Current Transformer Support Calculation Note R0
Current Transformer Support Calculation Note R0
Current Transformer Support Calculation Note R0
PROJECT:
TITLE:
PROJECT:
TITLE:
TABLE OF CONTENTS
1.0 DATA ........................................................................................................................................................... 3
1.1 MANUFACTURER DATA ......................................................................................................................... 3
1.2 CONDUCTOR PARAMETERS .................................................................................................................. 3
2.0 LOAD CALCULATION .............................................................................................................................. 4
2.1 WIND LOAD CALCULATION: ................................................................................................................. 4
2.3 SHORT-CIRCUIT LOADING ..................................................................................................................... 4
2.4 SEISMIC LOADING.................................................................................................................................... 4
2.5 VERTICAL LOAD AT THE TOP OF THE SUPPORT STRUCTURE ..................................................... 5
2.5.1 WEIGHT OF EQUIPMENT...................................................................................................................... 5
2.5.1 WEIGHT OF CONDUCTOR .................................................................................................................... 5
2.5.1 MAINTANENCE LOAD .......................................................................................................................... 5
3.0 LOAD COMBINATONS FOR RESULTANT TANSVERSE LOAD AT TOP OF SUPPORT ................ 5
3.1 LOADING CASES ....................................................................................................................................... 5
3.1.1 LOAD CASE 1 .......................................................................................................................................... 5
3.1.2 LOAD CASE 2 .......................................................................................................................................... 5
3.2 UNFACTORED LOADS AT TOP OF SUPPORT STRUCTURE ............................................................. 6
3.4 FACTORED LOADS AT TOP OF SUPPORT STRUCTURE ................................................................... 6
4.0 SUPPORT SECTION AND STEEL YIELD STRENGTH.......................................................................... 6
5.0 ULTIMATE BASE SUPPORT REACTIONS FOR FOUNDATION DESIGN ......................................... 7
1|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
2|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
1.0 DATA
1.1 MANUFACTURER DATA
a) Equipment Make: LVB-220W3
b) Equipment Drawing Number:
c) Schematic diagram dimensions of the Equipment
HE = 3.045 m Height of Equipment
HS = 2.50 m Height of Support Structure
HT = 0.665 m Height of Primary terminal from HE
H = 6.210 m Total Structure Height from Top of pedestal
C.G of Equipment = 2.345 m from Base of Equipment
C.G OF Support = 1.250 m Assumed conservatively
Weight of Equipment = 550 kg (Manufacture Drawings)
Weight of Support = 171 kg (Manufacture Drawings)
d) Height of Equipment, HE = 3.045 m (Manufacture Drawings)
e) Height of Primary Terminal, HE+HT = 3.710 m (Manufacture Drawings)
f) Dia. of Equipment = - m (Manufacture Drawings)
g) Equipment height from GL = 6.410 m Foundation 0.2m above F. G
h) Effective back span = 4.0 m
i) Effective front span = 6.0 m
F. G = Finished Grade
3|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
Where;
Z = 0.05 = Seismic Zone Factor:
REF: Earthquake Distribution for construction building code in Tanzania
Morogoro is within zone (Zone 1 = 0.025g and Zone 2 = 0.05g)
4|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
5|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
6|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING
AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM
KINGOLWIRA TO MSAMVU
TANESCO SINOHYDRO CORPORATION LIMITED
7|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Modeling options:
Offset Arms from Pole/Mast: Yes
Offset Braces from Pole/Mast: Yes
Offset Guys from Pole/Mast: Yes
Offset Posts from Pole/Mast: Yes
Offset Strains from Pole/Mast: Yes
Use Alternate Convergence Process: No
Steel poles checked with ASCE/SEI 48-
Steel Pole Stock Length Default Base Shape Tip Base Taper Default Tubes Modulus of Weight Shape Strength Distance Ultimate Ultimate
Property Number Embedded Plate Diameter Diameter Drag Elasticity Density At Check From Trans. Long.
