6ES72882QR160AA0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Data sheet 6ES7288-2QR16-0AA0

SIMATIC S7-200 SMART, Digital output EM DR16 16 DO, relay 2 A


General information
Product type designation SM DR16, DQ 16x relay/2 A
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 110 mA
from backplane bus 5 V DC, typ. 165 mA
Digital inputs
Number of digital inputs 0
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Digital outputs
Number of digital outputs 16
● in groups of 4
Short-circuit protection No
Switching capacity of the outputs
● with resistive load, max. 2A
● on lamp load, max. 30 W; 30 W with DC, 200 W with AC
Output current
● for signal "1" rated value 2A
● for signal "1" permissible range, max. 2A
Output delay with resistive load
● "0" to "1", max. 10 ms
● "1" to "0", max. 10 ms
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 10 A
Relay outputs
● Number of relay outputs 16
● Rated supply voltage of relay coil L+ (DC) 24 V
— Reverse polarity protection Yes
● Current consumption of relays (coil current of all relays), 150 mA
max.
Switching capacity of contacts
— with inductive load, max. 2A
— on lamp load, max. 30 W
— with resistive load, up to 50 °C, max. 2A
— with resistive load, up to 60 °C, max. 2A
— with resistive load, max. 2A
— Thermal continuous current, max. 2A
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Interrupts/diagnostics/status information
Diagnostics indication LED
● for status of the outputs Yes
Potential separation
Potential separation digital outputs
● between the channels Yes; Relay, dry contact

6ES72882QR160AA0 Subject to change without notice


11/17/2023
Page 1/2 © Copyright Siemens
Isolation
Isolation tested with 500 V AC for 1 minute for input isolation; 1500 V AC for 1 minute for output
isolation
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static Yes; ±4 kV contact discharge (to IEC 801-2/IEC 1000-4-2; ESD), ±8 kV air
electricity acc. to IEC 61000-4-2 discharge (to IEC 801-2/IEC 1000-4-2; ESD)
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 4 kV
Interference immunity against high-frequency electromagnetic fields
● Interference immunity against high-frequency radiation Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz,
acc. to IEC 61000-4-3 50% ED (to IEC 61000-4-3)
— Frequency range of the RF radiation 80 to 1000 MHz, 10 V/m, 1.4 to 2.0 GHz, 3 V/m, 2.0 to 2.7 GHz, 1 V/m(In the
range of 87 MHz to 187 MHz, 174 MHz to 230 MHz and 470 MHz to 790 MHz:
3V/m )
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000- Yes; ±2 kV acc. to IEC 61000-4-4, burst; surge measurements with additional
4-4 protective elements
● Interference immunity on signal cables acc. to IEC 61000- Yes; ±2 kV (to IEC 801-4/IEC 1000-4-4; Burst)
4-4
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to IEC 61000- Yes
4-5
● asymmetric interference ±2 kV acc. to IEC 61000-4-5, surge asymmetric
— Test voltage on supply cables 2 kV
— Test voltage on signal cables >30m 2 kV
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high frequency current feed Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6)
acc. to IEC 61000-4-6
● Interference immunity against high-frequency radiation Yes; 10 V/m, with 80% amplitude modulation at 1 kHz
acc. to IEC 61000-4-6
— Test voltage at 80% amplitude modulation with 1kHz 10 V
in the range 9 kHz to 80 MHz
Emission of radio interference acc. to EN 55 011
● Emission of radio interference Interference emission to EN 50081-2, testing to EN 55011, Class A, Group 1
● Limit class A, for use in industrial areas Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas.
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes; CE marking / EC Declaration of Conformity
Ambient conditions
Free fall
● Fall height, max. 0.3 m
Ambient temperature during operation
● min. 0 °C
● max. 55 °C
● horizontal installation, min. 0 °C
● horizontal installation, max. 55 °C
● vertical installation, min. 0 °C
● vertical installation, max. 45 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Dimensions
Width 45 mm
Height 100 mm
Depth 81 mm
Weights
Weight, approx. 220 g

last modified: 8/23/2023

6ES72882QR160AA0 Subject to change without notice


11/17/2023
Page 2/2 © Copyright Siemens