PDB - SCAC - Unidades Internas
PDB - SCAC - Unidades Internas
PDB - SCAC - Unidades Internas
MFL67986347
Region : Brazil
Published on Dec. 26, 2022
Single Indoor Unit
General Information
Model Line Up
Single Indoor Unit General Information
1. Model Line Up
Capacity
Product Chassis Index Model Name
kW
5.3 ATNW18GTLP1
Ceiling Cassette 1-Way TT
7.0 ATNW24GTLP1
5.3 ATNW18GPLP1
TP
7.0 ATNW24GPLP1
Ceiling Cassette 4-Way TN 10.6 ATNW36GNLP1
14.1 ATNW48GMLP1
TM
17.6 ATNW60GMLP1
VM1 10.6 AVNW36GM1P1
Ceiling Suspended 14.1 AVNW48GM2P1
VM2
17.6 AVNW60GM2P1
1
Single Indoor Unit
Product Data
Ceiling Cassette 1-Way
Ceiling Cassette 4-Way
Ceiling Suspended
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TT
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198 ~ 242
Limit Range of Voltage(Case 2) V -
kW 4.69
Cooling Capacity Nominal
Btu/h 16,000
kW 5.28
Heating Capacity Nominal
Btu/h 18,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 13.3 / 11.8 / 10.8
Air Flow Rate Range(Min~Max) m³/min 10.8~13.3
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 30
Output
No. 1
Dehumidification Rate - ℓ/h -
Rows x Columns x FPI - 2 x 12 x 18
No. - 1
Heat Exchanger
Fin Type - Slit(Half)
Face Area m² 0.24
Net(W x H x D) mm 1,180 x 132 x 450
Dimensions
Shipping(W x H x D) mm 1,445 x 252 x 538
Net kg 14.5
Weight
Shipping kg 17.5
Color - White
Exterior
RAL (Classic) - RAL 9003
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) Φ32(1-1/4)/Φ25(31/32)
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 45.0 / 42.0 / 39.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 45.0 / 42.0 / 39.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
1-1
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
1-2
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
1-3
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
1-4
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
1-5
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
1-6
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.4 Dimensions
1.4.1 Product_Panel : PT-UTC
DWG No. : TBA35228601_Rev.01
Chassis code : TT
1-7
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.4.2 Product_Panel : PT-TAHG0
P
DWG No. : TBA36268301_Rev02
Chassis code : TT
1-8
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.4.3 Product_Panel : PT-TPHG0
DWG No. : TBA36268303_Rev03
Chassis code : TT
1-9
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.4.4 Install Space
≥ 10(13/32)
Ceiling Ceiling
Ceiling board Indoor unit Ceiling board
Indoor unit Ceiling
Ceiling board
board
≤ 300(11-13/16)
≥ 1000(39-3/8)
Air Outlet
≥ 500(19-11/16) Air Inlet
≥ 500(19-11/16)
A*
≥ 20(25/32)
A*
≥ 1,500(59-1/16)
[Unit:mm(inch)] [Unit:mm(inch)]
Floor Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
1-10
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
Thermistor for
Evaporator inlet Humid sensor
temperature
1-11
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1-12
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
High
70
Octave Band Sound Pressure Level (0 dB = 20 μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1 000 2 000 4 000 8 000
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
1-13
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
.5
1
0.53
.5
0.5 1 4
2
5
0.
2m
1 0.5
5
2.
1
0.5
0.5
1.5
1.5
2
0.5
1m
1.5
1
1
0.5
0.5
.5
0.5
0
5m 4m 3m 2m 1m 0
Temperature [°C]
32 32
8
30
202
30
30
18
22
28 2m
22
26
30
2628
24
24
28
32
1m
28
24
28
30
26
2826 24
0
5m 4m 3m 2m 1m 0
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-14
Single Indoor Unit Ceiling Cassette 1-Way Product Data
1. ATNW18GTLP1
1.8.2 Heating operation
Discharge angle: 60°
1
43.5
01.5
5
0.
2
5
2.
