PDB - SCAC - Unidades Internas

Download as pdf or txt
Download as pdf or txt
You are on page 1of 150

Single Indoor Unit

Heat pump, R410A

MFL67986347

Region : Brazil
Published on Dec. 26, 2022
Single Indoor Unit
General Information
Model Line Up
Single Indoor Unit General Information

1. Model Line Up
Capacity
Product Chassis Index Model Name
kW
5.3 ATNW18GTLP1
Ceiling Cassette 1-Way TT
7.0 ATNW24GTLP1
5.3 ATNW18GPLP1
TP
7.0 ATNW24GPLP1
Ceiling Cassette 4-Way TN 10.6 ATNW36GNLP1
14.1 ATNW48GMLP1
TM
17.6 ATNW60GMLP1
VM1 10.6 AVNW36GM1P1
Ceiling Suspended 14.1 AVNW48GM2P1
VM2
17.6 AVNW60GM2P1

* The capacity index may differ from actual capacity values.

1
Single Indoor Unit
Product Data
Ceiling Cassette 1-Way
Ceiling Cassette 4-Way
Ceiling Suspended
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TT
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198 ~ 242
Limit Range of Voltage(Case 2) V -
kW 4.69
Cooling Capacity Nominal
Btu/h 16,000
kW 5.28
Heating Capacity Nominal
Btu/h 18,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 13.3 / 11.8 / 10.8
Air Flow Rate Range(Min~Max) m³/min 10.8~13.3
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 30
Output
No. 1
Dehumidification Rate - ℓ/h -
Rows x Columns x FPI - 2 x 12 x 18
No. - 1
Heat Exchanger
Fin Type - Slit(Half)
Face Area m² 0.24
Net(W x H x D) mm 1,180 x 132 x 450
Dimensions
Shipping(W x H x D) mm 1,445 x 252 x 538
Net kg 14.5
Weight
Shipping kg 17.5
Color - White
Exterior
RAL (Classic) - RAL 9003
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) Φ32(1-1/4)/Φ25(31/32)
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 45.0 / 42.0 / 39.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 45.0 / 42.0 / 39.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

1-1
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

1-2
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.2 List of Functions


Category Functions Availability
Air Supply Outlet 1
Airflow Direction Control (left & right) Auto
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) O
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* Advanced
Air Flow
Power Cool/Heat O/X
Swirl Wind* X
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** O
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille X
Human Detection Function*** X
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

1-3
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

1-4
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III) CREMTB100 White O
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II) CREMTB001 White O
Remote Controller PREMTBB01 Black O
PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only X
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only X
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) X
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) X
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m X
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way X
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way O
Air Purification Kit PTAHMP0 For Cassette 4-way X
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.

1-5
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

1-6
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.4 Dimensions
1.4.1 Product_Panel : PT-UTC
DWG No. : TBA35228601_Rev.01
Chassis code : TT

1-7
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
1.4.2 Product_Panel : PT-TAHG0

P
DWG No. : TBA36268301_Rev02
Chassis code : TT

1-8
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
1.4.3 Product_Panel : PT-TPHG0
DWG No. : TBA36268303_Rev03
Chassis code : TT

1-9
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
1.4.4 Install Space

< Minimum Installation Space >

≥ 10(13/32)
Ceiling Ceiling
Ceiling board Indoor unit Ceiling board
Indoor unit Ceiling
Ceiling board
board

≤ 300(11-13/16)
≥ 1000(39-3/8)

Air Outlet
≥ 500(19-11/16) Air Inlet
≥ 500(19-11/16)
A*

≥ 20(25/32)

A*
≥ 1,500(59-1/16)

[Unit:mm(inch)] [Unit:mm(inch)]

Floor Floor

Notes 1. * : A, Installation Height from the floor

Installation Height (A)


Type
Min. Standard ** Max.
Ceiling Mounted ** : Standard Height (Recommended)
1.8 m 2.7 m 3.3 m If it exceeds the standard height, set the ‘High Ceiling Mode’.
Cassette 1Way (5.91 ft) (8.86 ft) (9.84 ft) For details about function setting, refer to the installation manual.

< Cautions for Panel installation >

Good example Adjust the distance


Ceiling from unit body
Air conditioner to ceiling board
unit
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)
Air Conditioner body
Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

1-10
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.5 Piping Diagrams

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Cross Flow Fan Thermistor for


Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for
Evaporator inlet Humid sensor
temperature

Liquid pipe connection port


(flare connection)

1-11
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.6 Wiring Diagrams

1-12
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.7 Sound Levels


1.7.1 Pressure Levels
80

High

70
Octave Band Sound Pressure Level (0 dB = 20 μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1 000 2 000 4 000 8 000

Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 45.0 / 42.0 / 39.0
Heating ((SH)/H/M/L) - / 45.0 / 42.0 / 39.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

1-13
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1

1.8 Air flow and temperature distributions


1.8.1 Cooling operation
Discharge angle: 50°

Air velocity [m/s]


5

.5

1
0.53
.5
0.5 1 4

2
5
0.
2m

1 0.5
5
2.

1
0.5

0.5
1.5

1.5
2

0.5
1m

1.5
1

1
0.5
0.5

.5
0.5
0
5m 4m 3m 2m 1m 0

Temperature [°C]
32 32
8

30
202

30
30

18
22

28 2m
22
26

30
2628
24
24
28
32

1m
28

24

28
30

26
2826 24
0
5m 4m 3m 2m 1m 0

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-14
Single Indoor Unit Ceiling Cassette 1-Way Product Data

1. ATNW18GTLP1
1.8.2 Heating operation
Discharge angle: 60°

Air velocity [m/s]

1
43.5
01.5
5
0.
2

5
2.
0.5
2m

0.5
1.5
2
0.5

0.5

1.5
0.5

1
1m
1.5

1
0.5
0.5

0.5

0
5m 4m 3m 2m 1m 0

Temperature [°C]
31 32 32 34
35
3364

32 32 1
4
40
39

2m
38
3 5 33
31

33
31

32

36
37

1m
36
34
36

34
35

33
36
33

34
31
0
5m 4m 3m 2m 1m 0

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-15
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TT
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198 ~ 242
Limit Range of Voltage(Case 2) V -
kW 6.16
Cooling Capacity Nominal
Btu/h 21,000
kW 6.74
Heating Capacity Nominal
Btu/h 23,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 16.0 / 14.0 / 12.0
Air Flow Rate Range(Min~Max) m³/min 12.0~16.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 30
Output
No. 1
Dehumidification Rate - ℓ/h -
Rows x Columns x FPI - 2 x 12 x 18
No. - 1
Heat Exchanger
Fin Type - Slit(Half)
Face Area m² 0.24
Net(W x H x D) mm 1,180 x 132 x 450
Dimensions
Shipping(W x H x D) mm 1,445 x 252 x 538
Net kg 14.5
Weight
Shipping kg 17.5
Color - White
Exterior
RAL (Classic) - RAL 9003
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) Φ32(1-1/4)/Φ25(31/32)
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 46.0 / 43.0 / 40.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 46.0 / 43.0 / 40.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

2-1
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

2-2
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.2 List of Functions


Category Functions Availability
Air Supply Outlet 1
Airflow Direction Control (left & right) Auto
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) O
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* Advanced
Air Flow
Power Cool/Heat O/X
Swirl Wind* X
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** O
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille X
Human Detection Function*** X
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

2-3
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

2-4
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III) CREMTB100 White O
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II) CREMTB001 White O
Remote Controller PREMTBB01 Black O
PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only X
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only X
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) X
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) X
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m X
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way X
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way O
Air Purification Kit PTAHMP0 For Cassette 4-way X
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.

