Ref 620 2
Ref 620 2
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2014 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0 Issued: 2014-07-01
Revision: C
ABB 3
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
REF620
Uo
UL1UL2UL3
- IED self-supervision
- Local/Remote push-button on LHMI
I ESC Clear
3I - Sequence event
2× O R recorder
3I< I2> I2/I1> 3Ith>F
L AND
- User
37F 46 46PD 49F management OR
- Web HMI
3× 3×
ARC 3I>>>
50L/50NL CONDITION MONITORING COMMUNICATION 1 0 1 0 0 0 1 1 0 0 1 1 0 0
50P/51P 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
AND SUPERVISION
1 1 0 0 1 1 1 0 1 1 0 1 0
Protocols: 1 0 1 1 0 1 1 0 1 1 0 1 0 0
2× 2× IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I>/Io>BF 3I> 3I>> Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
51BF/51NBF 51P-1 51P-2 IEC 60870-5-1031 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
3I DNP3
2× 2× 2×
Interfaces:
3I>→ 3I>>→ 3I2f> FUSEF CBCM
Ethernet: TX (RJ-45), FX (LC)
67-1 67-2 68 60 CBCM
Serial: Serial glass fiber (ST),
RS-485, RS-232/485
U12 Io D-sub 9, IRIG-B
UL1UL2UL3
Redundant protocols:
Io HSR
PRP
2× 2× RSTP
Io>>> Io> Io>> MCS 3I TCS
50N/51N 51N-1 51N-2 MCS 3I TCM
Io
Io
Io>HA PHIZ
51NHA PHIZ
CONTROL AND INDICATION 1) MEASUREMENT
U12
3× 2× 2× 3× 2×
3U< U2> U1< 3U> SYNC O→I PQM3I PQM3U PQMU
27 47O- 47U+ 59 25 79 PQM3I PQM3V PQMV
3× 6×
Uo> f>/f<, PQUUB
df/dt
UL1UL2UL3 59G
81
PQVUB
REMARKS
6× 12× Optional 3× No. of Calculated OR Alternative
6xRTD
2xmA UFLS/R MAP function instances value function to be
81LSH MAP Io/Uo defined when
ordering
GUID-32A97F25-9496-4C91-8A43-62AF4C7EC107 V1 EN
4 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
- IED self-supervision
- Local/Remote push-button on LHMI
I ESC Clear
- Sequence event
2× O R recorder
3I< I2> I2/I1> 3Ith>F
L AND
- User
37F 46 46PD 49F management OR
3I
- Web HMI
3× 3×
ARC 3I>>>
50L/50NL CONDITION MONITORING COMMUNICATION 1 0 1 0 0 0 1 1 0 0 1 1 0 0
50P/51P 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
AND SUPERVISION
1 1 0 0 1 1 1 0 1 1 0 1 0
Protocols: 1 0 1 1 0 1 1 0 1 1 0 1 0 0
2× 2× IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I>/Io>BF 3I> 3I>> Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
51BF/51NBF 51P-1 51P-2 IEC 60870-5-1031 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
3I DNP3
2× 2× 2×
Interfaces:
3I>→ 3I>>→ 3I2f> FUSEF CBCM
Ethernet: TX (RJ-45), FX (LC)
UL1UL2UL3
3× 2× 2× 3× 2×
3U< U2> U1< 3U> O→I PQM3I PQM3U PQMU
27 47O- 47U+ 59 79 PQM3I PQM3V PQMV
3× 6×
Uo Uo> f>/f<, PQUUB
df/dt
59G PQVUB
81
REMARKS
6xRTD 6× 12× Optional
2xmA 3× No. of Calculated OR Alternative
UFLS/R MAP function instances value function to be
81LSH MAP Io/Uo defined when
ordering
GUID-1B3AD629-623E-44F8-893D-D04D5B8FC6A4 V1 EN
ABB 5
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Protection
6 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Control
ABB 7
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Auto-reclosing, instance 1 ● ●
Auto-reclosing, instance 2 ● ●
Condition monitoring
Measurement
Frequency measurement ● ●
Power quality
8 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Voltage variation ● ●
Voltage unbalance ● ●
Other
ABB 9
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Logging functions
Disturbance recorder ● ●
Fault recorder ● ●
Load profile ● ●
fault protection portfolio on the market. To further improve the option can be equipped with an I/O card featuring high-speed
arc fault protection and minimize the effects of an arc fault, outputs operating in one millisecond.