Label Length Coef. Override Override Base Type Tip Load Load
(m) (m) (mm) (mm) (mm/m) (MPa) (N/m^3) (m) (kN) (kN)
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
SUPPORT Current Transformer 2.50 0 No 0 299 299 0 1.2 1 tube 0 0 Calculated 0.000 0.0000 0.0000
Pole Tube Length Thickness Lap Lap Yield Moment Cap. Tube Calculated Tube Top Tube Bot. 1.5x Diam.
Property No. Length Gap Stress Override Weight Taper Diameter Diameter Lap Length
(m) (cm) (m) (mm) (MPa) (kN-m) (N) (mm/m) (cm) (cm) (m)
-----------------------------------------------------------------------------------------------------------------
SUPPORT 1 2.5 0.6 0.000 0.000 235.000 0.000 1063 0.00000 29.90 29.90 0.00
Pole Tip Base X of Y of Z of Inclin. Inclin. Property Attach. Base Embed % Embed C.
Label Joint Joint Base Base Base About X About Y Set Labels Connect Override Override
(m) (m) (m) (deg) (deg) (m)
-------------------------------------------------------------------------------------------------
CT SUPT 0 0 0 0 0 SUPPORT Fixed 0.00 0
8|Page
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Element Joint Joint Rel. Outer Area T-Moment L-Moment D/t W/t Fy Fa ASCE Cap ASCE Cap
Label Label Position Dist. Diam. Inertia Inertia Max. Min. Trans. Long.
(m) (cm) (cm^2) (cm^4) (cm^4) (MPa) (MPa) (kN-m) (kN-m)
------------------------------------------------------------------------------------------------------------------
CT SUPT CT SUPT:t CT SUPT:t Ori 0.00 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:0 Tube 1 End 0.50 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:0 Tube 1 Ori 0.50 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:1 Tube 1 End 1.00 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:1 Tube 1 Ori 1.00 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:2 Tube 1 End 1.50 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:2 Tube 1 Ori 1.50 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:3 Tube 1 End 2.00 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT #CT SUPT:3 Tube 1 Ori 2.00 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
CT SUPT CT SUPT:g CT SUPT:g End 2.50 29.90 55.23 5929.20 5929.20 49.83 0.0 235.00 235.00 93.20 93.20
Clamp Properties:
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Loads from file: c:\users\alex\desktop\substation equipments\support structures for equipment\ct support check\ct support loads.lca
Insulator dead and wind loads are already included in the point loads printed below.
Structure Height Summary (used for calculating wind/ice adjust with height):
Z of ground for wind height adjust 0.00 (m) and structure Z coordinate that will be put on the centerline ground profile in PLS-CADD.
Ground elevation shift 0.00 (m)
Z of ground with shift 0.00 (m)
Z of structure top (highest joint) 2.50 (m)
Structure height 2.50 (m)
Structure height above ground 2.50 (m)
Load Case Dead Wind SF for SF for SF for SF for SF for SF for SF for SF for SF for SF For Point Wind/Ice Trans. Longit. Ice Ice Pole Pole
Description Load Area Steel Poles Wood Conc. Conc. Conc. Guys Non Braces Insuls. Found. Loads Model Wind Wind Thick. Density Deflection Deflection
Factor Factor Tubular Arms Poles Ult. First Zero and Tubular Pressure Pressure Check Limit
and Towers Crack Tens. Cables Arms (Pa) (Pa) (cm) (N/m^3) % or (m)
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
LC 1. Wind + Short Circuit Loading-Unfactored 1.2000 1.0000 1.00000 0.0000 0.0000 0.0000 0.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1 load Wind on All 1128 0 0.000 0.000 % Pole Height 6
LC 2. Wind + Seismic Loading-Unfactored 1.2000 1.0000 1.00000 0.0000 0.0000 0.0000 0.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1 load Wind on All 1128 0 0.000 0.000 % Pole Height 6
LC 3. Wind + Short Circuit Loading-Factored 1.2000 1.0000 1.00000 0.0000 0.0000 0.0000 0.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1 load Wind on All 1466 0 0.000 0.000 % Pole Height 8
LC 4. Wind + Seismic Loading-Factored 1.2000 1.0000 1.00000 0.0000 0.0000 0.0000 0.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1 load Wind on All 1466 0 0.000 0.000 % Pole Height 8
