Smart Pulse Controller
Smart Pulse Controller
PLEASE NOTE:
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 3 of 123
Table of Contents
Abbreviations Used ................................................................................................ 7
General Abbreviations ............................................................................................ 8
1.GETTING STARTED ............................................................................................. 9
1.1.About the User Guide .................................................................................... 9
1.2.Panel Overview .......................................................................................... 10
1.2.1 Master Panel ........................................................................................................................ 10
1.2.2 Valve Panel ........................................................................................................................... 11
1.2.3 Hopper Panel ....................................................................................................................... 11
2. PANELS -INSTALLATION INSTRUCTION .............................................................. 12
2.1. Equipment’s Safety.................................................................................... 12
2.1.1. Static Discharge Warning .................................................................................................... 12
2.1.2. Radio-Frequency interference ............................................................................................ 12
2.1.3. Assembly ............................................................................................................................. 12
2.1.4. Do not expose to direct sunlight ......................................................................................... 13
2.1.5. Protect from rain................................................................................................................. 13
2.1.6. Continuous vibration........................................................................................................... 13
2.1.7. Electrical Connection .......................................................................................................... 13
2.1.8. Power Supply ...................................................................................................................... 13
2.2. General Instruction .................................................................................... 13
2.3. Applicable International Safety Standards .................................................... 14
2.4. Communication Wiring Diagram .................................................................. 15
2.5. Circular Connector ..................................................................................... 16
2.6. Pre Installation Checks Before Start-Up ........................................................ 18
2.6.1 Master panel check .............................................................................................................. 18
2.6.2 Valve panel check................................................................................................................. 19
2.6.3 Hopper panel check ............................................................................................................. 19
3. OVERVIEW ..................................................................................................... 20
3.1 SPC Master Controller ................................................................................. 20
3.1.1. Field Bus .............................................................................................................................. 20
3.1.2. Filter Bus ............................................................................................................................. 20
3.1.3. Differential Pressure ........................................................................................................... 20
3.1.4. Compressed Air Supply (System Pressure) ......................................................................... 20
3.1.5. Dust Sensor ......................................................................................................................... 20
3.1.6. Alarm Table ......................................................................................................................... 20
3.1.7. Local Control ....................................................................................................................... 20
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 4 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 5 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 6 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 7 of 123
Abbreviations Used
AD Analog Digital Max Maximum
AFC After Cleaning Min Minimum
AI Analog Input MM Month
Avg Average MPr Manifold Pressure
MBBD Manifold Burst Bag Detect
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 8 of 123
General Abbreviations
MCB Miniature Circuit Breakers
BBD Burst Bag Detection
CCS Client Control System
HMI Human Machine Interface
AIDI Analog Input Digital Input
SMPS Switched Mode Power Supply
AC Alternating current
DC Direct current
PLC Programmable Logic Controller
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 9 of 123
1.GETTING STARTED
1.1.About the User Guide
The version number of the manual and the corresponding firmware version can be seen on
the front page of this document.
To verify which firmware version a given controller is running, consult the view menu on
the controller in question by doing the following:
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 10 of 123
1.2.Panel Overview
The following illustrations are just panel layout examples. Please refer to your
project drawings for more specific information.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 11 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 12 of 123
WARNING!
The controller panels and associated equipment were checked before delivery according to
our prescribed tests and inspection schemes. In order to maintain their status and secure
safe operation, the user must consider the notes and warning notes, which are given
hereafter.
The panels shall be operated by trained peopleonly. Maintenance and repair shall be
executed only by trained, technical people, who are familiar with the associated dangers.
The panels can be operated without impairment of its security within the certified
environment condition.
This equipment is sensitive to electrostatic discharge, which can cause internal damage
and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge static potential.
• Wear an approved grounding wrist-strap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Store the equipment in appropriate anti-static safe packaging when not in use.
2.1.3. Assembly
The place of assembly has to correspond to the class of protection. The ambient
temperature in the Installation position may not exceed the admissible temperature for
the nominal use, specified in the data sheet. The devices shall be installed only outside of
explosion hazardous areas!
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 13 of 123
The device is to be examined for damages by inappropriate handling with feed and
Storage. If the device indicates damage, so that safe operation is not possible, then the
device may be taken not in operation.
Carefully unpack the system. Open door and Inspect the cabinet, door, printed circuit
board and other components for the possibility of shipping damage. It is recommended
that the cabinet stored in a clean dry area until mounting takes place.
Few field wiring connections are made to the terminal blocks, located along the edges of
the PCBs. Remaining wiring connections are made to the external terminal blocks i.e.
Outside the PCBs.
All field wires should enter the cabinet through glands only. The cable should enter into
cabinet from underneath to avoid the penetration of water or condensation; do not lead
cables in through the top of the cabinet. Gland Plate orientation need to be mounted with
Glands projecting outside panel. DIN plug on valves should be mounted with Gland facing
downward.
The Protective Earth connection in the panel must be connected to Field Earth only.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 14 of 123
EN 61010-1:2010
Low Voltage Directives
EN 60204-1:2006
EC Directive
UL 508A (E466549)
UL Standards UL 61010-2-201, UL 61010-1-
(E466547)
EN: EuropaischenNormen
EMC: Electromagnetic Compatibility
UL: Underwriters Laboratory
CSA: Canadian Standards Association
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 15 of 123
A
Hopper Controller
B
120 ohm End
termination
Sheild Resistor
Note 2: For MODBUS communication to CCS via Anybus module, the end termination
enabled by the same way as stated above in the Master Controller.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 16 of 123
Hopper Panel
Power supply
Female connectors
Communication
Female
connectors
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 17 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 18 of 123
All of the slaves can be connected to Master Cabinet via Filter bus.
Connections are made with 2 wire Modbus shielded cable.
Connection Topology is daisy-chain.
Connection of the cable shield to the Protective Earth should be made only at
Master.
Multiple connections of shield to protective Earth should be avoided.
Line Termination Resistor (120 ohms, 1 Watt) should be enabled at the last device.
Use the Jumper near X2.1 connector
Note: After powering on the Master Controller it scans for connected slave panels. That is
shown graphically on the master display. Each slave is shown as a squared symbol with its
NODE number. It displays like a white box if a slave communicates with the master. If a
slave is not communicating with the master, the squared symbol is displayed as a black
box.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 19 of 123
For Valve Controllers in SPC use Hand Held User Interface or Use Smart Tool software
connected by RS232 Cable
Go to “Manifold Pressure scale settings” menu and change the pressure scale as
per the sensor/transmitter specification.” Once this is done, ensure the Manifold
Pressure shown is correct. This is Not required if pressure switch is used.
Go to “Test Mode” and start testing individual outputs. If valve is not connected,
“WIR-BRK” is shown & if any short circuit is present “SHORT” is shown. If output
function properly, “Normal” is displayed.
Go to “Status Page” and check the Outlet damper feedback signals by giving OPEN
and Close commands
Also ensure Isolation Valve is open after power on.
For Valve Controller Menu Path, please refer the Valve Controller Menu Structure
For Using Smarttool, please refer the Smart Tool Manual.
Go to Test mode, Select Inlet Damper Number and select the action OPEN or
CLOSE.
Go to “Status Page” and check the following (Refer Hopper Controller Menu)
• Hopper level switch signals.
• Inlet damper feedback signals.
