ControlLogix - Redundancy Firmware Bundle Revision History
ControlLogix - Redundancy Firmware Bundle Revision History
Sales
Industries
Products Services Support&
& Solutions
Partners
Document ID IN2638
Summary
ControlLogix: Redundancy Firmware Bundle Revision History
Answer
Notes:
Please refer 29511 - Redundancy Module Configuration Tool (RMCT) for the correct
version of Redundancy Module Configuration Tool (RMCT).
All information about modules supported in bundles also applies to conformal
coating options of the same modules if available, including special coating orders.
Every bundle is a tested and supported combination of modules firmware. Any other
firmware combination is not supported and should not be used.
For information on versions that are Sil2 certified, please refer to Logix-CT007.
36.051_kit1
Release Notes attached:1756-Lxx Enhanced Redundancy Bundle_36.051_kit1.pdf
See Release Notes attached below for full description.
If you upgrade to this revision from revision 20.054, no v20 to v36 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v36.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail
35.011_kit3
Release Notes attached: TBD
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
This kit added new 1756-EN4TR firmware, 5.003, to the list of enhanced Ethernet modules firmware.
See Release Notes attached below for full description.
Firmware revision 5.029 is not included in the redundancy system, revision 35.011_kit3
firmware bundle. You must download and install this digitally signed firmware after the
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 2/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
35.011_kit2
Release Notes attached:1756-L8x Redundancy Bundle_35.011_kit2.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
See Release Notes attached below for full description.
Firmware revision 5.029 is not included in the redundancy system, revision 35.011_kit2
firmware bundle. You must download and install this digitally signed firmware after the
redundancy bundle is installed.
35.011_kit1
Release Notes attached:1756-L8x Redundancy Bundle__35.011_kit1.pdf
See Release Notes attached below for full description.
35.052_kit1
Release Notes attached:1756-L7x Redundancy Bundle__35.052_kit1.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 3/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
See Release Notes attached below for full description.
If you upgrade to this revision from revision 20.054, no v20 to v35 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v35.052.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
35.051_kit1
Release Notes attached:1756-L7x Redundant_B_35.051_kit1.pdf
See Release Notes attached below for full description.
If you upgrade to this revision from revision 20.054, no v20 to v35 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v35.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
34.011_kit2
Release Notes attached:1756-L8x Redundancy Bundle__34.011_kit2.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
See Release Notes attached below for full description.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 4/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
34.011_kit1
Release Notes attached:1756-L8x Redundancy Bundle__34.011_kit1.pdf
See Release Notes attached below for full description.
34.052_kit1
Release Notes attached:1756-L7x Redundancy Bundle__34.052_kit1.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
See Release Notes attached below for full description.
If you upgrade to this revision from revision 20.054, no v20 to v34 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v34.052.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 5/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v34 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v34.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
33.015_kit2
Release Notes attached:1756-L8x Redundancy Bundle__33.015_kit2.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
See Release Notes attached below for full description.
33.015 Enhanced_kit1
Release Notes attached 1756-L8x Redundancy Bundle__33.015_kit1.pdf
Corrected anomalies:
PlantPAx® Embedded Instruction PVSD - Returning from Hand While Drive Is Running Results in Running Wrong
Errors on I/O After Redundancy System Update
Online Edits of a Drive Peripheral for a Drive That Does Not Support ADC Can Cause a Controller MNRF
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 6/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
PlantPAx® Embedded Instruction PPID - Instruction Windup Inputs Do Not Affect the Instruction Windup Status B
ControlFLASH and ControlFLASH Plus Prevents Update to V33.011, V33.012, and V34.011 for ControlLogix 5580 XT C
PlantPAx® Embedded Instruction PAIM – Does not pass through all SrcQ values from Inp_SrcQ
PlantPAx® Embedded Instruction PAIM - Instruction Can Cause a Type 1 Code 60 MNRF
See Release Notes attached for full description.