Point Loads for Load Case "LC 1. Wind + Short Circuit Loading-Unfactored":
Point Loads for Load Case "LC 3. Wind + Short Circuit Loading-Factored":
10 | P a g e
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Maximum element usage is 42.10% for Steel Pole "CT SUPT" in load case "LC 3. Wind + Short Circuit Loading-Factored"
Maximum insulator usage is 23.74% for Clamp "11" in load case "LC 3. Wind + Short Circuit Loading-Factored"
Maximum pole deflection usage is 4.17% for "CT SUPT" in load case "LC 1. Wind + Short Circuit Loading-Unfactored"
*** Analysis Results for Load Case No. 1 "LC 1. Wind + Short Circuit Loading-Unfactored" - Number of iterations in SAPS 6
Equilibrium Joint Positions and Rotations for Load Case "LC 1. Wind + Short Circuit Loading-Unfactored":
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-Pos
Label (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
------------------------------------------------------------------------------------------
CT SUPT:g 0 0 0 0.0000 0.0000 0.0000 0 0 0
CT SUPT:t 1.054e-020 0.006259 -2.667e-005 -0.2117 0.0000 0.0000 1.054e-020 0.006259 2.5
Joint Support Reactions for Load Case "LC 1. Wind + Short Circuit Loading-Unfactored":
11 | P a g e
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Detailed Steel Pole Usages for Load Case "LC 1. Wind + Short Circuit Loading-Unfactored":
Element Joint Joint Rel. Trans. Long. Vert. Trans. Mom. Long. Mom. Tors. Axial Tran. Long. P/A M/S. V/Q. T/R. Res. Max. At
Label Label Position Dist. Defl. Defl. Defl. (Local Mx) (Local My) Mom. Force Shear Shear Usage Pt.
(m) (cm) (cm) (cm) (kN-m) (kN-m)(kN-m) (kN) (kN) (kN) (MPa) (MPa) (MPa) (MPa) (MPa) %
-------------------------------------------------------------------------------------------------------------------------------------------------
CT SUPT CT SUPT:t Origin 0.00 0.63 0.00 -0.00 -0.00 -0.00 -0.0 -7.16 13.78 0.00 -1.30 0.00 4.99 0.00 8.74 3.7 1
CT SUPT Tube 1 End 0.50 0.44 0.00 -0.00 6.89 0.00 -0.0 -7.16 13.78 0.00 -1.30 17.37 4.99 0.00 20.57 8.8 1
CT SUPT Tube 1 Origin 0.50 0.44 0.00 -0.00 6.89 0.00 0.0 -7.42 13.98 0.00 -1.34 17.37 5.06 0.00 20.66 8.8 1
CT SUPT Tube 1 End 1.00 0.27 0.00 -0.00 13.88 0.00 0.0 -7.42 13.98 0.00 -1.34 34.99 5.06 0.00 37.38 15.9 1
CT SUPT Tube 1 Origin 1.00 0.27 0.00 -0.00 13.88 0.00 0.0 -7.68 14.18 0.00 -1.39 34.99 5.13 0.00 37.45 15.9 1
CT SUPT Tube 1 End 1.50 0.13 0.00 -0.00 20.97 0.00 0.0 -7.68 14.18 0.00 -1.39 52.87 5.13 0.00 54.98 23.4 1
CT SUPT Tube 1 Origin 1.50 0.13 0.00 -0.00 20.97 0.00 0.0 -7.95 14.37 0.00 -1.44 52.87 5.21 0.00 55.05 23.4 1
CT SUPT Tube 1 End 2.00 0.04 0.00 -0.00 28.15 0.00 0.0 -7.95 14.37 0.00 -1.44 70.99 5.21 0.00 72.98 31.1 1
CT SUPT Tube 1 Origin 2.00 0.04 0.00 -0.00 28.15 0.00 0.0 -8.22 14.57 0.00 -1.49 70.99 5.27 0.00 73.05 31.1 1
CT SUPT CT SUPT:g End 2.50 0.00 0.00 0.00 35.44 0.00 0.0 -8.22 14.57 0.00 -1.49 89.35 5.27 0.00 91.30 38.8 1
Summary of Clamp Capacities and Usages for Load Case "LC 1. Wind + Short Circuit Loading-Unfactored":
*** Analysis Results for Load Case No. 2 "LC 2. Wind + Seismic Loading-Unfactored" - Number of iterations in SAPS 6
Equilibrium Joint Positions and Rotations for Load Case "LC 2. Wind + Seismic Loading-Unfactored":
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-Pos
Label (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
------------------------------------------------------------------------------------------
CT SUPT:g 0 0 0 0.0000 0.0000 0.0000 0 0 0
CT SUPT:t 1.054e-020 0.002049 -1.846e-005 -0.0689 0.0000 0.0000 1.054e-020 0.002049 2.5
Joint Support Reactions for Load Case "LC 2. Wind + Seismic Loading-Unfactored":
Detailed Steel Pole Usages for Load Case "LC 2. Wind + Seismic Loading-Unfactored":
Element Joint Joint Rel. Trans. Long. Vert. Trans. Mom. Long. Mom. Tors. Axial Tran. Long. P/A M/S. V/Q. T/R. Res. Max. At
Label Label Position Dist. Defl. Defl. Defl. (Local Mx) (Local My) Mom. Force Shear Shear Usage Pt.
