Appendix C
Appendix C
Appendix C
(i) All rising mains (dry & wet) shall be made operational for all storeys
(except the uppermost 3 storeys) as soon as the uppermost
completed storey reaches 24m. This is because the uppermost 3
storeys are likely to be strutted with props and scaffoldings for the
purpose of gaining structural strength. Moreover, some of the
staircases may not have been provided yet, hence no access
available to the upper storeys.
(ii) Dry & wet rising mains shall be installed progressively as the
building gains height, in order to provide to fire-fighting
capabilities to all stages of construction. All outlets, landing valves
inlets, water tanks and pumps, where required shall be provided
and made readily operational.
C1
d. Provision of fire engine accessway
(ii) For the testing of flow rate for wet riser system (residential & non-
residential buildings), the topmost landing valve should be tested
(under pump/gravity feed) with a flow rate of at least 27 L/s. This
minimum flow rate required for residential buildings will also be
applicable to non-residential buildings (commercial building), as
the fire hazard in both types of buildings are similar while under
construction.
C2
ANNEX A
C3
7. Flow rate and pressure of wet rising mains
are to comply with the following:
a. Flow rate of topmost 3 landing valves
is not less than 27 l/s;
b. Static pressure at landing valves is less
than 8 bars; and
c. Running pressure is between 2 bars
and 5.5 bars.
8 Lift/passenger hoist ready for firefighters'
use shall be provided for building
exceeding 8 storeys or habitable height
of 24m.
9 Generator set or adequate PUB power
supply shall be provided for emergency
lighting and fire-fighting purpose.
10 Provision of adequate fire engine
accessway (where practicable) for fire-
fighting purpose.
11 Adequate portable fire extinguishers to
be provided on each floor. Fire
extinguisher of 13A rating for every
500sq.m.
Date inspected:____________by______________________Signature_____________
*Delete as appropriate
C4
ANNEX A
RISER
5 Air relief valve provided
6 Labeled & numbered
accordingly
7 Earthing provided
LANDING VALVE
8 Blank cap provided
9 Strapped and padlock in
closed position
10 Clear of obstruction
TESTING OF PRESSURE/FLOW
11 Dry rising mains
a. Pressure constant at 300
psi (20.7 bar) for 30 mins.
b. Regularly tested
12 Wet rising mains
a. Static pressure shall not
be less than 8 bar
b. Topmost landing valve
Fully opened (under
pump/gravity feed) with
flow rate at 27 L/S
c. Provide break tank with
Minimum water
capacity of 11.5m
Date inspected:____________by______________________Signature_____________
Revised on 1 March 2002
C5