0.5
2m
0.5
1.5
2
0.5
0.5
1.5
0.5
1
1m
1.5
1
0.5
0.5
0.5
0
5m 4m 3m 2m 1m 0
Temperature [°C]
31 32 32 34
35
3364
32 32 1
4
40
39
2m
38
3 5 33
31
33
31
32
36
37
1m
36
34
36
34
35
33
36
33
34
31
0
5m 4m 3m 2m 1m 0
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-15
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TT
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198 ~ 242
Limit Range of Voltage(Case 2) V -
kW 6.16
Cooling Capacity Nominal
Btu/h 21,000
kW 6.74
Heating Capacity Nominal
Btu/h 23,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 16.0 / 14.0 / 12.0
Air Flow Rate Range(Min~Max) m³/min 12.0~16.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 30
Output
No. 1
Dehumidification Rate - ℓ/h -
Rows x Columns x FPI - 2 x 12 x 18
No. - 1
Heat Exchanger
Fin Type - Slit(Half)
Face Area m² 0.24
Net(W x H x D) mm 1,180 x 132 x 450
Dimensions
Shipping(W x H x D) mm 1,445 x 252 x 538
Net kg 14.5
Weight
Shipping kg 17.5
Color - White
Exterior
RAL (Classic) - RAL 9003
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) Φ32(1-1/4)/Φ25(31/32)
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 46.0 / 43.0 / 40.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 46.0 / 43.0 / 40.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
2-1
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
2-2
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
2-3
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
2-4
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
2-5
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
2-6
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.4 Dimensions
2.4.1 Product_Panel : PT-UTC
DWG No. : TBA35228601_Rev.01
Chassis code : TT
2-7
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.4.2 Product_Panel : PT-TAHG0
P
DWG No. : TBA36268301_Rev02
Chassis code : TT
2-8
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.4.3 Product_Panel : PT-TPHG0
DWG No. : TBA36268303_Rev03
Chassis code : TT
2-9
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.4.4 Install Space
≥ 10(13/32)
Ceiling Ceiling
Ceiling board Indoor unit Ceiling board
Indoor unit Ceiling
Ceiling board
board
≤ 300(11-13/16)
≥ 1000(39-3/8)
Air Outlet
≥ 500(19-11/16) Air Inlet
≥ 500(19-11/16)
A*
≥ 20(25/32)
A*
≥ 1,500(59-1/16)
[Unit:mm(inch)] [Unit:mm(inch)]
Floor Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
2-10
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
Thermistor for
Evaporator inlet Humid sensor
temperature
2-11
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2-12
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
70
Octave Band Sound Pressure Level (dB = 20 Pa )
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
Hearing NC-20
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
2-13
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.0 2m
1.0
1m
0.5
0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
2.7m
20
2m
22
24
1m
26
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-14
Single Indoor Unit Ceiling Cassette 1-Way Product Data
2. ATNW24GTLP1
2.8.2 Heating operation
Discharge angle: 60°
2.7m
2m
2.5
2.0 1m
0.5
1.5 1.0
0m
0m 1m 2m 3m 4m 5m 6m 7m
Temperature [°C]
2.7m
2m
32
26 1m
30
28
0m
0m 1m 2m 3m 4m 5m 6m 7m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-15
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TP
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 5.28
Cooling Capacity Nominal
Btu/h 18,000
kW 5.28
Heating Capacity Nominal
Btu/h 18,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 16.5 / 14.5 / 13.0
Air Flow Rate Range(Min~Max) m³/min 13.0~16.5
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Dehumidification Rate - ℓ/h 1.30
Rows x Columns x FPI - 2 x 8 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 36.0 / 34.0 / 32.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 36.0 / 34.0 / 32.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
1-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.6
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
1-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
1-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
1-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
1-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1.4 Dimensions
1.4.1 Product
PT-M*HW0
1-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1.4.2 Install Space
Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board
≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
1-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
High
70
Octave Band Sound Pressure Level (0dB = 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
1-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
2.7m
0.25 1.2
2m
0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
25 25 2.7m
3.2m
2m
24 24
2m
23 23
1m
22 22 1m
23 23
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data
1. ATNW18GPLP1
1.8.2 Heating
Discharge angle: 50°
2.7m
0.25 0.25
2m
0.25
0.25 0.25 1m
0.5 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
2.7m
27 27
2m
26 26
28 32 32 28
29 29
31 31 1m
30 30
25
25
23 23
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TP
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 7.03
Cooling Capacity Nominal
Btu/h 24,000
kW 7.62
Heating Capacity Nominal
Btu/h 26,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 17.0 / 15.0 / 13.0
Air Flow Rate Range(Min~Max) m³/min 13.0~17.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Dehumidification Rate - ℓ/h 2.40