the 620 series IEDs ordered with the arc fault protection
REF620 REF620
Example conf. N Example conf. N
ANSI IEC ANSI IEC
Io Io
25 SYNC 25 SYNC
3U 47O-/59 U2>/3U> 3U 47O-/59 U2>/3U>
47U+/27 U1</3U< Uo 47U+/27 U1</3U<
Uo
49F 3Ith>F 49F 3Ith>F
50L/50NL ARC 50L/50NL ARC
3I 3I
50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
67/67N 3I→/Io→ 67/67N 3I→/Io→
81 f>/f<,df/dt 81 f>/f<,df/dt
81LSH UFLS/R 81LSH UFLS/R
3U Uo
3I 3I 3I 3I
3U Uo
Io Io Io
GUID-944977FA-E5F6-4FCF-A9DF-0AA98B083493 V1 EN
Figure 3. Single busbar AIS 2 section switchgear with conventional instrument transformers
ABB 11
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
REF620 REF620
Io Example conf. N Io Example conf. N
ANSI IEC ANSI IEC
3I 3I 3I 3I 3I
3U 3U 3U 3U 3U
Io Io Io Io
21YN 1) Yo>→ 1) 32N 1) Po>→ 1) 47O-/59 U2>/3U> 47O-/59 U2>/3U> 47O-/59 U2>/3U>
47O-/59 U2>/3U> 47O-/59 U2>/3U> 47U+/27 U1</3U< 47U+/27 U1</3U< 47U+/27 U1</3U<
47U+/27 U1</3U< 47U+/27 U1</3U< 49F 3Ith>F 49F 3Ith>F 49F 3Ith>F
49F 3Ith>F 49F 3Ith>F 50L/50NL ARC 50L/50NL ARC 50L/50NL ARC
50L/50NL ARC 50L/50NL ARC 50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>>
50P/51P 3I>>> 50P/51P 3I>>> 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 67/67N 3I→/Io→ 51NHA 1) Io>HA 1) 51NHA 1) Io>HA 1)
67/67N 3I→/Io→ 67/67N 3I→/Io→ 67/67N 3I→/Io→ 67/67N 3I→/Io→
79 O→I 79 O→I 79 O→I 79 O→I
1)
or 32N (Po>→), 51NHA (Io>HA) 1)
or 21YN (Yo>→), 51NHA (Io>HA) 1)
or 32N (Po>→), 51NHA (Io>HA) 1)
or 32N (Po>→), 51NHA (Io>HA)
GUID-DA94AA0D-9113-4E41-9700-B03CDC7742E1 V1 EN
12 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
REF620
Example conf. N
ANSI IEC
Io
47O-/59 U2>/3U>
Uo 47U+/27 U1</3U<
3U 49F 3Ith>F
3I 50L/50NL ARC
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
51P/51N 3I/Io
81 f>/f<,df/dt
81LSH UFLS/R
3I 3U Uo 3U Uo 3I 3I 3I
Io Io Io Io
47O-/59 U2>/3U> 47O-/59 U2>/3U> 47O-/59 U2>/3U> 21YN 1) Yo>→ 1) 47O-/59 U2>/3U> 47O-/59 U2>/3U>
47U+/27 U1</3U< 47U+/27 U1</3U< 47U+/27 U1</3U< 47O-/59 U2>/3U> 47U+/27 U1</3U< 47U+/27 U1</3U<
49F 3Ith>F 50L/50NL ARC 50L/50NL ARC 47U+/27 U1</3U< 49F 3Ith>F 49F 3Ith>F
50L/50NL ARC 59G Uo> 59G Uo> 49F 3Ith>F 50L/50NL ARC 50L/50NL ARC
50P/51P 3I>>> 60 FUSEF 60 FUSEF 50L/50NL ARC 50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 50P/51P 3I>>> 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51NHA 1)
Io>HA 1)
51BF/51NBF 3I>/Io>BF 51P/51N 3I/3Io 51P/51N 3I/3Io
67/67N 3I→/Io→ 67/67N 3I→/Io→ 67NIEF Io>IEF→ 67NIEF Io>IEF→
79 O→I 79 O→I 79 O→I 79 O→I
81 f>/f<,df/dt 81 f>/f<,df/dt 81 f>/f<,df/dt 81 f>/f<,df/dt
81LSH UFLS/R 81LSH UFLS/R 81LSH UFLS/R 81LSH UFLS/R
1)
or 21YN (Yo>→), 32N (Po>→) 1)
or 32N (Po>→), 51NHA (Io>HA)
GUID-4C35C420-6F0C-4CD8-8A79-7AE6AEDA7DC3 V1 EN
Figure 5. DBB AIS system with one incomer only (with some arrangements simplified)
ABB 13
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
REF620
Example conf. N
ANSI IEC
Io
47O-/59 U2>/3U>
Uo 47U+/27 U1</3U<
49F 3Ith>F
3U
3I 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67/67N 3I→/Io→
81 f>/f<,df/dt
81LSH UFLS/R
3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
GUID-F87909F1-D40F-4DFA-B5D5-07644432D09B V1 EN
Figure 6. Back-to-back arrangement of AIS switchgear (two single-busbar panels with back walls facing each other), with two circuit
breakers and a higher number of disconnectors available. A type of DBB system.
