K
SHF-18.5K 205
390 370 270 248
SHF-22K 230
7
W1 SPF-22K 205
10 D 390 370 270 248
W SPF-30K 230
• SHF-30K ~ SHF-55K
• SPF-37K ~ SPF-75K
2-φ7
7 8 9
CLEAR
DISP 0 ・ ENTER
(Unit: mm)
Model H H1 W W1 D
SHF-30K
440 420 340 318 240
SHF-37K
H1
H
SHF-45K
550 530 340 318 260
SHF-55K
SPF-37K
440 420 340 318 240
SPF-45K
7
W1 SPF-55K
10 D 550 530 340 318 260
W SPF-75K
19
23.6
15.4
1.5
–0.5
54 +0 6.5
Ctrl
• Operation panel
DRIVE
MPa
V
STOP
%
DISP
32.5
rpm
PROG
CLEAR
A
Hz
104 +0
94 +0
–0.8
–0.8
0
1
4
7
2
5
8
・
3
6
9
ENTER
–0.5
67 +0
20
2-M3 anchoring screw
–0
101 +0.5
Panel mounting dimensions
1.5 –0
63 +0.5
External Dimension Diagrams
Control terminal Usage Options and Protection Software Terminal Terminal External Standard Operation Function
能
機
護
保
覧
一
能
機
ア
ェ
ウ
ト
フ
ソ
能
機
子
端
図
法
寸
形
外
様
仕
能
機
プ
ッ
ナ
ン
イ
ラ
DC reactor
*9
Optional
P1 PP PR
MCCB MC Motor
Brake resistor
power supply
Three-phase
R *8 U
S V IM
T W
FA *1
Grounding
*1
FB Alarm signal output terminal Grounding
ON contact capacity *7
OFF AC250V, 0.3A
FC
MC In operation 1
MC
DO1
Surge killer
Frequency matching Open collector
Multifunctional output terminal DO2 output
Forward run command FR
DI1 (Factory preset) Overload alarm level
*2 setting signal
Reverse run command RR
DI2 DO3
4 V, 50 mA or less
Multi-speed command 1 2DF
DI3
Digital signal common terminal
Multi-speed command 2 3DF DCM1 or DCM2
DI4 Multifunctional input terminal +24 V External power supply User load
*6 output
Free-run command MBS (Factory preset) +24V
DI5 *5 150 mA or less
External emergency stop
command ES Analog output
DI6
AOUT1 V
DC0∼10V
Alarm reset command RST
DI7
2nd or 4th acceleration/deceleration Analog output
command or up terminal AOUT2 V
AD2 DC0∼10V
DI8
21
Terminal Functions
Lineup
Symbol Terminal Description
R,S,T Input power terminals Connected to a three-phase commercial power supply.
Specifications
U,V,W Inverter output terminals Connected to a three-phase induction motor.
Function
Connected to a DC reactor.
reactor.
P,P1 DC reactor connection terminals
(Remove the short-circuit bar between the P1 and P terminals before connecting to a DC reactor.)
Connected to a brake resistor between P and PR. (SBT-0.75K/1.5K to SBT-7.5K/11K)
P,PR Brake resistor connection terminals Remove the internal brake resistor connecting line and insulate it with vinyl tape or some
other insulating material before using an external brake resistor.
Operation
Panel
P,X DC link voltage connection terminals P: DC positive terminal, X: DC negative terminal
Specifications
Standard
Symbol Terminal Description
DCM1
Function selection with Cd648 to Cd640 • Common terminals for digital I/O signal and for +24 V power supply
DCM2
Dimension
DI2
Diagrams
• Signal input "off" by disconnecting from either DCM1 or DCM2
External
DI3 Multifunctional input terminal
DI4 Function selection
DI5 with Cd630 to Cd637 DⅠ1 to DⅠ8 6.6kΩ
DI6
DI7 DCM1 or DCM2 0V
DI8
Connection
Terminal
Diagram
ACM Analog signal common terminal • Common terminal for analog signals
Input terminals
+V1 Variable resistor connection terminal for frequency setting VRF1 • Use a 5 kΩ variable resistor with a rating of 0.3 W or more.
+V2 Variable resistor connection terminal for frequency setting VRF2 • Power cannot be supplied from this terminal. Connect only a variable resistor.
• Input 0 to 10 VDC. When frequency setting is controlled by external input, the command
frequency is proportional to the input signal voltage and the set gain frequency (Cd055) is
Functions
Terminal
applied when the input signal is 10 V (when the setting of function code Cd002 specified
VRF1 Analog signal common terminal external control of VRF1.)
• The input impedance is approximately 31 kΩ. The input voltage range can be changed
from 0 to 5 V using the corresponding function code.
• When frequency setting is selected, current input IRF or voltage input VRF2 can be selected using Cd002.
• When IRF is selected, input 4 to 20 mA DC. When frequency setting is controlled by external input,
Function List
Analog current/voltage input terminal
IRF/VRF2 the command frequency is proportional to the input signal voltage and the set gain frequency
Software
(for current and voltage input)
(Cd063) is applied when the input signal is 20 mA. When IRF is selected, the input impedance is
approximately 500Ω.
+24V +24 V output power • +24 VDC power (maximum allowable output current: 150 mA)
• One monitor item is selected from Cd126 (AOUT1) and Cd128 (AOUT2), and indicated by an analog output.
• The output signal voltage is from 0 to 10 VCD and the maximum allowable current is 15 mA.
