AQT 1250 Edit
AQT 1250 Edit
AQT 1250 Edit
com
Diesel Power Generation
Control System & Power Solutions
Output Rating:
PRIME: STANDBY:
Standard Specifications:
50 Hz—1500 Rpm 400 V, 3ph
1125 kVA 900 kW 1250 kVA 1000 kW
1 PrimeRating:
60 Hz—1800 Rpm 480 V, 3ph
Unlimited hours usage, with an average
load factor of 80% over each 24 hour peri- 995 kVA 796 kW 1097 kVA 878 kW
od. 10% overload is available for 1 hour in ENGINE SPECIFICATIONS
every 12 hours operation. Engine Make PERKINS
o overload is permitted on standby power. Engine Model 4008-30TAG3
No. of Cylinders 8 vertical in-line
2 Standby Rating:
Cycle 4 Stroke
Limited to 500 hours annual usage, with an
Aspiration Turbocharged & air to air charged cooled
average load factor of 80% of the pub-
lished standby power rating over each 24 Cooling Method Water cooled
hour period. Up to 300 hours of annual Governing Type Electronic
usage may be run continuously. Governing Class G2 - ISO 8528 Part 1
No overload is permitted on standby pow- Compression Ratio 13.6:1
er. Displacement 30.561 L
Bore/Stroke 160 x 190 mm
3 Engine: Dynamic Charging Alternator 55AMP, 24V
Perkins, including air filters, fuel filters,
oil filter, starting motor and charging alter-
ALTERNATOR SPECIFICATIONS
Alternator Make Leroy Somer | STAMFORD | AQT
nator etc.
Alternator Model TAL-049-E
Number of Poles 4
4Alternator Type: Number of Winding Leads 6
brushless AC alternator Type of Bearing Single Bearing
Insulation Class - Temp Rise Cont. H - 125/40 C
5 Radiator: Ingress Protection Rating IP 23
50°C, fan protective shroud Excitation System Self Excited
AVR Model R150
Comply with Standards
ISO 3046, BS 5514, DIN 6271, NEMA-MGI, DIN EN, BS 5000, IEC 60034,IEC 60947-2
Powered By: Alternator Operating data
Over speed 2250 rpm
Voltage Regulation + 1%
Harmonic Coefficient THF < 2%
Tel. influence TIF < 50
Cooling air flow 1.0 m3/ Sec
www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Standard Specifications:
Control System:
6– Fuel Tank:
Large back-lit text display Fuel and start outputs, configurable when
(4-Line back-lit LCD text display) using CAN
Capacity of fuel tank is for 8 hours Multiple display languages 8 configurable DC outputs
running DSENet® expansion compatible 9configurable analogue/digital inputs
Built in fuel tank up to 800 kVA Data logging facility Automatically transfers between mains
Fully configurable via PC using USB com- (utility) and generator
munication (DSE7320 MKII only)
7- Circuit Breaker: Front panel configuration Increased input and output expansion
Efficient power save mode capability via DSENet®
3 phase generator sensing IP65 rating (with optional gasket) offers
3 pole LS MCCB increased resistance to water ingress
Accumulated power monitoring
DIGITAL INPUTS
(kW h, kVA h, kVAr h)
ANALOGUE INPUT
8– Control system alarms: Generator/load current monitoring and
protection
Generator overload protection (kW)
•Over and Under Speed Breaker control via fascia buttons
•Low and High Battery Volt.
•Start and Stop Failure
•Over Current
•Under / Over Generator Voltage DSE7320 MKII
•Low Oil Pressure AUTO START & AUTO MAINS
•Emergency stop FAILURE CONTROL
•High engine temperature
9– Warranty policy:
www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Engine: Optional configurations:
Engine accessories:
⦁ Heavy-duty air filter
⦁ Coolant heater
⦁ Lubricant oil heater
⦁ Fuel and Water Separator
⦁ Lube oil rotary pump
Cooling System:
⦁ 55 degree Radiator
⦁ Remote Radiator
Control System:
⦁ AMF
Perkins heavy duty high performance industrial type diesel engine. ⦁ Parallel
⦁ Practical type in low temperature environment
COOLING SYSTEM ⦁ Control Screen Heater
Total Coolant Capacity (L) 149 L ⦁ Remote Annunciators
Cooling Fan Air Flow 1095 m3/ min ⦁ Other(Comp, DEIF)
Radiator Fan Load 27 kW
Circuit Breaker:
Heat Radiation to Room (PRP) 80 Kw ⦁ 3/4 poles
Heat Radiation to Room (ESP) 100 kW ⦁ Fixed/handcart type
LUBRICATION SYSTEM ⦁ Electric mechanism
Oil Filter Type Spin-On Full Flow
Automatic Transfer Switch (ATS):
Total Oil Capacity 153 L ⦁ ATS cabinet
Oil Type API-CH-4 or ACEA E5 ⦁ Contractor type ATS
EXHAUST SYSTEM ⦁ Motorized changeover type ATS
www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703