• Hopper temperature signals.
During the pre-installation tests, it is IMPORTANT to check that none of the connected
outputs are faulty. Any discrepancy may be due to short-circuited or interrupted outputs.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 20 of 123
3. OVERVIEW
SPC is an advanced microprocessor based filter cleaning system for filter. SPC features an
easy to use menu through a graphic LCD and Menu Keys. SPC also features a tri-colour
LEDs to show the system status.SPC can also be remotely controlled.
A SPC System consists of one SPC Master Controller, one SPC Valve Controller for each
manifold and one or more Hopper Controller(s).
Note: A valve panel can have more than one Valve Controller installed
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 21 of 123
Note: One or more valve controllers are placed inside one valve panel.
Note: Purge valve outputs can be increased to 32 purge valve outputs by using one
additional Valve Add-on.
Note: 2 outlet dampers can be connected in one manifold.
Note: All outputs have wire break and shortcut monitoring
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 22 of 123
4. BASIC FUNCTION
1
7 3
6 5 4
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 23 of 123
Item In Valve
In Master In Hopper Controller
# Controller
1 Display Window Display Window Display Window
Menu Keys (Up, Menu Keys (Up,
Menu Keys (Up, Down, Left,
2 Down, Left, Right, Down, Left, Right,
Right, Enter, Escape)
Enter, Escape) Enter, Escape)
Filter State
Green - Valve
Indicator Heater ON Indicator
3 Controller Local
Green - Run Green – Run
Cleaning
Red – Stop
Stop Key – Local Stop Key – Local
4 Stop Key – Heater stop
Filter Stop Cleaning stop
Start Key – Local Start Key – Local
5 Start Key – Heater Run
Filter Run Cleaning Run
Function Key Function Key
Function Key
6 Toggle Local / Toggle Local /
Toggle Local / Remote
Remote Remote
Mode Indicator Mode Indicator Mode Indicator
7 ON-Local ON-Local ON-Local
OFF-Remote OFF-Remote OFF-Remote
Fault Indicator Fault Indicator Fault Indicator
From Bottom to From Bottom to From Bottom to Top
Top Top 18 Communication Fault -
18 CCR Bus Rx Tx 18 Communication Both Filter Bus and Add on
17 Filter bus Rx Tx Fault - 17 Manifold Pressure Fault
16 Alarm List Full Both Filter Bus and indicator
15 Hardware Add on 16 Isolation Valve Fault
14 Panel in Local 17 Manifold 15 Outlet Damper Fault
13 Hopper Heater Pressure Fault 01-14 Purge Valve Fault
12 Dust indicator Fault Indicator
11 Level 16 Isolation Valve From Bottom to Top
10Temperature Fault 18 Communication Fault
09 Inlet damper 15 Outlet Damper - Both Filter Bus and
08 Outlet damper Fault Add on
07 Manifold 01-14 Purge Valve 17 Temperature Fault
8
06 System Fault 09-16 Inlet Damper
pressure Fault Indicator Fault
05 Differential From Bottom to 01-08 Level Fault
pressure Top
04 Communication 18 Communication
03 Filter Running Fault
02 General fault - Both Filter Bus
01 Controller and
Ready Add on
17 Temperature
Fault
09-16 Inlet
Damper
Fault
01-08 Level Fault
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 24 of 123
6 7 8
2 3 4
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 25 of 123
Item
In Master In Valve Controller In Hopper Controller
#
1 Display window Display window Display window
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 26 of 123
Note:
(#n) – LED for alarm with lower ‘n’ will glow if there are multiple alarms.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 27 of 123
Start and stop of the system can also be done by giving a hardwired input. For this
condition the Master Controller should be in remote mode and also Hardwired should be
enabled in the settings. If hardwired interface is enabled the SPC1691 controller can be
turned ON/OFF remotely from the CCS by making hardwired remote input as a High/Low
and it will not accept the filter start and stop command (Through Modbus) from CCS. This
input however will be ignored if the controller is running in local mode.
The state indicator LED shows the state START–Green and STOP-Red.
Note: According to any PLC program in use, the start command will work only if
the system pressure is correct. In case the system pressure is outside its pre-set
limits the start command is handed over from the PLC to the controller.
Master Controller
When the controller is in local mode the controller ignores commands from the CCS. The
same applies to remote mode – the controller will ignore START/STOP and alarm reset
from the keypad.
Note: From CCS only the mode change command is accepted if the controller is in Local
mode.
Valve Controller
When the Valve Controller is in local mode the user can access test mode to test individual
solenoid valves in the valve controller. In Remote mode user can’t access test mode in
valve controller.
Note: Valve Controller can be accessed through handheld user interface or Smart Tool.
Hopper Controller
When a Hopper Controller is in local mode the controller ignores commands from the
Master Controller, and test mode can be accessed in the local mode only to test individual
inlet damper in hopper.
Note: When Valve or Hopper Controller is in local mode, a general alarm is raised in
Master Controller to indicate that one or more Valve or Hopper Controller is in local mode.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 28 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 29 of 123
Figure 3
Sys Pr.: Displays the real time system pressure (X.X bar) in the main pressure line if the
Master Controller is connected to a 4-20 mA pressure transmitter.
Diff Pr.: Displays the real time Differential air pressure (XX.X mbar) if the Master
Controller is connected to a 4-20 mA differential pressure transmitter.
Messages: 3rd, 4th and 5th lines will display the Possible Faults or Warning Messages.
(Example: System Pressure Faults/ Differential pressure Faults.)
Cleaning Mode: 7th line indicates the present mode in which cleaning is going on –
“Online Cleaning”, “Offline Cleaning”, ”After Cleaning”, “Forced Cleaning”,” Semi offline
Cleaning”. ”Double Purge”
8th Line: Indicates which mode is selected if Remote mode then “R” is displayed else if
local mode is selected then “L” is displayed else if Hardwire interface is selected then “H”
is displayed.
Date and Time: In the bottom right side corner Date and left side corner Time will be
displayed.
Communication Tower: This is used to show the communication strength in the filter
system, according to the number of slave communicating with Master Controller the
number of signal bar will be displayed
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 30 of 123
Press and hold “left and right” keysfor 2 Sec to view all alarm status
Various Alarms are generated in Master, Valve, hopper Controller and most of
them displayed in Masters Alarm Page. Each of the alarm is detailed in menu
section. Wire break & Short Cut alarms which are common to Analog inputs &
Digital Outputs are explained below.
Note: Wire break & Short cut alarm for purge valve will be detected only when it
is activated
What is Wire break:If the wire is broken in analog inputs as well in digital outputs will
generate Wire break alarm and for the analog inputs, if the current value is less than <
3.5mA will also generate the wire break alarm.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 31 of 123
Short cut Alarms for Manifold Pressure Transmitter, Isolation Valve, Purge Valve and
Outlet Damper Solenoids are generated in SPC Valve Controllers.
Short cut Alarms for Inlet Damper Solenoids, PT100 transmitters and Heater are
generated in SPC Hopper Controller.
What is Shortcut: For the digital output, if the output is in permanent “ON” condition
irrespective of the command is called Shortcut fault.
For the analog input, if the current value is exceeded the >23.5mA will generate the
shortcut alarm.