Rows x Columns x FPI - 2 x 8 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Mornig Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
2-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.6
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
2-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
2-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
2-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
2-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2.4 Dimensions
2.4.1 Product
PT-M*HW0
2-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2.4.2 Install Space
Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board
≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
2-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
80
■ High
▲ Middle
75 ● Low
70
Octave Band Sound Pressure Level (dB = 20μPa )
65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25
20 NC-25
Approximate
Hearing NC-20
15 Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
2-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
0.25
2.7m
3.2m
0.25
0.25 0.25
0.25 2m
2m
2.0 2.0
0.25
0.5 0.25
1m
1m
0.25 0.25
1.0 1.0
0.5 1.5
1.5 0.5
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Temperature [°C]
2.7m
3.2m
24 24
21 21 2m
23 23 2m
23
1m
1m
22 22 22
23
23 23
22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data
2. ATNW24GPLP1
2.8.2 Heating
Discharge angle: 50°
2.7m
0.25 0.25
0.25
0.25 0.25
2m
0.25 0.25
0.25
1m
1.0 0.25 1.0
0.5 0.5
0.25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
27
2.7m
27
29 2m
32
28
26 27
27 32 29
1m
31 31 27
26
29
27
28 26
25 24 25 24 25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TN
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 9.09
Cooling Capacity Nominal
Btu/h 31,000
kW 10.55
Heating Capacity Nominal
Btu/h 36,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Trubo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 23.0 / 21.0 / 19.0
Air Flow Rate Range(Min~Max) m³/min 19.0~23.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 2.50
Rows x Columns x FPI - 2 x 10 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.43
Net(W x H x D) mm 840 x 246 x 840
Dimensions
Shipping(W x H x D) mm 922 x 318 x 917
Net kg 25.5
Weight
Shipping kg 29.7
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
3-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
3-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
3-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
3-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
3-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3.4 Dimensions
3.4.1 Product
3-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3.4.2 Install Space
Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board
≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
3-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
High
Octave Band Sound Pressure Level (0dB = 20µPa)
70
NC -65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
3-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
2.7m
3.2m
0.25 0.25
0.5
2m
2m
Temperature [°C]
23 23 2.7m
3.2m
2m
2m
21 21
22 22
20 20 1m
1m
21
21 21 21
22 22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
3-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data
3. ATNW36GNLP1
3.8.2 Heating
Discharge angle: 50°
2.7m
2m
0.25 0.25
0.25 0.25
0.25
0.25 1m
1.0
1.5 0.5 1.5
0.5 1.0 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
25 25
2.7m
26 26
27 27
2m
31 31
29 29
33
1m
27 28 28 27
32 32 28
28
25 29 30 30 29 25
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
3-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TM
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 13.78
Cooling Capacity Nominal
Btu/h 47,000
kW 15.53
Heating Capacity Nominal
Btu/h 53,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 31.0 / 28.0 / 25.0
Air Flow Rate Range(Min~Max) m³/min 25.0~31.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 5.20
Rows x Columns x FPI - 3 x 12 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.53
Net(W x H x D) mm 840 x 288 x 840
Dimensions
Shipping(W x H x D) mm 922 x 360 x 917
Net kg 28.5
Weight
Shipping kg 33.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
4-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
4-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
4-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
4-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
4-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4.4 Dimensions
4.4.1 Product
PT-M*HW0
4-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4.4.2 Install Space
Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board
≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
4-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
70
Sound Pressure Level (dB re 20Pa )
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
0.5 0.5 2m
2m
0.5
Temperature [°C]
23 23 3.2m
3.2m
3m
20 20 2m
22 22 22 22
21 23 23 21 1m
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
4-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data
4. ATNW48GMLP1
4.8.2 Heating
Discharge angle: 50°
2m
1.0 1.0
0.25 1.5 1.5 0.25 1m
0.25
0.25 0.25
0.5 0.5 0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
26 26 3.2m
28 31 27 3m
27 28
29 29
2m
34 34
33 32 33
1m
32 32
30 30
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
4-12
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - TM
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 14.65