33.012 Enhanced_kit1
Release Notes attached: V33.012_kit1 5580 Redun Release Notes.pdf
Features:
iTRAK 5730: Actual Position of Mover Axis does not match the physical location (TN 1130414)
PVLV outputs incorrectly energize when changing the valve type while online (TN 1130941)
Product Notice 2021-02-002: ControlLogix 5580 Redundancy Unexpected Power-Up Handler Fault
(TN 1130013)
Product Notice 2021-03-002: PlantPAx 5.0 Execution Anomaly with PVLV Instruction (TN 1130523)
Product Notice 2021-04-006 - Compact GuardLogix 5380 and GuardLogix 5580 May Experience a
Major Non-Recoverable Fault / Assert On Power-Up Following Online Deletion of Safety Tags (TN
1131169)
1769-LxxERM: showing UNCONNECTED CIP Axis State to the Kinetix 5300 in Studio 5000 (TN 1130115)
Anomalies associated with PVSD, PMTR, and PPID
Anomaly associated with Safety Signature generation with a Fanuc Robot
Anomaly associated with custom communication drivers showing error code 0x04 or 0x05
Anomaly associated with connecting to a controller with a large ACD file utilizing Phase Manager
SD Card remote access enhancement for all controllers
See Release Notes attached for full description.
Download includes RMCT v8.06.03 (separate install)
Catalog Number Revision
1756-L8xE, 1756- L8xEK, 1756-L8xE-NSE, 1756-L8xEXT,
33.012
1756-L8xEP
1756-EN2T, 1756-EN2TXT, ser. C and before 5.008 or 5.028
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
1756-EN2TP ser. A 11.003
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.003
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.003
1756-RM2, 1756-RM2K, 1756-RM2XT 20.030
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 7/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
-------------------------------------------------------------------------------------------------------------
----------------------------------------------
33.011 Enhanced_kit2
Release Notes attached: V33.011_Kit2 5580 Redun Release Notes.pdf
Corrected anomalies:
SFC routines do not execute properly after power cycle.
Connected Cached Messages Do Not Time Out after Repeated Connection Requests
Controller Does Not Transition to Run Mode after Online Edit of PowerFlex Drive Parameters
Nested SFC with Selection Branch execution on first transition may be incorrect
Online Editing of PowerFlex Drives
SRT (Sort) instruction with a large length can cause the controller to MNRF
...and 3 more
See Release Notes attached for full description.
Download includes RMCT v8.06.03 (separate install)
Catalog Number Revision
1756-L8xE, 1756- L8xEK, 1756-L8xE-NSE, 1756-L8xEXT,
33.011
1756-L8xEP
1756-EN2T, 1756-EN2TXT, ser. C and before 5.008 or 5.028
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
1756-EN2TP ser. A 11.003
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.003
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.003
1756-RM2, 1756-RM2K, 1756-RM2XT 20.030
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
For more information on how to install, configure and use your ControlLogix
redundancy system, see:
ControlLogix Redundancy Modules Installation Instructions, publication 1756-
in087
ControlLogix 5580 Redundant Controller User Manual, publication 1756-um015
ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, publication 1756-rm010
High Availability Systems Reference Manual, publication HIGHAV-rm002
33.011 Enhanced_kit1
Release Notes attached: V33.011_Kit1 5580_Red_Release Note.pdf
Corrected anomalies:
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 8/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010, High Availability Systems Reference Manual ,
Publication HIGHAV-RM002
33.053_kit1
Release Notes attached: 1756-L7X Redundancy Bundle__33.053_kit1.pdf
This release includes security enhancements as a part of our ongoing efforts to improve security. For
information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation Vulnerability Policy.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 9/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
33.052_kit1
Release Notes attached: 1756-L7x Redundant_33.052_kit1_Release Notes.pdf
Improved Product Resiliency for V33.013 and V33.052
See Release Notes attached below for full description.
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
33.051 Enhanced_kit2
Release Notes attached: V33.051_Kit2 1756-L7x Release Notes.pdf
Corrected anomalies:
SFC routines do not execute properly after power cycle.
Connected Cached Messages Do Not Time Out after Repeated Connection Requests
Controller Does Not Transition to Run Mode after Online Edit of PowerFlex Drive Parameters
Nested SFC with Selection Branch execution on first transition may be incorrect
Online Editing of PowerFlex Drives
SRT (Sort) instruction with a large length can cause the controller to MNRF
...and 3 more
See Release Notes attached below for full description.
Download includes RMCT v8.5.1.0 (separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 33.051
1756-CN2, 1756-CN2R, 1756-CN2RXT ser. B 20.022
1756-CN2, 1756-CN2R, 1756-CN2RXT, 1756-CN2RK ser. C 25.006
1756-EN2T, 1756-EN2TXT, ser. C and before 5.008 or 5.028
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 10/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
33.051 Enhanced_kit1
Release Notes attached: V33.051_Kit1 1756-L7x_Release Note.pdf
Corrected anomalies:
SFC routines do not execute properly after power cycle.