Note: Wire break & Short cut alarm for purge valve will be detected only when it
is activated
Short circuit is a connection between two nodes that forces them to be at the same
voltage. In an ideal short circuit, this means there is no resistance and no voltage drop
across the short. In real circuits, the result is a connection with almost no resistance.
Note:Arrow mark will be shown in the Right corner of LCD if the accessing Screen having
more no of pages or details.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 32 of 123
– Up and Down keys are used to scroll the menu and increment or decrement
the values in the settings
-Left and -Right keys are used to shift the cursor position in the value setting
-Enter Key is used to enter to the menu and to save the selected settings
–Escape key is used to come out of the current menu to the previous menu and return
from the settings without save
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 33 of 123
6.1.1. Settings
Settings
DP HH Alarm
DP H Alarm
DP L Alarm
DP Scale
DP TH High
DP TH Low
SP Scale
Sys Pr HH
Sys Pr H
Sys Pr L
Sys Pr LL
Cmpt Jump
Unit ID
BGC Valves
BGC delay
BGC En/Dis
AFC cycles
Valve jump
Pulse off time
Pulse on time
6.1.2. Service
Service
Cycle Counts:
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 34 of 123
Run Hours:
1 Power ON
Counts the hours when the controller is powered ON
2 Cleaning activated
counts hours when cleaning is activated, irrespective of DP or cleaning cycle in
operation
3 DP cleaning-Low
counts hours when the DP is between DP_TH_LOW and Minimum DP for BGC
cleaning and cleaning is activated
4 DP cleaning - Idle
Counts hours when DP is reached the threshold Low limit and cleaning cycle is not
in operation
5 DP cleaning-Normal
Counts hours when cleaning cycle is in operation and DP is below the threshold
High limit
6 DP cleaning-High
Counts hours when cleaning cycle is in operation and DP is above the threshold High
limit + offset for abnormal DP value (eg. If offset is set to 0.3 and threshold High
limit is 15mbar, this counter works when the DP is greater than 15.3mbar)
7 Forced Cleaning
Counts hours when the Forced cleaning is activated and cleaning cycle is in
operation
8 BGC Cleaning
Counts hours when BGC cleaning is activated and cleaning cycle is in operation
9 Cleaning Cycle in Operation
Counts hours when the Cleaning cycle in operation bit is ON(when purging takes
place).
10 Outside defined cleaning
Counts hours when DP is less than 2mbar(fixed in coding) and forced cleaning is not
activated
6.1.3. Version
Version
Master Controller
Version
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 35 of 123
In Menu go to “Main Menu > View > Alarm & Event Report” to view the last 200 faults
& events occurred.
Note:
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 36 of 123
Communication Related alarms Available in the Alarm page (Refer Section 4.1.1)
From the above image Manifold-1in the Filter not communicating with Master Controller.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 37 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 38 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 39 of 123
Status screen 1
Note: If any of the outputs are disabled, display will show “Not Applicable” for that
output.
Outlet Damper:
Go to “Main Menu > View> Status Report > Outlet Damper” to check the
status for Outlet Damper
Inlet Damper:
Go to “Main Menu > View> Status Report > Inlet Damper” to check the status
for Inlet Damper
Status screen 2
In both OD and ID status will be displayed as given below,
Isolation Valve:
Go to “Main Menu >View>Status Report > Isolation Valve” to check the
status for Isolation Valve
Status screen 3
Isolation valve status will be OPENor CLOSE.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 40 of 123
Level Switch:
Go to “Main Menu > View> Status Report > Level Switch” to check the status
for Level Switch
Status screen 4
Level switch status will be L-low or H-high
Status screen 5
BBD Sensors:
Go to “Main Menu >View>Status Report > BBD Sensors” to check the status for BBD.
Status screen 6
Status screen 7
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 41 of 123
Go to “Main Menu > View> Status Report >Manif. Pressure” to check the status of
the Manifold Pressure
Status screen 8
Note: Use DOWN key to view the next compartment Manifold Pressure
6.2. Field
This Field settings menu used to edit operational values. Thismenu require password to
access. Please refer to the tree structure for various sections of the Field Menu.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 42 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 43 of 123
In Menu go to “Main Menu >Settings & Local Operation >Field >Master Controller”
set the Fabric Clean Master Settings. This Master Setting menu is used to edit Master’s
operational values.
Master Settings contains:
-Control modes
-Pressure settings
-Time settings
-Network settings
-Mode Parameters
In Menu go to “Main Menu >Settings & Local Operation > Field >Master
Controller> Control mode >Cleaning Modes” set the cleaning mode.
Cleaning modes are:
-Online mode
-Forced Cleaning
-After cleaning mode
-Offline mode
-Semi – Offline
-Double Purge
-Single cycle
-Continuous cycle
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 44 of 123
If Single cycle selected then, the cleaning sequence started by Master Controller. It purges
all valves once and automatically stopped. It cannot be stopped using stop key or filter
stop from CCS. Emergency stop can be used to stop the cleaning from CCS.
If Continuous cycle selected then, the cleaning sequence can be started and stopped by
Master Controller. The sequence is like Online cleaning sequence.
Both the cleaning sequences will be started, when differential pressure is higher than
upper threshold limit. Adjacent compartments will be cleaned at the same time.
In Menu go to “Main Menu >Settings & Local Operation > Field >Master
Controller> Control mode > Hard-Wire interface “enable/disable the Hardwired
interface.
Note: Should be enabled only if the Master Controller has the necessary components for
this.
Two Digital Inputs & Five Digital Outputs are present for Hardwired Interface.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 45 of 123
Note: In Hard wired interface Differential Pressure and System pressure values can be
shared to CCS by adding isolator board (optional).
Note: Hardwired interface availability is depends upon the hardware selection and project
specification.
The differential pressure should go above the Differential Pressure high threshold
(in Menu “DP TH Limit”) value for pulsing starts
If pressure falls below the Differential Pressure low threshold (in Menu “DP TL
Limit”) value pulsing will be stopped.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 46 of 123
Pulse ON*
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 47 of 123
*Note: “Pulse ON” settings Go to Main Menu >Settings & Local Operation >
Field> Valve Controller > Time settings> Pulse on Time
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 48 of 123
In Menu go to “Main Menu > Settings & Local Operation > Field >Master
Controller>Mode parameters > Max Close Compart” set the number of maximum
allowed compartment. Below table describe the set value and units.
Note: If the no of compartments closed is equal to the Max Close Cmpt, controller won’t
allow further closing of any compartment or any dampers. Controller withdraws the
command and displays “Close CMD limited”.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 49 of 123
Note: Controller will not allow entering valve jump value more than or equal to
the total no of valve in a compartment.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 50 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 51 of 123
Note: The normal pause time multiplied by number of manifolds is recommended value.
Note: If IV Logic is enabled, then the isolation valve in the manifold will automatically
close whenever the Manifold Pressure is getting low.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 52 of 123
6.2.3. HopperController
In Menu go to “Main Menu >Settings & Local Operation > Field > Hopper
Controller” edit Hopper related operational values.
Hopper Controller contains:
-Heater Control
-Alarm settings
-Temperature scale
-No Communication Delay
-Level SW (switch) per Compartment
Note: During Level High Condition purging in the respective compartment is stopped till
alarm is cleared. This automatic stop can be disabled via menu.