2-5
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

2-6
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.4 Dimensions
2.4.1 Product_Panel : PT-UTC
DWG No. : TBA35228601_Rev.01
Chassis code : TT

2-7
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
2.4.2 Product_Panel : PT-TAHG0

P
DWG No. : TBA36268301_Rev02
Chassis code : TT

2-8
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
2.4.3 Product_Panel : PT-TPHG0
DWG No. : TBA36268303_Rev03
Chassis code : TT

2-9
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
2.4.4 Install Space

< Minimum Installation Space >

≥ 10(13/32)
Ceiling Ceiling
Ceiling board Indoor unit Ceiling board
Indoor unit Ceiling
Ceiling board
board

≤ 300(11-13/16)
≥ 1000(39-3/8)

Air Outlet
≥ 500(19-11/16) Air Inlet
≥ 500(19-11/16)
A*

≥ 20(25/32)

A*
≥ 1,500(59-1/16)

[Unit:mm(inch)] [Unit:mm(inch)]

Floor Floor

Notes 1. * : A, Installation Height from the floor

Installation Height (A)


Type
Min. Standard ** Max.
Ceiling Mounted ** : Standard Height (Recommended)
1.8 m 2.7 m 3.3 m If it exceeds the standard height, set the ‘High Ceiling Mode’.
Cassette 1Way (5.91 ft) (8.86 ft) (9.84 ft) For details about function setting, refer to the installation manual.

< Cautions for Panel installation >

Good example Adjust the distance


Ceiling from unit body
Air conditioner to ceiling board
unit
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)
Air Conditioner body
Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

2-10
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.5 Piping Diagrams

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Cross Flow Fan Thermistor for


Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for
Evaporator inlet Humid sensor
temperature

Liquid pipe connection port


(flare connection)

2-11
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.6 Wiring Diagrams

2-12
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.7 Sound Levels


2.7.1 Pressure Levels
80

70
Octave Band Sound Pressure Level (dB = 20 Pa )

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

20 NC-25

Approximate
Hearing NC-20
Threshold

NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 46.0 / 43.0 / 40.0
Heating ((SH)/H/M/L) - / 46.0 / 43.0 / 40.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

2-13
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1

2.8 Air flow and temperature distributions


2.8.1 Cooling operation
Discharge angle: 50°

Air velocity [m/s]


2.7m

2.0 2m

1.0
1m
0.5
0.25

0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]
2.7m
20
2m
22
24

1m
26

0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-14
Single Indoor Unit Ceiling Cassette 1-Way Product Data

2. ATNW24GTLP1
2.8.2 Heating operation
Discharge angle: 60°

Air velocity [m/s]

2.7m

2m

2.5

2.0 1m
0.5

1.5 1.0
0m
0m 1m 2m 3m 4m 5m 6m 7m

Temperature [°C]

2.7m

2m
32

26 1m

30
28
0m
0m 1m 2m 3m 4m 5m 6m 7m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-15
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TP
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 5.28
Cooling Capacity Nominal
Btu/h 18,000
kW 5.28
Heating Capacity Nominal
Btu/h 18,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 16.5 / 14.5 / 13.0
Air Flow Rate Range(Min~Max) m³/min 13.0~16.5
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Dehumidification Rate - ℓ/h 1.30
Rows x Columns x FPI - 2 x 8 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 36.0 / 34.0 / 32.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 36.0 / 34.0 / 32.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

1-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.6
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

1-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.2 List of Functions


Category Functions Availability
Air Supply Outlet 4
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* X
Air Flow
Power Cool/Heat O/X
Swirl Wind* O
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** X
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille Accessory(PTEGM0)
Human Detection Function*** Accessory
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

1-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

1-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III)
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II)
PREMTBB01 Black O
Remote Controller PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only X
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only X
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way O
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way O
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

1-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.4 Dimensions
1.4.1 Product

PT-M*HW0

Head of Water lift : 700 or less


DWG No. : TBA36388101_rev01
Chassis Code : TP

1-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1
1.4.2 Install Space

< Minimum Installation Space >

Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board

≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor

Installation Height (A)


Capacity Class
Min. Standard *** Max.
≥ 1000(39-3/8)

≥ 1,500(59-1/16)* ≥ 1,500(59-1/16) * 2.0 m 2.7 m 3.6 m


< 10 kW (6.56 ft) (8.86 ft) (11.81 ft)
A**

2.5 m 3.2 m 4.2 m


≥ 10 kW (8.20 ft) (10.50 ft) (13.78 ft)

*** : Standard Height (Recommended)


If it exceeds the standard height, set the ‘High Ceiling Mode’.
Floor For details about function setting, refer to the installation manual.

< Cautions for Panel installation >


Good example
Ceiling Adjust the distance
Air conditioner
from unit body
unit to ceiling board
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)

Air Conditioner body


Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Indoor unit Indoor unit


Ventilator
< Series installation >
Lighting

1,500mm or more 1,500mm or more


2,000mm or more
3,000mm or more

※ According to type of indoor unit, external appearance could be different.

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

1-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.5 Piping Diagrams


1.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humidity Sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

1-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.6 Wiring Diagrams

1-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.7 Sound Levels


1.7.1 Pressure Levels
80

High

70
Octave Band Sound Pressure Level (0dB = 20µPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 36.0 / 34.0 / 32.0
Heating ((SH)/H/M/L) - / 36.0 / 34.0 / 32.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

1-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1

1.8 Air flow and temperature distributions


1.8.1 Cooling
Discharge angle: 40°

Air velocity [m/s]

2.7m
0.25 1.2

2m

0.25 0.25 1.5


0.25
0.5
1m
1.0 1.5

0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

25 25 2.7m
3.2m

2m
24 24
2m
23 23

1m
22 22 1m
23 23

0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data

1. ATNW18GPLP1
1.8.2 Heating
Discharge angle: 50°

Air velocity [m/s]

2.7m

0.25 0.25
2m
0.25

0.25 0.25 1m
0.5 0.5

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

2.7m

27 27
2m
26 26

28 32 32 28
29 29
31 31 1m
30 30
25
25
23 23
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TP
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 7.03
Cooling Capacity Nominal
Btu/h 24,000
kW 7.62
Heating Capacity Nominal
Btu/h 26,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 17.0 / 15.0 / 13.0
Air Flow Rate Range(Min~Max) m³/min 13.0~17.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Dehumidification Rate - ℓ/h 2.40
Rows x Columns x FPI - 2 x 8 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Mornig Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

2-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.6
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

2-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.2 List of Functions


Category Functions Availability
Air Supply Outlet 4
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* X
Air Flow
Power Cool/Heat O/X
Swirl Wind* O
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** X
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille Accessory(PTEGM0)
Human Detection Function*** Accessory
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

2-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

2-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III)
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II)
PREMTBB01 Black O
Remote Controller PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only X
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only X
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way O
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way O
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

2-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.4 Dimensions
2.4.1 Product

PT-M*HW0

Head of Water lift : 700 or less


DWG No. : TBA36388101_rev01
Chassis Code : TP

2-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1
2.4.2 Install Space

< Minimum Installation Space >

Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board

≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor

Installation Height (A)


Capacity Class
Min. Standard *** Max.
≥ 1000(39-3/8)

≥ 1,500(59-1/16)* ≥ 1,500(59-1/16) * 2.0 m 2.7 m 3.6 m


< 10 kW (6.56 ft) (8.86 ft) (11.81 ft)
A**

2.5 m 3.2 m 4.2 m


≥ 10 kW (8.20 ft) (10.50 ft) (13.78 ft)

*** : Standard Height (Recommended)


If it exceeds the standard height, set the ‘High Ceiling Mode’.
Floor For details about function setting, refer to the installation manual.

< Cautions for Panel installation >


Good example
Ceiling Adjust the distance
Air conditioner
from unit body
unit to ceiling board
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)

Air Conditioner body


Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Indoor unit Indoor unit


Ventilator
< Series installation >
Lighting

1,500mm or more 1,500mm or more


2,000mm or more
3,000mm or more

※ According to type of indoor unit, external appearance could be different.

