0124 Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DFC-0124

REACTIVE POWER
CONTROLLER
The DFC-0124 is an advanced, precision 24 step power
factor control and metering device offering unrivalled
internet monitoring capabilities in a standard 144x144mm
panel mount enclosure.
The unit can drive thyristor based solid state contactors for
the precise compensation of fast changing reactive loads.

FEATURES
• User friendly menu system, ease of use
• Easy and fast setup
• Automatically corrects faulty voltage/current connections
• Automatic setup under load
COMMUNICATION PORTS
• MV current measuring version available • Internal GPRS modem
• Adjustable measurement period: 10-100ms
• Internal Ethernet 10/100Mb
• Power factor correction delay as low as 20ms
• RS-485 isolated (Modbus RTU)
• 100 MIPS, 32 bit ARM core microprocessor
• 24-18-12 step output options • RS-232 for external GPRS modem
• All outputs can drive static contactors • USB Host for data recording on flash memory
• All outputs can drive 1-2-3 phase capacitors or reactors • USB Device for PC connection
• Always exact correction with SVC outputs
• 0.5% measurement accuracy, true RMS measurements
• 32 bit power measurements
COMMUNICATIONS
• Operation in low currents (3mA) • Modbus RTU RS-485, 2400-115200 baud
• Ready for remote monitoring through Ethernet and GPRS • Modbus TCP/IP
• Remote control of steps • SNMP
• Remote parameter editing • TCP/IP server
• Automatic geo-positioning through GPRS • TCP/IP client
• Embedded website • UDP
• Long term data recording on USB flash memory • SMTP
• 250 event records with date-time and measurements • SNTP
• Dynamic DNS support
• Independent target COS for the generator
• Embedded website, HTML
• Display of 1-2-3 phased steps on screen
• GSM-SMS sending
• Harmonic distortion display (31 harmonics) • E-mail sending
• Oscilloscope, waveform display • Central Monitoring through IP
• Battery backed-up real time clock
• User configurable display screens
• User configurable relay outputs MEASUREMENTS
• Voltage transformer ratio for MV applications
• Password protected front panel programming • Phase to phase voltages: U12-U23-U31-Uavg
• Reduced panel depth: 69mm • Phase to neutral voltages: V1-V2-V3-Vavg
• Sealed front panel (IP65 with gasket) • Phase currents: I1-I2-I3-In-Iavg-Itot
• Active power: P1-P2-P3-∑P
SVC OUTPUTS • Reactive power: Q1-Q2-Q3-∑Q
• Apparent power: S1-S2-S3-∑S
SVC stands for “Static Var Compensation”.
• Power factor: cos1-cos2-cos3-∑cos
The unit has 3 SVC outputs which are duty cycle
controlled PWMs that control 3 reactors with a • 1...31 Harmonics of any voltage or current
precision of 1000 steps.
Thus the controller is able to supply almost any
required reactive power, enabling matching the exact
required PF, independently from capacitor bank
selection.
o
COMMUNICATION DIAGRAM

INTERNAL GSM MODEM SNMP COMMUNICATION


SMS, e-mail, geo-positioning, central monitoring and The device allows SNMP communication through its
remote parameter edit features are provided through the ethernet port. The MIB file is available at Datakom
internal GSM modem of the controller. Technical Support.

EXTERNAL GSM MODEM DETAILED DATA RECORDING


The external Datakom DKG-090 modem provides SMS, e- The unit records all measured values with the required
mail, geo-positioning, central monitoring and remote period to the USB flash memory placed in the USB Host
parameter edit features. port. The memory capacity is unlimited and detailed data
recording may continue during years.
INTERNAL ETHERNET PORT
RAINBOW PLUS SOFTWARE
The internal 10/100Mbits ethernet port of the controller
provides e-mail, central monitoring, embedded website, The free Rainbow Plus software allows monitoring, control
Modbus TCP/IP, SNMP communication and remote and parameter edit of the device. It works both through
parameter edit features. USB, RS-485 and internet. In case of inaccessible devices
behind firewall, an access path through the central
E-MAIL SENDING monitoring program is also provided.

In case of fault or preprogrammed conditions, the device is


able to send e-mail messages to 3 addresses through both
ethernet and internal / external GSM-modems.

SMS SENDING
In case of fault or in preprogrammed conditions, the device
is able to send SMS messages to a maximum of 4
addresses through internal / external GSM-modems.

MODBUS RTU – MODBUS TCP/IP


The device allows MODBUS RTU communication through
its isolated RS-485 port. The MODBUS TCP/IP
communication is performed through the ethernet port.
EMBEDDED WEBSITE CENTRAL MONITORING
All important information of the device may be monitored An unlimited number of units are monitored though internet
through internet with any web browser. The embedded with the free central monitoring software. The software
website is available through the ethernet port. Thanks to the supports devices with local IP or dynamic IP. This feature is
dynamic DNS support, no static IP is required. provided through both ethernet and GSM modem.
The central monitoring program allows remote control of the
operating mode and the manual control of step outputs for
remote testing purposes.

Central Monitoring on Map


Daily & Monthly Performance

Performance Statistics

Real-time Measurements

Step Monitoring & Remote Control

Smartphone support
Steps
o
INSTALLATION DIAGRAM

o
TECHNICAL SPECIFICATIONS

Power Supply Input: Voltage burden: < 0.1VA per phase


85 to 270V AC Current burden: < 0.5VA per phase
50 - 60Hz nominal (± 10%) Number of step outputs: 24
Power Consumption: < 15 VA Relay Outputs: 5A @ 250V AC
Measurement Input Range: Static Contactor Outputs: 50mA @ 12V DC
Voltage: 5 - 300 V AC (L-N) SVC Outputs: 50mA @ 12V DC
10 - 520 V AC (L-L) Temperature Input: PT100 sensor or switch (optional)
Current: 0.005 - 5.5 A AC Operating Temperature:
Frequency: 30 - 100 Hz -20°C to +70°C (-4 to +176 °F).
Accuracy: Maximum humidity: 95% non-condensing.
Voltage: 0.5%+1digit Degree of Protection: IP 65 (Front with gasket)
Current: 0.5%+1 digit IP 30 (Back)
Frequency: 0.2%+1 digit Enclosure: Non-flammable, ROHS compliant
Power(kW,kVAr): 1.0%+2digit Installation: Flush mounting with rear brackets
Power factor: 0.5%+1digit Dimensions: 164x164x69mm (WxHxD)
Measurement Range: Panel Cutout: 140x140mm
CT range: 5/5A to 10’000/5A Weight: 700 gr
VT range: 0.1/1 to 5000.0/1 EU Directives: Norms of reference:
kW range: 0.1 kW to 6.5MW 2006/95/EC (LVD) EN 61010 (safety)
2004/108/EC (EMC) EN 61326 (EMC)

REV-2