In Master Controller Go to Main Menu >Settings & Local Operation > Field > Master>Mode
parameters>Bypass on Level High
Note: Bypass on Level H is applicable for pyramid type hopper only
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 53 of 123
In Menu go to “Main Menu >Settings & Local Operation > Field > Hopper
Controller>Alarm settings” set the alarm. Below table describe set value range and
units for the Hopper Controller Alarm settings.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 54 of 123
Travel time Travel time is the time a dust cloud use to travel from compartment outlet to
the Dust Transmitters. Based on gas speed, it has to be calculated and entered in each
Manifold.
Sampling Window Peak time Sampling Window Peak time is the time a dust cloud use
to travel from back of the compartment to filter outlet + a safe margin time. The Sampling
Peak time has to be entered in the controller. When the Dust Transmitters detect a peak
dust value, the bag row creating the peak dust is identified, based on travelling time +
Sampling Window Peak Time. A BBD alarm is given with Valve Number for the bag row
that has been calculated to give the Dust Peak. The SPC can be configured to By Pass the
bag row with a Broken Bag, as default this function is Disabled.
Note: It is expected Manifolds are cleaned in the order 1, 2...6.
Warning!!!!
The BBD alarm detection can give false alarms if Pulse off time between shooting Valves is
shorter than Travel time + Sampling Window PK time
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 55 of 123
-Bypass valves/Manif
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 56 of 123
If a peak dust value is detected, the valve generating the peak can be by passed by
enabling this function. The function is Default disabled and it is recommended to keep the
function Disabled until the system is considered stable. The client can then decide if he will
enable this function.
Warning!!!
If not proper adjusted and stable system, enabling this function can block the whole filter
from cleaning.
Note:
After some years of bag wear the alarm limits might need to be adjusted.
Select the Compartment number (1 to 24) and then select the state of the damper
(Open/Close).
The Outlet Damper operation is controlled by operator through the above menu or through
command from CCS.
If the outlet dampers per manifold are ‘2’ then refer the following instruction.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 57 of 123
In option “Cn_Damper” Select the compartment number (1 to 24) with the damper
number and then select the state (Open/Close) in “Action”.
Exception:
Automatic Open and Close of Outlet Damper will be done by Master in off line & semi
offline mode only.
Select the Inlet damper number (1 to 99) and then select the state of the damper
(Open/Close).
The Inlet Damper operation is controlled by operator through the above menu or through
command from CCS.
Exception:
Automatic Open and Close of Inlet Damper will be done by Master in Offline mode only.
Note:
When Inlet or Outlet damper is open/close, master waits for the limit switch feedback
before accepting next command. “Busy” message is displayed in Master.
Note:
If Inlet damper or all Outlet dampers of a compartment is closed that compartment is
considered closed. Master Controller will monitor the number of closed compartments &
checks with the maximum allowed setting. If the value exceeds, no more compartment
will be closed. Warning message is displayed in Master.
Damper command:
Wire break (or) Shortcut alarm will not affect the close state of the damper, Master hold
the close command until it gets the Open command from User
Feedback related alarms also not affect the Close command from Master
Damper Alarms:
Any alarms which is related to damper will be cleared when alarm reset is given from
Master
Select the Compartment number (1 to 99) and Isolation valve number then select the
state of the isolation, either Open (or) Close.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 58 of 123
The Isolation Valve Open/Close is controlled by operator through the above menu or
through command from CCS.
Automatic Control of Isolation Valve:
Isolation valve will close if manifold pressure is lower than regain% of Manifold Pressure
before purge. This checking is done after Regain delay after a purge. The Isolation Valve
must be re-opened “manually” by Operator command.
Example for Pressure Transmitter:
If regain% is 50,
If manifold pressure is 3.0 bar before purge &10sec after a purge if manifold pressure is
1.6bar then isolation valve will NOT close
If manifold pressure is 3.0 bar before purge &10sec after a purge if manifold pressure is
1.4bar then isolation valve will close.
Note: Manifold fill Time is the delay after the Isolation Valve is opened to allow the
Manifold Pressure to build. This happens during powering on or after the Isolation Valve
unlock
Note: If Low system Pressure Alarm exists then automatic isolation valve close will NOT
happen.
Note: If isolation valve control is override, then automatic isolation valve close will NOT
happen. Isolation valve control can be override from CCS command.
IV Open All:
In Menu, go to “Main Menu > Settings & Local Operation > Local operation
>Isolation valve >IV Open all” and open all isolation valves.
In Menu go to “Main Menu > Settings & Local Operation > Local operation > Purge
valve > Purge valve individual”
Select the Compartment number (1 to 24) & Valve number and then press enter to
test the solenoids in valve controller.
In Menu go to “Main Menu >Settings & Local Operation > Local operation > Purge
valve> Purge valve sequence”
Select the Compartment number (1 to 24) and then press enter to test the solenoids in
valve controller
All the valves in the Compartments are activated one by one in sequence until “ESC”
key is pressed
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 59 of 123
Manifold Pr. (Manifold Pressure): Displays the real time air pressure (XX.X) in the
manifold pressure line if the Valve Controller is connected to a 4-20 mA pressure
transmitter.
In case of Pressure switch High / Low is displayed.
Messages: Possible Faults or Warning Messages that are displayed in decreasing order of
priority.
Cleaning Mode: Indicates the present mode in which cleaning is going on – “Online
Cleaning”, “Offline Cleaning”, ”After Cleaning”, “Forced Cleaning”, “Semi offline cleaning”,
“Double Purge”.
L/R (Local / Remote): Indicates which mode is selected. If Remote mode then an “R”
is displayed else if in local mode an “L” is displayed.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 60 of 123
– Up and Down keys are used to scroll the menu and increment or decrement
the values in the settings
-Left and -Right keys are used to shift the cursor position in the value setting
-Enter Key is used to enter to the menu and to save the selected settings
–Escape key is used to come out of the current menu to the previous menu and
return from the settings without save
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 61 of 123
8.1. View
View menu
- Settings
- Service
- Version
Settings
OD Move time
No of Valves
Valve jump
Pulse ON
N.C. Delay
N.C. Pulse off
Drop Limit
Drop Delay
Regain Limit
Regain Delay
MPr H. Limit
MPr L. Limit
Pr. Scale
Manifold ID
Service
Cycle count Manifold: Count for One Total Manifold Cleaning Cycle
Version
Valve Controller
version
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 62 of 123
This Field settings menu used to edit operational values. This menu required password to
access.
MainMenu
Field Settings
• Valve Jump
• Pressure Settings
♦ Drop Settings
♦ Regain Settings
♦ Manifold Pressure High& Low Settings
♦ Pressure Scale
• Time Settings
♦ Outlet Damper Move Time
♦ Pulse ON Time
♦ No Communication Pulse Off
♦ No Communication Delay
♦ Manifold fill Time
• IV Logic
• BBD Settings
♦ Sampling Window
♦ Alarm value
♦ Travel Time
♦ Minimum Range
♦ Maximum Range
♦ BBD Valve Bypass
♦ Bypass Valve/Manifold
• IV Auto Open Option
Test Mode
• Single Solenoid ON
• Isolation Valve Open
• Outlet Damper Open/Close
• All Solenoid ON
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 63 of 123
8.3.3. OD open/close
In Menu go to “Main Menu >Test Mode > OD Open/close” set the Outlet Damper
Open/Close in the test mode. Below table describe Outlet Damper test.