Connected Cached Messages Do Not Time Out after Repeated Connection Requests
Controller Does Not Transition to Run Mode after Online Edit of PowerFlex Drive Parameters
Nested SFC with Selection Branch execution on first transition may be incorrect
Online Editing of PowerFlex Drives
SRT (Sort) instruction with a large length can cause the controller to MNRF
...and 3 more
See Release Notes attached for full description.
Downloads includes RMCT v8.5.1.0 (separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 33.051
1756-CN2, 1756-CN2R, 1756-CN2RXT ser. B 20.022
1756-CN2, 1756-CN2R, 1756-CN2RXT, 1756-CN2RK ser. C 25.005
1756-EN2T, 1756-EN2TXT, ser. C and before 5.008 or 5.028
1756-EN2T, 1756-EN2TXT, ser. D 11.002
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.002
1756-EN2TP ser. A 11.002
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.002
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.002
1756-RM2, 1756-RM2K, 1756-RM2XT 20.010
If you upgrade to this revision from revision 20.054, no v20 to v33 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v33.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
32.051 Enhanced_kit3
Release Notes attached: 32.051_Kit3 RN.pdf
Download includes RMCT v8.05.01(separate install)
This release includes security enhancements as a part of our ongoing efforts
to improve security. For information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation
Vulnerability Policy.
Catalog Number Revision
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 11/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v32 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v32.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
32.051 Enhanced_kit2
Release Notes attached: 32_051_Kit2_RN.pdf
Supports1756-ENxT v11.003 which corrected VxWorks Vulnerabilities
and Explicit Protected Mode on 1756 ControlLogix EtherNet/IP Modules with
ControlLogix Redundancy anomalies. See ControlLogix EtherNet/IP Module
Version 11.003 Release Notes.
Supports 1756-CN2, 1756-CN2R ser. C v25.006 which corrected Channel
Faults/Late Clock Lock anomaly. See ControlLogix ControlNet Bridge Module
Version 25.006 Release Notes.
Download includes RMCT v8.05.01(separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 32.051
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.022
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.006
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
1756-EN2TP ser. A 11.003
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.003
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.003
1756-RM2, 1756-RM2K, 1756-RM2XT 20.010
If you upgrade to this revision from revision 20.054, no v20 to v32 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v32.051.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 12/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v32 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v32.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
31.052_kit4
Release Notes attached: 31.052_kit4 RN.pdf
Download includes RMCT v8.05.01(separate install)
This release includes security enhancements as a part of our ongoing efforts
to improve security. For information regarding Rockwell Automation's
vulnerability disclosure process, please reference the Rockwell Automation
Vulnerability Policy.
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 31.052
1756-CN2, 1756-CN2R, 1756-CN2RXT ser
20.022
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.006
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.009 or 5.029
before
1756-EN2T, 1756-EN2TXT, ser. D 11.004
1756-EN2TR ser. B 5.009 or 5.029
1756-EN2TR ser. C 11.004
1756-EN2TP ser. A 11.004
1756-EN2F ser. B 5.009 or 5.029
1756-EN2F ser. C 11.004
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 13/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v31 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v31.052.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
31.052_kit3
Release Notes attached: 31.052_kit3 RN.pdf
Allows RSU (Redundant System Upgrade) from v 30 latest kit to this one
Download includes RMCT v8.05.01(separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 31.052
1756-CN2, 1756-CN2R, 1756-CN2RXT se.r
20.022
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.006
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
1756-EN2TP ser. A 11.003
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.003
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.003
1756-RM2, 1756-RM2K, 1756-RM2XT 20.010
If you upgrade to this revision from revision 20.054, no v20 to v31 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v31.052.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
31.052_kit2
Release Notes attached: 31.052_kit2 RN.pdf
Download includes RMCT v8.05.01(separate install)
Corrected anomalies:
VxWorks Vulnerability ((TN 1088561)
Explicit Protected Mode and Time Synchronization enabled on Ethernet
modules in Redundancy (TN 63189)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 31.052
1756-CN2, 1756-CN2R, 1756-CN2RXT se.r
20.022
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005
1756-CN2RK ser. C
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 14/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v31 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v31.052.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
31.052 Enhanced_kit1
Release Notes attached: 31.052_kit1 RN.pdf
Download includes RMCT v8.05.01(separate install)
Corrected anomaly of v30.051 Redundancy on failed uploads and downloads
and remote controller connection drops.
See Relese Notes attached for full description.