Functions
Protection
AOUT1 Built-in analog output terminals Set the output coefficient because the output voltage decreases as the output current
AOUT2 (2-channel output) increases.)
• The output signal can be varied from 0 to 20 times using function codes Cd127 (AOUT1)
Output terminals
Multifunctional output terminals • The signals turn on according to the function selected.DO1 to DO3
Peripheral
4.7Ω
Devices
DO2 (Function selection with Cd638 to • The common terminal is common to the digital
DO3 Cd640) signal common terminals DCM1 to DCM2 0.01µF
DCM1 or DCM2
Alarm signal output terminal and • These are contact output terminals indicating that the protective function has stopped the inverter.
FA multifunctional contact output • Cd674: Multifunctional setting output is performed according to the settings of the relay
FB FA contact output selection.
Cautions
FC
Usage
• Send/receive terminals
TRB RS485 serial communication
terminals
terminals
Control terminal
compatibility
JP1 Upgrade jumper • Do not connect anything to these terminals except when upgrading.
22
Multifunctional Input Terminals
Control terminals DI1 to DI8 are multifunctional input terminals. The following functions can be set with
Cd630 to Cd637.
Data Data Data
No. Symbol Function No. Symbol Function No. Symbol Function
0 Unused 23 Multiplexed FR+AD2+2DF 46 PID PID control switching signal
- terminal
1 FR Forward run command 24 Multiplexed RR+AD2+2DF 47 PM1 External motor M1 selecting signal *
terminal
2 RR Reverse run command 25 Multiplexed FR+AD2+3DF 48 PM2 External motor M2 selecting signal *
terminal
3 2DF Multi-speed command 1 26 Multiplexed RR+AD2+3DF 49 PM3 External motor M3 selecting signal *
terminal
4 3DF Multi-speed command 2 27 Multiplexed FR+AD2+2DF+3DF 50 PM4 External motor M4 selecting signal *
terminal
5 MBS Free-run command 28 Multiplexed RR+AD2+2DF+3DF 51 PM5 External motor M5 selecting signal *
terminal
6 ES External anomaly stop command 29 Multiplexed FR+AD3+2DF 52 PM6 External motor M6 selecting signal *
terminal
7 RST Alarm reset command 30 Multiplexed RR+AD3+2DF 53 PM7 External motor M7 selecting signal *
terminal
8 AD2 2nd or 4th acceleration/deceleration 31 Multiplexed FR+AD3+3DF 54 Reserved
terminal
9 AD3 3rd or 4th acceleration/deceleration 32 Multiplexed RR+AD3+3DF 55 P0 Zero-speed command *
terminal
10 JOG Jog operation command 33 Multiplexed FR+AD3+2DF+3DF 56 Multiplexed FR+CCL*
terminal terminal
11 Multiplexed FR+JOG 34 Multiplexed RR+AD3+2DF+3DF 57 Multiplexed RR+CCL *
terminal terminal terminal
Multiplexed Reset command for simple
12 terminal RR+JOG 35 PTR scheduled operation timer 58 to 61 Reserved
13 Multiplexed FR+AD2 36 IF IRF terminal signal priority
62 Multiplexed FR+MBS
terminal command terminal
14 Multiplexed RR+AD2 37 5DF
Multi-speed (5th-8th speed)
63 Multiplexed RR+MBS
terminal selection command terminal
15 Multiplexed FR+AD3 38 HD Operation signal hold command 64 Reserved
terminal
16 Multiplexed RR+AD3 39 2P 2nd pressure switching command * 65 Multiplexed 2DF+AD2
terminal terminal
17 Multiplexed FR+2DF 40 2PT 2nd pump switching time
66 Multiplexed 2DF+AD3
terminal terminal
Multiplexed selection
18 RR+2DF 41 TCL command * 67 Multiplexed 3DF+AD2
terminal terminal
19 Multiplexed FR+3DF 42 Multiplexed 2P+2PT 68 Multiplexed 3DF+AD3
terminal terminal terminal
20 Multiplexed RR+3DF 43 CP Command pulse blocking signal * 69 Ax10 Electric gear x 10 *
terminal
21 Multiplexed FR+2DF+3DF 44 CCL Deviation counter clearing signal * 70 Ax100 lectric gear x 100 *
terminal
22 Multiplexed RR+2DF+3DF 45 PC P control signal * 71 to 99 Reserved
terminal
* Option
1 In operation 1 On when the gate is on 13 Excitation and DC braking 25 MBS signal Input terminal status output
signal
Voltage low Lower frequency limit ES signal
2 14 matching signal 26 Input terminal status output
Operation cycle end Simple schedule operation Upper frequency limit RST signal
3 15 matching signal 27 Input terminal status output
In operation 2 Off during DC braking Servo on signal Switching standby signal Option
4 and excitation 16 Option 28
5 Frequency matching 1st speed frequency only 17 Zero servo completion Option 29 Positioning completion signal Option
Frequency matching 1st to 8th speed frequencies FR signal Brake resistor completion
6 18 Input terminal status output 30 signal