8.4. Status
In Menu go to “Main Menu > Field Settings > Status“
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 64 of 123
9. HOPPER CONTROLLER
9.1. General Screen
COLUMN 4, 5: Displays the Current state of a Level switch “LO” or “HI” which is
connected to the Hopper Controller.
Note: During Power ON the Hopper controller displays “Add-on No Reply” for 3 sec.
After the communication established with add-on board it displays as shown in the above
image. When the Hopper Add-on board is not Connected/Communicated with Hopper
Controller “Add-on No Reply” message is displayed instead of above screen.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 65 of 123
Press and hold “left and right” keys to view all alarms and status for first level switch
COLUMN 1, 2: Indicates the fault status of Temperature inputs from 1 to 8 (T1 to T8).
“HH”-High High or “LL”-Low Low or “H”-High or “L”-Low or ”WB”-Wire break or“SC”-
Short cut
COLUMN 3, 4: Indicates the fault status of the Level switches from 1 to 8 (L1 to L8).
“H”-Highor “OK”-Normal.
COLUMN 5, 6: Indicates the fault status of damper inputs from 1 to 8 (D1 to D8).
“FO”- Open feedback erroror “FC”-Close feedback error or “WB”- Wire Break or
“SC”- Shortcut or “OK”- Normal.
Press and hold “UP” key to view all alarm status for second level switch
Status
It Displays the Current status of a Level switch “LO” or “HI”, which is connected to the
Hopper Controller.
Alarm
Indicates the fault status of the Level switches from 1 to 8 (L1 to L8).
“H”-High or “OK”-Normal.
Note: Second Level switch is optional. The above screen is displayed only if Second Level
switch is available. Number of Level switches per compartment can be set via menu.
In Hopper Controller Go to Main Menu > Field Settings > Level switch per
compartment
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 66 of 123
– Up and Down keys are used to scroll the menu and increment or decrement
the values in the settings
-Left and -Right keys are used to shift the cursor position in the value setting
-Enter Key is used to enter to the menu and to save the selected settings
–Escape key is used to come out of the current menu to the previous menu and
return from the settings without save
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 67 of 123
View
Temp. HH
Temp. H
Temp. LL
Temp. L
No of ID
Level H
Damper Time
Heater On <
Heater Off >
No comm. Time
Level Switch/Cmpt
Temp. Scale
No of Heater
Unit ID
Version No
This Field settings menu used to edit operational values. This menu required password to
access.
Field Settings
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 68 of 123
11. Troubleshooting
EFFECT POSSIBLE CAUSE CORRECTIVE ACTION
Turn On Power &Check
Loss of mains voltage
connections on power supply
No Operation, input terminals
No Display, LED&
MCB tripped
No Response Reset MCB
Fuse blown
Replace Fuse
Check the wire connection for the
filter bus, whether A&B swapped.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 69 of 123
Note: Before taking any corrective action please refer to “Alarm and Event Report” in
the Master Controller to find the possible cause
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 70 of 123
APPENDIX
Smart Tool
HMI
Port
Interface
board
Programming
Port (ISP)
Hardwired
Remote
Input 2
24V DC (+)
5V DC (+)
No Connection
0V DC
Relay
Anybus Outputs Filter bus
Communication Communication
Port Port
Hardwired
Remote Input 1
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 71 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 72 of 123
PIN
DETAILS
NO
1 +24 V DC INPUT POWER SUPPLY
2 +5V DC INPUT POWER SUPPLY
3 NC
4 -24 V DC INPUT POWER SUPPLY
5 RS485 COMMUNICATION1 A
6 RS485 COMMUNICATION1 B
7 RELAY1 INPUT (24V DC)
8 RELAY1 OUTPUT
9 RELAY2 INPUT (24V DC)
10 RELAY2 OUTPUT
11 RELAY3 INPUT (24V DC)
12 RELAY3 OUTPUT
13 RELAY4 INPUT (24V DC)
14 RELAY4 OUTPUT
15 RELAY5 INPUT (24V DC)
16 RELAY5 OUTPUT
17 DIGITAL INPUT1 + (24VDC or AC)
18 DIGITAL INPUT1 - (24VDC or AC)
19 RS485 COMMUNICATION2 A
20 RS485 COMMUNICATION2 B
21 CURRENT INPUT1 LOOP + (24VDC)
22 CURRENT INPUT1 LOOP -
23 CURRENT INPUT2 LOOP + (24VDC)
24 CURRENT INPUT2 LOOP -
25 DIGITAL INPUT2 + (24VDC or AC)
26 DIGITAL INPUT2 - (24VDC or AC)
P2 RS232 COMMUNICATION PORT
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 73 of 123
LCD Screen
Fault
Indicator Menu Keys
(Up, Down,
Left, Right,
Enter,
Escape)
Mode
Indicator
On – Local
Off - Remote
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 74 of 123
Programmin
g Port (ISP)
24 DC (+)
Touch Screen
Port
Anybus
No Connection Filter bus Smart tool
Communication
Port Communication Port
Port
0V DC
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 75 of 123
PIN
DETAILS
NO.
1 +24 V DC INPUTPOWER SUPPLY
2 NC
3 -24 V DC INPUTPOWER SUPPLY
4 RS485 COMMUNICATION1 A
5 RS485 COMMUNICATION1 B
6 RS485 COMMUNICATION2 A
7 RS485 COMMUNICATION2 B
8 RS485 COMMUNICATION2 A Looping to Next Electronic Board
9 RS485 COMMUNICATION2 B Looping to Next Electronic Board
P1 RS232 COMMUNICATION PORT1(For connecting smart tool)
P2 RS232 COMMUNICATION PORT2 (For connecting Touch screen)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 76 of 123
LCD
Menu Keys
(Up,Down,
Left,
Right,Enter,
Escape)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 77 of 123
Programming
Port (ISP)
End
Termination
Switch
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 78 of 123
SPC DO Electronic Board Unit / DO16 DC Electronic Board Unit – Pin Details
PIN
DETAILS
NO
1 +24 V DC INPUTPOWER SUPPLY
2 -24 V DC INPUTPOWER SUPPLY
3 +24 V DC Looping to Next Electronic Board
4 -24 V DC Looping to Next Electronic Board
5 5V DC Looping to Next Electronic Board
6 DC SOLENOID O/P1
7 DC SOLENOID O/P2
8 DC SOLENOID O/P3
9 DC SOLENOID O/P4
10 DC SOLENOID O/P5
11 DC SOLENOID O/P6
12 DC SOLENOID O/P7
13 DC SOLENOID O/P8
14 DC SOLENOID O/P9
15 DC SOLENOID O/P10
16 DC SOLENOID O/P11
17 DC SOLENOID O/P12
18 DC SOLENOID O/P13
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 79 of 123
19 DC SOLENOID O/P14
20 DC SOLENOID O/P15
21 DC SOLENOID O/P16
22 RS485 COMMUNICATION A
23 RS485 COMMUNICATION B
