KIDDE® Catalog u Power Supplies and Accessories

Technology that saves lives

Remote Booster
Power Supplies
MIRBPS6A, MIRBPS10A
S3424
MEA
476-91-E
Vol.13

7300-1483:
0174

Overview • Cost effective system expansion


The Booster Power Supply (MIRBPS) is a UL 864, 10th Edition • Provides for Genesis and Enhanced Integrity notification ap-
listed power supply. It is a 24 Vdc filtered-regulated, and su- pliance synchronization
pervised unit that can easily be configured to provide additional • Supports coded output operation
notification appliance circuits (NACs) or auxiliary power for Mass • Self-restoring overcurrent protection
Notification/Emergency Communication (MNEC), as well as life
• Multiple signal rates
safety applications.
• Can be cascaded or controlled independently
The MIRBPS contains the circuitry to monitor and charge internal
• Easy field configuration
or external batteries. Its steel enclosure has room for up to two
10 ampere-hour batteries. The MIRBPS has four Class B (convert- • On-board diagnostic LEDs identify wiring or internal faults
ible to two Class A) NACs. These can be activated in one or two • Standard Kidde keyed lockable steel cabinet with removable
groups from the MIRBPS’s unique dual input circuits. door
The MIRBPS is available in 6.5 or 10 ampere models. Each output • 110 and 230 Vac models available
circuit has a capacity of three amperes; total current draw cannot • Accommodates 18 to 12 AWG wire sizes
exceed the unit’s rating. • Optional tamper switch
The MIRBPS meets current UL requirements and is listed under • Dual battery charging rates
the following standards: • Optional earthquake hardening: OSHPD seismic pre-approval
Standard (CCN) Description
UL864 10th ed.ition (UOXX)Fire Alarm Systems
for component Importance Factor 1.5
UL636 (ANET, UEHX7) Holdup Alarm Units and Systems
UL609 (AOTX, AOTX7) Local Burglar Alarm Units and Systems
UL365 (APAW, APAW7) Police Station Connected Burglar Alarm Units and Systems
UL1076 (APOU, APOU7) Proprietary Burglar Alarm System Units
UL1610 (AMCX) Central Station Alarm Unit
ULC-S527 (UOXXC) Control Units, Fire Alarm (Canada)
ULC-S303 (AOTX7) Local Burglar Alarm Units and Systems (Canada)
C22.2 No. 205 Signaling Equipment (Canada)

Standard Features
• Allows for reliable filtered and regulated power to be installed
where needed

Page 1 of 4 D ATA S H E E T K85005-0125


Not to be used for installation purposes. Issue 1.2
Application Dimensions
The MIRBPS provides additional power and circuits for notification
appliances and other 24 Vdc loads. It is listed for indoor dry loca-
tions and can easily be installed where needed. D5
Top View
Fault conditions are indicated on the on-board diagnostic LEDs,
opening the MIRBPS input sense circuit and the trouble relay (if D2 D3
programmed). While this provides indication to the host system,
the MIRBPS can still be activated upon command. A separate AC
Fail contact is available on the MIRBPS circuit board, which can D4
be programmed for trouble or AC Fail. There are seven on-board

Side View
diagnostic LEDs: one for each NAC fault, one for battery fault, one Front View
for ground fault, and one for AC power.
The unique dual-input activation circuits of the MIRBPS can be
activated by any voltage from 6 to 45 VDC (filtered-regulated) or
D1 D6
11 to 33 Vdc (full-wave rectified, unfiltered). The first input circuit

Side View
can be configured to activate 1-4 of the four possible outputs. The
second input circuit can be configured to control circuits 3 and 4. All knockouts
When outputs are configured for auxiliary operation, these circuits for 3/4 in conduit
can be configured to stay on or automatically deactivate 30 sec- (1.9 cm)
onds after AC power is lost. This feature makes these circuits ideal
for door holder applications. The MIRBPS also has a separate 200
mA 24 Vdc output that can be used to power internal activation
modules.
D1 D2 D3 D4 D5 D6
MIRBPS NACs can be configured for a 3-3-3 temporal or continu-
ous output. This makes the MIRBPS ideal for applications requir- 17.0 in 3.5 in 13.0 in 6.5 in 3.375 in 12.0 in
ing signaling rates that are not available from the main system. (43.2 cm) (8.9 cm) (33.0 cm) (16.5 cm) (8.6 cm) (30.4 cm)

In addition to the internally generated signal rates, the MIRBPS


can also be configured to follow the coded signal rate of the main
system NACs. This allows for the seamless expansion of existing Wire routing
NACs.
The MIRBPS enclosure has mounting brackets for up to three
Signature modules to the right of the circuit board.