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

2-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.5 Piping Diagrams


2.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humidity Sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

2-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.6 Wiring Diagrams

2-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.7 Sound Levels


2.7.1 Pressure Levels

80
■ High
▲ Middle
75 ● Low

70
Octave Band Sound Pressure Level (dB = 20μPa )

65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25

20 NC-25

Approximate
Hearing NC-20
15 Threshold

NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 38.0 / 36.0 / 34.0
Heating ((SH)/H/M/L) - / 38.0 / 36.0 / 34.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

2-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1

2.8 Air flow and temperature distributions


2.8.1 Cooling
Discharge angle: 40°

Air velocity [m/s]

0.25
2.7m
3.2m
0.25
0.25 0.25

0.25 2m
2m
2.0 2.0
0.25
0.5 0.25
1m
1m
0.25 0.25
1.0 1.0
0.5 1.5
1.5 0.5
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m

Temperature [°C]

2.7m
3.2m
24 24

21 21 2m
23 23 2m

23
1m
1m
22 22 22
23
23 23
22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data

2. ATNW24GPLP1
2.8.2 Heating
Discharge angle: 50°

Air velocity [m/s]

2.7m
0.25 0.25
0.25
0.25 0.25
2m
0.25 0.25

0.25
1m
1.0 0.25 1.0

0.5 0.5
0.25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

27
2.7m
27

29 2m
32
28
26 27
27 32 29
1m
31 31 27
26
29
27
28 26
25 24 25 24 25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TN
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 9.09
Cooling Capacity Nominal
Btu/h 31,000
kW 10.55
Heating Capacity Nominal
Btu/h 36,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Trubo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 23.0 / 21.0 / 19.0
Air Flow Rate Range(Min~Max) m³/min 19.0~23.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 2.50
Rows x Columns x FPI - 2 x 10 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.43
Net(W x H x D) mm 840 x 246 x 840
Dimensions
Shipping(W x H x D) mm 922 x 318 x 917
Net kg 25.5
Weight
Shipping kg 29.7
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

3-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

3-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.2 List of Functions


Category Functions Availability
Air Supply Outlet 4
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* X
Air Flow
Power Cool/Heat O/X
Swirl Wind* O
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** X
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille Accessory(PTEGM0)
Human Detection Function*** Accessory
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

3-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

3-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III)
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II)
PREMTBB01 Black O
Remote Controller PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way O
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way O
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

3-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.4 Dimensions
3.4.1 Product

Head of Water lift : 700 or less


P/No. : TBA36468004_rev01
Chassis code : TN

3-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1
3.4.2 Install Space

< Minimum Installation Space >

Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board

≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor

Installation Height (A)


Capacity Class
Min. Standard *** Max.
≥ 1000(39-3/8)

≥ 1,500(59-1/16)* ≥ 1,500(59-1/16) * 2.0 m 2.7 m 3.6 m


< 10 kW (6.56 ft) (8.86 ft) (11.81 ft)
A**

2.5 m 3.2 m 4.2 m


≥ 10 kW (8.20 ft) (10.50 ft) (13.78 ft)

*** : Standard Height (Recommended)


If it exceeds the standard height, set the ‘High Ceiling Mode’.
Floor For details about function setting, refer to the installation manual.

< Cautions for Panel installation >


Good example
Ceiling Adjust the distance
Air conditioner
from unit body
unit to ceiling board
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)

Air Conditioner body


Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Indoor unit Indoor unit


Ventilator
< Series installation >
Lighting

1,500mm or more 1,500mm or more


2,000mm or more
3,000mm or more

※ According to type of indoor unit, external appearance could be different.

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

3-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.5 Piping Diagrams


3.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humidity Sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

3-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.6 Wiring Diagrams

3-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.7 Sound Levels


3.7.1 Pressure Levels
80

High
Octave Band Sound Pressure Level (0dB = 20µPa)

70

NC -65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 40.0 / 38.0 / 36.0
Heating ((SH)/H/M/L) - / 40.0 / 38.0 / 36.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

3-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1

3.8 Air flow and temperature distributions


3.8.1 Cooling
Discharge angle: 40°

Air velocity [m/s]

2.7m
3.2m
0.25 0.25
0.5
2m
2m

0.25 1.0 1.0 0.25 1m


1m
2.0
1.0 0.25 0.25 0.5
0.5 1.5 1.5 1.5
0.5 1.5 1.0 0.5
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m

Temperature [°C]

23 23 2.7m
3.2m

2m
2m
21 21
22 22
20 20 1m
1m
21
21 21 21
22 22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

3-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data

3. ATNW36GNLP1
3.8.2 Heating
Discharge angle: 50°

Air velocity [m/s]

2.7m

2m
0.25 0.25

0.25 0.25
0.25
0.25 1m

1.0
1.5 0.5 1.5
0.5 1.0 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

25 25
2.7m
26 26

27 27
2m
31 31
29 29
33

1m
27 28 28 27
32 32 28
28
25 29 30 30 29 25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

3-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TM
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 13.78
Cooling Capacity Nominal
Btu/h 47,000
kW 15.53
Heating Capacity Nominal
Btu/h 53,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 31.0 / 28.0 / 25.0
Air Flow Rate Range(Min~Max) m³/min 25.0~31.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 5.20
Rows x Columns x FPI - 3 x 12 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.53
Net(W x H x D) mm 840 x 288 x 840
Dimensions
Shipping(W x H x D) mm 922 x 360 x 917
Net kg 28.5
Weight
Shipping kg 33.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

4-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

4-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.2 List of Functions


Category Functions Availability
Air Supply Outlet 4
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* X
Air Flow
Power Cool/Heat O/X
Swirl Wind* O
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** X
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille Accessory(PTEGM0)
Human Detection Function*** Accessory
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

4-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

4-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III)
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II)
PREMTBB01 Black O
Remote Controller PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way O
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way O
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

4-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.4 Dimensions
4.4.1 Product

PT-M*HW0

Head of Water lift : 700 or less


P/No. : TBA36388001_rev01
Chassis code : TM

4-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1
4.4.2 Install Space

< Minimum Installation Space >

Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board

≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor

Installation Height (A)


Capacity Class
Min. Standard *** Max.
≥ 1000(39-3/8)

≥ 1,500(59-1/16)* ≥ 1,500(59-1/16) * 2.0 m 2.7 m 3.6 m


< 10 kW (6.56 ft) (8.86 ft) (11.81 ft)
A**

2.5 m 3.2 m 4.2 m


≥ 10 kW (8.20 ft) (10.50 ft) (13.78 ft)

*** : Standard Height (Recommended)


If it exceeds the standard height, set the ‘High Ceiling Mode’.
Floor For details about function setting, refer to the installation manual.

< Cautions for Panel installation >


Good example
Ceiling Adjust the distance
Air conditioner
from unit body
unit to ceiling board
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)

Air Conditioner body


Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Indoor unit Indoor unit


Ventilator
< Series installation >
Lighting

1,500mm or more 1,500mm or more


2,000mm or more
3,000mm or more

※ According to type of indoor unit, external appearance could be different.

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

4-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.5 Piping Diagrams


4.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humidity Sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

4-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.6 Wiring Diagrams

4-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.7 Sound Levels


4.7.1 Pressure Levels
80

70
Sound Pressure Level (dB re 20Pa )

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0
Heating ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

4-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1

4.8 Air flow and temperature distributions


4.8.1 Cooling
Cooling
Discharge angle: 40°

Air velocity [m/s]


0.5 0.5 3.2m
3.2m
0.25 0.5 0.5 0.25 3m
1.0

0.5 0.5 2m
2m
0.5

0.25 3.0 3.0 0.25


1m
1m
1.0 0.25 1.0 2.5
0.5 2.5 0.5
1.0 1.5 2.0 0.25 0.25 2.01.5 1.0
0.5 0m
0m
5m
5m 4m
4m 3m
3m 2m 1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m

Temperature [°C]
23 23 3.2m
3.2m
3m

20 20 2m

22 22 22 22

21 23 23 21 1m

0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

4-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data

4. ATNW48GMLP1
4.8.2 Heating
Discharge angle: 50°

Air velocity [m/s]


3.2m
3m
0.25 0.25
0.5

2m

1.0 1.0
0.25 1.5 1.5 0.25 1m
0.25
0.25 0.25
0.5 0.5 0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]
26 26 3.2m
28 31 27 3m
27 28