24 RS485 COMMUNICATION A Looping to Next Electronic Board
25 RS485 COMMUNICATION B Looping to Next Electronic Board
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 80 of 123
Programming
Port (ISP)
SW 1SW 2
1 – ON 1 – ON
2 – OFF 2 – OFF
3 – ON 3 – OFF SW 1
4 – OFF 4 – ON
SW 2
End
Termination
Switch
Communication Port
Power Supply 24V
DC
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 81 of 123
SPC DO Electronic Board Unit / DO16 AC Electronic Board Unit – Pin Details
PIN
DETAILS
NO
1 +24 V DC INPUTPOWER SUPPLY
2 -24 V DC INPUTPOWER SUPPLY
3 +24V DC Looping to Next Electronic Board
4 -24 V DC Looping to Next Electronic Board
5 5V DC Looping to Next Electronic Board
6 230V AC/PHASE(P) INPUT
7 230V AC/NEUTRAL(N) INPUT
8 SOLENOID O/P 1
9 SOLENOID O/P 2
10 SOLENOID O/P 3
11 SOLENOID O/P 4
12 SOLENOID O/P 5
13 SOLENOID O/P 6
14 SOLENOID O/P 7
15 SOLENOID O/P 8
16 SOLENOID O/P 9
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 82 of 123
17 SOLENOID O/P 10
18 SOLENOID O/P 11
19 SOLENOID O/P 12
20 SOLENOID O/P 13
21 SOLENOID O/P 14
22 SOLENOID O/P 15
23 SOLENOID O/P 16
A RS485 COMMUNICATION A
B RS485 COMMUNICATION B
A RS485 COMMUNICATION A Looping to Next Electronic Board
B RS485 COMMUNICATION B Looping to Next Electronic Board
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 83 of 123
Digital
outputs
Programming
Port (ISP)
End Termination
Power supply Switch
24V DC
Communication
Port
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 84 of 123
DO2 Module Electronic Board Unit / DO2 DC Electronic Board Unit - Specification
DO2 Module Electronic Board Unit / DO2 DC Electronic Board Unit – Pin Details
PIN
DETAILS
NO
1 +24 V DC INPUT POWER SUPPLY
2 -24 V DC INPUT POWER SUPPLY
3 RS485 COMMUNICATION A
4 RS485 COMMUNICATION B
5 24VDC SOLENOID OUTPUT 1
6 24VDC SOLENOID OUTPUT 2
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 85 of 123
Programming Port
(ISP)
SW 1 SW 2
SW 1 SW 2
SW 3 SW 4 1 – ON 1 – ON
2 – OFF 2 – OFF
3 – OFF 3 – OFF
4 – ON 4 – ON
SW 3 SW 4
1 – OFF 1 – OFF
2 – ON 2 – ON
3 – OFF 3 – OFF
4 – ON 4 – ON
End
Terminati
on Switch
Solenoid Digital
Communicat
Input Outputs
ion Port
Power Supply
24V DC
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 86 of 123
DO2 Module Electronic Board Unit / DO2 AC Electronic Board Unit - Specification
DO2 Module Electronic Board Unit / DO2 AC Electronic Board Unit – Pin Details
PIN
DETAILS
NO.
1 +24 V DC INPUT POWER SUPPLY
2 -24 V DC INPUT POWER SUPPLY
3 +24 V DC Looping to Next Electronic Board
4 -24 V DC Looping to Next Electronic Board
5 RS485 COMMUNICATION A
6 RS485 COMMUNICATION B
7 RS485 COMMUNICATION A Looping to Next Electronic Board
8 RS485 COMMUNICATION B Looping to Next Electronic Board
9 230V AC/PHASE(P) INPUT
10 230V AC/NEUTRAL(N) INPUT
11 SOLENOID OUTPUT 1
12 SOLENOID OUTPUT 2
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 87 of 123
Programming
Port (ISP)
Communication
Port
Power Supply 24V
DC
Analog Inputs
Digital Inputs
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 88 of 123
PIN
DETAILS
NO
1 +24 V DC INPUT POWER SUPPLY
2 -24 V DC INPUT POWER SUPPLY
3 +24V DC COMMON FOR DIGITAL INPUT
4 DIGITAL INPUT (24VDC)
5 DIGITAL INPUT (24VDC)
6 DIGITAL INPUT (24VDC)
7 DIGITAL INPUT (24VDC)
8 DIGITAL INPUT (24VDC)
9 DIGITAL INPUT (24VDC)
10 DIGITAL INPUT (24VDC)
11 DIGITAL INPUT (24VDC)
12 DIGITAL INPUT (24VDC)
13 DIGITAL INPUT (24VDC)
14 DIGITAL INPUT (24VDC)
15 DIGITAL INPUT (24VDC)
16 DIGITAL INPUT (24VDC)
17 DIGITAL INPUT (24VDC)
18 DIGITAL INPUT (24VDC)
19 DIGITAL INPUT (24VDC)
20 DIGITAL INPUT (24VDC)
21 DIGITAL INPUT (24VDC)
22 DIGITAL INPUT (24VDC)
23 DIGITAL INPUT (24VDC)
24 DIGITAL INPUT (24VDC)
25 DIGITAL INPUT (24VDC)
26 DIGITAL INPUT (24VDC)
27 DIGITAL INPUT (24VDC)
28 DIGITAL INPUT (24VDC)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 89 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 90 of 123
Programming Port
(ISP)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 91 of 123
PIN
DETAILS
NO
1 CURRENTOUTPUT 1LOOP+ (24VDC INPUT)
2 CURRENTOUTPUTLOOP-
3 CURRENTOUTPUT 2 LOOP + (24VDC INPUT)
4 CURRENTOUTPUT 2 LOOP -
5 +24 V DC INPUT POWER SUPPLY
6 -24 V DC INPUTPOWER SUPPLY
7 RS485 COMMUNICATION A
8 RS485 COMMUNICATION B
9 SWITCH
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 92 of 123
Analog
Digital Inputs Inputs
Programming
Port (ISP)
0V DC Communication Port
0V DC Loop to next board
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 93 of 123
PIN
DETAILS
NO
1 CURRENT INPUT1 LOOP -
2 CURRENT INPUT1 LOOP + (24VDC)
3 CURRENT INPUT2 LOOP -
4 CURRENT INPUT2 LOOP + (24VDC)
5 DIGITAL INPUT1 (24VDC)
6 DIGITAL INPUT2 (24VDC)
7 DIGITAL INPUT3 (24VDC)
8 DIGITAL INPUT4 (24VDC)
9 DIGITAL INPUT5 (24VDC)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 94 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 95 of 123
Isolator Input
Isolator Outputs
Programming Port
(ISP)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 96 of 123
PIN
DETAILS
NO.
1 +24 V DC INPUTPOWER SUPPLY
2 -24 V DC INPUTPOWER SUPPLY
3 RS485 COMMUNICATION A
4 RS485 COMMUNICATION B
5 CURRENT OUTPUT1 LOOP + (24VDC INPUT)
6 CURRENT OUTPUT1 LOOP -
7 CURRENT OUTPUT 2 LOOP + (24VDC INPUT)
8 CURRENT OUTPUT 2 LOOP -
9 +24V DC COMMON
10 -24 V DC COMMON
11 CURRENT INPUT1 LOOP
12 NO CONNECTION
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 97 of 123
Analog
Inputs
Digital
Inputs
Programming Port
(ISP)
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 98 of 123
PIN
DETAILS
NO
1 +24 V DC INPUTPOWER SUPPLY
2 -24 V DC INPUTPOWER SUPPLY
3 RS485 COMMUNICATION A
4 RS485 COMMUNICATION B
5 CURRENT INPUT1 LOOP + (24VDC)
6 CURRENT INPUT1 LOOP -
7 CURRENT INPUT2 LOOP + (24VDC)
8 CURRENT INPUT2 LOOP -
9 CURRENT INPUT3 LOOP + (24VDC)
10 CURRENT INPUT3 LOOP -
11 CURRENT INPUT4 LOOP + (24VDC)
12 CURRENT INPUT4 LOOP -
13 +24V DC COMMON FOR DIGITAL INPUT
14 DIGITAL INPUT1 (24VDC)
15 +24V DC COMMON FOR DIGITAL INPUT
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 99 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 100 of 123
24V AC Input
5VDC Output
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 101 of 123
PIN
DETAILS
NO.