Engineering Specification
Supply, where needed, Kidde MIRBPS Series Booster Power Sup-
plies (MIRBPS) that are interconnected to and supervised by the
main system. The MIRBPS shall function as a stand-alone auxiliary
power supply with its own fully-supervised battery compliment.
The MIRBPS battery compliment shall be sized to match the
requirements of the main system. The MIRBPS shall be capable
of supervising and charging batteries having the capacity of 24
ampere-hours for Mass Notification/Emergency Communication
(MNEC) and life safety applications.
<<The MIRBPS shall be capable of installation for a seismic com-
ponent Importance Factor of 1.5.>> The MIRBPS shall provide
a minimum of four independent, fully supervised Class B circuits
that can be field configurable for notification appliance circuits or
auxiliary 24 Vdc power circuits. MIRBPS NACs shall be convertible
to a minimum of two Class A NACs. Each MIRBPS output circuit
shall be rated at 3 amperes at 24 Vdc. Each output circuit shall
be provided with automatically restoring overcurrent protection. Notes
The MIRBPS shall be operable from the main system NAC and/or 1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited
wiring or use type FPL, FPLR, or FPLP cable per NEC.
Kidde Signature Series control modules. MIRBPS NACs shall be [2] Power-limited and supervised when not configured as auxiliary power. Non-
configurable for continuous or 3-3-3 temporal rate. Fault condi- supervised when configured as auxiliary power.
tions on the MIRBPS shall not impede operation of main system [3] Source must be power-limited. Source determines supervision.
NAC. The MIRBPS shall be provided with ground fault detection 4. When using larger batteries, make sure to position the battery terminals towards
circuitry and a separate AC fail relay. the door.

Page 2 of 4 D ATA S H E E T K85005-0125


Not to be used for installation purposes. Issue 1.2
Typical Wiring
To next signaling
Single or cascaded booster NAC Circuit
NAC Circuit
device, booster, or
anywhere on a notification appliance circuit EOL resistor

Sense 1 Input

Sense 2 Input
NAC output #1
Existing NAC end-of-line resistors are not required to be Fire Alarm NAC output #2
installed at the booster’s terminals. This allows multiple Control Panel NAC output #3
boosters to be driven from a single NAC circuit without the NAC output #4
need for special configurations.
Booster Power
Supply

Configuring the Booster for Multiple CC1(S) modules using the


AC Power Fail delay operation* MIRBPS’s sense inputs

Notification appliance circuit (NAC) Notification appliance circuit (NAC)


TB1 TB1
+

NAC1/
+

NAC1/ UL listed UL listed


AUX1 EOL 15 kÙ AUX1 EOL 15 KW
NAC2/
+

NAC2/
Notification appliance circuit (NAC) AUX2 Notification appliance circuit (NAC)
AUX2
UL listed
+

UL listed
+

NAC3/ NAC3/
AUX3 EOL 15 kÙ AUX3 EOL 15 KW
+

NAC4/ NAC4/
AUX4 AUX4
+

200 mA AUX 200 mA AUX


TB5

TB5

Continuous Continuous
+

IN IN
Sense 1 COM Sense 1 COM
OUT + OUT EOL 47 K
+

IN IN
Sense 2 COM EOL 47 kÙ 10 9 Sense 2 COM
OUT OUT EOL 47 K
CC1(S) module [1][3]
NO NO + +
Trouble COM 8765 4 321 Trouble COM
10 9 10 9
NC NC
TB2
+ + +
TB2 CC1(S) module CC1(S) module
Data in from Data out to 8765 4 321 8765 4 321
CT1 previous device
module [4] next device
or Signature [1] [1]
+ + + +
controller

Data in from previous + + *The Booster supports AC Power fail delay [3]
Data out to of three hours via its trouble contact when
device or Signature
next device dip switch SW2-6 is on. All other troubles
controller
are reported to supervising module or panel
without delay via Sense inputs.