29 29
2m
34 34

33 32 33

1m
32 32

30 30
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

4-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TM
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 14.65
Cooling Capacity Nominal
Btu/h 50,000
kW 17.00
Heating Capacity Nominal
Btu/h 58,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 31.0 / 28.0 / 25.0
Air Flow Rate Range(Min~Max) m³/min 25.0~31.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 6.30
Rows x Columns x FPI - 3 x 12 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.53
Net(W x H x D) mm 840 x 288 x 840
Dimensions
Shipping(W x H x D) mm 922 x 360 x 917
Net kg 28.5
Weight
Shipping kg 33.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

5-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

5-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.2 List of Functions


Category Functions Availability
Air Supply Outlet 4
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/4
Fan Speed Auto* X
Air Flow
Power Cool/Heat O/X
Swirl Wind* O
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify Accessory
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** X
Auto Restart O
Child Lock* O
Forced Operation O
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump O
Installation
High Ceiling Operation* O
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille Accessory(PTEGM0)
Human Detection Function*** Accessory
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

5-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

5-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White O
Wired - RS3 (Standard III)
PREMTBB10 Black O
PREMTB001 White O
Wired - RS2 (Standard II)
PREMTBB01 Black O
Remote Controller PQRCVCL0QW White O
Wired - Simple
PQRCVCL0Q Black O
PQRCHCA0QW White O
Wired - Simple for hotel
PQRCHCA0Q Black O
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way O
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way O
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units X
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units X
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

5-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.4 Dimensions
5.4.1 Product

PT-M*HW0

Head of Water lift : 700 or less


P/No. : TBA36388001_rev01
Chassis code : TM

5-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1
5.4.2 Install Space

< Minimum Installation Space >

Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board

≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor

Installation Height (A)


Capacity Class
Min. Standard *** Max.
≥ 1000(39-3/8)

≥ 1,500(59-1/16)* ≥ 1,500(59-1/16) * 2.0 m 2.7 m 3.6 m


< 10 kW (6.56 ft) (8.86 ft) (11.81 ft)
A**

2.5 m 3.2 m 4.2 m


≥ 10 kW (8.20 ft) (10.50 ft) (13.78 ft)

*** : Standard Height (Recommended)


If it exceeds the standard height, set the ‘High Ceiling Mode’.
Floor For details about function setting, refer to the installation manual.

< Cautions for Panel installation >


Good example
Ceiling Adjust the distance
Air conditioner
from unit body
unit to ceiling board
Keep the length of the bolt (refer to
Ceiling
board from the bracket to 40mm dimensional drawing)

Air Conditioner body


Decorative panel
Ceiling board Ceiling board
Fit the insulator (this part) and
be careful for cool air leakage
Keep the specified length
Bad example between the air conditioner bottom
surface and the ceiling surface
Cool Air Air conditioner
Leakage unit Adjust the same height Set screw of
(not good) paper model (4 pieces)
Ceiling (Ceiling board ~ Front panel)
board Paper model Open the ceiling board
for installation along the outer edge of the
Decorative panel paper model

Indoor unit Indoor unit


Ventilator
< Series installation >
Lighting

1,500mm or more 1,500mm or more


2,000mm or more
3,000mm or more

※ According to type of indoor unit, external appearance could be different.

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.

5-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.5 Piping Diagrams


5.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humidity Sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

5-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.6 Wiring Diagrams

5-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.7 Sound Levels


5.7.1 Pressure Levels
80

70
Sound Pressure Level (dB re 20Pa )

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0
Heating ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

5-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1

5.8 Air flow and temperature distributions


5.8.1 Cooling
Cooling
Discharge angle: 40°

Air velocity [m/s]


0.5 0.5 3.2m
3.2m
0.25 0.5 0.5 0.25 3m
1.0

0.5 0.5 2m
2m
0.5

0.25 3.0 3.0 0.25


1m
1m
1.0 0.25 1.0 2.5
0.5 2.5 0.5
1.0 1.5 2.0 0.25 0.25 2.01.5 1.0
0.5 0m
0m
5m
5m 4m
4m 3m
3m 2m 1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m

Temperature [°C]
23 23 3.2m
3.2m
3m

20 20 2m

22 22 22 22

21 23 23 21 1m

0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

5-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data

5. ATNW60GMLP1
5.8.2 Heating
Discharge angle: 50°

Air velocity [m/s]


3.2m
3m
0.25 0.25
0.5

2m

1.0 1.0
0.25 1.5 1.5 0.25 1m
0.25
0.25 0.25
0.5 0.5 0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]
26 26 3.2m
28 31 27 3m
27 28

29 29
2m
34 34

33 32 33

1m
32 32

30 30
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

5-12
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM1
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 8.79
Cooling Capacity Nominal
Btu/h 30,000
kW 9.97
Heating Capacity Nominal
Btu/h 34,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 20.0 / 18.0 / 16.0
Air Flow Rate Range(Min~Max) m³/min 16.0~20.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 85.9
Output
No. 1
Dehumidification Rate - ℓ/h 3.80
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.31
Net(W x H x D) mm 1,200 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,315 x 317 x 768
Net kg 28.4
Weight
Shipping kg 34.3
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

1-1
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.5
x)

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

1-2
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.2 List of Functions


Category Functions Availability
Air Supply Outlet 1
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/5
Fan Speed Auto* O
Air Flow
Power Cool/Heat O/O
Swirl Wind* X
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify X
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** O
Auto Restart O
Child Lock* O
Forced Operation X
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump X
Installation
High Ceiling Operation* X
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille X
Human Detection Function*** X
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

1-3
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

1-4
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White X
Wired - RS3 (Standard III)
PREMTBB10 Black X
PREMTB001 White X
Wired - RS2 (Standard II)
PREMTBB01 Black X
Remote Controller PQRCVCL0QW White X
Wired - Simple
PQRCVCL0Q Black X
PQRCHCA0QW White X
Wired - Simple for hotel
PQRCHCA0Q Black X
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way X
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way X
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units O
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units O
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

1-5
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.4 Dimensions
1.4.1 Product
DWG No. : TAZ35326401_Rev01
Chassis code : VM1

1-6
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1
1.4.2 Installation Space

[Unit: mm(inch)]

≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle

≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)

Floor

≥ 700(27-9/16) ≥ 700(27-9/16)

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

1-7
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.5 Piping Diagrams


1.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)

Heating

Cooling Cross Flow Fan Thermistor for


Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for Humid sensor


Evaporator inlet
temperature

Liquid pipe connection port


(flare connection)

Strainer

1-8
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.6 Wiring Diagrams


220-240V~ 50/60 Hz

CN1
CN_PTC

MEZ67351819

1-9
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.7 Sound Levels


1.7.1 Pressure Levels

■ High
▲ Middle
● Low

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0
Heating ((SH)/H/M/L) - / 47.0 / 45.0 / 42.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

1-10
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1

1.8 Air flow and temperature distributions


1.8.1 Cooling operation
Discharge angle: 0°

Air velocity [m/s]


2.7m
2.7m
2.5
2.0

1.5 2m

1.0

1m
0.5
0.25
0m
10m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Temperature [°C]
18 2.7m
2.7m
20 19
21
22
2m
23
24
25
26 1m

0m
10m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-11
Single Indoor Unit Ceiling Suspended Product Data

1. AVNW36GM1P1
1.8.2 Heating operation
Discharge angle: 0°

Air velocity [m/s]

Temperature [°C]

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

1-12
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM2
Case 1 - 220-230-240, 1, 50
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 13.78
Cooling Capacity Nominal
Btu/h 47,000
kW 15.53
Heating Capacity Nominal
Btu/h 53,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 2
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Air Flow Rate Range(Min~Max) m³/min 20.0~30.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 125
Output
No. 1
Dehumidification Rate - ℓ/h 6.50
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.46
Net(W x H x D) mm 1,600 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,715 x 317 x 768
Net kg 36.9
Weight
Shipping kg 45.5
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