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 31.052
1756-CN2, 1756-CN2R, 1756-CN2RXT se.r
20.022
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 11.001
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.001
1756-EN2TP ser. A 11.001
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.001
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.001
1756-RM2, 1756-RM2K, 1756-RM2XT 20.010
If you upgrade to this revision from revision 20.054, no v20 to v31 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v31.052.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
30.051 Enhanced_kit3
Release Notes attached: 30.051_kit3 RN.pdf
Download includes RMCT v8.05.01(separate install)
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 15/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v30 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v30.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
If a system is at 30.051_kit2, and uses Ethernet modules with firmware revision 11.003
or ControlNet modules with firmware revision 25.006, it is not possible to lock update
to 31.052_kit1 or 31.052_kit2.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
30.051 Enhanced_kit2
Release Notes attached: 30.051_kit2 RN.pdf
Download includes RMCT v8.05.01(separate install)
Corrected anomaly of v 20, 24 Redundancy (Specific Output Modules May
Fail to Update After Switchover) and 2 others - See Release Notes
New feature: Component Change detection
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 30.051
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.006
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 11.003
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 11.003
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 11.003
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 11.003
1756-RM2, 1756-RM2K, 1756-RM2XT 20.010
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 16/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
If you upgrade to this revision from revision 20.054, no v20 to v30 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v30.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
If a system is at 30.051_kit2, and uses Ethernet modules with firmware revision 11.003
or ControlNet modules with firmware revision 25.006, it is not possible to lock update
to 31.052_kit1 or 31.052_kit2.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
30.051 Enhanced_kit1
Release Notes attached: 30.051_kit1 RN.pdf
Download includes RMCT v8.4.1(separate install)
Corrected anomaly of v 20, 24 Redundancy (Specific Output Modules May
Fail to Update After Switchover) and 2 others - See Release Notes
New feature: Component Change detection
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 30.051
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 10.010
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 10.010
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 10.010
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 10.010
1756-RM2, 1756-RM2K, 1756-RM2XT 20.009
If you upgrade to this revision from revision 20.054, no v20 to v30 upgrade directly is
allowed. You must first update to v24.052 or greater in order to update to v30.051.
If you attempt to perform a Redundancy System Update from V24.05x to V30.051 or
later, and you have LINT tags inside a UDT, the Lock for Update will fail.
See more in ControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual, Publication 1756-RM010
24.053 Enhanced_kit1
Release Notes attached: 24.053_kit1 RN.pdf
Download includes RMCT v8.4.1(separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 24.053
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005*
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and 5.008 or 5.028
before
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 17/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
24.052 Enhanced_kit1
Release Notes attached: 24.052_kit1 RN.pdf
Download includes RMCT v8.3.1(separate install)
Catalog Number Revision
1756-L71, -L72, -L73, -L73XT, -L74, -L75 24.052.124
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020.6028
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005.23*
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 10.007.113
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 10.007.217
1756-EN2F ser. B 5.008 or 5.028
1756-EN2F ser. C 10.009
1756-EN2TRXT ser. B 5.028**
1756-EN2TRXT ser. C 10.007
1756-RM2, 1756-RM2XT 20.007.4
20.058 Enhanced_kit2
Release Notes attached below: 1756-RN694P-EN-P
Corrected in v20.022 of 1756-CN2/B, -CN2R/B: Channel faults (Late clock
lock); Assert in File CnetSchedTransmitList.cpp Line 258; Rack-optimized
outputs transition to a non-commanded state. See Release Notes
All firmware in the bundle are .dmk type and require ControlFLASH v 13 or
higher to be used (separate download)
Download includes RMCT v8.4.1.0(separate install)
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 18/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
*There is no v25 of 1756-CN2, 1756-CN2R profile in the RSLogix 5000 v20 project; no Add-
On profile available as well. Use major revision 20 and Compatible electronic keying.
20.058 Enhanced_kit1
Release Notes attached below: 1756-RN694O-EN-P
Corrected Specific Output Modules May Fail to Update After Switchover
anomaly, see Release Notes
All firmware in the bundle are .dmk type and require ControlFLASH v 13 or
higher to be used (separate download)
Download includes RMCT v8.4.1.0(separate install)
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT, -L64, -L65 20.058
1756-L71, -L72, -L73, -L73XT, -L74, -L75 20.058
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005*
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008 or 5.028
before
1756-EN2T, 1756-EN2TXT, ser. D 10.010
1756-EN2TR ser. B 5.008 or 5.028
1756-EN2TR ser. C 10.010
1756-EN2F ser. C 10.010
1756-EN2F ser. B 5.008 or 5.028
1756-EN2TRXT ser. B 5.028
1756-EN2TRXT ser. C 10.010
1756-RM, 1756-RMXT 3.004
1756-RM2, 1756-RM2XT 20.009
*There is no v25 of 1756-CN2, 1756-CN2R profile in the RSLogix 5000 v20 project; no Add-
On profile available as well. Use major revision 20 and Compatible electronic keying.