7 Frequency approach 19 RR signal Input terminal status output 31 Reserved
Overload alarm level Value of Cd048 2DF signal
8 setting signal***2 (Output only in constant operation) 20 Input terminal status output 32 Frequency counter output Output frequency
Electrothermal 3DF signal
9 level prediction Output at 80% or more 21 Input terminal status output 33 Frequency counter output Command frequency
Overload alarm level Value of Cd048
10 Radiator heat prediction 22 AD2 signal Input terminal status output 34 setting signal (Output at all operations)
Auxiliary pump
11 driving signal Option 23 AD3 signal Input terminal status output 35 to 99 Reserved
23
Terminal Functions
Lineup
Circuit Magnetic Contactor (MC) Main Circuit *1 Control Circuit
Motor Breaker Rated Rated Recommended wire size [mm2] Maximum Screw Maximum
200V Type Model Load Screw
Capacity (MCCB) current applied wire size
current Input wire P/P1 wire Output wire diameter wire 2size diameter
Specifications
[A] [A] [mm ] *2 [mm2] *2
Function
[A]
Hcharacteristic 0.75kW 10 11 20 1.25(1.25) 1.25(1.25) 1.25(1.25)
SBT-0.75K/1.5K
Pcharacteristic 1.5kW 10 11 20 1.25(1.25) 1.25(1.25) 1.25(1.25)
Hcharacteristic 1.5kW 15 11 20 1.25(1.25) 1.25(1.25) 1.25(1.25)
SBT-1.5K/2.2K
Operation
Pcharacteristic 2.2kW 15 11 20 1.25(1.25) 1.25(1.25) 1.25(1.25)
Panel
M4 5.5
Hcharacteristic 2.2kW 20 11 20 2.0(1.25) 2.0(1.25) 1.25(1.25)
SBT-2.2K/3.7K
Pcharacteristic 3.7kW 20 11 20 2.0(1.25) 2.0(1.25) 1.25(1.25)
Hcharacteristic 3.7kW 30 18 25 3.5(1.25) 3.5(1.25) 2.0(1.25)
SBT-3.7K/5.5K
Specifications
Pcharacteristic 5.5kW 30 18 25 3.5(1.25) 3.5(2.0) 2.0(1.25)
Standard
Hcharacteristic 5.5kW 40 18 32 5.5(2.0) 3.5(2.0) 3.5(2.0)
SBT-5.5K/7.5K
Pcharacteristic 7.5kW 50 26 50 5.5(3.5) 5.5(3.5) 3.5(2.0)
Hcharacteristic 7.5kW 60 26 50 8(3.5) 8(3.5) 5.5(2.0)
SBT-7.5K/11K
Dimension
Pcharacteristic 11kW 75 50 80 14(8) 14(5.5) 8(3.5)
Diagrams
External
M6 22 M3 1.25
Hcharacteristic 11kW 75 50 80 14(8) 14(5.5) 8(3.5)
SBT-11K/15K
Pcharacteristic 15kW 100 65 100 22(14) 14(8) 14(5.5)
Hcharacteristic 15kW 100 65 100 22(14) 22(8) 14(5.5)
SBT-15K/18.5K
Connection
Pcharacteristic 18.5kW 125 65 100 14 ×2(14) 22(14) 14(8)
Terminal
Diagram
Hcharacteristic 18.5kW 125 80 135 38(14) 22(14) 22(8)
SBT-18.5K/22K
Pcharacteristic 22kW 150 80 135 38(22) 38(14) 22(14)
M8 38
Hcharacteristic 22kW 150 80 135 38(22) 38(14) 22(14)
SBT-22K/30K
Pcharacteristic 30kW 175 152 200 22 ×2(38) 22 ×2(22) 38(14)
Functions
Terminal
SBT-30K Hcharacteristic 30kW 200 152 200 60(38) 60(22) 38(22)
M10 100
SBT-37K Hcharacteristic 37kW 250 180 260 100(60) 60(38) 60(22)
SBT-45K Hcharacteristic 45kW 300 220 260 150(60) 100(60) 100(38)
M10 150
Function List
SBT-55K Hcharacteristic 55kW 350 300 350 150(100) 150(60) 100(60)
Software
Functions
Protection
Options and
Peripheral
Devices
Cautions
Usage
Control terminal
compatibility
diagram
24
Terminal Functions
SPF-2.2K 2.2kW
15 7 20 2.0(2.0) 2.0(2.0) 2.0(2.0)
SHF-2.2K 2.2kW
SPF-4.0K 4.0kW
20 7 20 2.0(2.0) 2.0(2.0) 2.0(2.0)
SHF-4.0K 4.0kW
M4 5.5
SPF-5.5K 5.5kW 7 20
30 2.0(2.0) 2.0(2.0) 2.0(2.0)
SHF-5.5K 5.5kW 17 32
SPF-7.5K 7.5kW 30
17 32 3.5(2.0) 3.5(2.0) 3.5(2.0)
SHF-7.5K 7.5kW 50
SPF-15K 15kW
60 32 60 14 5.5(3.5) 5.5(3.5)
SHF-15K 15kW
*1 The values for wires in the main circuit are for 600 V IV PVC-insulated wires (60°C) when the inverter ambient temperature is 40°C. The values in
parentheses are for 600 V bridged-polyethylene insulated wires (90°C).
*2 The maximum wire size indicates the maximum size of wire that can be used with the terminal board.
25
Software Function List
Control algorithms for various types of applications are provided as standard, and through the provision of
software customized to customer requirements, each inverter can be used as a dedicated inverter that precisely
Lineup
fills system needs.
Function Applications Purpose Description
In the 200 V type SBT series, 150%/minute for the H mode and
Rating selection function SBT, general industry Selection of optimal rating 120%/minute for the P mode can be selected based on the overload
Specifications
capacity. Select the rating according to the motor capacity and load status.
Function
Control software can be upgraded according to special
Upgrade function Special applications Function extension
applications and requests.
