Generator-Protection-Functions-And-Test-Methods-Part 3
Generator-Protection-Functions-And-Test-Methods-Part 3
multiplied by a safety factor of 1.05, the setting value of CHAR. 1 = 1.05 x 0.42 = 0.44 with an
angle of 80deg. Time delay setting 2.0 Second.
CHAR. 2 is set to 0.9 times CHAR. 1 = 0.9 x 0.44 = 0.4 with an angle of 90deg. Time delay
setting 2.0 Second.
CHAR. 3 is set to 2 times CHAR. 1 = 2 x 0.44 = 0.88 with an angle of 100deg. Time delay
setting 0.3 Second.
Note: The below test was performed by means of voltage and current. But an actual setting is given in
susceptance. The susceptance value will be calculated(given above) inside the relay, when we are
injecting voltage and current.
Settings:
Under excitation Protection(with out U/V) : ON
Susceptance Intersect Characteristic 1 : 0.52
Inclination Angle of Characteristic 1 : 80 °
Characteristic 1 Time Delay : 2.00 sec
Susceptance Intersect Characteristic2 : 0.47
Inclination Angle of Characteristic 2 : 90 °
Characteristic 2 Time Delay : 2.00 sec
Susceptance Intersect Characteristic 3 : 0.94
Inclination Angle of Characteristic 3 : 100 °
Characteristic 3 Time Delay : 0.30 sec
9
Characteristics 1 set value 0.52 at 80 deg & 2sec. ( ) Ir from 100mA..
Alarm stage can be set at 50% of continuous withstand capability of the machine with a time delay of 3 to
5 Sec.
10
Settings:
SET % OF I calculated=3 times Injected current Set Time (S) Optd Time
In=Ir Ir=I injected = Ix (A) (S)
Note: In Omicron, for this test change the R, Y, B--Y, B, R or change the Phase angle 0, -120, 120--120, 120, 0
This operates for phase faults in the unit, in the HV yard or in the adjacent transmission lines, with a
suitable time delay. It operates as a backup when the corresponding main protection fails. In A.P. System
the reach is set as 120% of generator transformer with a time delay of about 1.0 to 1.5 Sec.
Settings:
Impedance Protection :ON
Fault Detection I> Pickup :6.50 A
State of Under voltage Seal-in :ON
Under voltage Seal-in Pickup :77.0V
Duration of Under voltage Seal-in :3.00 sec
11
8. OVER FLUXING PROTECTION V/F (24):
It is basically a relay which measures v/f of the generator and transformers. As modern power
transformers are designed to operate at very near saturation flux levels under normal operating conditions,
any increase in the voltage or decrease in the frequency, results in the saturation of the core and the
additional flux tries to find its fault through core bolts damaging the core bolt insulation. To prevent this,
over fluxing relay is used.
Settings:
Calculation:
V/F=110volts/50Hz (Normal)
=2.2=1 P.U
PH-E=121/1.732=69.9V
Note: Here we can keep voltage constant and vary the frequency or frequency constant and voltage is
variable one.
Stage 1:
Voltage Applied in (V) Calc Value in (V) Set Value in Optd Value Set Time Optd
@ 50Hz, Ph-N(In Each V/F in V/F (S) Time(S)
Phase Separately)
69.9 121/ 3=69.85 1.10 1.10 10 10.06
Stage 2:
Voltage Applied Calc Value In Set Value Optd Value Set Time Optd
In Volts At @ 50hz Ph- Volts In V/F V/F (S) Time(S)
N (In Each Phase
Separately)
88.9 154.0/ 3=88.9 1.40 1.40 1.0 0.99
In thermal machines, when the steam flow through turbine is interrupted by closing the ESVs(Electro static
valves) or the governor valves, the remaining steam in the turbine generates (low) power and the machine
enters to motoring conditions drawing power from the system. This protection detects low forward
power conditions of the generator and trips generator breaker after a time delay, avoiding motoring of
generator.
12