AQT 50 Edit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

www.aqtgenerators.

com
Diesel Power Generation
Control System & Power Solutions

AQT-50 Generating Set


TECHNICAL DATA SHEET

Output Rating:
Standard Specifications: PRIME: STANDBY:
50 Hz—1500 Rpm 400 V, 3ph
1 Prime Rating: 45 kVA 36 kW 49.6 kVA 39.7 kW
Unlimited hours usage, with an average 60 Hz—1800 Rpm 480 V, 3ph
load factor of 80% over each 24 hour peri- 53 kVA 43 kW 59 kVA 47 kW
od. 10% overload is available for 1 hour in
every 12 hours operation.
ENGINE SPECIFICATIONS
Engine Make PERKINS
o overload is permitted on standby power.
Engine Model 1103A-33TG1
No. of Cylinders 3 vertical in-line
2 Standby Rating: Cycle 4 Strokes
Limited to 500 hours annual usage, with an Aspiration Turbocharged
average load factor of 80% of the pub- Cooling Method Water cooled
lished standby power rating over each 24 Governing Type Mechanical
hour period. Up to 300 hours of annual Governing Class G2 - ISO 8528 Part 1
usage may be run continuously. Compression Ratio 17.25:1
No overload is permitted on standby pow- Displacement 3.3 L
er. Bore/Stroke 105 x 127 mm
Dynamic Charging Alternator 65AMP, 12V
3 Engine: ALTERNATOR SPECIFICATIONS
Perkins, including air filters, fuel filters, Alternator Make Leroy Somer | STAMFORD | AQT
oil filter, starting motor and charging alter- Alternator Model TAL-042-F
nator etc. Number of Poles 4
Number of Winding Leads 6
4 Alternator Type: Type of Bearing Single Bearing
brushless AC alternator Insulation Class - Temp Rise Cont. H - 125/40 ̊C
Ingress Protection Rating IP 23
5 Radiator: Excitation System Self Excited
50°C, fan protective shroud AVR Model R120

Comply with Standards


ISO 3046, BS 5514, DIN 6271, NEMA-MGI, DIN EN, BS 5000, IEC 60034,IEC 60947-2

Powered By: Alternator Operating data


Over speed 2250 rpm
Voltage Regulation + 1%
Harmonic Coefficient THF < 2%
Tel. influence TIF < 50
Cooling air flow 0.10 m3/ Sec

www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Standard Specifications:
Control System:
6– Fuel Tank:
Large back-lit text display protection
Capacity of fuel tank is for 8 hours Multiple display languages Generator overload protection (kW)
DSENet® expansion Breaker control via fascia buttons
running compatible Fuel and start outputs, configurable when
Built in fuel tank up to 800 kVA Data logging facility using CAN
Fully configurable via PC using USB com- 4 configurable DC outputs
munication 4 configurable analogue/digital inputs
7- Circuit Breaker: Front panel configuration Automatically transfers between mains
Efficient power save mode (utility) and generator
3 phase generator sensing Increased input and output expansion
3 pole LS MCCB capability via DSENet ®
Accumulated power
monitoring IP65 rating (with optional gasket) offers
8– Control system alarms: (kW h, kVA h, kVAr h) increased resistance to water ingress
Generator/load current monitoring and
DIGITAL INPUTS
•Over and Under Speed ANALOGUE INPUT
•Low and High Battery Volt.
•Start and Stop Failure
•Over Current
•Under / Over Generator Voltage DSE4520 MKII
•Low Oil Pressure AUTO START & AUTO MAINS
•Emergency stop FAILURE CONTROL
•High engine temperature

9– Warranty policy:

• AQT GENERATOR products has a Dimensions:


warranty for 12 Months or 1000
Length Width Height Fuel Tank Weight
hours whichever occurs first Type
(mm) (mm) (mm) (L) (KG)
against any manufacturing defects
OPEN 1950 775 1175 100 850
•Wearing parts (filters), incorrect man
made operation, maintenance 2260 1110 1500 100 1350
failures are excluded from the
warranty policy

Acoustic Enclosure Specifications:


Acoustic & Weather
Enclosure Type
Proof
Fuel and Water Drainage
Drainage
Provision
Tested Single Point Lifting
Transportation
Facility & Forklift Pockets

Ingress Protection Rating IP 23

Lifting ISO Standard Lifting


Canopy RAL Color TAL 9010
Base frame RAL Color RAL 9011

Noise Pressure level @ 7m 68db(A) @ 7mt

www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Engine:
Optional configurations:
Engine accessories:
🗆 Heavy-duty air filter
🗆 Coolant heater
🗆 Lubricant oil heater
🗆 Fuel and Water Separator
🗆 Lube oil rotary pump

Alternator And Accessories:


🗆 Leroy somer/stamford
🗆 Anti condensation heater
🗆 PMG + AVR ◇Double bearing alternator
🗆 High voltage kV
🗆 RTDs for Bearing and winding

Cooling System:
🗆 55 degree Radiator
🗆 Remote Radiator

Control System:
🗆 AMF
Perkins heavy duty high performance industrial type diesel engine.
🗆 Parallel
🗆 Practical type in low temperature environment
COOLING SYSTEM 🗆 Control Screen Heater
Total Coolant Capacity (L) 10.2 L 🗆 Remote Annunciators
Cooling Fan Air Flow 53 m3/ min 🗆 Other(ComP, DEIF)
Radiator Fan Load 0.4 kW
Heat Radiation to Room (PRP) 7.0kW Circuit Breaker:
🗆 3/4 poles
Heat Radiation to Room (ESP) 8.0 kW
🗆 Fixed/handcart type
LUBRICATION SYSTEM 🗆 Electric mechanism
Oil Filter Type Spin-On Full Flow
Automatic Transfer Switch (ATS):
Total Oil Capacity 8.3L
🗆 ATS cabinet
Oil Type API-CH-4 or ACEA E5
🗆 Contractor type ATS
EXHAUST SYSTEM 🗆 Motorized changeover type ATS
Mufler Type Industrial Grade
Start Battery:
Max. Back Pressure 10 kPa
🗆 Nickel-cadmium battery
🗆
3
Exhaust Gas Flow (PRP/ESP) 7.0/7.7 m / min Maintenance-free battery
Exhaust Gas Temperature < 5510C 🗆 Battery charger and selector switch
FUEL SYSTEM 🗆 Charging current meter

Recommended Fuel Class A2 Diesel External Fuel Tank:


Fuel Consumption Standby 11.70 L/hr 🗆 Single /double wall fuel tank (500-5000 L)
Fuel Consumption 100% PRP 10.80 L/hr 🗆 Fuel Transfer pump

Fuel Consumption 75% PRP 8.23 L/hr Exhaust Muffler:


Fuel Consumption 50% PRP 5.83 L/hr 🗆 Residential grade
AIR SYSTEM 🗆 Critical grade
🗆 Hospital grade
Air Filter Type Dry Element
Combustion Air Flow (PRP) 2.9 m3/min Available for voltages :
Combustion Air Flow (ESP) 3
3.1 m /min
🗆 400/230V, 480/277V, 380/220V, 440/254V,
416/240V,220/127V, 208/120V
Max Air Filter Intake Restriction 8 kPa

www.aqtgenerators.com | [email protected] | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703