Communication function General industry Centralized monitoring control RS-232C and RS-485 serial communication functions are provided as standard.
Operation
Frequency setting General industry Frequency range extension
Panel
(V/f mode).
Digital frequency setting The frequency can be gradually raised and lowered with the up
Terminal board step setting General industry
from remote location and down control input terminals.
Specifications
Multifunctional input terminal General industry
terminal board input function multiple multifunctional input terminals.
Standard
Multi-functionalization of The open collector output terminals for 3 channels can be
General industry
Multifunctional output terminal terminal board output function allocated to multiple multifunctional output terminals.
Dimension
Diagrams
External
Monitor and sequential Two channels of analog output of 0 to 10 V are provided, enabling
General industry
Analog output operation the selection of frequency, current, voltage, and other data.
Frequency connection Counter outputs proportional to the inverter output frequency can be output
Frequency counter output General industry
with upper-level controller up to 10 times to any one of 3 channel open collector output terminal.
Connection
Loading of command value Command values such as frequency and pressure, and various feedback
Terminal
Diagram
Analog input General industry
and feedback values signals can be input with analog signals of 0 to 5V, 10 V, and 4 to 20 mA.
User-supplied power supply General industry Reduction of peripheral devices A power supply of 24 VDC, 150 mA max. can be provided to external peripheral devices.
Functions
Terminal
Improvement of operability The setting value of the status following function code
User default function General industry
and maintainability adjustment data verification can be saved as an initial value.
Changed data display function General industry Improvement of operability and maintainability The changed function code number and data contents can be displayed sequentially.
Improvement of The current function code adjustment data can be copied via
Copy function General industry
Function List
operability the operation panel.
Software
Constant-time inching Circular weaving machines, Improvement of Even if the operation switch On time differs according to the operator, constant-time
function machine tools position accuracy operation is performed, for improved position accuracy. (Minimum operation time function)
I/O open-phase detection General industry Improvement of Protection is performed by detecting open phases for inverter input
function protection functions and output. The availability of functions can also be selected.
Functions
Protection
The inverter output frequency and voltage can be freely changed and the
V/f separation function Winders Free torque control
V/f ratio type and complete separation type can be selected for the load.
Free V/f pattern Lifts, elevators Free torque control In addition to linear V/f patterns, two intermediate points can be freely set.
Cooling fan lock detection machines, general detecting the cooling fan lock status. Moreover, the availability
Peripheral
protection functions
Devices
operation
Usage
Automatic process Automatic process control according to various control factors such as
PID control operation Air conditioning, pumps
control speed, flow amount, and pressure is possible through PID control.
Feedback control through PID and open loop control with V/f constant
Control terminal
Automatic/manual
compatibility
PID, V/f switch operation Air conditioning, pumps control can be switched with a control terminal input signal. This is effective
diagram
switching
for switching during production and adjustments, and during preparations.
Vector, V/f switch Operation mode Sensorless vector control and V/f constant control can be switched with the control terminal input
Conveyers
operation switching signal. This is effective for switching during production and adjustments, and during preparations.
26
Software functions
Acceleration-deceleration Variable Depending on the combination of control input terminals, the acceleration/deceleration
General industry
switch operation acceleration/deceleration time time can be switched between up to 4 levels toward the set frequency.
Operation signal hold Operation with one-shot Continuous operation is possible even if using operation signal
General industry.
function connection signal contacts by using one-shot momentary switches, etc.
Scheduled operation Scheduled operation is performed with up to 7 patterns for which frequency, time,
Simple schedule operation General industry
following the set pattern acceleration/deceleration time, operation direction, etc., have been set in advance.
The inverter output switching carrier frequency can be freely adjusted. This function is
Carrier frequency General industry Noise reduction
effective for reducing motor noise and other mechanical noises, as well as leak current.
Unstable phenomena Extruding machines, This function reduces output current instability that tends to
Current ripple elimination
removal function etc. occur in the case of low frequency or light load.
This function displays the frequency, current, voltage, load factor, etc., to the operation
Monitor display General industry Status monitoring panel LED. Moreover, when no unit display is selected, status such as that of feedback
frequency, fin temperature, and direct current voltage, can be displayed.
Improvement of This function automatically performs acceleration in the optimum acceleration time
Current control function General industry
protection functions in order to reduce the overcurrent during inverter acceleration to the set value.
Overvoltage stall Improvement of Automatically adjusts the deceleration curve to reduce the circuit voltage
Machine tools
prevention function protection functions during inverter deceleration. Function availability can also be selected.
Momentary power failure Air conditioning, Following power recovery after a momentary power failure, shock-less
Trip-less operation
restart function pumps restart is automatically performed through scooping-up operation.
Using this function, the inverter is placed in the regeneration status through
Momentary drop deceleration, the chronic energy on the load side is effectively used, and
Winders, inertial load Trip-less operation
compensation function the time until a trip is considerably lengthened, in order to suppress
undervoltage trips upon occurrence of a momentary power failure.
Even when the inverter operation command is set to on with the motor in the
freewheel-spinning status, the number of motor rotations and the rotation direction
scooping-up operation Fans, inertial load Trip-less operation are detected, and shock-less start is performed from the current rotating speed. If the
rotation direction differs from the command, deceleration is performed after scooping-
up, and acceleration is performed again in the command direction.
Constant tension, wide Control of winders, feeders, rewinders, etc., supporting a wide range of line
Winding control Winders speed range winder, speeds for a constant tension is possible without a dedicated controller, through
feeding control dedicated winding patterns and a dedicated dancer correction control function.