1 24V AC Phase
2 Earth
3 Neutral
4 +5V DC OUTPUT
5 -5V DC OUTPUT
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 102 of 123
Connection Method
20 Pin Connector
26 Pin Connector
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 103 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 104 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 105 of 123
Posi
tion Bit Function Description
15 Close Compartment - 8 Bit=1: To close cmpt 8
2
0 Clean Compartment - 1 Bit=1: To clean cmpt 1
1 Clean Compartment - 2 Bit=1: To clean cmpt 2
2 Clean Compartment - 3 Bit=1: To clean cmpt 3
3 Clean Compartment - 4 Bit=1: To clean cmpt 4
4 Clean Compartment - 5 Bit=1: To clean cmpt 5
5 Clean Compartment - 6 Bit=1: To clean cmpt 6
6 Clean Compartment - 7 Bit=1: To clean cmpt 7
7 Clean Compartment - 8 Bit=1: To clean cmpt 8
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 106 of 123
Posi
tion Bit Function Description
7 Reserved ( Do not Use ) N/A
8 Reserved ( Do not Use ) N/A
9 Reserved ( Do not Use ) N/A
10 Test Function : Compartment No Provide compartment number
Test command selection(0 - No Test,1
- Purge Valve Command,3 - Damper
Test Command ( Refer Note1 ) Control,4 - Isolation Valve)
11
0 Test Function: Inlet Damper 1 Bit=1:To test inlet damper 1
1 Reserved ( Do not Use ) N/A
2 Test Function: Outlet Damper 1 Bit=1:To test outlet damper
3 Test Function: Outlet Damper 2 Bit=1:To test outlet damper 2
Test Function: Damper Direction ( To open any damper bit -0,To close
4 0-Open 1-Close ) any damper bit -1
Test Function: Unlock Isolation
Bit=1:To open isolation valve
5 Valve
Test Function: Unlock All Isolation
Bit=1:To open all isolation valve
6 Valve
7 Reserved ( Do not Use ) N/A
Test Function : Valve Number (
Provide isolation valve number
Refer Note-2 )
12 Reserved ( Do not Use ) N/A
13 Reserved ( Do not Use ) N/A
14 Reserved ( Do not Use ) N/A
*** Note 2
For Isolation Valve Test Consider Valve
Number as Isolation Valve No
For Purge Valve Command-Individual
Consider Valve Number as Purge Valve
No
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 107 of 123
Posi
tion Bit Function Description
0
0 Reserved ( Do not Use ) N/A
1 Watchdog Timer This bit toggles every 3 seconds
2 BGC Cleaning Activated Bit=1:Back ground cleaning activated
3 Semi-Offline Cleaning Activated Bit=1:Semi offline cleaning activated
Double Purge Single Bit=1:Double purge single cleaning
4 cycleActivated activated
Double Purge Continuous cycle Bit=1:Double purge continuous cycle
5 Activated activated
6 Reserved ( Do not Use ) N/A
7 Reserved ( Do not Use ) N/A
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 108 of 123
Posi
tion Bit Function Description
14 Compartment - 7 Closed Bit=1: Cmpt 7 closed
15 Compartment - 8 Closed Bit=1: Cmpt 8 closed
3
0 Cleaning in Compartment - 1 Bit=1: Cleaning in Cmpt 1
1 Cleaning in Compartment - 2 Bit=1: Cleaning in Cmpt 2
2 Cleaning in Compartment - 3 Bit=1: Cleaning in Cmpt 3
3 Cleaning in Compartment - 4 Bit=1: Cleaning in Cmpt 4
4 Cleaning in Compartment - 5 Bit=1: Cleaning in Cmpt 5
5 Cleaning in Compartment - 6 Bit=1: Cleaning in Cmpt 6
6 Cleaning in Compartment - 7 Bit=1: Cleaning in Cmpt 7
7 Cleaning in Compartment - 8 Bit=1: Cleaning in Cmpt 8
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 109 of 123
Posi
tion Bit Function Description
5 Reserved ( Do not Use ) N/A
6 Reserved ( Do not Use ) N/A
7 Reserved ( Do not Use ) N/A
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 110 of 123
Posi
tion Bit Function Description
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 111 of 123
Posi
tion Bit Function Description
13 Dust High( Manifold-1 ) Bit=0: BBD alarm present in Manifold 1
14 Dust High( Manifold-2 ) Bit=0: BBD alarm present in Manifold 2
15 Reserved ( Do not Use ) N/A
Analog Input Card - 1 (Master)
42 DP(Low)
DP live value
DP(High) ( See Note1 )
43 SP(Low)
SP live value
SP(High) ( See Note1 )
44 BBD Average Value(Low)
BBD Average Value(High) (See BBD Average live value
Note1)
45 Reserved ( Do not Use ) N/A
Reserved ( Do not Use ) N/A
Analog Input Card - 2(Hopper -1 )
46 Temperature-1(Low)
Hopper-1 Temp-1 live value
Temperature-1(High)
47 Temperature-2(Low)
Hopper-1 Temp-2 live value
Temperature-2(High)
48 Temperature-3(Low)
Hopper-1 Temp-3 live value
Temperature-3(High)
49 Temperature-4(Low)
Hopper-1 Temp-4 live value
Temperature-4(High)
Analog Input Card - 3(Hopper -1 )
50 Temperature-5(Low)
Hopper-1 Temp-5 live value
Temperature-5(High)
51 Temperature-6(Low)
Hopper-1 Temp-6 live value
Temperature-6(High)
52 Temperature-7(Low)
Hopper-1 Temp-7 live value
Temperature-7(High)
53 Temperature-8(Low)
Hopper-1 Temp-8 live value
Temperature-8(High)
Analog Input Card - 4(Hopper -2 )
54 Temperature-1(Low)
Hopper-2 Temp-1 live value
Temperature-1(High)
55 Temperature-2(Low)
Hopper-2 Temp-2 live value
Temperature-2(High)
56 Temperature-3(Low)
Hopper-2 Temp-3 live value
Temperature-3(High)
57 Temperature-4(Low)
Hopper-2 Temp-4 live value
Temperature-4(High)
Analog Input Card - 5(Hopper -2 )
58 Temperature-5(Low)
Hopper-2 Temp-5 live value
Temperature-5(High)
59 Temperature-6(Low) Hopper-2 Temp-6 live value
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 112 of 123
Posi
tion Bit Function Description
Temperature-6(High)
60 Temperature-7(Low)
Hopper-2 Temp-7 live value
Temperature-7(High)
61 Temperature-8(Low)
Hopper-2 Temp-8 live value
Temperature-8(High)
Analog Input Card -6(BBD Card -1)
62 BBD-1 pA (Low)
BBD-1 pA live value
BBD-1 pA (High) ( See Note1 )
63 BBD-2 pA (Low)
BBD-2 pA live value
BBD-2 pA (High) ( See Note1 )