20.057 Enhanced_kit1
Release Notes attached below: 1756-RN694N-EN-P
Corrected several anomalies, see list in Release Notes
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 19/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
All firmware in the bundle are .dmk type and require ControlFLASH v 13 or
higher to be used (separate download)
Download includes RMCT v8.3.1.0(separate install)
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT, -L64, -L65 20.057
1756-L71, -L72, -L73, -L73XT, -L74, -L75 20.057
1756-CN2, 1756-CN2R, 1756-CN2RXT ser
20.020.6028
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005.23****
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008.*
before
1756-EN2T, 1756-EN2TXT, ser. D 10.007.113***
1756-EN2TR ser. B 5.008.7003*
1756-EN2TR ser. C 10.007.217***
1756-EN2F ser. C 10.009***
1756-EN2F ser. B 5.008.7003*
1756-EN2TRXT ser. B 5.028**
1756-EN2TRXT ser. C 10.007***
1756-RM, 1756-RMXT 3.003.7
1756-RM2, 1756-RM2XT 20.007
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
Note: Once flashed with digitally signed firmware, module cannot revert to regular
firmware
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
***1756-EN2T/D modules do not support firmware revisions prior to 10.006. 1756-
EN2TR/C, 1756-EN2TRXT/C modules do not support firmware revisions prior to 10.007.
1756-EN2F/C modules do not support firmware revisions previous to revision 10.009. Do
not attempt to flash the modules to previous revisions.
****1756-CN2/C, 1756-CN2R/C, 1756-CN2RXT/C, 1756-CN2RK/C modules do not support
firmware revisions previous to revision 25.004. Do not attempt to update the firmware to
earlier revisions.
Note: There is no v25 of 1756-CN2, 1756-CN2R profile in the RSLogix 5000 v20 project; no
Add-On profile available as well. Use major revision 20 and Compatible electronic keying.
20.056 Enhanced_kit1
Release Notes attached below: 1756-RN694L-EN-P
Support using the 1756-CN2/C, 1756-CN2R/C, 1756-CN2RXT/C, 1756-CN2RK/C
modules rev. 25.005
Support using the 1756-EN2F/C modules with firmware rev. 10.009
Download includes RMCT v8.2.1.0(separate install)
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT, -L64, -L65 20.056.115
1756-L71, -L72, -L73, -L73XT, -L74, -L75 20.056.115
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020.6028
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.005.23****
1756-CN2RK ser. C
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 20/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
Note: Once flashed with digitally signed firmware, module cannot revert to regular
firmware
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
***1756-EN2T/D modules do not support firmware revisions prior to 10.006. 1756-
EN2TR/C, 1756-EN2TRXT/C modules do not support firmware revisions prior to 10.007.
1756-EN2F/C modules do not support firmware revisions previous to revision 10.009. Do
not attempt to flash the modules to previous revisions.
****1756-CN2/C, 1756-CN2R/C, 1756-CN2RXT/C, 1756-CN2RK/C modules do not support
firmware revisions previous to revision 25.004. Do not attempt to update the firmware to
earlier revisions.
Note: There is no v25 of 1756-CN2, 1756-CN2R profile in the RSLogix 5000 v20 project; no
Add-On profile available as well. Use major revision 20 and Compatible electronic keying.
20.055 Enhanced_kit4
Release Notes attached below: 1756-RN694J-EN-P
Added support for 1756-CN2/C
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT, -L64, -L65 20.055.112
1756-L71, -L72, -L73, -L73XT, -L74, -L75 20.055.112
1756-L73, 1756-L73XT 20.055.112
1756-CN2, 1756-CN2R, 1756-CN2RXT ser.
20.020.6028
B
1756-CN2, 1756-CN2R, 1756-CN2RXT,
25.004****
1756-CN2RK ser. C
1756-EN2T, 1756-EN2TXT, ser. C and
5.008.7003*
before
1756-EN2T, 1756-EN2TXT, ser. D 10.007***
1756-EN2TR ser. B 5.008.7003*
1756-EN2TR ser. C 10.007***
1756-EN2F ser. B 5.008.7003*
1756-EN2TRXT ser. B 5.028**
1756-RM, 1756-RMXT 3.003.7
1756-RM2, 1756-RM2XT 20.005
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 21/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
Note: Once flashed with digitally signed, module cannot revert to regular firmware
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
***1756-EN2T/D modules do not support firmware revisions prior to 10.006. 1756-
EN2TR/C modules do not support firmware revisions prior to 10.007. Do not attempt to
flash the modules to previous revisions.