Speed control and position control are possible by mounting the SB-PG option
Point-to-point control board and performing feedback of the speed detected by the PG speed sensor. In
Position control Machine tools
Continuous path control the case of position control, by directly setting the travel distance on the operation
panel, point-to-point control is possible even when there is no command pulse.
Current monitoring, By mounting the SAS option board, current output proportional to inverter output
Current output function General industry
sequential operation frequency is performed with 4 to 20 mA. A gain of up to 20 times can be set.
27
Protection Functions
Lineup
When the current exceeds the set value, the frequency curves are adjusted to limit the
increase in current.
Acceleration: After the output current reaches the set value during acceleration, the frequency
Overcurrent limiting increases at a slower rate for a while to accelerate the motor within the current limit,
Specifications
(Anti-breakdown) preventing breakdown from occurring.
Function
Constant power operation: When the output current reaches the set value due to an overload
during constant power operation, the frequency is reduced to keep the output current below
the setting. When the overload is removed, the frequency returns to its previous setting.
When the energy regenerated during deceleration of the motor exceeds the
Operation
dissipation capacity of the brake resistor, raising the DC voltage of the
Panel
Overload prevention inverter, the drive frequency stops decreasing and actually increases as
necessary to prevent an over-voltage trip. After the regenerated energy
decreases, deceleration is continued at a slower rate.
Specifications
Standard
Overcurrent shutdown When a current exceeding the allowable current range of the inverter is
input, the protection circuit activates and stops the inverter.
When the inverter-DC link voltage exceeds the specified voltage due to
Dimension
Diagrams
External
Overvoltage shutdown excessive regenerated energy, a protection circuit is activated to stop the
inverter.
Protection against
undervoltage When the DC voltage falls below the specified value due to an abnormal
Connection
power supply voltage, the inverter stops operating.
Terminal
Diagram
(momentary power failure)
Overloading and overheating of the motor during low speed operation are
Overload shutdown detected by the electrothermal protector to stop the inverter. Different
values can be specified to trip electrothermal protector depending on the
type, rated current, etc., of the motor.
Functions
Terminal
Overload shutdown The inverter stops operating when a current greater than the current rating
of the inverter flows for one second or longer.
Function List
Software
Warning (tH) is issued at a temperature 10°C below the abnormal radiator fin
temperature (oH) when the ambient temperature rises sharply or the cooling fan
stops. If it continues to rise further and exceeds the abnormal radiator fin
Fin overheat protection temperature (oH), the protection function stops the motor drive. (The abnormal
radiator fin temperature (oH) differs depending upon the output frequency and
Functions
Protection
output current.) This function also stops the drive when the main switching device
(power module) is overheating. This function is released when the temperature
decreases to more than 10°C below the abnormal radiator fin temperature (oH).
Brake resistor As the regenerative energy of the motor increases, and the allowable brake
resistor value (%ED) is exceeded, the brake resistor becomes temporarily
overheating
Options and
Peripheral
protection
down, it becomes usable again.
External thermal An external thermal protector can be attached to a motor. By inputting this
signal to the ES control signal terminal, the inverter can be set to stop
protection
when the thermal protector is activated.
Control terminal
compatibility
diagram
28
Options and Peripheral Devices
•Install this option when the system power supply Power supply
voltage and inverter rated input voltage must match.
Input power supply
•Install this option to reduce the effect of harmonic
transformer
current on other load machines when using multiple
inverters. Input power
supply transformer
•Connect for protection of the power system and
Wiring circuit breaker
and
protection against overload of wiring.
leak circuit breaker •When using a leak breaker, use a harmonic-resistant
Wiring circuit breaker
breaker.
or
leak breaker
Electromagnetic
contactor •Surge absorber must be installed for coil.
29
DC Reactor
Lineup
<Figure 1>
Terminal hole
Specifications
Function
MAX.H
MAX.E
B C
Operation
4-øG
A Anchoring hole D
Panel
Applicable Dimensions [mm] Weight
Series motor Inverter Type Reactor Type
capacity[kW] Terminal Hole [kg]
A B C D G H
Specifications
Diameter
Standard
0.75/1.5 SBT-0.75K/1.5K ST-DCL-1.5K 75 50 56 60 5 150 M4 2
1.5/2.2 SBT-1.5K/2.2K ST-DCL-1.5K 75 50 56 60 5 150 M4 2
2.2/3.7 SBT-2.2K/3.7K ST-DCL-3.7K 110 95 65 75 6 170 M4 4