(m) (cm) (cm) (cm) (kN-m) (kN-m)(kN-m) (kN) (kN) (kN) (MPa) (MPa) (MPa) (MPa) (MPa) %
-------------------------------------------------------------------------------------------------------------------------------------------------
CT SUPT CT SUPT:t Origin 0.00 0.20 0.00 -0.00 -0.00 -0.00 -0.0 -7.20 4.32 0.00 -1.30 0.00 1.56 0.00 3.01 1.3 1
CT SUPT Tube 1 End 0.50 0.15 0.00 -0.00 2.16 0.00 -0.0 -7.20 4.32 0.00 -1.30 5.45 1.56 0.00 7.27 3.1 1
CT SUPT Tube 1 Origin 0.50 0.15 0.00 -0.00 2.16 0.00 0.0 -7.46 4.52 0.00 -1.35 5.45 1.64 0.00 7.36 3.1 1
CT SUPT Tube 1 End 1.00 0.09 0.00 -0.00 4.42 0.00 0.0 -7.46 4.52 0.00 -1.35 11.15 1.64 0.00 12.81 5.5 1
CT SUPT Tube 1 Origin 1.00 0.09 0.00 -0.00 4.42 0.00 0.0 -7.71 4.72 0.00 -1.40 11.15 1.71 0.00 12.89 5.5 1
CT SUPT Tube 1 End 1.50 0.04 0.00 -0.00 6.78 0.00 0.0 -7.71 4.72 0.00 -1.40 17.10 1.71 0.00 18.73 8.0 1
CT SUPT Tube 1 Origin 1.50 0.04 0.00 -0.00 6.78 0.00 0.0 -7.97 4.92 0.00 -1.44 17.10 1.78 0.00 18.80 8.0 1
CT SUPT Tube 1 End 2.00 0.01 0.00 -0.00 9.24 0.00 0.0 -7.97 4.92 0.00 -1.44 23.31 1.78 0.00 24.94 10.6 1
CT SUPT Tube 1 Origin 2.00 0.01 0.00 -0.00 9.24 0.00 0.0 -8.23 5.12 0.00 -1.49 23.31 1.86 0.00 25.00 10.6 1
CT SUPT CT SUPT:g End 2.50 0.00 0.00 0.00 11.81 0.00 0.0 -8.23 5.12 0.00 -1.49 29.77 1.86 0.00 31.42 13.4 1
12 | P a g e
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Summary of Clamp Capacities and Usages for Load Case "LC 2. Wind + Seismic Loading-Unfactored":
*** Analysis Results for Load Case No. 3 "LC 3. Wind + Short Circuit Loading-Factored" - Number of iterations in SAPS 6
Equilibrium Joint Positions and Rotations for Load Case "LC 3. Wind + Short Circuit Loading-Factored":
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-Pos
Label (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
----------------------------------------------------------------------------------------
CT SUPT:g 0 0 0 0.0000 0.0000 0.0000 0 0 0
CT SUPT:t 1.37e-020 0.006771 -2.984e-005 -0.2289 0.0000 0.0000 1.37e-020 0.006771 2.5
Joint Support Reactions for Load Case "LC 3. Wind + Short Circuit Loading-Factored":
Detailed Steel Pole Usages for Load Case "LC 3. Wind + Short Circuit Loading-Factored":
Element Joint Joint Rel. Trans. Long. Vert. Trans. Mom. Long. Mom. Tors. Axial Tran. Long. P/A M/S. V/Q. T/R. Res. Max. At
Label Label Position Dist. Defl. Defl. Defl. (Local Mx) (Local My) Mom. Force Shear Shear Usage Pt.