Page 3 of 4 D ATA S H E E T K85005-0125


Not to be used for installation purposes. Issue 1.2
Specifications
Model 6.5 amp Booster 10 amp Booster
120VAC or 220-240VAC 50/60Hz 120VAC or 220-240VAC 50/60Hz
AC Line Voltage
390 watts 580 watts
Notification Appliance 3.0A max. per circuit @ 24Vdc 3.0A max. per circuit @ 24Vdc
Circuit Ratings nominal 6.5A max total all NACs nominal 10A max total all NACs
Technology that saves lives Trouble Relay 2 Amps @ 30Vdc
Four configurable outputs replace NACs 1, 2, 3 or 4. as auxiliary
Auxiliary Outputs
Contact us outputs and 200 mA dedicated auxiliary. (See note 1.)
Phone: 888.244.9979 (Option 4) Input Current
3mA @ 12Vdc, 6mA @ 24Vdc
Email: [email protected] (from an existing NAC)
Website: kidde-esfire.com Booster Internal 70mA + 35 mA for each circuit set to AUX
Kidde is a Carrier brand. Supervisory Current
8985 Town Center Pkwy, Booster Internal Alarm 270mA
Bradenton, FL 34202 Current
Signature Mounting
© 2021 Carrier Accomodates three two-gang modules.
All rights reserved.
Space
10 Amp Hours (2 of 12V10A) in cabinet up to 24 Amp hours with
Maximum Battery Size
external battery cabinet for fire applications.

Terminal Wire Gauge 18-12 AWG


Relative Humidity 0 to 93% non condensing @ 32°C
Temperature Rating 32° to 120°F (0° to 49°C)
NAC Wiring Styles Class A or Class B
Continuous, 3-3-3 temporal,
Output Signal Rates
or follow installed panel’s NAC.
Ground Fault Detection Enable or Disable via jumper
Agency Listings UL, ULC, CSFM
1. Maximum of 8 Amps can be used for auxiliary output.

Ordering Information
Catalog Number Description Shipping Wt.
lb (kg)
MIRBPS6A 6.5 Amp Booster Power Supply 13 ( 5.9)
MIRBPS6AC 6.5 Amp Booster Power Supply (ULC) 13 ( 5.9)
MIRBPS6A/230 6.5 Amp Booster Power Supply (220V) 13 ( 5.9)
MIRBPS10A 10 Amp Booster Power Supply 13 ( 5.9)
MIRBPS10AC 10 Amp Booster Power Supply (ULC) 13 ( 5.9)
MIRBPS10A/230 10 Amp Booster Power Supply (220V) 13 ( 5.9)

Related Equipment
12V6A5 7.2 Amp Hour Battery, two required 3.4 (1.6)
12V10A 10 Amp Hour Battery, two required 9.5 (4.3)
3-TAMP Tamper switch
BPS-CVR Electronics Protective Cover
BC-1 Battery Cabinet (up to 2 - 40 Amp Hour Batteries) 58 (26.4)
Notes: BC-2 Battery Cabinet (up to 2 - 17 Amp Hour Batteries) 19 (8.6)
1. Requires installation of separate battery BC-1EQ Seismic hardening Kit for BC-1 cabinets. Includes battery hard-
cabinet. ening order BC-1 enclosure separately.
2. For earthquake anchorage, including BPSEQ Seismic kit for MIRBPS6A or MIRBPS10 Booster Power Sup-
detailed mounting weights and center of plies. See note 2.
gravity detail, please refer to Seismic Ap-
plication Guide 3101987-EN. Approval of 12V17A 18 Amp Hour Battery, two required (see note 1) 13 ( 5.9)
panel anchorage to site structure may re- 12V24A 24 Amp Hour Battery, two required (see note 1) 20 (9.07)
quire local AHJ, structural, or civil engineer
review.
03/31/21

Page 4 of 4 D ATA S H E E T K85005-0125


Not to be used for installation purposes. Issue 1.2