3.7/5.5 SBT-3.7K/5.5K ST-DCL-3.7K 110 95 65 75 6 170 M4 4
5.5/7.5 SBT-5.5K/7.5K ST-DCL-7.5K 110 95 70 80 6 185 M6 7
Dimension
Diagrams
External
7.5/11 SBT-7.5K/11K ST-DCL-7.5K 110 95 70 80 6 185 M6 7
200V
11/15 SBT-11K/15K ST-DCL-15K 110 95 80 90 6 185 M6 7
SBT
15/18.5 SBT-15K/18.5K ST-DCL-15K 110 95 80 90 6 185 M6 7
Series
18.5/22 SBT-18.5K/22K ST-DCL-22K 110 95 95 110 6 210 M8 12
Connection
22/30 SBT-22K/30K ST-DCL-22K 110 95 95 110 6 210 M8 12
Terminal
Diagram
30 SBT-30K ST-DCL-37K 135 120 110 125 6 210 M10 15
37 SBT-37K ST-DCL-37K 135 120 110 125 6 210 M10 15
45 SBT-45K ST-DCL-55K 150 135 115 130 6 220 M10 20
55 SBT-55K ST-DCL-55K 150 135 115 130 6 220 M10 20
Functions
1.5/2.2 SHF-1.5K/SPF-2.2K SF-DCL-2.2K 75 50 62 72 5 150 M4 3.5
Terminal
2.2/4.0 SHF-2.2K/SPF-4.0K SF-DCL-2.2K 75 50 62 72 5 150 M4 3.5
4.0/5.5 SHF-4.0K/SPF-5.5K SF-DCL-4.0K 75 50 62 72 5 160 M4 3.5
5.5/7.5 SHF-5.5K/SPF-7.5K SF-DCL-7.5K 110 95 80 90 6 175 M4 7
400V
7.5/11 SHF-7.5K/SPF-11K SF-DCL-7.5K 110 95 80 90 6 175 M4 7
Function List
SHF/SPF
Software
11/15 SHF-11K/SPF-15K SF-DCL-15K 110 95 80 90 6 185 M6 7
Series
15/18.5 SHF-15K/SPF-18.5K SF-DCL-15K 110 95 80 90 6 185 M6 7
18.5/22 SHF-18.5K/SPF-22K SF-DCL-22K 135 120 95 110 6 190 M6 13
22/30 SHF-22K/SPF-30K SF-DCL-22K 135 120 95 110 6 190 M6 13
30/37 SHF-30K/SPF-37K SF-DCL-37K 135 120 110 125 6 200 M8 15 Functions
Protection
The shape of the reactor may change according to the circumstances, please contact us for more details.
Peripheral
Devices
* The reactor will become hot during the operation, please install the reactor in an airy place and keep a distance of at least 30 cm away from
nearby equipment. The reactor will become very hot during operation – do not touch.
22
ø4.3
11
12
26.0±1 11
A 85 103
5.5
31±1
A
5.5
Soldering
B 64 84 Yellow/
Green Black Black Black UL-1015AWG18
3
Control terminal
B
300mm
C 130 140
compatibility
14 R3.5 Ø7
10±2
30mm
diagram
7
D 150 160
47.0±1
35.0±1
C
4.5
4.5
D
E 23 25 48.0±1
55.0±1
30
Option (Built-in Card)
The following types of optional boards are provided for installation inside the inverters.
Name Type Function Applicable Inverter
PG feedback board SB-PG Detect the motor speed with the detector (PG) to operate speed SAMCO-vm05
control function and position control function. All models
<.> Keep the motor speed constant when the load changes.
<.> Can stop machine tools, etc., at fixed position.
Feed pump system SWS A constant feed pump system comprising up to 4 pumps can be SAMCO-vm05
board constructed without PDI controller or PLC controller. Models less
An inverter drive fixed system and circuit system, automatic than 75 Kw
control function for auxiliary pumps, periodic switching function
and other control functions are available.
In addition, this can be used as a multifunctional relay output
function.
Current output board SAS The various status monitoring values in the inverter (output frequency) can SAMCO-vm05
be output with a 4 to 20 mA current. All models
Digital input board SDI The frequency setting of the inverter can be performed very SAMCO-vm05
accurately with the external 4 digits BCD or 16-bit binary digital All models
signal input.
PC transfer program for FMTP This application software upgrades the control program of the SAMCO-vm05
upgrade inverter using an external PC. All models *
* Provided free of charge. For details, contact Sanken Electric Co., Ltd.
Two optional boards can be mounted in the inverter simultaneously (Install the first optional board to slot
1 in the inverter. Install the second optional board to slot 2 on the first optional board mounted in slot 1.)
However, simultaneous mounting of two boards is not possible for some board combinations. See the list
of combinations in the following table.
Slot 1
Slot 2 Not Mounted SB-PG SWS SAS SDI
Not Mounted − ○ ○ ○ ○
SB-PG − × × × ×
SWS − × × × ×
SAS − ○ ○ × ○
SDI − × × × ×
○: Simultaneous mounting possible ×: Simultaneous mounting not possible
31
Options and Peripheral Devices
Brake Circuit
Lineup
<External brake resistor selection examples>
Model External Brake Resistor Option Resistor Type and
Specifications
Number Connectable in
Function
SBT Series SHF Series SPF Series Resistance Capacity *1 Series*2
SBT-0.75K/1.5K - - 120Ω or higher 150W EA220R121J-300
SBT-1.5K/2.2K - - 60Ω or higher 300W EC300R600J-300
SBT-2.2K/3.7K - - 60Ω or higher 300W EC300R600J-300
Operation
SBT-3.7K/5.5K - - 40Ω or higher 400W EC400R400J-300
Panel
SBT-5.5K/7.5K - - 20Ω or higher 800W EC800R200J-300
SBT-7.5K/11K - - 20Ω or higher 800W EC800R200J-300
- SHF-1.5K SPF-2.2K 320Ω or higher 200W EA220R321J-300
Specifications
Standard
- SHF-2.2K SPF-4.0K 160Ω or higher 400W EC400R161J-300
- SHF-4.0K SPF-5.5K 120 or higher 600W EC600R121J-300
- SHF-5.5K SPF-7.5K 80Ω or higher 800W EC800R800J-300
- SHF-7.5K SPF-11K 60Ω or higher 1000W EC1000R600J-300
Dimension
Diagrams
External
- SHF-11K SPF-15K 40Ω or higher 1500W EC800R200J-300 × 2
- SHF-15K SPF-18.5K 40Ω or higher 1500W EC800R200J-300 × 2
*1: In this example, the maximum duty cycle of the brake resistor is assumed to be 10%.