64 BBD-1 mA (Low)
BBD-1 mA live value
BBD-1 mA (High) ( See Note1 )
65 BBD-2 mA (Low)
BBD-2 mA live value
BBD-2 mA (High) ( See Note1 )
Analog Input Card -7(BBD Card-2 )
66 BBD-3 pA (Low)
BBD-3 pA live value
BBD-3 pA (High) ( See Note1 )
67 Reserved ( Do not Use ) N/A
Reserved ( Do not Use ) N/A
68 BBD-3 mA (Low)
BBD-3 mA live value
BBD-3 mA (High) ( See Note1 )
69 Reserved ( Do not Use ) N/A
Reserved ( Do not Use ) N/A
70 Digital Input Card - 2 ( Hopper-2 )
0 Level Switch - 1 Bit=1: Hopper-2 L1S -1 High
1 Level Switch - 2 Bit=1: Hopper-2 L1S -2 High
2 Level Switch - 3 Bit=1: Hopper-2 L1S -3 High
3 Level Switch - 4 Bit=1: Hopper-2 L1S -4 High
4 Level Switch - 5 Bit=1: Hopper-2 L1S -5 High
5 Level Switch - 6 Bit=1: Hopper-2 L1S -6 High
6 Level Switch - 7 Bit=1: Hopper-2 L1S -7 High
7 Level Switch - 8 Bit=1: Hopper-2 L1S -8 High
Digital Input Card - 1 ( Hopper-1 )
8 Level Switch - 1 Bit=1: Hopper-1 L1S -1 High
9 Level Switch - 2 Bit=1: Hopper-1 L1S -2 High
10 Level Switch - 3 Bit=1: Hopper-1 L1S -3 High
11 Level Switch - 4 Bit=1: Hopper-1 L1S -4 High
12 Level Switch - 5 Bit=1: Hopper-1 L1S -5 High
13 Level Switch - 6 Bit=1: Hopper-1 L1S -6 High
14 Level Switch - 7 Bit=1: Hopper-1 L1S -7 High
15 Level Switch - 8 Bit=1: Hopper-1 L1S -8 High
71 Digital Input Card - 4 ( Hopper-2 )
0 Level Switch - 1 Bit=1: Hopper-2 L2S -1 High
1 Level Switch - 2 Bit=1: Hopper-2 L2S -2 High
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 113 of 123
Posi
tion Bit Function Description
2 Level Switch - 3 Bit=1: Hopper-2 L2S -3 High
3 Level Switch - 4 Bit=1: Hopper-2 L2S -4 High
4 Level Switch - 5 Bit=1: Hopper-2 L2S -5 High
5 Level Switch - 6 Bit=1: Hopper-2 L2S -6 High
6 Level Switch - 7 Bit=1: Hopper-2 L2S -7 High
7 Level Switch - 8 Bit=1: Hopper-2 L2S -8 High
Digital Input Card - 3 ( Hopper-1 )
8 Level Switch - 1 Bit=1: Hopper-1 L2S -1 High
9 Level Switch - 2 Bit=1: Hopper-1 L2S -2 High
10 Level Switch - 3 Bit=1: Hopper-1 L2S -3 High
11 Level Switch - 4 Bit=1: Hopper-1 L2S -4 High
12 Level Switch - 5 Bit=1: Hopper-1 L2S -5 High
13 Level Switch - 6 Bit=1: Hopper-1 L2S -6 High
14 Level Switch - 7 Bit=1: Hopper-1 L2S -7 High
15 Level Switch - 8 Bit=1: Hopper-1 L2S -8 High
72 Digital Input Card - 6 ( Hopper-2 )
0 Heater On Command - 1 Bit=1: Hopper-2 Heater-1 ON
1 Heater On Command - 2 Bit=1: Hopper-2 Heater-2 ON
2 Heater On Command - 3 Bit=1: Hopper-2 Heater-3 ON
3 Heater On Command - 4 Bit=1: Hopper-2 Heater-4 ON
4 Heater On Command - 5 Bit=1: Hopper-2 Heater-5 ON
5 Heater On Command - 6 Bit=1: Hopper-2 Heater-6 ON
6 Heater On Command - 7 Bit=1: Hopper-2 Heater-7 ON
7 Heater On Command - 8 Bit=1: Hopper-2 Heater-8 ON
Digital Input Card - 5 ( Hopper-1 )
8 Heater On Command - 1 Bit=1: Hopper-1 Heater-1 ON
9 Heater On Command - 2 Bit=1: Hopper-1 Heater-2 ON
10 Heater On Command - 3 Bit=1: Hopper-1 Heater-3 ON
11 Heater On Command - 4 Bit=1: Hopper-1 Heater-4 ON
12 Heater On Command - 5 Bit=1: Hopper-1 Heater-5 ON
13 Heater On Command - 6 Bit=1: Hopper-1 Heater-6 ON
14 Heater On Command - 7 Bit=1: Hopper-1 Heater-7 ON
15 Heater On Command - 8 Bit=1: Hopper-1 Heater-8 ON
73 Digital Input Card -8(BBD Card-2 )
0 Reserved ( Do not Use ) N/A
1 Reserved ( Do not Use ) N/A
2 Reserved ( Do not Use ) N/A
3 Reserved ( Do not Use ) N/A
4 Reserved ( Do not Use ) N/A
5 Reserved ( Do not Use ) N/A
6 Reserved ( Do not Use ) N/A
7 Reserved ( Do not Use ) N/A
Digital Input Card -7(BBD Card-1 )
8 Reserved ( Do not Use ) N/A
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 114 of 123
Posi
tion Bit Function Description
9 Reserved ( Do not Use ) N/A
10 Reserved ( Do not Use ) N/A
11 Reserved ( Do not Use ) N/A
12 Reserved ( Do not Use ) N/A
13 Reserved ( Do not Use ) N/A
14 Reserved ( Do not Use ) N/A
15 Reserved ( Do not Use ) N/A
*** Note 1
Actual Diff. Pressure =
Dp(HL)/10.0
Actual System Pressure =
SP(HL)/10.0
Actual BBD value = BBD(HL)/10.0
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 115 of 123
Step 1:Connect your PC (or) Laptop with Anybus module like shown in following image.
Make sure that Anybus module connected properly
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 116 of 123
Step 3: Go to Device manager and note down the port number in which ATEN converter
connected. If any driver problem reported kindly install the driver software which is
supplied with CD.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 117 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 118 of 123
Step 6:Select the Port number in Configuration tool(Port in which the ATEN converter is
connected)
Step 7: Click the connect button to connect with the Anybus module
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 119 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 120 of 123
Step 10:Select the file below the subnetwork & Click the download button to download
the new file.
Then it shows download dialog, after it get completed the file was successfully downloaded
to the module.
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 121 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 122 of 123
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.
SmartPulse® Controller User Manual
[Doc_No]-1.0
Page 123 of 123
17 Revision history
Doc. Revision Date Comments
3.0 05-May-16 • This is the first doc. release for SPC
• It is based on the latest version of User manual 2.0
The information transmitted by this document is the proprietary and confidential property of FLSmidthand may
not be duplicated, disclosed or utilized without written consent from FLSmidth.