DIII-NET/Modbus Adapter
Connect VRV System through Modbus Protocol Model Compatibility
The DIII-NET/Modbus Adapter enables the connection of VRV For use with the following VRV outdoor unit models:
system through Modbus communication to an automated RXYQ_TTJU, RXYQ_TYDN, RXYMQ_PVJU*
frontend system. With this adapter, third-party controllers For use with all VRV indoor unit models and the following
can monitor and control VRV indoor units through the RS485 SkyAir indoor units: FAQ, FBQ, FCQ, FHQ, FTQ
Modbus Protocol. This adapter can be mounted to the VRV
outdoor or indoor unit. A maximum of 2 outdoor units and For use with the following Daikin Ductless indoor unit models:
16 indoor units can be connected to the adapter. CDXS, CTXS, FDXS, FTXS, FTXN (FTXN requires KRP980B1/2
interface adapter) with the use of the KRP928BB2S
(DIII-Net Adapter)
*Notes:
1. Outdoor unit models not listed above will require a separate
16 VDC field supplied power supply and mounting box.
2. For outdoor units not listed above the adapter may be
mounted in the indoor unit and used to provide 16 VDC
to the adapter.
KRP928BB2S
VRV III-S
DTA116A51
SPECIFICATIONS COMMUNICATIONS SPECIFICATIONS
Connection DIII-NET (F1F2) Communication protocol Modbus RTU
Protocol Modbus (RS485) Communication speed 9600/19200bps
Connectable indoor units Up to 16 VRV indoor units Stop bit 1/2 bit
Connectable outdoor units Up to 2 VRV outdoor units Parity odd/even/none
Communication wire 18AWG-2, no polarity, stranded, non-shielded Data length 8 bit
Total wiring length less than 1,640 ft Modbus address range 1 to 15
FUNCTIONS
Monitor
On/Off On/Off status of indoor units
Operation mode Cool, Heat, Fan, Dry, Auto
Setpoint Setpoint for indoor units
Room temperature Return air temperature at indoor unit or remote controller
Louver direction Swing, louver position (depend on indoor unit model)
Fan speed L, M, H (depend on indoor unit model)
Forced off status Forced off status of indoor units
Error Malfunction, Warning with Error code
Filter sign Filter sign indicator of indoor units
Communication status Communication normal/error of indoor units
Control
On/Off On/Off status of indoor units
Operation mode Cool, Heat, Fan, Dry, Auto
Setpoint Setpoint for indoor units
Louver direction Swing, Stop, louver position (depend on indoor unit model)
Fan speed L, M, H (depend on indoor unit model)
Filter sign reset Reset filter sign indicator of indoor units
OPERATING CONDITIONS
Power supply 16VDC (+10, -5%)
Operating temperature limit -4° to 149° F
Operating humidity limit 0 to 95% non-condensing
Storage temperature range -13° to 167° F
Mass Approximately 0.18 lbs.
Dimensions 3.94” x 3.94”
Modbus is a registered trademark of Schneider Electronic S. A.
PF-DIINET-11_15