*2: "<X>" indicates the number of units connected in series. (Products handled by Micron Electric Co., Ltd.)
Connection
Terminal
Diagram
<Brake circuit mounting list>
Model Brake Resistance Drive Device
SBT-0.75K/1.5K ○ ○
Functions
Terminal
SBT-1.5K/2.2K ○ ○
SBT-2.2K/3.7K ○ ○
200 V
SBT-3.7K/5.5K ○ ○
SBT Series
SBT-5.5K/7.5K ○ ○
Function List
Software
SBT-7.5K/11K ○ ○
SBT-11K/15K ∼ SBT-55K − −
SHF-1.5K − ○
SHF-2.2K − ○ Functions
Protection
SHF-4.0K − ○
SHF-5.5K − ○
400 V
SHF-7.5K − ○
SHF Series
Options and
SHF-11K − ○
Peripheral
Devices
SHF-15K − ○
SHF-18.5K ∼ SHF-55K − −
SPF-2.2K − ○
SPF-4.0K − ○
Cautions
Usage
SPF-5.5K − ○
400 V
SPF-7.5K − ○
SPF Series
SPF-11K − ○
Control terminal
compatibility
SPF-15K − ○
diagram
SPF-18.5K − ○
SPF-22K ∼ SPF-75K − −
32
Usage Cautions
Inverter capacity If driving multiple motors in series with one inverter, select the inverter capacity so that 1.1 times the
selection motors' rated current is less than the inverter's rated output current. Moreover, if a large starting
torque is required, select an inverter capacity one rank higher.
Applying power to the U, V, and W output terminals of the inverter will damage the inverter block.
Wiring
Prior to applying power, carefully check that there are no wiring errors.
Install the inverter in a well-ventilated indoor location away from direct sunlight, avoiding locations that have
Installation location
high temperature, humidity, or where condensation can easily occur, as well as locations with fly, dust, corrosive
and operating
gases, grinding fluid mist or a salty atmosphere. When housing an inverter into controller, establish a cooling
environment
method and controller dimensions such that the inverter's ambient temperature remains within the allowable
range. If the inverter's ambient temperature exceeds +30°C or +40°C , the ventilation cover must be removed.
Also, the surface of the inverter and the dynamic braking resistors reach high temperatures due to the operating
conditions, so mount them on incombustible materials.
Maintenance and Even if the inverter's power supply is shut off, the internal capacitors take time to discharge, so
inspections perform maintenance and inspections only after the charge lamp has gone out. Since residual
voltage remains in the capacitors, they present a risk of electrocution.
Control circuit To perform remote control operation, keep the wiring distance with the inverter within 20 m, and use
wiring distance twisted-pair shielded wire for wiring. Also, to prevent inductance from peripheral devices, perform
wiring away from heavy-current circuits (main circuit and relay sequence circuit).
Wiring length between If the wiring length until the motor is long, the inverter overheats due to the high-frequency current that flows as
inverter and motor stray capacitance between the wires on each layer, and overcurrent trip may occur. Set the carrier frequency to
50m if Cd051 = 130 or less, 100m if Cd051 = 090 or less, and 200m if Cd051 = 040 or less.
If the wiring distance between the inverter and motor is long (particularly during low-frequency output), the motor
Wire size
torque declines due to the declining cable voltage, so perform wiring with sufficiently thick wire.
Installation of circuit Install a wiring circuit breaker (MCCB) for wiring protection on the inverter's input side.
breakers for wiring Use a harmonic-resistant leak breaker.
Application of input Do not perform high-frequency opening/closing (more than once per hour) using the input-side
side electromagnetic electromagnetic contactor (MC), as this may damage the inverter. If high-frequency
contactor starting/stopping is required, do so through control terminal signal input.
As a rule, provide an electromagnetic contactor between the inverter and motor, and do not perform
Application of output
ON/OFF switching during operation. If an electromagnetic contactor has been provided on the
side electromagnetic
inverter output side for switching to a commercial power supply, etc., use it when the inverter and
contactor
motor are stopped.
Since power factor improvement capacitors on the inverter input side are not effective, do not install
Elimination of phase
them. Perform converter power factor improvement with an AC reactor or a DC reactor. Also, do not
advance capacitor to
insert power factor improvement capacitors on the inverter's output side, as this would cause
improve power factor
overcurrent trips and prevent operation.
Installation of thermal The inverter has an electrothermal protection function, but when driving multiple motors with one
relay inverter, install a thermal relay for each motor.
The inverter's main circuit I/O includes harmonic components that may cause damage to
Radio disturbance
communication equipment, radios, and sensors used near the inverter. Such damage can be
(high-frequency noise)
minimized by installing a noise filter. Using metal pipes for wiring between the inverter and motor and
countermeasures
on the power supply side, and grounding these metal pipes, is also effective.
33
Cautions Related to Motors
Lineup
When using a 400 V type motor with a voltage-type PWM inverter that uses IGBT,
Insulating voltage insulation degradation of the motor coil may occur due to surge voltage caused by the
cable length, etc. Consider using a motor with reinforced insulation.
Specifications
Function
When driving a general-purpose motor with an inverter, the temperature rises slightly
Temperature rise higher than during operation with a commercial power supply. Moreover, the cooling
effect in the low-speed range is reduced, so the allowable output torque is lower.