2-1
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

2-2
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.2 List of Functions


Category Functions Availability
Air Supply Outlet 1
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/5
Fan Speed Auto* O
Air Flow
Power Cool/Heat O/O
Swirl Wind* X
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify X
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** O
Auto Restart O
Child Lock* O
Forced Operation X
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump X
Installation
High Ceiling Operation* X
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille X
Human Detection Function*** X
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

2-3
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

2-4
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White X
Wired - RS3 (Standard III)
PREMTBB10 Black X
PREMTB001 White X
Wired - RS2 (Standard II)
PREMTBB01 Black X
Remote Controller PQRCVCL0QW White X
Wired - Simple
PQRCVCL0Q Black X
PQRCHCA0QW White X
Wired - Simple for hotel
PQRCHCA0Q Black X
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way X
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way X
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units O
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units O
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

2-5
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.4 Dimensions
2.4.1 Product
DWG No. : TAZ35266401_Rev01
Chassis code : VM2

2-6
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1
2.4.2 Installation Space

[Unit: mm(inch)]

≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle

≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)

Floor

≥ 700(27-9/16) ≥ 700(27-9/16)

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

2-7
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.5 Piping Diagrams


2.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Cross Flow Fan Thermistor for


evaporator outlet
temperature Thermistor for
M suction air
temperature

Humid sensor
Thermistor for
evaporator outlet
temperature
Liquid pipe connection port
(flare connection)
Capillary Tube

Strainer

2-8
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.6 Wiring Diagrams


220-240V~ 50/60 Hz

CN1
CN_PTC

MEZ67351819

2-9
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.7 Sound Levels


2.7.1 Pressure Levels

■ High
▲ Middle
● Low

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 50.0 / 46.0 / 42.0
Heating ((SH)/H/M/L) - / 50.0 / 46.0 / 42.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

2-10
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1

2.8 Air flow and temperature distributions


2.8.1 Cooling operation
Cooling
Discharge angle: 0°

Air velocity [m/s]

3.0
2.7m
2.7m
2.5
2.0
1.5
2m
2m
1.0
0.5

1m
1m
0.25

0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Temperature [°C]

16 2.7m
2.7m
17
18
19
20 2m
2m
21

1m
1m

22
0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-11
Single Indoor Unit Ceiling Suspended Product Data

2. AVNW48GM2P1
2.8.2 Heating operation
Discharge angle: 0°

Air velocity [m/s]

Temperature [°C]

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

2-12
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM2
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 15.24
Cooling Capacity Nominal
Btu/h 52,000
kW 17.00
Heating Capacity Nominal
Btu/h 58,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 2
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Air Flow Rate Range(Min~Max) m³/min 20.0~30.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 125
Output
No. 1
Dehumidification Rate - ℓ/h 6.50
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.46
Net(W x H x D) mm 1,600 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,715 x 317 x 768
Net kg 36.9
Weight
Shipping kg 45.5
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4

3-1
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.

3-2
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.2 List of Functions


Category Functions Availability
Air Supply Outlet 1
Airflow Direction Control (left & right) X
Airflow Direction Control (up & down) Auto
Auto Swing (left & right) X
Auto Swing (up & down) O
Airflow Steps (fan/cool/heat) 4/5/5
Fan Speed Auto* O
Air Flow
Power Cool/Heat O/O
Swirl Wind* X
Refresh Mode** X
Smart Mode** X
Indirect Wind* O
Direct Wind* O
Dry Operation O
Air Purify X
Ionizer X
UV-C X
Air Purification
Allergy Filter X
Pre-Filter O
PM1.0 Filter X
Hot Start O
Reliability
Self Diagnosis O
Auto Mode O
Auto Dry Operation** O
Auto Restart O
Child Lock* O
Forced Operation X
Group Control* O
Convenience
Sleep Timer** O
Turn On/Off Reservation** O
Schedule** O
Two Thermistor Control* O
Time Limit Control (Energy saving)*** O
External On/Off O
Drain Pump X
Installation
High Ceiling Operation* X
Wi-Fi Control Accessory
Comfort Cooling (Humidity Control)*** O
Special Functions Auto Elevation Grille X
Human Detection Function*** X
Floor Detection Function*** X

Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)

3-3
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.

3-4
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.3 Accessory Compatibility List


Category Accessory Name Model Name Description Compatibility
PREMTA000 - O
Wired - Premium PREMTA000A - O
PREMTA000B - O
PREMTB100 White X
Wired - RS3 (Standard III)
PREMTBB10 Black X
PREMTB001 White X
Wired - RS2 (Standard II)
PREMTBB01 Black X
Remote Controller PQRCVCL0QW White X
Wired - Simple
PQRCVCL0Q Black X
PQRCHCA0QW White X
Wired - Simple for hotel
PQRCHCA0Q Black X
PQWRCQ0FDB For Cooling only O
PQWRHQ0FDB For Heat pump O
Wireless
PWLSSB21C For Cooling only O
PWLSSB21H For Heat pump O
PDRYCB000 1 input port, AC 220 - 240V O
Simple
PDRYCB100 1 input port, AC 24V O
PDRYCB400 2 input port O
Dry Contact
PDRYCB300 8 input port, For 3rd party Themostat O
Communication
PDRYCB320 8 input port, For 3rd Party Thermostat (Analog Input) O
PDRYCB500 For 3rd Party Controller(Modbus RTU) O
Remote Temperature sensor PQRSTA0 - O
Integration Device Cable Assembly for group control (Y-type cable : 0.25m,
Group Control wire PZCWRCG3 O
cable : 9.6m)
Extension wire PZCWRC1 Extension wire for IDU-wired remote controller (9.6m) O
2-Remo Control wire PZCWRC2 - X
Wi-Fi Modem PWFMDD200 - O
Wi-Fi Extension cable PWYREW000 USB Extension cable : 10 m O
Independent Power Module PRIP0 For Multi V Indoor Unit X
Multi-tenant Power module PINPMB001 For Multi V Indoor Unit X
Refrigerant Leakage Detector PRLDNVS0 For Multi V Indoor Unit (R410A) X
PTVSMA0 For Cassette 4-way X
Human Detection Sensor
PTVSAA0 For Cassette Dual Vane 4-way X
Floor Detection Sensor PTFSMA0 For Cassette Dual Vane 4-way X
Auto Elevation Grille PTEGM0 For Cassette 4-way X
ETC
PTAHTP0 For Cassette 1-way X
Air Purification Kit PTAHMP0 For Cassette 4-way X
PTAHYP0 For Cassette Round X
EEV Kit PRGK024A0 For Multi V Indoor Unit X
PRARS1 For Wall Mounted / Art Cool Indoor Units O
Auxiliary Heater Relay Kit
PRARH1 For Cassette / Duct Indoor Units O
PTVK430 For TR/TQ/TP/TN/TM Chassis X
Ventilation Kit
PTVK410 / PTVK420 For TP/TN/TM Chassis X
PTDCQ For TR/TQ Chassis X
Cassette Cover PTDCM For TP/TN/TM Chassis X
PTDCA For TM-A/TP-B Chassis X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).