Cooling Capacity Nominal
Btu/h 50,000
kW 17.00
Heating Capacity Nominal
Btu/h 58,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - 2D Turbo
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 31.0 / 28.0 / 25.0
Air Flow Rate Range(Min~Max) m³/min 25.0~31.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Dehumidification Rate - ℓ/h 6.30
Rows x Columns x FPI - 3 x 12 x 19
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.53
Net(W x H x D) mm 840 x 288 x 840
Dimensions
Shipping(W x H x D) mm 922 x 360 x 917
Net kg 28.5
Weight
Shipping kg 33.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) 32.0 / 25.0
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
5-1
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.8
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
5-2
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
5-3
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
5-4
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
5-5
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5.4 Dimensions
5.4.1 Product
PT-M*HW0
5-6
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5.4.2 Install Space
Notes
≥ 10(13/32)
[Unit:mm(inch)]
1. * : Minimum Installation Space to Air flow direction
A separation distance of at least 1,500 mm is required
Ceiling throughout the airflow direction.
Ceiling board
≤ 300(11-13/16)
Ceiling board
2. ** : A, Installation Height from the floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
5-7
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5-8
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5-9
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
70
Sound Pressure Level (dB re 20Pa )
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5-10
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
0.5 0.5 2m
2m
0.5
Temperature [°C]
23 23 3.2m
3.2m
3m
20 20 2m
22 22 22 22
21 23 23 21 1m
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
5-11
Single Indoor Unit Ceiling Cassette 4-Way Product Data
5. ATNW60GMLP1
5.8.2 Heating
Discharge angle: 50°
2m
1.0 1.0
0.25 1.5 1.5 0.25 1m
0.25
0.25 0.25
0.5 0.5 0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
26 26 3.2m
28 31 27 3m
27 28
29 29
2m
34 34
33 32 33
1m
32 32
30 30
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
5-12
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
1.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM1
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 8.79
Cooling Capacity Nominal
Btu/h 30,000
kW 9.97
Heating Capacity Nominal
Btu/h 34,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 1
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 20.0 / 18.0 / 16.0
Air Flow Rate Range(Min~Max) m³/min 16.0~20.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 85.9
Output
No. 1
Dehumidification Rate - ℓ/h 3.80
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.31
Net(W x H x D) mm 1,200 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,315 x 317 x 768
Net kg 28.4
Weight
Shipping kg 34.3
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
1-1
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA / Ma
A 0.5
x)
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
1-2
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
1-3
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
1-4
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
1-5
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
1.4 Dimensions
1.4.1 Product
DWG No. : TAZ35326401_Rev01
Chassis code : VM1
1-6
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
1.4.2 Installation Space
[Unit: mm(inch)]
≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle
≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)
Floor
≥ 700(27-9/16) ≥ 700(27-9/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
1-7
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
Heating
Strainer
1-8
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
CN1
CN_PTC
MEZ67351819
1-9
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
■ High
▲ Middle
● Low
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
1-10
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
1.5 2m
1.0
1m
0.5
0.25
0m
10m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Temperature [°C]
18 2.7m
2.7m
20 19
21
22
2m
23
24
25
26 1m
0m
10m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-11
Single Indoor Unit Ceiling Suspended Product Data
1. AVNW36GM1P1
1.8.2 Heating operation
Discharge angle: 0°
Temperature [°C]
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
1-12
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
2.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM2
Case 1 - 220-230-240, 1, 50
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 13.78
Cooling Capacity Nominal
Btu/h 47,000
kW 15.53
Heating Capacity Nominal
Btu/h 53,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 2
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Air Flow Rate Range(Min~Max) m³/min 20.0~30.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 125
Output
No. 1
Dehumidification Rate - ℓ/h 6.50
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.46
Net(W x H x D) mm 1,600 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,715 x 317 x 768
Net kg 36.9
Weight
Shipping kg 45.5
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
2-1
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
2-2
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
2-3