****1756-CN2/C, 1756-CN2R/C, 1756-CN2RXT/C, 1756-CN2RK/C modules do not support
firmware revisions previous to revision 25.004. Do not attempt to update the firmware to
earlier revisions.
Note: There is no v25 of 1756-CN2, 1756-CN2R profile in the RSLogix 5000 v20 project; no
Add-On profile available as well. Use major revision 20 and Compatible electronic keying.
20.055 Enhanced_kit3
Release Notes attached below: 1756-RN694I-EN-P
Added support for 1756-EN2TR/C
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT,
20.055.112
-L64, -L65
1756-L71, -L72, -L73, -L73XT,
20.055.112
-L74, -L75
1756-CN2, 1756-CN2R, 1756-
20.020.6028
CN2RXT ser. B
1756-EN2T, 1756-EN2TXT,
5.008.7003*
ser. C and before
1756-EN2T, 1756-EN2TXT,
10.007***
ser. D only
1756-EN2TR ser. B 5.008.7003*
1756-EN2TR ser. C 10.007***
1756-EN2F ser. B 5.008.7003*
1756-EN2TRXT ser. B 5.028**
1756-RM, 1756-RMXT 3.003.7
1756-RM2, 1756-RM2XT 20.004.6
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
Note: Once flashed with digitally signed, module cannot revert to regular firmware
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
***1756-EN2T/D modules do not support firmware revisions prior to 10.006. 1756-
EN2TR/C modules do not support firmware revisions prior to 10.007. Do not attempt to
flash the modules to previous revisions.
20.055 Enhanced_kit2
Release Notes attached below: 1756-RN694H-EN-P
Added support for 1756-EN2T/D, 1756-EN2TXT/D
Catalog Number Revision
1756-L61, -L62, -L63, -L63XT, 20.055.112
-L64, -L65
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 22/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
Note: Once flashed with digitally signed, module cannot revert to regular firmware
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
***1756-EN2T/D modules do not support firmware revisions previous to revision 10.006.
Do not attempt to flash the firmware to previous revisions.
Note: Firmware revision 10.006 is digitally-signed. Module cannot use a regular firmware.
20.055 Enhanced_kit1
Release Notes attached below: 1756-RN694G-EN-P
* These Ethernet modules can also use digitally signed 5.028** firmware with this
redundancy version.
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
Note: Once flashed with digitally signed, module cannot revert to regular firmware
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 23/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
20.055 Enhanced_kit1
Release Notes attached below: 1756-RN694F-EN-P
Corrected Drives ADC controller stuck transitioning to
Run issue (493802 - Logix controllers V20 Drives ADC
(Automatic Drive Configuration) anomalies, PSN 2012-
10-004)
Added support for 1756-EN2TRXT
Catalog Number Revision
1756-L61,-L62,-L63,-L63XT,
20.055.112
L64,-L65
1756-L71,-L72,-L73,-L73XT,-
20.055.112
L74, -L75
1756-CN2, 1756-CN2R, 1756-
20.020.6028
CN2RXT
1756-EN2T, 1756-EN2TR ,
5.008.7003
1756-EN2TXT
1756-EN2TR 5.008.7003
1756-EN2F 5.008.7003
1756-EN2TRXT 5.028**
1756-RM, 1756-RMXT 3.003.7
1756-RM2, 1756-RM2XT 20.004
**Firmware 5.028 is not a part of this bundle; in order to use, it has to be downloaded and
installed separately
Note: Once flashed with digitally signed, module cannot revert to regular firmware
20.054 Enhanced_kit1
Release Notes attached below: 1756-RN694D-EN-P
1756-EN2T, 1756-EN2TR,
5.008.700300
1756-EN2TXT
1756-EN2F 5.008.700300
1756-RM, 1756-RMXT 3.003.7
1756-RM2, 1756-RM2XT 20.004
20.054 Enhanced
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 24/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-EN2T,1756-EN2TR,
5.008.700300
1756-EN2TXT
1756-EN2F 5.008.700300
1756-RM, 1756-RMXT 3.003.7
19.053 Enhanced_kit2
Release Notes attached below: 1756-RN684E-EN-P
1756-CN2,1756-CN2R, 1756-
20.013
CN2RXT ser B
1756-CN2,1756-CN2R, 1756-
25.004**
CN2RXT ser C
19.053 Enhanced_kit1
Release Notes attached below: 1756-RN684D-EN-P
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 25/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-CN2,1756-CN2R, 1756-
20.13
CN2RXT ser B
19.053 Enhanced
1756-EN2T 4.3.501500
1756-EN2TR 4.3.501500
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 26/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
19.052 Enhanced
Release Notes attached below: 1756-RN684A
1756-CN2/B, 1756-CN2R/B,
20.13.501400
1756-CN2RXT/B
1756-EN2T, 1756-EN2TR
4.2.501400
1756-EN2TXT
16.081 Enhanced_kit4
Release Notes attached below: 1756-RN650H-EN-E
* The 1756-EN2T/C (or earlier) modules do not support firmware revision 10.006. Do not
attempt to flash the firmware to revision 10.006.
