The DIII-NET/Modbus Adapter enables connection of VRV systems to automated control systems through the Modbus communication protocol. It allows up to 2 outdoor units and 16 indoor units to be monitored and controlled via an RS485 connection. Key functions include monitoring operation modes, temperatures, and errors, as well as controlling on/off status, operation modes, setpoints, and more.

Uploaded by

Shum Kah Yan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views2 pages

PF Diiinet

The DIII-NET/Modbus Adapter enables connection of VRV systems to automated control systems through the Modbus communication protocol. It allows up to 2 outdoor units and 16 indoor units to be monitored and controlled via an RS485 connection. Key functions include monitoring operation modes, temperatures, and errors, as well as controlling on/off status, operation modes, setpoints, and more.

Uploaded by

Shum Kah Yan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DTA116A51

DIII-NET/Modbus Adapter
Connect VRV System through Modbus Protocol Model Compatibility
The DIII-NET/Modbus Adapter enables the connection of VRV For use with the following VRV outdoor unit models:
system through Modbus communication to an automated RXYQ_TTJU, RXYQ_TYDN, RXYMQ_PVJU*
frontend system. With this adapter, third-party controllers For use with all VRV indoor unit models and the following
can monitor and control VRV indoor units through the RS485 SkyAir indoor units: FAQ, FBQ, FCQ, FHQ, FTQ
Modbus Protocol. This adapter can be mounted to the VRV
outdoor or indoor unit. A maximum of 2 outdoor units and For use with the following Daikin Ductless indoor unit models:
16 indoor units can be connected to the adapter. CDXS, CTXS, FDXS, FTXS, FTXN (FTXN requires KRP980B1/2
interface adapter) with the use of the KRP928BB2S
(DIII-Net Adapter)
*Notes:
1. Outdoor unit models not listed above will require a separate
16 VDC field supplied power supply and mounting box.
2. For outdoor units not listed above the adapter may be
mounted in the indoor unit and used to provide 16 VDC
to the adapter.

Up to 2 outdoor units and 16 indoor units can be connected


VRV IV

KRP928BB2S

VRV indoor unit


RA unit

VRV III-S

VRV indoor unit VRV indoor unit

RS485 Modbus Protocol


Master Controller

DTA116A51
SPECIFICATIONS COMMUNICATIONS SPECIFICATIONS
Connection DIII-NET (F1F2) Communication protocol Modbus RTU
Protocol Modbus (RS485) Communication speed 9600/19200bps
Connectable indoor units Up to 16 VRV indoor units Stop bit 1/2 bit
Connectable outdoor units Up to 2 VRV outdoor units Parity odd/even/none
Communication wire 18AWG-2, no polarity, stranded, non-shielded Data length 8 bit
Total wiring length less than 1,640 ft Modbus address range 1 to 15

FUNCTIONS

Monitor
On/Off On/Off status of indoor units
Operation mode Cool, Heat, Fan, Dry, Auto
Setpoint Setpoint for indoor units
Room temperature Return air temperature at indoor unit or remote controller
Louver direction Swing, louver position (depend on indoor unit model)
Fan speed L, M, H (depend on indoor unit model)
Forced off status Forced off status of indoor units
Error Malfunction, Warning with Error code
Filter sign Filter sign indicator of indoor units
Communication status Communication normal/error of indoor units

Control
On/Off On/Off status of indoor units
Operation mode Cool, Heat, Fan, Dry, Auto
Setpoint Setpoint for indoor units
Louver direction Swing, Stop, louver position (depend on indoor unit model)
Fan speed L, M, H (depend on indoor unit model)
Filter sign reset Reset filter sign indicator of indoor units

Retrieve System Information


Connected indoor units DIII-NET address of connected indoor units can be retrieved.
Indoor unit capabilities Indoor unit capabilities such as operation mode, fan control, setpoint can be retrieved

OPERATING CONDITIONS
Power supply 16VDC (+10, -5%)
Operating temperature limit -4° to 149° F
Operating humidity limit 0 to 95% non-condensing
Storage temperature range -13° to 167° F
Mass Approximately 0.18 lbs.
Dimensions 3.94” x 3.94”
Modbus is a registered trademark of Schneider Electronic S. A.

Find out more about DIII-NET/Modbus Adapter, visit www.daikincity.com or www.daikinac.com