14 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
REF620
Example conf. N
ANSI IEC
Io
47O-/59 U2>/3U>
47U+/27 U1</3U<
Uo
49F 3Ith>F
3U 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
3I
51P/51N 3I/Io
81 f>/f<,df/dt
81LSH UFLS/R
3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
GUID-A4F8E8B6-F572-40DB-9CB1-42CB6808AE77 V1 EN
Figure 7. SBB GIS switchgear with the possibility to control the three-position disconnector switch
5. Supported ABB solutions Ethernet LAN offers an advanced and versatile platform for
ABB’s 620 series protection and control IEDs together with power system protection. Among the distinctive features of
the Grid Automation controller COM600 constitute a genuine the protection system approach, enabled by the full
IEC 61850 solution for reliable power distribution in utility and implementation of the IEC 61850 substation automation
industrial power systems. To facilitate and streamline the standard, are fast communication capability, continuous
system engineering, ABB's IEDs are supplied with supervision of the integrity of the protection and
connectivity packages. The connectivity packages include a communication system, and an inherent flexibility regarding
compilation of software and IED-specific information, reconfiguration and upgrades.
including single-line diagram templates and a full IED data
model. The data model also includes event and parameter At substation level, COM600 uses the data content of the bay-
lists. With the connectivity packages, the IEDs can be readily level IEDs to enhance substation level functionality. COM600
configured using PCM600 and integrated with the grid features a Web browser-based HMI, which provides a
automation controller COM600 or the network control and customizable graphical display for visualizing single-line mimic
management system MicroSCADA Pro. diagrams for switchgear bay solutions. The Web HMI of
COM600 also provides an overview of the whole substation,
The 620 series IEDs offer native support for the IEC 61850 including IED-specific single-line diagrams, which makes
standard also including binary and analog horizontal GOOSE information easily accessible. Substation devices and
messaging. Compared to traditional hard-wired, inter-device processes can also be remotely accessed through the Web
signaling, peer-to-peer communication over a switched HMI, which improves personnel safety.
ABB 15
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
In addition, COM600 can be used as a local data warehouse A better understanding of the process dynamics is achieved
for the substation's technical documentation and for the by combining time-based process measurements with
network data collected by the IEDs. The collected network production and maintenance events.
data facilitates extensive reporting and analyzing of network
fault situations, by using the data historian and event handling COM600 can also function as a gateway and provides
features of COM600. The history data can be used for seamless connectivity between the substation IEDs and
accurate monitoring of process and equipment performance, network-level control and management systems, such as
using calculations based on both real-time and history values. MicroSCADA Pro and System 800xA.
Product Version
GUID-8E5ABC5B-5A9B-4248-B2B1-DB5AFA42D801 V1 EN
Figure 8. Industrial power system example using IEDs, Grid Automation controller COM600 and System 800xA
16 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
sufficient, connecting an external input or output module, for are used for monitoring the current total demand distortion
example RIO600, to the IED can extend binary inputs and and the voltage total harmonic distortion.
outputs utilizable in the IED configuration. The binary inputs
and outputs of the external I/O module can be used for the Power quality monitoring is an essential service that utilities
less time-critical binary signals of the application. The can provide for their industrial and key customers. Not only
integration enables releasing of some initially reserved binary can a monitoring system provide information about system
inputs and outputs of the IED. disturbances and their possible causes, it can also detect
problem conditions throughout the system before they cause
The suitability of the binary outputs of the IED which have customer complaints, equipment malfunctions and even
been selected for the controlling of primary devices should be equipment damage or failure. Power quality problems are not
carefully verified, for example, the make and carry as well as limited to the utility side of the system. In fact, the majority of
the breaking capacity. In case the requirements for the power quality problems are localized within customer
control circuit of the primary device are not met, the use of facilities. Thus, power quality monitoring is not only an
external auxiliary relays should be considered. effective customer service strategy but also a way to protect
a utility's reputation for quality power and service.
The graphical LCD of the IED's HMI includes a single-line
diagram (SLD) with position indication for the relevant primary REF620 has the following power quality monitoring functions.
devices. Interlocking schemes required by the application are
configured using the Signal Matrix or the Application • Voltage variation
Configuration tools in PCM600. • Voltage unbalance
• Current harmonics
Default configuration A incorporates a synchrocheck function • Voltage harmonics
to ensure that the voltage, phase angle and frequency on
either side of an open circuit breaker satisfy the conditions for The voltage unbalance and voltage variation functions are
a safe interconnection of two networks. An autoreclosing used for measuring short-duration voltage variations and
function attempts to restore the power by reclosing the monitoring voltage unbalance conditions in power
breaker with one to five programmable autoreclosing shots of transmission and distribution networks.
desired type and duration. The function can be used with
The voltage and current harmonics functions provide a
every circuit breaker that has the ability for a reclosing
method for monitoring the power quality by means of the
sequence. A load-shedding function is capable of performing
current waveform distortion and voltage waveform distortion.
load shedding based on underfrequency and the rate of
The functions provides a short-term 3-second average and a
change of the frequency.
long-term demand for total demand distortion TDD and total
harmonic distortion THD.
7. Measurement
The IED continuously measures the phase currents and the
9. Disturbance recorder
neutral current. Furthermore, the IED measures the phase
The IED is provided with a disturbance recorder with up to 12
voltages and the residual voltage. In addition, the IED
analog and 64 binary signal channels. The analog channels
calculates the symmetrical components of the currents and
can be set to record either the waveform or the trend of the
voltages, the system frequency, the active and reactive
currents and voltages measured.
power, the power factor, the active and reactive energy
values as well as the demand value of current and power over The analog channels can be set to trigger the recording
a user-selectable preset time frame. Calculated values are function when the measured value falls below, or exceeds,
also obtained from the protections and condition monitoring the set values. The binary signal channels can be set to start
functions of the IED. a recording either on the rising or the falling edge of the
binary signal or on both.