(m) (cm) (cm) (cm) (kN-m) (kN-m)(kN-m) (kN) (kN) (kN) (MPa) (MPa) (MPa) (MPa) (MPa) %
-------------------------------------------------------------------------------------------------------------------------------------------------
CT SUPT CT SUPT:t Origin 0.00 0.68 0.00 -0.00 -0.00 -0.00 -0.0 -7.86 14.84 0.00 -1.42 0.00 5.38 0.00 9.42 4.0 1
CT SUPT Tube 1 End 0.50 0.48 0.00 -0.00 7.42 0.00 -0.0 -7.86 14.84 0.00 -1.42 18.71 5.38 0.00 22.18 9.4 1
CT SUPT Tube 1 Origin 0.50 0.48 0.00 -0.00 7.42 0.00 0.0 -8.12 15.10 0.00 -1.47 18.71 5.47 0.00 22.30 9.5 1
CT SUPT Tube 1 End 1.00 0.29 0.00 -0.00 14.97 0.00 0.0 -8.12 15.10 0.00 -1.47 37.75 5.47 0.00 40.35 17.2 1
CT SUPT Tube 1 Origin 1.00 0.29 0.00 -0.00 14.97 0.00 0.0 -8.38 15.36 0.00 -1.52 37.75 5.56 0.00 40.44 17.2 1
CT SUPT Tube 1 End 1.50 0.14 0.00 -0.00 22.65 0.00 0.0 -8.38 15.36 0.00 -1.52 57.12 5.56 0.00 59.43 25.3 1
CT SUPT Tube 1 Origin 1.50 0.14 0.00 -0.00 22.65 0.00 0.0 -8.65 15.62 0.00 -1.57 57.12 5.66 0.00 59.50 25.3 1
CT SUPT Tube 1 End 2.00 0.04 0.00 -0.00 30.46 0.00 0.0 -8.65 15.62 0.00 -1.57 76.81 5.66 0.00 78.99 33.6 1
CT SUPT Tube 1 Origin 2.00 0.04 0.00 -0.00 30.46 0.00 0.0 -8.93 15.87 0.00 -1.62 76.81 5.75 0.00 79.06 33.6 1
CT SUPT CT SUPT:g End 2.50 0.00 0.00 0.00 38.40 0.00 0.0 -8.93 15.87 0.00 -1.62 96.82 5.75 0.00 98.94 42.1 1
Summary of Clamp Capacities and Usages for Load Case "LC 3. Wind + Short Circuit Loading-Factored":
*** Analysis Results for Load Case No. 4 "LC 4. Wind + Seismic Loading-Factored" - Number of iterations in SAPS 6
Equilibrium Joint Positions and Rotations for Load Case "LC 4. Wind + Seismic Loading-Factored":
Joint X-Displ Y-Displ Z-Displ X-Rot Y-Rot Z-Rot X-Pos Y-Pos Z-Pos
Label (m) (m) (m) (deg) (deg) (deg) (m) (m) (m)
----------------------------------------------------------------------------------------
CT SUPT:g 0 0 0 0.0000 0.0000 0.0000 0 0 0
CT SUPT:t 1.37e-020 0.002561 -2.061e-005 -0.0860 0.0000 0.0000 1.37e-020 0.002561 2.5
13 | P a g e
Project:
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF EXTENSION FOR
SGR-1 220kV TRANSMISSION LINE FROM KINGOLWIRA TO MSAMVU
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Joint Support Reactions for Load Case "LC 4. Wind + Seismic Loading-Factored":
Detailed Steel Pole Usages for Load Case "LC 4. Wind + Seismic Loading-Factored":
Element Joint Joint Rel. Trans. Long. Vert. Trans. Mom. Long. Mom. Tors. Axial Tran. Long. P/A M/S. V/Q. T/R. Res. Max. At
Label Label Position Dist. Defl. Defl. Defl. (Local Mx) (Local My) Mom. Force Shear Shear Usage Pt.