Therefore, use a motor provided with a power-operated ventilation fan.
Operation
Resonance may occur due to natural frequency including the mechanical section.
Panel
Vibrations Providing rubber pads or an inverter frequency jump function is effective.
When operating a general-purpose motor with an inverter, the noise level is higher than
Specifications
Noise during operation using a commercial power supply. For noise reduction, set a high carrier
Standard
frequency for the inverter. Also, the wind noise becomes noticeable during high-speed
operation at 60 Hz or higher.
Dimension
Diagrams
External
The continuous use rotation range differs according to the lubrication method and the
Geared motor
manufacturer. (Particular care is required for the low-frequency range for the oil
lubrication method.)
Connection
Terminal
Diagram
Use a brake motor with an independent brake power supply. Connect the brake power
Brake motor supply to the inverter's primary power supply and switch off the inverter output using the
free-run command (MBS allocation to multifunctional input terminal) during brake
operation (motor stopped).
Functions
Terminal
Submersible motor Since the rated current for these motors is larger compared to that of general-purpose
Submersible pump motors, when choosing an inverter, select one with a suitable inverter capacity based on
the motor's rated current.
Function List
Explosion-proof motor
combination that has been tested for explosion-proof characteristics.
Software
Since design is frequently performed in specifications that best suit the type of motor,
Synchronous motor
consult Sanken Electric when selecting an inverter.
Since single-phase motors are not suitable for variable speed operation via an inverter, Functions
Protection
Single-phase motor
use a three-phase motor instead.
Options and
Peripheral
Devices
Cautions
Usage
Control terminal
compatibility
diagram
34
Control terminal compatibility diagram
① VT, VF compatibility
VT, VF series
ARM +4 2 -4 2 GND VRC VR+ FM+ COM RST RUN REV EMG 2 DF 3 DF 12V INT-EXT
* RUN is only for operation signal.
In reverse run, REV terminal is ON
In forward run, REV terminal is OFF.
FC FB FA RXR TRB TRA DCM2 DO3 DO2 DO1 DCM1 +2 4 V AOUT1 +V2 +V1 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1 AOUT2 IRF/ VRF2 VRF1 ACM
Vm05 series
② VP compatibility
VP series
AL M 4 2 0 GND GND VRC VR+ FM+ COM RST RUN REV EMG ARM FEQ POW LCK
FC FB FA RXR TRB TRA DCM2 DO3 DO2 DO1 DCM1 +2 4 V AOUT1 +V2 +V1 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1 AOUT2 IRF/ VRF2 VRF1 ACM
Vm05 series
③ MT, MF compatibility
FB FC FA FRQ IRF +V COM VRF ES FR DRV UPF RR 2 DF 3 DF AC2 DC2 JOG RST MBS
M series
FC FB FA RXR TRB TRA DCM2 DO3 DO2 DO1 DCM1 +2 4 V AOUT1 +V2 +V1 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1 AOUT2 IRF/ VRF2 VRF1 ACM
Vm05 series
IHF/IPF, IT series
FC FB FA RXR TRB TRA DCM2 DO3 DO2 DO1 DCM1 +2 4 V AOUT1 +V2 +V1 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1 AOUT2 IRF/ VRF2 VRF1 ACM
Vm05 series
35
VVVF Inverter
Safety Cautions
Please observe the following cautions when using Series inverters.
• Prior to use, carefully read the INSTRUCTION MANUAL to ensure correct use.
• Please observe the usage conditions and environmental conditions described in this catalog.
• Use these products for variable speed applications that employ general-purpose industrial three-phase AC-driven motors.
*If considering use of these products for other applications, consult a Sanken Electric sales representative beforehand.
• If considering use of these products for the following equipment and applications, for which there is the risk that failure or
malfunction of these products may directly endanger human life or cause injury, consult beforehand a Sanken Electric
sales representative.
a. Passenger transportation vehicles b. Medical equipment c. Nuclear reactor and powered control systems
d. Aerospace applications e. Transportation equipment f. Safety equipment g. Special applications
• When using these products for equipment where failure of these products may cause loss of life or equipment where
failure of these products is likely to cause major losses, implement safety measures in the equipment.
• These products required electrical work. Have such work performed by a specialist.
● http://www.sanken-ele.co.jp/en/index.html
ISO9001/14001 certified
Sanken Electric products are brought to you only through our
SANKEN ELECTRIC CO., LTD. stringent quality control and environment control based on the
ISO9001 and ISO14001 authentication standards.
■Business product line-up: Switching power supplies,uninterruptible power supplies,motor control inverters, DC power units,high-intensity obstacle lights system,various types of power
supply equipment,hybrid ICs,monolithic ICs,Hall ICs,transistors,MOS-FETs,thyristors, rectification diodes,Schottky barrier diodes,light-emitting diodes,and
cold-cathode dischage tubes
Sanken L.D. Electric (Jiang Yin) Co., Ltd. Sanken Power Systems (UK) Limited
Yungu Road (North Side), Yimincun, Abercynon, Mountain Ash, Mid Glamorgan, CF45 4XA, U.K.
Luqiaozhen, Jiangyin City, Jiangsu, China Tel: 44-1443-742333 Fax: 44-1443-742100
Tel:86-510-637-7888 Fax:86-510-637-6969
•New publication, effective Mar., 2006. The company names and product names that appear in this catalog
•Specifications are subject to change without notice. are trademarks or registered trademarks of their respective owners.