The values measured can be accessed locally via the user
interface on the IED front panel or remotely via the By default, the binary channels are set to record external or
communication interface of the IED. The values can also be internal IED signals, for example, the start or trip signals of
accessed locally or remotely using the Web browser-based the IED stages, or external blocking or control signals. Binary
user interface. IED signals, such as protection start and trip signals, or an
external IED control signal via a binary input, can be set to
8. Power quality trigger the recording. The recorded information is stored in a
In the EN standards, power quality is defined through the non-volatile memory and can be uploaded for subsequent
characteristics of the supply voltage. Transients, short- fault analysis.
duration and long-duration voltage variations and unbalance
and waveform distortions are the key characteristics
describing power quality. The distortion monitoring functions
ABB 17
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
10. Event log by the delta voltage and delta current algorithm. Upon the
To collect sequence-of-events information, the IED has a non- detection of a failure, the fuse failure supervision function
volatile memory with a capacity of storing 1024 events with activates an alarm and blocks voltage-dependent protection
associated time stamps. The non-volatile memory retains its functions from unintended operation.
data also in case the IED temporarily loses its auxiliary supply.
The event log facilitates detailed pre- and post-fault analyses
15. Current circuit supervision
of feeder faults and disturbances. The increased capacity to
Current circuit supervision is used for detecting faults in the
process and store data and events in the IED offers
current transformer secondary circuits. On detecting of a fault
prerequisites to support the growing information demand of
the current circuit supervision function activates an alarm LED
future network configurations.
and blocks certain protection functions to avoid unintended
The sequence-of-events information can be accessed either operation. The current circuit supervision function calculates
locally via the user interface on the IED front panel, or the sum of the phase currents from the protection cores and
remotely via the communication interface of the IED. The compares the sum with the measured single reference current
information can also be accessed using the Web browser- from a core balance current transformer or from separate
based user interface, either locally or remotely. cores in the phase current transformers.
13. Self-supervision The IED variant equipped with current and voltage sensors
The IED’s built-in self-supervision system continuously has three sensor inputs for the direct connection of three
monitors the state of the IED hardware and the operation of combisensors with RJ-45 connectors. As an alternative to the
the IED software. Any fault or malfunction detected is used combisensors, separate current and voltage sensors can be
for alerting the operator. utilized using adapters. Furthermore, the adapters also enable
the use of sensors with Twin-BNC connectors. Additionally,
14. Fuse failure supervision the IED includes one conventional residual-current input 0.2/1
The fuse failure supervision detects failures between the A normally used in applications requiring sensitive earth-fault
voltage measurement circuit and the IED. The failures are protection and featuring core balance current transformers. In
detected either by the negative sequence-based algorithm or
18 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
addition to current and voltage measurements, the IED basic thresholds are selectable within the range of 18…176 V DC
configuration includes 16 binary inputs and 14 binary outputs. by adjusting the IED’s parameter settings.
As an optional addition, the IED basic configuration includes All binary input and output contacts are freely configurable
one empty slot which can be equipped with one of the with the Signal Matrix or Application Configuration tool of
following optional modules. The first option, additional binary PCM600.
inputs and outputs module, adds eight binary inputs and four
binary outputs to the IED. This option is especially needed See the Input/output overview table and the terminal
when connecting the IED to several controllable objects, still diagrams for detailed information about the inputs and
leaving room for additional inputs and outputs for other outputs.
signals needed in configuration. The second option, an
If the number of the IED’s own inputs and outputs does not
additional RTD/mA input module, increases the IED with six
cover all the intended purposes, connecting to an external
RTD inputs and two mA inputs when additional sensor
input or output module, for example RIO600, increases the
measurements e.g. for temperatures, pressures, levels and so
number of binary inputs and outputs utilizable in the IED
on are of interest. The third option is a high-speed output
configuration. In this case, the external inputs and outputs are
board including eight binary inputs and three high-speed
connected to the IED via IEC 61850 GOOSE to reach fast
outputs. The high-speed outputs have a shorter activation
reaction times between the IED and RIO600 information. The
time compared to the conventional mechanical output relays,
needed binary input and output connections between the IED
shortening the overall IED operation time with very time-
and RIO600 units can be configured in a PCM600 tool and
critical applications like arc protection. The high-speed
then utilized in the IED configuration.
outputs are freely configurable in the IED application and not
limited to arc protection only.
A 4 5 - - 24(32)1) 14(18)1)
- 24(32)2) 14(17)2)
(6/2)3) 24 14
- 16(24)2) 14(17)2)
(6/2)3) 16 14
18. Station communication accessed using the IEC 61850 protocol. Disturbance
The IED supports a range of communication protocols recordings are available to any Ethernet-based application in
including IEC 61850, IEC 60870-5-103, Modbus ® and DNP3. the standard COMTRADE file format. The IED supports
Operational information and controls are available through simultaneous event reporting to five different clients on the
these protocols. However, some communication functionality, station bus. The IED can exchange signals with other IEDs
for example, horizontal communication between the IEDs, is using the IEC 61860 protocol.
only enabled by the IEC 61850 communication protocol.