** The 1756-EN2T/D modules do not support firmware revisions previous to revision
10.006. Do not attempt to flash the firmware to earlier revisions.
Note: Firmware revision 10.006, 10.007 is digitally-signed. Module cannot use a regular
firmware once has a digitally-signed one.
*** The 1756-CN2/C, 1756-CN2R/C, 1756-CN2RXT/C, 1756-CN2RK/C modules do not
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 27/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
support firmware revisions previous to revision 25.004. Do not attempt to update the
firmware to earlier revisions.
16.081 Enhanced_kit3
Release Notes attached below: 1756-RN650G-EN-E
* The 1756-EN2T/C (or earlier) modules do not support firmware revision 10.006. Do not
attempt to flash the firmware to revision 10.006.
** The 1756-EN2T/D modules do not support firmware revisions previous to revision
10.006. Do not attempt to flash the firmware to earlier revisions.
Note: Firmware revision 10.006, 10.007 is digitally-signed. Module cannot use a regular
firmware once has a digitally-signed one.
16.081 Enhanced_kit2
Release Notes attached below: 1756-RN650F-en-e
* The 1756-EN2T/C (or earlier) modules do not support firmware revision 10.006. Do not
attempt to flash the firmware to major revision 10.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 28/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
16.081 Enhanced_kit1
16.081 Enhanced
16.080 Enhanced
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 29/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
16.054 Enhanced
Release Notes attached below: 1756-RN650B
1756-RM/A 2.3.15
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 30/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-ENBT 6.006.4
1756-EWEB 4.016
1756-RM 2.006.87
1757-SRM 5.004.1
16.57 Standard_Aug2012
Release Notes attached below: 1756-RN628L
16.57 Standard
1756-ENBT 4.008
1756-EWEB 4.9.12
1756-RM/A 2.6.87
1757-SRM/A 5.003
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 31/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
16.56 Standard
1756-ENBT 4.8.14
1756-EWEB 4.9.12
1756-RM/A 2.6.87
1757-SRM/A 5.3.41
16.53 Standard
Release Notes attached below: 1756-RN628G
1756-EWEB 4.8.14
1757-SRM 5.1.42
16.50 Standard
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 32/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-ENBT 4.7.19
1756-EWEB 4.8.14
1757-SRM 5.1.42
15.61 Standard
1756-L55Mxx 15.61.1
1756-ENBT 4.4.24
1756-EWEB 4.4.24
1757-SRM 4.6.1
15.60 Standard
Release Notes attached below: 1756-RN628E
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 33/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
15.57/15.56 Standard
Release Notes attached below: 1756-RN628D
15.56 Standard
Release Notes attached below: 1756-RN628C
1756-L55Mxx 15.56.5
1756-EWEB 4.3.2
1757-SRM 4.3.5
13.71 Standard
Release Notes attached below: 1756-RN608F
Must review:
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 34/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
13.70 Standard
13.60 Standard
Release Notes attached below: 1756-RN608D
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 35/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
13.53 Standard
Release Notes attached below: 1756-RN608C
Available for customers upon request as Megabundle for
SIL-2 systems
Must review:
63365 - Product Notice 2009-08-002 - ControlLogix
Redundancy System, Version 13.53 and Later, When
Used with 1757-SRM Modules (200908002)
56914 - Product Notice - ControlLogix Redundancy
System (200811003)
53307 - Service Advisory - 1756-CNB, -CNBR,
ControlLogix ControlNet Interface Modules
(200411002)
NOT for use in 1756-L6x/B revision 1.10 or higher
controllers
Catalog Number Revision
1756-L55Mxx 13.53.30
1756-L61, 1756-L62, 1756-L63 13.53.30
1756-CNB, 1756-CNBR ser D 5.44.30
1756-ENBT 3.3.7
1756-EWEB 2.2.8