3-5
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.4 Dimensions
3.4.1 Product
DWG No. : TAZ35266401_Rev01
Chassis code : VM2

3-6
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1
3.4.2 Installation Space

[Unit: mm(inch)]

≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle

≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)

Floor

≥ 700(27-9/16) ≥ 700(27-9/16)

Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

3-7
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.5 Piping Diagrams


3.5.1 Normal

Gas pipe connection port


Heat exchanger
(flare connection)
Heating

Cooling Cross Flow Fan Thermistor for


evaporator outlet
temperature Thermistor for
M suction air
temperature

Humid sensor
Thermistor for
evaporator outlet
temperature
Liquid pipe connection port
(flare connection)
Capillary Tube

Strainer

3-8
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.6 Wiring Diagrams


220-240V~ 50/60 Hz

CN1
CN_PTC

MEZ67351819

3-9
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.7 Sound Levels


3.7.1 Pressure Levels

■ High
▲ Middle
● Low

Sound level [ dB(A), @ Standard condition ]


Cooling ((SH)/H/M/L) - / 50.0 / 46.0 / 42.0
Heating ((SH)/H/M/L) - / 50.0 / 46.0 / 42.0

Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

3-10
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1

3.8 Air flow and temperature distributions


3.8.1 Cooling operation
Cooling
Discharge angle: 0°

Air velocity [m/s]

3.0 2.7m
2.7m
2.5
2.0
1.5
1.0 2m
2m

0.5
0.25
1m
1m

0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Temperature [°C]

16 2.7m
2.7m
17
18
19
20 2m
2m
21

1m
1m

0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

3-11
Single Indoor Unit Ceiling Suspended Product Data

3. AVNW60GM2P1
3.8.2 Heating operation
Discharge angle: 0°

Air velocity [m/s]

Temperature [°C]

Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.

3-12
Accessory

Front Panel
Air Purification Kit
Front Panel Accessory

1. PT-AAGW0

1.1 Specifications
Category
Unit Specification
Major Minor
Factory model - PT-AAGW0
Model Name
Buyer model - PT-AAGW0
Panel Type - - Standard
Glossy / Matt - -
Color - White
Panel Exterior
RAL (Classic) - RAL 9003
Grille Type (Grille / Grid) - Grid
Net (W x H x D) mm 950 x 35 x 950
Panel Dimension
Shipping (W x H x D) mm 1,006 x 102 x 1,006
Net kg 7.1
Panel Weight
Shipping kg 9.3
Panel Function PM1.0 Sensor - X
Air Purification Kit - X
Panel Accessory Floor Detection Sensor - PTFSMA0
Human Detection Sensor - PTVSAA0

Note
■ Some functions need to connect to the Standard III wired remote controller.
■ Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field

1
Front Panel Accessory

2. PT-AFGW0

2.1 Specifications
Category
Unit Specification
Major Minor
Factory model - PT-AFGW0
Model Name
Buyer model - PT-AFGW0
Panel Type - - Premium
Glossy / Matt - -
Color - White
Panel Exterior
RAL (Classic) - RAL 9003
Grille Type (Grille / Grid) - Grid
Net (W x H x D) mm 950x35x950
Panel Dimension
Shipping (W x H x D) mm 1,006x117x1,006
Net kg 7.50
Panel Weight
Shipping kg 9.40
Panel Function PM1.0 Sensor - O
Air Purification Kit - PTAHMP0
Panel Accessory Floor Detection Sensor - PTFSMA0
Human Detection Sensor - PTVSAA0

Note
■ Some functions need to connect to the Standard III wired remote controller.
■ Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field

2
Air Purification Kit Accessory

1. PTAHMP0

1.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TP/TN/TM/TP-B/TM-A
Air Purification Kit
Applied Panel - PT-MPGW0 (U-style) / PT-AFGW0 (Dual Vane)
Size(W x H x D) mm 59 x 45 x 22
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 X 50 X 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.2kV
Size(W x H x D) mm 500 x 38 x 395
PM 1.0 Filter
Weight g 2,090
Material - Pulp + Carbon (Corrugate)
Deodorization Filter Size(W x H x D) mm 478 x 14 x 138
Weight g 180
Size(W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer
Output - -3.2kV
Amount of Ion Emission EA / cc 3,000,000

3
Air Purification Kit Accessory

2. PTAHTP0

2.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TU / TT
Air Purification Kit
Applied Panel - PT-UPHG0 / PT-TPHG0
Size(W x H x D) mm 59 x 45 x 22
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 X 50 X 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.2kV
Size(W x H x D) mm 524 x 18 x 141
PM 1.0 Filter
Weight g 430
Material - Pulp + Carbon (Corrugate)
Deodorization Filter Size(W x H x D) mm 301 x 11 x 100
Weight g 40
Size(W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer
Output - -3.2kV
Amount of Ion Emission EA / cc 3,000,000

4
Air Purification Kit Accessory

3. PTAHYP0

3.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TY
Air Purification Kit
Applied Panel - -
Size(W x H x D) mm 59 x 45 x 16.6
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 x 50 x 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.7kV
Size(W x H x D) mm 500 x 38 x 395
PM 1.0 Filter
Weight g 2,090
Material - Pulp + Carbon(corrugate)
Deodorization Filter Size(W x H x D) mm 478 x 14 x 138
Weight g 180
Size(W x H x D) mm -
Input - -
Ionizer
Output - -
Amount of Ion Emission EA / cc -

5
Installation

Installation of Indoor Unit


Installation of Indoor Unit Installation

1. Information for Refrigerant

1.1 R410A as an Alternative Refrigerant

The type of refrigerant applied depends on the outdoor unit cycle configuration. Ensure the refrigerant type
in the specification of the indoor unit and outdoor unit to be installed.

■ Alternative Refrigerant _ R410A


• The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than ones of R22 and this characteristic should
also be considered during the installation.
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure.
(R410A 3.8MPa)
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential(ODP) of R410A is 0.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.

1
Installation of Indoor Unit Installation

1. Information for Refrigerant

1.2 Cautions for Refrigerant Leaks of R410A

< Needs to Calculation of Refrigeran concentration >


Outdoor unit Flow of
(No.1 system) refrigerant

Indoor unit Room where refrigerant leaks


(Refrigerant of the whole No.1
system flows out.)

< Calculation of Room Space > : Range ov Room space


Outdoor unit Outdoor unit Outdoor unit

Indoor unit Indoor unit


Indoor unit
Opening
Smallest
Partition room

In the case of opening without door,


or openings both above and below door
which is more than 0.15 % to floor space)

< Countermeasure Gas leak alarm


when concentration is exceed > Countermeasure 2
Mechanical ventilator

Indoor unit

Countermeasure 1 Opening effective to ventilation

The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.

■ Concentration limit : 0.44 kg/m³ (for R410A)


Concentration limit (Freon gas weight per unit air volume, kg/m³) is the limit of Freon gas concentration where immediate
measures can be taken without hurting human body when refrigerant leaks in the air.

■ Calculate refrigerant concentration


Check concentration limit along following steps and take appropriate measure depending on the situation.
(1) Calculate total amount of refrigerant per each system (A, kg)
Total amount of refrigerant in the system (A, kg)
= Amount of pre-charged refrigerant per single system(B, kg) + Amount of additional replenished refrigerant(C, kg)
(B : Amount of replenished refrigerant at factory shipment)
(C : Amount of additionally replenished refrigerant depending on piping length or piping diameter by customer)

2
Installation of Indoor Unit Installation

1. Information for Refrigerant


※ In case one refrigerant facility is divided into 2 or more refrigerant systems and each system is independent, amount of
replenished refrigerant of each system shall be adopted.
(2) Calculate the volume of the room where indoor unit is installed as single room or the smallest room. (D, m³)
In case of room with partition and without opening which serve as passage of air to adjoining room, calculate the room
space only.
- In case of room with partition but opened which serve passage of air to adjoining room, calculate the room space include
space of adjoining room. (In the case of opening without door, or openings both above and below door which is more than
space 0.15 % to floor space)
(3) Calculate refrigerant concentration.
Refrigerant concentration
= Total amount of refrigerant system (A, kg) ÷ Volume of smallest room where indoor unit is installed (D, m³)
[ Refrigerant concentration ≤ Maximum concentration (kg/m³, R410A is 0.44) ]
In case the result of calculation exceeds the concentration limit, perform the same calculations by shifting to the second
smallest, and the third smallest rooms until at last the result is below the concentration limit.

■ In case the concentration exceeds the limit


When the concentration exceeds the limit, change original plan or take one of the counter measure shown below:
- Counter measure 1
Provide opening 0.15% or more size of opening to floor space both above and below door for ventilation,
or provide opening without door.
- Counter measure 2
Provide gas leak alarm linked with mechanical ventilator.
- Counter measure 3
Reducing the system’s refrigerant quantity by deviding into smaller separate system.