The IED can send binary signals to other IEDs (so called
The IEC 61850 communication implementation supports horizontal communication) using the IEC 61850-8-1 GOOSE
monitoring and control functions. Additionally, parameter (Generic Object Oriented Substation Event) profile. Binary
settings, disturbance recordings and fault records can be GOOSE messaging can, for example, be employed for
protection and interlocking-based protection schemes. The
ABB 19
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
IED meets the GOOSE performance requirements for tripping using RSTP in managed switches. Ethernet redundancy can
applications in distribution substations, as defined by the IEC be applied to all Ethernet-based IEC 61850, Modbus and
61850 standard. The IED also supports the sending and DNP3 protocols.
receiving of analog values using GOOSE messaging. Analog
GOOSE messaging enables fast transfer of analog The IEC 61850 standard specifies network redundancy which
measurement values over the station bus, thus facilitating for improves the system availability for the substation
example sharing of RTD input values, such as surrounding communication. The network redundancy is based on two
temperature values, to other IED applications. complementary protocols defined in the IEC 62439-3
standard: PRP and HSR protocols. Both the protocols are
For redundant Ethernet solution, the IED offers a fibre-optic able to overcome a failure of a link or switch with a zero
communication module providing two optical and one switch-over time. In both the protocols, each network node
galvanic Ethernet network interfaces. Alternatively, the IED has two identical Ethernet ports dedicated for one network
features a galvanic communication module with two galvanic connection. The protocols rely on the duplication of all
and one optical Ethernet network interfaces or three galvanic transmitted information and provide a zero switch-over time if
interfaces. The third Ethernet interface provides connectivity the links or switches fail, thus fulfilling all the stringent real-
for any other Ethernet devices to an IEC 61850 station bus time requirements of substation automation.
inside in a switchgear bay. The redundant solution can be
applied to the Ethernet-based IEC 61850, Modbus and DNP3 In PRP, each network node is attached to two independent
protocols. networks operated in parallel. The networks are completely
separated to ensure failure independence and can have
Ethernet network redundancy can be achieved using the high- different topologies. The networks operate in parallel, thus
availability seamless redundancy (HSR) protocol or the providing zero-time recovery and continuous checking of
parallel redundancy protocol (PRP) or a with self-healing ring redundancy to avoid failures.
COM600
SCADA
HSR applies the PRP principle of parallel operation to a single directions over the ring. Every node forwards the frames it
ring. For each message sent, the node sends two frames, receives from one port to another to reach the next node.
one through each port. Both the frames circulate in opposite When the originating sender node receives the frame it sent,
20 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
the sender node discards the frame to avoid loops. The HSR recommended to split the network into several rings to
ring with 620 series IEDs supports the connection of up to guarantee the performance for real-time applications.
thirty IEDs. If more than 30 IEDs are to be connected, it is
COM600
Devices not supporting HSR
SCADA
Ethernet switch
The choice between the HSR and PRP redundancy protocols communication switch-over. The IEDs in the ring topology act
depends on the required functionality, cost and complexity. as unmanaged switches forwarding unrelated data traffic. The
Ethernet ring solution supports the connection of up to thirty
The self-healing Ethernet ring solution enables a cost-efficient 620 series IEDs. If more than 30 IEDs are to be connected, it
communication ring controlled by a managed switch with is recommended to split the network into several rings. The
standard Rapid Spanning Tree l Protocol (RSTP) support. The self-healing Ethernet ring solution avoids single point of failure
managed switch controls the consistency of the loop, routes concerns and improves the reliability of the communication.
the data and corrects the data flow in case of a
ABB 21
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Client A Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
All communication connectors, except for the front port supported. DNP3 can also be used at the same time with the
connector, are placed on integrated optional communication IEC 61850 protocol.
modules. The IED can be connected to Ethernet-based
communication systems via the RJ-45 connector (100Base- When the IED uses the RS-485 bus for the serial
TX) or the fibre-optic LC connector (100Base-FX). If communication, both two- and four wire connections are
connection to a serial bus is required, the 10-pin RS-485 supported. Termination and pull-up/down resistors can be
screw-terminal or the fibre-optic ST connector can be used. configured with jumpers on the communication card so
external resistors are not needed.
Modbus implementation supports RTU, ASCII and TCP
modes. Besides standard Modbus functionality, the IED The IED supports the following time synchronization methods
supports retrieval of time-stamped events, changing the with a time-stamping resolution of 1 ms:
active setting group and uploading of the latest fault records.