(m) (cm) (cm) (cm) (kN-m) (kN-m)(kN-m) (kN) (kN) (kN) (MPa) (MPa) (MPa) (MPa) (MPa) %
-------------------------------------------------------------------------------------------------------------------------------------------------
CT SUPT CT SUPT:t Origin 0.00 0.26 0.00 -0.00 -0.00 -0.00 -0.0 -7.91 5.38 0.00 -1.43 0.00 1.95 0.00 3.67 1.6 1
CT SUPT Tube 1 End 0.50 0.18 0.00 -0.00 2.69 0.00 -0.0 -7.91 5.38 0.00 -1.43 6.79 1.95 0.00 8.89 3.8 1
CT SUPT Tube 1 Origin 0.50 0.18 0.00 -0.00 2.69 0.00 0.0 -8.17 5.65 0.00 -1.48 6.79 2.04 0.00 8.99 3.8 1
CT SUPT Tube 1 End 1.00 0.11 0.00 -0.00 5.51 0.00 0.0 -8.17 5.65 0.00 -1.48 13.90 2.04 0.00 15.79 6.7 1
CT SUPT Tube 1 Origin 1.00 0.11 0.00 -0.00 5.51 0.00 0.0 -8.42 5.91 0.00 -1.52 13.90 2.14 0.00 15.87 6.8 1
CT SUPT Tube 1 End 1.50 0.05 0.00 -0.00 8.47 0.00 0.0 -8.42 5.91 0.00 -1.52 21.35 2.14 0.00 23.17 9.9 1
CT SUPT Tube 1 Origin 1.50 0.05 0.00 -0.00 8.47 0.00 0.0 -8.68 6.17 0.00 -1.57 21.35 2.23 0.00 23.25 9.9 1
CT SUPT Tube 1 End 2.00 0.02 0.00 -0.00 11.55 0.00 0.0 -8.68 6.17 0.00 -1.57 29.13 2.23 0.00 30.94 13.2 1
CT SUPT Tube 1 Origin 2.00 0.02 0.00 -0.00 11.55 0.00 0.0 -8.94 6.43 0.00 -1.62 29.13 2.33 0.00 31.01 13.2 1
CT SUPT CT SUPT:g End 2.50 0.00 0.00 0.00 14.76 0.00 0.0 -8.94 6.43 0.00 -1.62 37.23 2.33 0.00 39.06 16.6 1
Summary of Clamp Capacities and Usages for Load Case "LC 4. Wind + Seismic Loading-Factored":
*** Overall summary for all load cases - Usage = Maximum Stress / Allowable Stress
DOCUMENT TITLE: CURRENT TRANSFORMER SUPPORT CALCULATION NOTE PREPARED BY: BAWA ALEX
Pole Load Case Deflection Deflection Height Length Tip Allowable Actual Usage
Label Check Limit Diameter Deflection Deflection
% (m) (m) (cm) (m) (m) %
----------------------------------------------------------------------------------------------------------------------------------
CT SUPT LC 1. Wind + Short Circuit Loading-Unfactored % Pole Height 6.00 2.50 2.50 29.90 0.15 0.01 4.17
CT SUPT LC 2. Wind + Seismic Loading-Unfactored % Pole Height 6.00 2.50 2.50 29.90 0.15 0.00 1.37
CT SUPT LC 3. Wind + Short Circuit Loading-Factored % Pole Height 8.00 2.50 2.50 29.90 0.20 0.01 3.39
CT SUPT LC 4. Wind + Seismic Loading-Factored % Pole Height 8.00 2.50 2.50 29.90 0.20 0.00 1.28
15 | P a g e