< ! > CAUTIONS


Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier
than air.

3
Installation of Indoor Unit Installation

1. Information for Refrigerant

1.3 R32 as an Alternative Refrigerant

The type of refrigerant applied depends on the outdoor unit cycle configuration. Ensure the refrigerant type
in the specification of the indoor unit and outdoor unit to be installed.

■ Alternative Refrigerant _ R32


• The refrigerant R32 has a lower GWP (Global Warming Potential) value, and higher efficiency than R410A.
The Ozone Depletion Potential (ODP) of R32 is 0, and Global Warming Potential(GWP) is 675.
• Refrigerant piping consists of copper/steel pipes, joints, and other fittings.All components must be selected and installed in
conformity with the standards pertaining to the Refrigeration Safety Regulation.
• Same piping as for R410A can be used.

< ! > WARNING


• This product contains fluorinated greenhouse gases (Refrigerant type : R32).
DO NOT LEAK refrigerant gases into the atmosphere.
• The refrigerant R32 is a Slightly Flammable gas. It does not leak normally. If the refrigerant leaks in the installed place and
is in contact with a flaming source, it may cause fire, or a harmful gas.
• If there is some leak, turn off any combustion devices, ventilate the installation location, and contact the dealer from which
you purchased the unit. Do not use the unit until the refrigerant leaked is repaired.
• Only use R32 as refrigerant. Other substances may cause explosions and accidents.

< ! > CAUTIONS


• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.

4
Installation of Indoor Unit Installation

1. Information for Refrigerant

1.4 Minimum Floor Area for Installation fo R32 model : accordance with IEC05

600

Floor location
500
Minimum Area for installation ( m² )

400

300

200

100
Wall mounted
Ceiling mounted
0
0 1 2 3 4 5 6 7 8
Total refrigerant amount in the system ( kg )

<!> CAUTIONS
• "Minimum Area for installation" might be different by revision of IEC regulation. "Minimum Area for installation" should be
selected in accordance with that revision based on the local and national environment.

• The following information is according to 'IEC 60335-2-40:2013+A1:2016 Edition 5.1'.


• Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is
smaller than minimum area for installation.
• The unit should be installed, operated and stored in a room with a floor area larger than the minimum area.
Use the upper graph or the below table to determine the minimum area.
- mc : Total refrigerant amount in the system = factory refrigerant charge + additional refrigerant amount (kg)
- Amin : Minimum Area for installation of unit
Amin
mc(kg)
Floor Location Wall Mounted Ceiling Mounted
1.0 8.58 0.95 0.64
1.224 12.90 1.43 0.958
1.4 16.82 1.87 1.25
1.6 21.97 2.44 1.63
1.8 27.80 3.09 2.07
2.0 34.32 3.81 2.55
2.2 41.53 4.61 3.09
2.4 49.42 5.49 3.68
2.6 58.00 6.44 4.31
2.8 67.27 7.47 5.00
3.0 77.22 8.58 5.74
3.2 87.86 9.76 6.54
3.4 99.19 11.02 7.38
3.6 111.20 12.36 8.27
3.8 123.90 13.77 9.22
4.0 137.29 15.25 10.21
4.2 151.36 16.82 11.26
4.4 166.12 18.46 12.36
4.6 181.56 20.17 13.50
4.8 197.70 21.97 14.70
5.0 214.51 23.83 15.96
5.2 232.02 25.78 17.26
5.4 250.21 27.80 18.61
5.6 269.09 29.90 20.01
5.8 288.65 32.07 21.47
6.0 308.90 34.32 22.98
6.2 329.84 36.65 24.53
6.4 351.46 39.05 26.14
6.6 373.77 41.53 27.80
6.8 396.76 44.08 29.51
7.0 420.45 46.72 31.27
7.2 444.81 49.42 33.09
7.4 469.87 52.21 34.95
7.6 495.61 55.07 36.86
7.8 522.04 58.00 38.83

5
Installation of Indoor Unit Installation

1. Information for Refrigerant

1.5 Minimum Floor Area for Installation fo R32 model : accordance with IEC06

2500

Floor standing
2000
Minimum Area for installation ( m² )

1500

1000

500

Wall mounted
Ceiling mounted
0
0 2 4 6 8 10 12 14 16
Total refrigerant amount in the system ( kg )

<!> CAUTIONS
• "Minimum Area for installation" might be different by revision of IEC regulation. "Minimum Area for installation" should be
selected in accordance with that revision based on the local and national environment.

• The following information is according to 'IEC 60335-2-40:2018 Edition 6.0'.


• Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is
smaller than minimum area for installation.
• The unit should be installed, operated and stored in a room with a floor area larger than the minimum area.
Use the below calcuation formula to determine the minimum area.
- mc : Total refrigerant amount in the system = factory refrigerant charge + additional refrigerant amount (kg)
- Amin : Minimum Area for installation of unit
- LFL : Lower flammability limit (kg/m3). In case of R32, LFL is 0.307 kg/m3
- h0 : Height of unit installation
Choose the higher of the two values.
Amin = [mc / (2.5 x LFL5/4 x h0)]2 or Amin = mc / (0.75 x LFL x h0)
* The table below is a reference value, and the exact value is calculated and applied.
mc(kg) Amin mc(kg) Amin mc(kg) Amin
< 1.842 No Limit 6.6 27.6 11.6 85.2
1.842 3.6 6.8 29.3 11.8 88.1
2.0 3.9 7.0 31.0 12.0 91.2
2.2 4.3 7.2 32.8 12.2 94.2
2.4 4.7 7.41 34.7 12.4 97.3
2.6 5.1 7.6 36.6 12.6 100.5
2.8 5.5 7.8 38.5 12.8 103.7
3.0 5.9 8.0 40.5 13.0 107.0
3.2 6.5 8.2 42.6 13.2 110.3
3.4 7.3 8.4 44.7 13.4 113.7
3.6 8.2 8.6 46.8 13.6 117.1
3.8 9.1 8.8 49.0 13.8 120.6
4.0 10.1 9.0 51.3 14.0 124.1
4.2 11.2 9.2 53.6 14.2 127.6
4.4 12.3 9.4 55.9 14.4 131.3
4.6 13.4 9.6 58.3 14.6 134.9
4.8 14.6 9.8 60.8 14.8 138.7
5.0 15.8 10.0 63.3 15.0 142.4
5.2 17.1 10.2 65.9 15.2 146.3
5.4 18.5 10.4 68.5 15.4 150.1
5.6 19.9 10.6 71.1 15.6 154.1
5.8 21.3 10.8 73.8 15.8 158.0
6.0 22.8 11.0 76.6 15.964 161.3
6.2 24.3 11.2 79.4
6.4 25.9 11.4 82.3

6
Installation of Indoor Unit Installation

2. Selection of the best Location

When selecting a location the product is installed, it is recommended to consider the following:

• The unit must be installed indoor area.


• Do not install the unit near the door.
• There should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling, or other
obstacles.
• The place where the unit is leveled.
• The place shall allow easy water drainage.
• The place where bear a load exceeding four times of weight of the unit.
• The mounting ceiling or wall should be solid enough to protect it from the vibration.
• The place where the unit is not affected by an electrical noise.
• The place where noise prevention is taken into consideration.
• The place where the maintenance space for product is sufficient.
• The servicing inspection hole of the ceiling should be larger than the indoor unit, and that location should be approved by
the customer.
• There should not be any heat source or steam near the unit. Avoid the following installation location.
1) Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
- Make sure that ventilation fan is enough to cover all noxious gases from this place.
- Ensure enough distance from the cooking room to install the unit in such a place where it may not suck oily steam.
2) Avoid installing the unit in such places where cooking oil or iron powder is generated.
3) Avoid places where inflammable gas is generated.
4) Avoid places where noxious gas is generated.
5) Avoid places near high frequency generators.

< ! > CAUTIONS


• If the temperature rise above 30℃ or the humidity rise above RH 80%, additional insulation working is needed to the unit
body for protection of dew formation.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.