Ethernet-based:
If a Modbus TCP connection is used, five clients can be
• SNTP (Simple Network Time Protocol)
connected to the IED simultaneously. Further, Modbus serial
and Modbus TCP can be used in parallel, and if required both
IEC 61850 and Modbus protocols can be run simultaneously. With special time synchronization wiring:
• IRIG-B (Inter-Range Instrumentation Group - Time Code
The IEC 60870-5-103 implementation supports two parallel Format B)
serial bus connections to two different masters. Besides
basic standard functionality, the IED supports changing of the
active setting group and uploading of disturbance recordings In addition, the IED supports time synchronization via the
in IEC 60870-5-103 format. Further, IEC 60870-5-103 can be following serial communication protocols:
used at the same time with the IEC 61850 protocol. • Modbus
• DNP3
DNP3 supports both serial and TCP modes for connection to • IEC 60870-5-103
one master. Further, changing of the active setting group is
22 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
IEC 61850 ● ● - -
MODBUS RTU/ASCII - - ● ●
MODBUS TCP/IP ● ● - -
DNP3 (serial) - - ● ●
DNP3 TCP/IP ● ● - -
IEC 60870-5-103 - - ● ●
● = Supported
ABB 23
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Table 5. Dimensions
Description Value
Case 246 mm
Case 160 mm
Depth 201 mm
Uaux nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
Burden of auxiliary voltage supply under DC <16.0 W (nominal)/<19.0 W (max) DC <16.5 W (nominal)/<19.0 W (max)
quiescent (Pq)/operating condition AC <17.0 W (nominal)/<21.0 W (max)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
• Continuously 4A 20 A
Voltage withstand:
• Continuous 240 V AC
• For 10 s 360 V AC
24 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Description Value
1) Equals the current range of 40A - 1250A with a 80A, 3mV/Hz Rogowski
2) Depending on the used nominal current (hardware gain)
3) This range is covered (up to 2*rated) with sensor division ratio of 10 000 : 1
Description Value
Description Value
RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C
ABB 25
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Description Value 1)
Breaking capacity when the control-circuit time constant L/R <40 ms 1 A/0.25 A/0.15 A
1) X100: SO1
X105: SO1, SO2, when any of the IEDs is equipped with BIO0005.
X110: SO1, SO2 when REF620 or RET620 is equipped with BIO0005
X115: SO1, SO2 when REF620 or REM620 is equipped with BIO0005
Description Value 1)
Breaking capacity when the control-circuit time constant L/R <40 ms, at 1 A/0.25 A/0.15 A
48/110/220 V DC
1) X100: IRF,SO2
X105: SO3, SO4, when any of the IEDs is equipped with BIO0005
X110: SO3, SO4, when REF620 or RET620 is equipped with BIO0005
X115:SO3, SO4, when REF620 or REM620 is equipped with BIO0005
Table 13. Double-pole power outputs with TCS function X100: PO3 and PO4
Description Value 1)
Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC (two contacts connected in a series)
26 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Table 14. Signal/trip output with high make and carry and with TCS function
Description Value
Breaking capacity when the control-circuit time constant L/R < 40 ms, 1A/0.25A/0.15A
at 48/110/220 V DC (two contacts connected in series)
Table 15. Single-pole power output relays X100: PO1 and PO2
Description Value
Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC
Description Value 1)
Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC
Start 1 ms
1) X105: HSO1, HSO2 HSO3, when any of the IEDs is equipped with BIO0007
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
ABB 27
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)
Description Value
Modulation Unmodulated
Table 20. Lens sensor and optical fibre for arc protection
Description Value
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
28 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
• Contact discharge 8 kV
• Air discharge 15 kV
• All ports 4 kV
• 2s 100 A/m
ABB 29
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
• Conducted
• Radiated
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27
30 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C
Description Reference
LV directive 2006/95/EC
Description Reference
Description
ABB 31
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
32 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 x In
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 x I n, voltage before fault = 1.0 x U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
ABB 33
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
EFIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 x I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
34 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
EFHPTOC 40...200000 ms 10
EFIPTOC 20...200000 ms 10
ABB 35
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 x In
Voltage
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF
IFault = 2 x set Start value 42 ms 44 ms 46 ms
DEFLPDEF 61 ms 64 ms 66 ms
IFault = 2 x set Start value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
36 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
DEFHPDEF 40...200000 ms 10
Characteristic Value
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
56 ms 60 ms 64 ms
Reset time 40 ms
1) Uo = 1.0 × Un
2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
ABB 37
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode ±5.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 × U n = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, f n = 50 Hz,
results based on statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact.
38 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the current measured: fn ±2 Hz
ABB 39
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms
-3 dB at f = 13 × fn
1) Fundamental frequency current = 1.0 × I n. Harmonics current before fault = 0.0 × I n , harmonics fault current 2.0 × Start value . Results based on statistical distribution of 1000
measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 2...20
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5...20
40 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 × U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
ABB 41
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
42 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 x Un, Voltage before fault = 0.9 x U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 x U n, Start value multiples in range of 1.10 to 2.00
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 1.0 × Un, Positive sequence voltage before fault = 1.1 × U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 43
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
df/dt <120 ms
44 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
ABB 45
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode mode ±1.0% of the set value or ±20 ms
Characteristic Value
46 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value
Characteristic Value
1) Phase start value = 1.0 × I n, current before fault = 2.0 × set Phase start value , f n = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output
ABB 47
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
48 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Control functions
Characteristic Value
Characteristic Value
Voltage:
±3.0% of the set value or ±0.01 × Un
Frequency:
±10 mHz
Phase angle:
±3°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 49
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
df/dt <120 ms
50 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Measurement functions
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±0.5% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±0.5% or ±0.002 × Un
Characteristic Value
±1.0% or ±0.002 × Un
ABB 51
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Characteristic Value
±0.5% or ±0.002 × Un
Characteristic Value
Characteristic Value
52 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Supervision functions
Characteristic Value
Characteristic Value
Operate time1) NPS function UFault = 1.1 × set Neg Seq voltage <33 ms
Lev
UFault = 5.0 × set Neg Seq voltage <18 ms
Lev
1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
ABB 53
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
LEDs can be configured to show alarms and indications as Figure 12. Example of the LHMI
needed by PCM600 graphical configuration tool. The LEDs
include two separately controllable colors, red and green,
making one LED able to indicate better the different states of
the monitored object. 21. Mounting methods
By means of appropriate mounting accessories, the standard
The IED also includes 16 configurable manual push buttons,
IED case for the 620 series IED can be flush-mounted, semi-
which can freely be configured by the PCM600 graphical
flush-mounted or wall-mounted.