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
2-4
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
2-5
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
2.4 Dimensions
2.4.1 Product
DWG No. : TAZ35266401_Rev01
Chassis code : VM2
2-6
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
2.4.2 Installation Space
[Unit: mm(inch)]
≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle
≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)
Floor
≥ 700(27-9/16) ≥ 700(27-9/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
2-7
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
Humid sensor
Thermistor for
evaporator outlet
temperature
Liquid pipe connection port
(flare connection)
Capillary Tube
Strainer
2-8
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
CN1
CN_PTC
MEZ67351819
2-9
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
■ High
▲ Middle
● Low
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
2-10
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
3.0
2.7m
2.7m
2.5
2.0
1.5
2m
2m
1.0
0.5
1m
1m
0.25
0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Temperature [°C]
16 2.7m
2.7m
17
18
19
20 2m
2m
21
1m
1m
22
0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-11
Single Indoor Unit Ceiling Suspended Product Data
2. AVNW48GM2P1
2.8.2 Heating operation
Discharge angle: 0°
Temperature [°C]
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
2-12
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
3.1 Specifications
Category
Unit Specification
Major Minor
Classification Chassis - VM2
Case 1 - 220, 1, 60
Case 2 - -
Power Supply
Limit Range of Voltage(Case 1) V 198~242
Limit Range of Voltage(Case 2) V -
kW 15.24
Cooling Capacity Nominal
Btu/h 52,000
kW 17.00
Heating Capacity Nominal
Btu/h 58,000
Power Input(Indoor) H/M/L W -
Running Current H/M/L A -
Type - CFF
Quantity EA 2
Indoor Fan Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Air Flow Rate Range(Min~Max) m³/min 20.0~30.0
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 125
Output
No. 1
Dehumidification Rate - ℓ/h 6.50
Rows x Columns x FPI - 3 x 18 x 18
No. - 1
Heat Exchanger
Fin Type - Louver
Face Area m² 0.46
Net(W x H x D) mm 1,600 x 235 x 690
Dimensions
Shipping(W x H x D) mm 1,715 x 317 x 768
Net kg 36.9
Weight
Shipping kg 45.5
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - Thermal Protector for Fan Motor
Type - R410A
Refrigerant
Control Type - -
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.5 / 16.0
Drain Pipe(using Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) - / 50.0 / 46.0 / 42.0
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
3-1
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
Category
Unit Specification
Major Minor
Power Supply Type to Indoor - - -
Electrical Characteristic Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code.
And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard.
Therefore, these values depend on the ambient conditions and values are normally higher in actual operation.
3-2
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
3-3
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard II / III wired remote controller.
■ *** : This functions need to connect to the Standard III wired remote controller.
3-4
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ Air Purification Kit and Auto Elevation Grille are not appliable at the same time.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
3-5
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
3.4 Dimensions
3.4.1 Product
DWG No. : TAZ35266401_Rev01
Chassis code : VM2
3-6
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
3.4.2 Installation Space
[Unit: mm(inch)]
≥ 10 (13/32)
≥ 300 (11-13/16)
Obstacle
≥ 2500 (98-3/7)
≥ 300 (11-13/16)
≤ 200 (7-7/8)
Floor
≥ 700(27-9/16) ≥ 700(27-9/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
3-7
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
Humid sensor
Thermistor for
evaporator outlet
temperature
Liquid pipe connection port
(flare connection)
Capillary Tube
Strainer
3-8
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
CN1
CN_PTC
MEZ67351819
3-9
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
■ High
▲ Middle
● Low
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
3-10
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
3.0 2.7m
2.7m
2.5
2.0
1.5
1.0 2m
2m
0.5
0.25
1m
1m
0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Temperature [°C]
16 2.7m
2.7m
17
18
19
20 2m
2m
21
1m
1m
0m
0m
10m
10m 9m 8m
8m 7m 6m
6m 5m 4m
4m 3m 2m
2m 1m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
3-11
Single Indoor Unit Ceiling Suspended Product Data
3. AVNW60GM2P1
3.8.2 Heating operation
Discharge angle: 0°
Temperature [°C]
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
3-12
Accessory
Front Panel
Air Purification Kit
Front Panel Accessory
1. PT-AAGW0
1.1 Specifications
Category
Unit Specification
Major Minor
Factory model - PT-AAGW0
Model Name
Buyer model - PT-AAGW0
Panel Type - - Standard
Glossy / Matt - -
Color - White
Panel Exterior
RAL (Classic) - RAL 9003
Grille Type (Grille / Grid) - Grid
Net (W x H x D) mm 950 x 35 x 950
Panel Dimension
Shipping (W x H x D) mm 1,006 x 102 x 1,006
Net kg 7.1
Panel Weight
Shipping kg 9.3
Panel Function PM1.0 Sensor - X
Air Purification Kit - X
Panel Accessory Floor Detection Sensor - PTFSMA0
Human Detection Sensor - PTVSAA0
Note
■ Some functions need to connect to the Standard III wired remote controller.
■ Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field
1
Front Panel Accessory
2. PT-AFGW0
2.1 Specifications
Category
Unit Specification
Major Minor
Factory model - PT-AFGW0
Model Name
Buyer model - PT-AFGW0
Panel Type - - Premium
Glossy / Matt - -
Color - White
Panel Exterior
RAL (Classic) - RAL 9003
Grille Type (Grille / Grid) - Grid
Net (W x H x D) mm 950x35x950
Panel Dimension
Shipping (W x H x D) mm 1,006x117x1,006
Net kg 7.50
Panel Weight
Shipping kg 9.40
Panel Function PM1.0 Sensor - O
Air Purification Kit - PTAHMP0
Panel Accessory Floor Detection Sensor - PTFSMA0
Human Detection Sensor - PTVSAA0
Note
■ Some functions need to connect to the Standard III wired remote controller.
■ Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field
2
Air Purification Kit Accessory
1. PTAHMP0
1.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TP/TN/TM/TP-B/TM-A
Air Purification Kit
Applied Panel - PT-MPGW0 (U-style) / PT-AFGW0 (Dual Vane)
Size(W x H x D) mm 59 x 45 x 22
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 X 50 X 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.2kV
Size(W x H x D) mm 500 x 38 x 395
PM 1.0 Filter
Weight g 2,090
Material - Pulp + Carbon (Corrugate)
Deodorization Filter Size(W x H x D) mm 478 x 14 x 138
Weight g 180
Size(W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer
Output - -3.2kV
Amount of Ion Emission EA / cc 3,000,000
3
Air Purification Kit Accessory
2. PTAHTP0
2.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TU / TT
Air Purification Kit
Applied Panel - PT-UPHG0 / PT-TPHG0
Size(W x H x D) mm 59 x 45 x 22
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 X 50 X 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.2kV
Size(W x H x D) mm 524 x 18 x 141
PM 1.0 Filter
Weight g 430
Material - Pulp + Carbon (Corrugate)
Deodorization Filter Size(W x H x D) mm 301 x 11 x 100
Weight g 40
Size(W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer
Output - -3.2kV
Amount of Ion Emission EA / cc 3,000,000
4
Air Purification Kit Accessory
3. PTAHYP0
3.1 Specifications
Category
Unit Specification
Major Minor
Applied Chassis - TY
Air Purification Kit
Applied Panel - -
Size(W x H x D) mm 59 x 45 x 16.6
PM 1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size(W x H x D) mm 99 x 50 x 30
HVPS Input - DC 12V
Output(Electrification / Dust Collection) - -7.7kV / -5.7kV
Size(W x H x D) mm 500 x 38 x 395
PM 1.0 Filter
Weight g 2,090
Material - Pulp + Carbon(corrugate)
Deodorization Filter Size(W x H x D) mm 478 x 14 x 138
Weight g 180
Size(W x H x D) mm -
Input - -
Ionizer
Output - -
Amount of Ion Emission EA / cc -
5
Installation
The type of refrigerant applied depends on the outdoor unit cycle configuration. Ensure the refrigerant type
in the specification of the indoor unit and outdoor unit to be installed.
1
Installation of Indoor Unit Installation
Indoor unit
The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.