7
Installation of Indoor Unit Installation

3. Precautions regarding cassette indoor unit installation

Fig1. High Ceiling Space Fig2. Surface adjacent with outdoor air Fig3. High temperature or humidity
Fig.3-1 Additional insulation required
Indoor

Low temperature
of the floor
High elevation of the ceiling

Discharge
Suction
Hot air Fig.3-2 Ceiling near the tight seal places
Outdoor side (50~100mm
Cold air Outdoor (ex. Garage... ) Insulation required)
(Entering of air by
frequent opening side
Outdoor side Outdoor side
and closing of door)

Grill for ventilation

■ In case of High Ceiling space installation [Fig.1]


In general commercial places and offices though the height of the ceiling is 2.7m, and the ceiling height could be over 3 m.
In such cases because of the temperature difference with the floor the heating effect can fall down.
• Countermeasure method
- Air conditioner should be able to operate in high ceiling operation mode.
- Plan to install the circulator.
- The air discharge port should be made to give more airflow to the down floor directions.
- The gate or exit of the building is protected by dual door system to minimize inflow of outdoor air.

■ In case the floor or surfaces is contact with the outdoor air directly [Fig.2]
If the floor of air conditioned room contact with the outside air, like the store room or garage, the floor temperature will be
decreased and users can have a cold feeling in the feet.
In such places where the feet comes in direct contact with floors will give a cold feeling to the foot.
• Countermeasure method
- Use the carpet on the floor.
(compared to the tiles the carpet over it will have a 3 degree rise in temperature)
- Insulating the floor.
- Floor heating.
<!> CAUTIONS
In case there is a cold air intake, the duct surface may have some dew drops.
So a insulation on the duct is a must.(Insulation material: a glass wool of thickness 25 mm will be appropriate.)

■ In case of installation where high temperature or humidity [Fig.3]


• In case of places having the temperature and humidity of the surrounding water sources(sea, river etc.)
• In case the steam is generated between the false ceiling and the ceiling slab due to some nearby by steam source.
• In case of temperature of 30 degree and humidity above 80%, the units body as well as the piping insulation should be
strengthened. Refer to the psychrometric chart.
• Countermeasure method
- Indoor unit: Insulate the unit body with some insulation like glass wool at least 10 mm in thickness.
- Refrigerant piping: Increase the piping insulation thickness with thickness above 20 mm.
- Others: Inside the ceiling near the air tight seal places. (To escape of the humidity inside false ceiling)

8
Installation of Indoor Unit Installation

4. Connecting pipes

■ Refrigerant piping work


To detail information for connecting the refrigerant pipes, please refer to the installation manual included with product.

< ! > CAUTIONS


• When mechanical connectors are reused, indoors’ sealing parts shall be renewed.
• When flared joints are reused, indoors’ the flare part shall be re-fabricated.

■ Piping insulation work


• Perform heat insulation work completely on both gas and the liquid pipe.
Because improper insulation will result condensate formation over pipe.
• Use the heat insulation material for the refrigerant piping which has an excellent heat resistance (over 120°C (248°F)).
• Precautions in high humidity circumstance
- This air conditioner has been tested according to the "KS Conditions" and confirmed.
- If it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C(73°F)), water drops
are liable to fall. In this case, add heat insulation material according to the following procedure.
: Heat insulation material : Adiabatic glass wool with thickness of 10~20mm(13/32 ~13/16 inch).
: Stick glass wool on all air conditioners that are located in ceiling atmosphere.

< ! > CAUTIONS


• Make sure to insulate any field piping all the way to the piping connection inside the unit.
Any exposed piping may cause condensation or burns if touched.

9
Installation of Indoor Unit Installation

5. Electrical Wiring

5.1 General Instruction

For wiring work, it is recommended to consider the following:


• All field supplied parts and materials, electric works must conform to local codes. Use copper wire only.
• Follow the "WIRING DIAGRAM” attached to the unit body to wire the outdoor unit, indoor units and the remote controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down the power supply to the entire system must be installed.
< ! > CAUTIONS
After the confirmation of the above conditions, prepare the wiring as follows:
• Never fail to have separate power specially for this unit.
• Provide a circuit breaker switch between power source and the unit.
• Confirm the Specification of power source. Confirm that electrical capacity is sufficient.
• Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
• Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
• Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit.
• The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function
of a overload protection device.
- Proper starting power is not given to the compressor.
- All of the indoor units and outdoor units shoul be grounded. If grounding is not properly done, there is a risk of electric
shock. Grounding must be done by a qualified technician.

■ Wiring Connections
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the terminal board
wiring to the outdoor unit and indoor units are properly matched.
If wiring and piping between the outdoor unit and indoor unit are mismatched, the system may cause a malfunction.
< ! > CAUTIONS
• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of the wires.)
• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign particle
from outside. Otherwise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly by arranging the
wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts box cover, make sure no
wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the
same locations outside of the unit, separating them properly, otherwise electrical noise (external static) could cause
product malfunction.

10
Installation of Indoor Unit Installation

5. Electrical Wiring

5.2 Installation of Wired remote controller(Optional)

• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
• Install the remote controller about 1.5m (5ft) above the floor in an area with good air circulation at an average temperature.
• Do not install the remote controller where it can be affected by :
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED display. For proper display of the remote controller LED's,
the remote controller should be installed properly.
(The standard height is 1.2~1.5 m (4~5ft) from floor level.)

11
Installation of Indoor Unit Installation

6. Drain pipe connection

Fig.1 Fig.2

Pipe clamp Upward


routing Hanger
distance
not allowed Max 300mm Hanger bracket
Indoor unit 1~15m
Metal
clamp

drain head
* height of
slope (1/50~1/100 )
Flexible drain hose

Thermal Insulation
Drain Pump
※ According to type of indoor unit, external appearance could be different.
※ * : drain head height should be considered by dimensional drawings of each models.
※ According to type of indoor unit, external appearance could be different.

Fig.4 Fig.3 Additional extension drain piping


(Field supply part) Insulating tape

Indoor
Unit

Indoor Bigger Ø drain pipes Indoor unit drain hose


Unit
Extension drain piping
(Field supply part)
Indoor
Unit Fig.5 Indoor Unit Indoor Unit Indoor Unit

Face piping
downward
Vent pipe

Face the vent pipe opening facing downward to


keep foreign matter from penetrating the system (Slope of at least 1/100)

• The drain pipe should be at least equal in size to drain conduit of the indoor unit.
• The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
• The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected
a little of water should be added to the drain pan and the drain pump to check and see if it is functioning correctly.
• All connections should be secure. (Special care is needed with PVC pipe)

■ Dimension of drain pipe connection [Fig.1, Fig.2]


• Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit and drain piping fittings should be referenced from
‘Specifications’ of each models.
- Piping material: Use the Polyvinyl chloride pipe. VP 20 or VP 25 pipe fittings.
• Be sure to install heat insulation on the drain piping.
- Heat insulation material: Polyethylene foam with thickness more than 8 mm (5/16 inch).
• Possible drain head height is specified to range of 700 ~ 800 mm(27-6/19 ~ 31-1/2 inch).
So the drain head should be installed below that (Refer to Dimensional Drawings of each).

■ Connection of an auxiliary(flexible) drain hose [Fig.3]


• To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used.
Auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.
< ! > CAUTIONS
• The supplied flexible drain hose should not be curved, neither screwed.
The curved or screwed hose may cause a leakage of water.
• It is need to insulate the auxiliary drain hose with thermal insulation material.
- When extending the drain hose, use a commercially available drain extension hose, and be sure to insulate the extended
section of the drain hose which is indoors.
- Make sure the diameter of the extension drain piping is the same as the indoor unit drain hose size or bigger.

■ Ground drain piping [Fig.4, Fig.5]


• Select diameter of drain piping which adapts to the capacity of the unit connected. The pipe down from the combination
should be as large as possible.
• The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.
• Face the vent pipe opening facing downward to keep foreign matter from penetrating the system.

12
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com

Copyright 2022 LG Electronics Inc.


All Rights Reserved.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.