configuration tool. These buttons can be configured to control
the IED's internal features e.g. changing setting group, trigger Furthermore, the IEDs can be mounted in any standard 19”
disturbance recordings and changing operation modes for instrument cabinet by means of 19” mounting panels available
functions or to control IED external equipment, e.g. opening with cut-outs for one IED.Alternatively, the IED can be
or closing the equipment, via IED binary outputs. These mounted in 19” instrument cabinets by means of 4U
buttons also include a small indication LED for each button. Combiflex equipment frames.
This LED is freely configurable, making it possible to use push
button LEDs to indicate button activities or as additional Mounting methods:
indication/alarm LEDs in addition to the 11 programmable
LEDs. • Flush mounting
• Semi-flush mounting
The local HMI includes a push button (L/R) for the local/ • Rack mounting
remote operation of the IED. When the IED is in the local • Wall mounting
mode, the IED can be operated only by using the local front- • Mounting to a 19" equipment frame
panel user interface. When the IED is in the remote mode, the
IED can execute commands sent remotely. The IED supports Panel cut-out for flush mounting:
the remote selection of local/ remote mode via a binary input. • Height: 162 ±1 mm
This feature facilitates, for example, the use of an external • Width: 248 ±1 mm
switch at the substation to ensure that all the IEDs are in the
local mode during maintenance work and that the circuit
breakers cannot be operated remotely from the network
control center.
54 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
")
(19
.6
280 482
,2
246 262 246 246
177
160
160
160
177
177
153 103
153
48 98
48
Figure 13. Flush mounting Figure 14. Semi-flush mounting Figure 15. Rack mounting
259
318
186
GUID-65A893DF-D304-41C7-9F65-DD33239174E5 V1 EN
ABB 55
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
23. Selection and ordering data consists of a string of letters and digits generated from the
The IED type and serial number label identifies the protection IED's hardware and software modules.
IED. The label is placed above the HMI on the upper part of
the plug-in-unit. An order code label is placed on the side of Use the ordering key information to generate the order code
the plug-in unit as well as inside the case. The order code when ordering complete IEDs.
NBFNAANNABC1BNN1XF
# Description
1 IED
620 series IED (including case) N
2 Standard
IEC B
CN C
3 Main application
Feeder protection and control F
4 Functional application
Example configuration N
5-6 Analog inputs and outputs
4I (I0 1/5 A) + 5U + 24BI + 14BO AA
4I (I0 0,2/1 A) + 5U + 24BI + 14BO AB
Sensors (3I + 3U) + 1CT + 16BI + 14BO AC
7-8 Optional board
Optional I/Os 8BI+ 4BO AA
Optional RTDs 6RTD in + 2mA in AB
Optional Fast I/Os 8BI + 3HSO AC
No optional board NN
9 Communication modules (Serial)
-
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
10 AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1
AB
x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST) + Serial RS-485 connector, RS-232/485
D-Sub 9 connector + input for IRIG-B (cannot be combined with BN
arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (1 x RJ-45) + Serial
RS-485 connector, RS-232/485 D-Sub 9 connector + input for BB
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (3 x RJ-45) with
BD
HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC
+ 1 x LC) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE
+ 2 x LC) with HSR/PRP
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX and -FX (2 x RJ-45 + 1 x LC) with HSR/
NC
PRP
Ethernet 100Base-TX (3 x RJ-45) with HSR/PRP ND
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) with HSR/
NE
PRP
No communication module NN
If serial communication is chosen, please choose a serial communication module
including Ethernet (for example “BC”) if a service bus for PCM600 or the WebHMI is
required.
