Data sheet 3RV1011-0JA10

Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.7...1 A N-
release 13 A Screw terminal Standard switching capacity

product brand name SIRIUS


product designation Circuit breaker
design of the product For motor protection
product type designation 3RV1
General technical data
size of the circuit-breaker S00
size of contactor can be combined company-specific S00
product extension auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 5.5 W
● at AC in hot operating state per pole 1.8 W
insulation voltage with degree of pollution 3 at AC rated value 690 V
surge voltage resistance rated value 6 kV
mechanical service life (operating cycles)
● of the main contacts typical 100 000
● of auxiliary contacts typical 100 000
electrical endurance (operating cycles) typical 100 000
type of protection according to ATEX directive 2014/34/EU Ex II (2) GD
certificate of suitability according to ATEX directive 2014/34/EU DMT 02 ATEX F 001
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 01/01/2013
SVHC substance name Blei - 7439-92-1
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
relative humidity during operation 10 ... 95 %
Main circuit
number of poles for main current circuit 3
adjustable current response value current of the current- 0.7 ... 1 A
dependent overload release
operating voltage
● rated value 20 ... 690 V
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operating frequency rated value 50 ... 60 Hz
operational current rated value 1A
operational current

3RV10110JA10 Subject to change without notice


11/27/2023
Page 1/6 © Copyright Siemens
● at AC-3 at 400 V rated value 1A
● at AC-3e at 400 V rated value 1A
operating power
● at AC-3
— at 230 V rated value 0.1 kW
— at 400 V rated value 0.25 kW
— at 500 V rated value 0.4 kW
— at 690 V rated value 0.6 kW
● at AC-3e
— at 230 V rated value 0.1 kW
— at 400 V rated value 0.25 kW
— at 500 V rated value 0.4 kW
— at 690 V rated value 0.6 kW
operating frequency
● at AC-3 maximum 15 1/h
● at AC-3e maximum 15 1/h
Auxiliary circuit
number of CO contacts for auxiliary contacts 0
Protective and monitoring functions
product function
● ground fault detection No
● phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 100 kA
● at AC at 500 V rated value 100 kA
● at AC at 690 V rated value 100 kA
operating short-circuit current breaking capacity (Ics) at AC
● at 240 V rated value 100 kA
● at 400 V rated value 100 kA
● at 500 V rated value 100 kA
● at 690 V rated value 100 kA
response value current of instantaneous short-circuit trip unit 13 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value 1A
● at 600 V rated value 1A
yielded mechanical performance [hp]
● for 3-phase AC motor
— at 575/600 V rated value 0.5 hp
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit trip magnetic
design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V none required
● at 400 V gL/gG 10 A
● at 500 V gL/gG 10 A
● at 690 V gL/gG 10 A
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
height 90 mm
width 45 mm
depth 75 mm
required spacing
● for grounded parts at 400 V
— downwards 20 mm
— upwards 20 mm

3RV10110JA10 Subject to change without notice


11/27/2023
Page 2/6 © Copyright Siemens
— at the side 9 mm
● for live parts at 400 V
— downwards 20 mm
— upwards 20 mm
— at the side 9 mm
● for grounded parts at 500 V
— downwards 20 mm
— upwards 20 mm
— at the side 9 mm
● for live parts at 500 V
— downwards 20 mm
— upwards 20 mm
— at the side 9 mm
● for grounded parts at 690 V
— downwards 20 mm
— upwards 20 mm
— backwards 0 mm
— at the side 9 mm
— forwards 0 mm
● for live parts at 690 V
— downwards 20 mm
— upwards 20 mm
— backwards 0 mm
— at the side 9 mm
— forwards 0 mm
Connections/ Terminals
type of electrical connection
● for main current circuit screw-type terminals
arrangement of electrical connectors for main current Top and bottom
circuit
type of connectable conductor cross-sections
● for main contacts
— solid or stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
tightening torque
● for main contacts with screw-type terminals 0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals 0.8 ... 1.2 N·m
size of the screwdriver tip Pozidriv size 2
design of the thread of the connection screw
● for main contacts M3
Safety related data
proportion of dangerous failures
● with low demand rate according to SN 31920 50 %
● with high demand rate according to SN 31920 50 %
failure rate [FIT] with low demand rate according to SN 50 FIT
31920
B10 value with high demand rate according to SN 31920 5 000
protection class IP on the front according to IEC 60529 IP20
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
display version for switching status Rocker switch
Approvals Certificates
General Product Approval For use in hazardous locations

Confirmation

3RV10110JA10 Subject to change without notice


11/27/2023
Page 3/6 © Copyright Siemens
Declaration of Conformity Test Certificates Marine / Shipping

Type Test Certific- Special Test Certific-


ates/Test Report ate

Marine / Shipping other

Confirmation

other Railway

Miscellaneous Special Test Certific-


ate

Further information
Siemens has decided to exit the Russian market (see here).
https://press.siemens.com/global/en/pressrelease/siemens-wind-down-russian-business
Siemens is working on the renewal of the current EAC certificates.
Please contact your local Siemens office on the status of validity of the EAC certification if you intend to import or offer to supply these products to an
EAC relevant market (other than the sanctioned EAEU member states Russia or Belarus).
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1011-0JA10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1011-0JA10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-0JA10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1011-0JA10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV1011-0JA10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1011-0JA10&objecttype=14&gridview=view1

3RV10110JA10 Subject to change without notice


11/27/2023
Page 4/6 © Copyright Siemens
1/L1

3/L2

5/L3

-F

I> I> I>


2/T1

4/T2

6/T3

last modified: 9/1/2023

3RV10110JA10 Subject to change without notice


11/27/2023
Page 5/6 © Copyright Siemens
3RV10110JA10 Subject to change without notice
11/27/2023
Page 6/6 © Copyright Siemens

You might also like