1757-SRM 3.37.5
11.72 Standard
1756-L55Mxx 11.72
1756-ENBT 2.3
1757-SRM 3.29
11.71 Standard
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 36/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-L55 11.71
1756-ENBT 2.3
1757-SRM 3.29
11.70 Standard
1756-L55Mxx 11.70
1756-ENBT 2.3
1757-SRM 3.29
11.60 Standard
1756-L55Mxx 11.60
1757-SRM 3.25
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 37/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
11.52 Standard
1756-L55 11.52
1757-SRM 3.13
8.90 Standard
1756-L55 8.90
1757-SRM 3.13
8.89 Standard
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 38/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
1756-L55Mxx 8.89
1757-SRM 3.13
8.88 Standard
Release Notes attached below: 1756-RN581G
1757-SRM 3.11
8.85 Standard
Release Notes attached below: 1756-RN582F
1757-SRM 2.15
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 39/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
8.84 Standard
Release Notes attached below: 1756-RN582E
1757-SRM 2.15
8.78 Standard
1756-L55 8.78
1757-SRM 2.15
Attachments
File
1756-RN582Q-EN-E.pdf
File
1756-RN608D-EN-E.pdf
File
1756-RN628D-EN-E.pdf
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 40/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
File
1756-RN582N-EN-E.pdf
File
1756-RN628G-EN-E.pdf
File
1756-RN628J-EN-E.pdf
File
1756-RN612A-EN-E.pdf
File
1756-RN628K-EN-E.pdf
File
1756-RN608F-EN-E.pdf
File
1756-RN650B-EN-E.pdf
File
1756-RN650C-EN-E.pdf
File
1756-RN628F-EN-E.pdf
File
1756-RN650D-EN-E.pdf
File
1756-RN668A-EN-E.pdf
File
1756-RN582G-EN-E.pdf
File
1756-RN628E-EN-E.pdf
File
1756-RN582E-EN-E.pdf
File
1756-RN582F-EN-E.pdf
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 41/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
File
1756-RN582I-EN-E.pdf
File
1756-RN582O-EN-E.pdf
File
1756-RN582P-EN-E.pdf
File
1756-RN608E-EN-E.pdf
File
1756-RN684B-EN-P.pdf
File
1756-RN694A-EN-P.pdf
File
1756-RN628M-EN-E.pdf
File
1756-RN694C-EN-P.pdf
File
1756-RN694B-EN-P.pdf
File
1756-RN684A-EN-P.pdf
File
1756-RN684C-EN-P.pdf
File
1756-RN684D-EN-P.pdf
File
1756-RN650E-EN-E.pdf
File
1756-RN628C-EN-E.pdf
File
1756-RN608C-EN-E.pdf
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 42/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
File
1756-RN582K-EN-E.pdf
File
1756-RN694D-EN-P.pdf
File
1756-RN694F-EN-P.pdf
File
1756-RN694G-EN-P.pdf
File
1756-rn650F-en-e.pdf
File
1756-RN694H-EN-P.pdf
File
1756-RN694I-EN-P.pdf
File
1756-RN650G-EN-E.pdf
File
1756-RN694J-EN-P.pdf
File
1756-RN650H-EN-E.pdf
File
1756-RN684E-EN-P.pdf
File
1756-RN694L-EN-P.pdf
File
1756-RN608C.pdf
File
1756-RN694N-EN-P.pdf
File
24.052_kit1 RN.pdf
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 43/45
7/3/24, 15:06 ControlLogix: Redundancy Firmware Bundle Revision History
File
30.051_kit1 RN.pdf
File
1756-RN694O-EN-P.pdf
File
24.053_kit1 RN.pdf
File
1756-RN694P-EN-P.pdf
File
31.052_kit1 RN.pdf
File
32.051_kit1 RN.pdf
File
31.052_kit2 RN.pdf
Answer IDs
IN18371
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is
not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to constitute
application, design, software or other professional engineering advice or services. Before making any decision or taking any
action, which might affect your equipment, you should consult a qualified professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF
THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE
DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS
IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT,
INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN
ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE
INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS
FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not
countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/165251/loc/en_US 44/45