GUID-1C296D79-C6BC-46CF-AA99-4E92E387C869 V1 EN
56 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
GUID-A3B88F58-2CD5-4EB6-8F34-4CA57C1E2B4A V2 EN
Example code: N B F N A A N N A B C 1 B N N 1 X F
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-F3C93D20-6442-4D87-865F-4CDED43FDDFF V1 EN
ABB 57
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
58 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Signal monitoring ● ●
Application configuration - ●
Event viewing ● ●
Online monitoring - ●
● = Supported
ABB 59
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
L1
L2
L3
A A
N N
n n
a
REF620
a
da dn da dn
Positive X120 X100
Current +
Direction 1 1
BI 1 Uaux
2 2
-
3 3
Uab BI 2
IRF
4
4 5
BI 3
P1
PO1
5
S1 BI 4
6 6
S2 2) 7
7 1/5A
IL1
8 N PO2
P2 9 1/5A
IL2 8
10 N 9
11 1/5A 10
IL3 SO1
12 N
13 1/5A 11
Io 12
P1 S1
14 N 13
S2 SO2
P2
14
X130
16
1 PO3
BI 1
2
17
3 15
BI 2 19
4 TCS1 18
20
5 22
BI 3
6 PO4
7 21
BI 4 23
8
TCS2 24
60 -
9 210V
U_SYN
10 N
60 -
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N
X110 X110
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X115 X115
1 14
BI 1
2 SO1
16
3 15
BI 2
4 17
SO2
5
BI 3 19
6 18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
GUID-AEA0ACBE-C8F6-476A-8218-5E93EC040D85 V2 EN
Figure 18. Connection diagram for the configuration with CTs and VTs
60 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
L1
L2
L3
L1
L2
L3
REF620
X130 X100
Positive + 1
Current 1 0.2/1A Uaux
Direction Io 2
2 N
-
3
X131 IRF
4
I 4 5
IL1
5
PO1
U 7
U1
8 6
7
X132
I 4 PO2
IL2
5 8
U 7 9
U2 10
8
SO1
X133
11
I 4 12
IL3 13
5
SO2
U 7
U3
8 14
16
PO3
17
P1 S1
15
19
TCS1 18
S2
P2 20
22
PO4
21
23
TCS2 24
X110 X110
1 14
BI 1
2 SO1
3 16
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4
7 SO3
22
8 21
BI 5
9 23
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X115 X115
1 14
BI 1
2 SO1
3 16
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4
7 SO3
22
8 21
BI 5
9 23
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
X15
1)
Light sensor input 3
1) Order selectable -Optional
GUID-A93F2F56-35BD-4C2D-BC28-F3DEB59CC8DD V1 EN
ABB 61
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
11
BI 7
12
BI 8
13
GUID-5298DCA3-4597-44C2-850A-889384DF423B V1 EN
8
BI 7
9
BI 8
10
GUID-D019E095-29EF-41B1-BDF4-D9D427201B88 V1 EN
Figure 21. Optional BIO0007 module for fast outputs (slot X105)
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22
GUID-987D427B-C5F7-4073-8D5F-D0C37BEAF5E5 V1 EN
62 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
ABB 63
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Protection
Directional earth-fault protection, low stage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Directional earth-fault protection, low stage, instance 3 DEFLPDEF3 Io> -> (3) 67N-1 (3)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Admittance based earth-fault protection, instance 1 EFPADM1 Yo> -> (1) 21YN (1)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)
Wattmetric based earth-fault protection, instance 1 WPWDE1 Po> -> (1) 32N (1)
Wattmetric based earth-fault protection, instance 2 WPWDE2 Po> -> (2) 32N (2)
Wattmetric based earth-fault protection, instance 3 WPWDE3 Po> -> (3) 32N (3)
Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
64 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Circuit breaker failure protection, instance 1 CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)
Circuit breaker failure protection, instance 2 CCBRBRF2 3I>/Io>BF (2) 51BF/51NBF (2)
ABB 65
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Control
Disconnector control, instance 1 DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
Disconnector control, instance 2 DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control, instance 1 ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Disconnector control, instance 3 DCXSWI3 I <-> O DCC (3) I <-> O DCC (3)
Disconnector control, instance 4 DCXSWI4 I <-> O DCC (4) I <-> O DCC (4)
Earthing switch control, instance 2 ESXSWI2 I <-> O ESC (2) I <-> O ESC (2)
Earthing switch position indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch position indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Load shedding and restoration, instance 1 LSHDPFRQ1 UFLS/R (1) 81LSH (1)
Load shedding and restoration, instance 2 LSHDPFRQ2 UFLS/R (2) 81LSH (2)
Load shedding and restoration, instance 3 LSHDPFRQ3 UFLS/R (3) 81LSH (3)
Load shedding and restoration, instance 4 LSHDPFRQ4 UFLS/R (4) 81LSH (4)
Load shedding and restoration, instance 5 LSHDPFRQ5 UFLS/R (5) 81LSH (5)
Load shedding and restoration, instance 6 LSHDPFRQ6 UFLS/R (6) 81LSH (6)
Condition monitoring
Measurement
Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
66 ABB
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Power quality
Other
Time delay off (8 pcs), instance 1 TOFGAPC1 TOF (1) TOF (1)
Time delay off (8 pcs), instance 2 TOFGAPC2 TOF (2) TOF (2)
Time delay off (8 pcs), instance 3 TOFGAPC3 TOF (3) TOF (3)
Time delay off (8 pcs), instance 4 TOFGAPC4 TOF (4) TOF (4)
ABB 67
Feeder Protection and Control 1MRS757844 C
REF620
Product version: 2.0
Logging functions
68 ABB
69