2
Installation of Indoor Unit Installation
3
Installation of Indoor Unit Installation
The type of refrigerant applied depends on the outdoor unit cycle configuration. Ensure the refrigerant type
in the specification of the indoor unit and outdoor unit to be installed.
4
Installation of Indoor Unit Installation
1.4 Minimum Floor Area for Installation fo R32 model : accordance with IEC05
600
Floor location
500
Minimum Area for installation ( m² )
400
300
200
100
Wall mounted
Ceiling mounted
0
0 1 2 3 4 5 6 7 8
Total refrigerant amount in the system ( kg )
<!> CAUTIONS
• "Minimum Area for installation" might be different by revision of IEC regulation. "Minimum Area for installation" should be
selected in accordance with that revision based on the local and national environment.
5
Installation of Indoor Unit Installation
1.5 Minimum Floor Area for Installation fo R32 model : accordance with IEC06
2500
Floor standing
2000
Minimum Area for installation ( m² )
1500
1000
500
Wall mounted
Ceiling mounted
0
0 2 4 6 8 10 12 14 16
Total refrigerant amount in the system ( kg )
<!> CAUTIONS
• "Minimum Area for installation" might be different by revision of IEC regulation. "Minimum Area for installation" should be
selected in accordance with that revision based on the local and national environment.
6
Installation of Indoor Unit Installation
When selecting a location the product is installed, it is recommended to consider the following:
7
Installation of Indoor Unit Installation
Fig1. High Ceiling Space Fig2. Surface adjacent with outdoor air Fig3. High temperature or humidity
Fig.3-1 Additional insulation required
Indoor
Low temperature
of the floor
High elevation of the ceiling
Discharge
Suction
Hot air Fig.3-2 Ceiling near the tight seal places
Outdoor side (50~100mm
Cold air Outdoor (ex. Garage... ) Insulation required)
(Entering of air by
frequent opening side
Outdoor side Outdoor side
and closing of door)
■ In case the floor or surfaces is contact with the outdoor air directly [Fig.2]
If the floor of air conditioned room contact with the outside air, like the store room or garage, the floor temperature will be
decreased and users can have a cold feeling in the feet.
In such places where the feet comes in direct contact with floors will give a cold feeling to the foot.
• Countermeasure method
- Use the carpet on the floor.
(compared to the tiles the carpet over it will have a 3 degree rise in temperature)
- Insulating the floor.
- Floor heating.
<!> CAUTIONS
In case there is a cold air intake, the duct surface may have some dew drops.
So a insulation on the duct is a must.(Insulation material: a glass wool of thickness 25 mm will be appropriate.)
8
Installation of Indoor Unit Installation
4. Connecting pipes
9
Installation of Indoor Unit Installation
5. Electrical Wiring
■ Wiring Connections
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the terminal board
wiring to the outdoor unit and indoor units are properly matched.
If wiring and piping between the outdoor unit and indoor unit are mismatched, the system may cause a malfunction.
< ! > CAUTIONS
• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of the wires.)
• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign particle
from outside. Otherwise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly by arranging the
wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts box cover, make sure no
wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the
same locations outside of the unit, separating them properly, otherwise electrical noise (external static) could cause
product malfunction.
10
Installation of Indoor Unit Installation
5. Electrical Wiring
• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
• Install the remote controller about 1.5m (5ft) above the floor in an area with good air circulation at an average temperature.
• Do not install the remote controller where it can be affected by :
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED display. For proper display of the remote controller LED's,
the remote controller should be installed properly.
(The standard height is 1.2~1.5 m (4~5ft) from floor level.)
11
Installation of Indoor Unit Installation
Fig.1 Fig.2
drain head
* height of
slope (1/50~1/100 )
Flexible drain hose
Thermal Insulation
Drain Pump
※ According to type of indoor unit, external appearance could be different.
※ * : drain head height should be considered by dimensional drawings of each models.
※ According to type of indoor unit, external appearance could be different.
Indoor
Unit
Face piping
downward
Vent pipe
• The drain pipe should be at least equal in size to drain conduit of the indoor unit.
• The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
• The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected
a little of water should be added to the drain pan and the drain pump to check and see if it is functioning correctly.
• All connections should be secure. (Special care is needed with PVC pipe)
12
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.