HD 242 Flexible Hose
HD 242 Flexible Hose
HD 242 Flexible Hose
PVT. LTD.
TECHNICAL DATA
TYPE Braided & Unbraided
SIZES 700mm, 1000mm, 1200mm,
1500mm, 1800mm
MAXIMUM RATED 200 psi and 175 psi*
PRESSURE
HYDRO TEST 263 psi
PRESSURE
BURST PRESSURE 875 psi
MAXIMUM AMBIENT *Mentioned on Pages 2 of 4
TEMPERATURE
END CONNECTION Inlet: 1” BSPT (M) UNBRAIDED
Outlet: 1/2” or 3/4” BSPT (F)
LARGEST SPRINKLER HD-UB: 5.6
K-FACTOR FOR HD-28B: 5.6
1/2” OUTLET
LARGEST HD-UB: 8.0, 11.2
SPRINKLER HD-28B: 8.0, 11.2
K-FACTOR FOR
3/4” OUTLET
FLEXIBILITY Limited
APPROVALS UL Listed / FM Approved
ORDERING Size, Type of Bracket,
INFORMATION Length of Square Bar
*175 psi is only for FM Approved Flexible Drops
BRAIDED
APPLICATION
Sprinkler Flexible Drop system is a ready to use
Min.Bend Radius as
assembly to fit sprinkler heads in desired location in per Technical Details
a suspended ceiling. It easily positions the sprinkler
in center of the ceiling tile at a correct height.
Installation can be done in 10 to 15 minutes and does
not require any special preparation.
The flexible drop system is a complete unit in itself
which includes a corrugated stainless steel flexible PART
NO
DESCRIPTION
Equivalent
Rated Max. No.
Nominal Min. Bend Length of 1 in.
Pressure Max. Assembly of
Inlet Radius in. Schedule, 40
Model psig Ambient Length, ft. 90o Bends
X Outlet Steel Pipe, ft
Temp.oF (mm)
Size, In.
UL FM UL FM UL FM UL FM
(Figure 4)
Disconnect the nipple from Flexible Sprinkler Drop.
Assemble nipple to the main piping system of the
building with normal sealing procedures and tighten
it closely to ensure a leak-proof connection as shown
in the picture (Fig 4). Recommended torque for this
work is 950~1,000 kgf.cm. Check that the gasket
and the isolation ring are properly placed at the end
of the Flexible Drop. Connect the Flexible Drop to the
(Figure1) Nipple by tightening the nut closely. Recommended
torque for this work is 320 kgf.cm
(General features of HD-FLEX Sprinkler Drop with
fittings and ceiling structure when assembled) C. Connecting square bar on the ceiling structure
2. Parts List
(Figure 5)
a) Join the two end brackets and middle bracket to the
(Figure 2) square bar and place the end brackets properly the
aimed ceiling structure as shown in the picture.
Part No. Part Name Material Qty. Remark (Figure 5) (The maximum distance between two end
1 Flexible Tube STS304 1 0.3mm brackets is 1500mm & minimum 600mm).
2 Reducer STPG370 1 Zn plated
b) Fasten the wing bolts on top of the end brackets
3 Nipple STPG370 1 Zn plated tightly. Recommended torque for this work is 20-25
4 Nut S10C 2 Zn plated kgf.cm (Figure 5).
5 Gasket EPDM 2 -
c) Push the end brackets into the ceiling structure
6 Isolation Ring NYLON66 2 - rail and check that the end brackets sit on the
7 Middle Bracket STEEL 1 Zn plated ceiling structure properly.
8 End Bracket STEEL 2 Zn plated d) Fasten the wing bolts on the side of the end
9 Square Bar GI PIPE 1 Zn plated brackets. Recommended torque for this work
700mm Long is 25~30 kgf.cm.
CENTRE BRACKET
B-CC-B CENTRE BRACKET
B-C1-H
SIDE BRACKET
B-ES-H
(Figure 6)
Open the middle bracket cover and position the
Reducer inside the middle bracket properly.
SIDE BRACKET SIDE BRACKET
Close the middle bracket cover and fasten the wing B11 B12
bolt firmly. Recommended torque for this work is
25~30 kgf.cm (Figure 6). Every Flexible Drop is accompanied by inlet nipple,
outlet reducing nipple, 700mm square bar and
brackets suitable to ceiling type.
Contact HD Sales for more information on type of
brackets and accessories to be used.
LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.