Multichiller - Bacnet - Modbus - Mapping - MC - Evo

This document provides instructions for installing and configuring a Carel pCOweb controller to interface with BACnet and Modbus networks. It describes mounting the pCOweb card in a pCO controller and accessing the web configuration interface. The configuration process involves setting the protocol, IP address, and BACnet object properties. Finally, it outlines the mapping of Carel analog variables to BACnet and Modbus addresses.

Uploaded by

liton
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
773 views23 pages

Multichiller - Bacnet - Modbus - Mapping - MC - Evo

This document provides instructions for installing and configuring a Carel pCOweb controller to interface with BACnet and Modbus networks. It describes mounting the pCOweb card in a pCO controller and accessing the web configuration interface. The configuration process involves setting the protocol, IP address, and BACnet object properties. Finally, it outlines the mapping of Carel analog variables to BACnet and Modbus addresses.

Uploaded by

liton
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

BACnet / Modbus gateway

Multichiller Evo
CONTENTS

PCOWEB INSTALLATION AND CONFIGURATION (FOR BACNET) ....................................... 3

Mounting ...................................................................................................................................................................................... 3

Configuration ............................................................................................................................................................................... 5

RS485 INSTALLATION AND CONFIGURATION (FOR MODBUS) ........................................... 9

Mounting ...................................................................................................................................................................................... 9

Configuration ............................................................................................................................................................................. 10

PCO5+ CONFIGURATION FOR BACNET AND MODBUS ...................................................... 11

CAREL/BACNET/MODBUS MAPPING .................................................................................... 13

EXAMPLE BACNET SOFTWARE TOOLS ............................................................................... 22

YABE .......................................................................................................................................................................................... 22

BACEYE ..................................................................................................................................................................................... 23
pCOweb installation and configuration (for BACnet)

Mounting
Equipment required:

• a 3 mm flat‐head screwdriver;
• a map of the installation (only when installing two or more pCOWeb devices);
• a pair of scissors.

Figure 1.a – pCOWeb and the accessories supplied

Figure 1.b – Removing the BMS card cover from the pCO controller

IMPORTANT: to avoid damage, before inserting pCOWeb disconnect power to the pCO controller
Figure 1.c – Inserting pCOWeb in the pCO controller

Figure 1.d – Securing pCOWeb with the cover


Configuration
pCOweb has this parameters
address: http://172.16.0.1
Subnet mask: 255.255.0.0

1.Open a browser web (for example Internet Explorer) at the address http://172.16.0.1 and click Go to
Administrator Area

2.Insert username and password

Username: admin
Password: fadmin
3.Click Configuration

4.Click tab pCO Com, set Protocol Modbus Extended and click Submit
5.Click tab BACnet, set pCO Mapping Parameters = 2048, 2048, 2048 and click Submit
6. Click Reboot and wait 2 minutes for reconnect the browser web

NOTE: If you don’t remember pCOweb IP address you can find below the reset procedure of the pCOweb
RS485 installation and configuration (for Modbus)

Mounting
To install the card in the pCO unit respect the following instructions

1.Disconnect power to the pCO controller and remove the "BMS card" placement cover with a screwdriver

2. removing the pre‐punctured plastic you get the hole which corresponds to the tree‐pole terminal out

3. insert the optional card into the corresponding connector, taking care that the card is firmly placed on both plastic
supports on the pCO case

4. close the cover using the screwdriver making the outside card terminal fits with the punched hole made on the cover
Configuration
No software configuration is necessary.
pCO5+ configuration for BACnet and Modbus
From main menù

push

Insert password 0000 and push  (for software version < 1.2.0 password 0442)

From Service Menu

Push
The correct setting is visualized below
If BMS master uses Modbus protocol and requires different “Address”, “Speed”, “Stop bit” and “Parity” you can change
them.
Carel/BACnet/Modbus mapping
Analog variables

Carel Carel BACnet Modbus


Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
External air/condenser temperature multichiller
A 1 A0001 1 °C ‐999.9 999.9 R
Temperatura aria esterna/condensatore multichiller
Inlet plant temperature multichiller
A 11 A0011 11 °C ‐999.9 999.9 R
Temperatura ingresso impianto multichiller
Outlet plant temperature multichiller
A 12 A0012 12 °C ‐999.9 999.9 R
Temperatura uscita impianto multichiller
Inlet recovery (2/4 pipes) temperature multichiller
A 13 A0013 13 °C ‐999.9 999.9 R
Temperatura ingresso recupero (2/4 tubi) multichiller
Outler recovery (2/4 pipes) temperature multichiller
A 14 A0014 14 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) multichiller
Setpoint plant cold Limited by PLC
A 27 A0027 27 °C ‐999.9 999.9 RW
Setpoint impianto a freddo Limitato da PLC
Setpoint 2 plant cold Limited by PLC
A 28 A0028 28 °C ‐999.9 999.9 RW
Setpoint 2 impianto a freddo Limitato da PLC
Setpoint plant heat Limited by PLC
A 29 A0029 29 °C ‐999.9 999.9 RW
Setpoint impianto a caldo Limitato da PLC
Setpoint 2 plant heat Limited by PLC
A 30 A0030 30 °C ‐999.9 999.9 RW
Setpoint 2 impianto a caldo Limitato da PLC
Setpoint recovery (2/4 pipes) Limited by PLC
A 31 A0031 31 °C ‐999.9 999.9 RW
Setpoint recupero (2/4 tubi) Limitato da PLC
Setpoint 2 recovery (2/4 pipes) Limited by PLC
A 32 A0032 32 °C ‐999.9 999.9 RW
Setpoint 2 recupero (2/4 tubi) Limitato da PLC
Differential plant cold
A 33 A0033 33 °C 0.0 999.9 RW
Differenziale impianto a freddo
Differential plant heat
A 34 A0034 34 °C 0.0 999.9 RW
Differenziale impianto a caldo
Differential recovery (2/4 pipes)
A 35 A0035 35 °C 0.0 999.9 RW
Differenziale recupero (2/4 tubi)
Set plant cold active
A 36 A0036 36 °C ‐999.9 999.9 R
Set impianto freddo attivo
Set plant heat active
A 37 A0037 37 °C ‐999.9 999.9 R
Set impianto caldo attivo
Set recovery (2/4 pipes) active
A 38 A0038 38 °C ‐999.9 999.9 R
Set recupero (2/4 tubi) attivo
Outlet plant temperature chiller 1
A 1053 A1053 1053 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 1
Outlet plant temperature chiller 2
A 1054 A1054 1054 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 2
Outlet plant temperature chiller 3
A 1055 A1055 1055 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 3
Outlet plant temperature chiller 4
A 1056 A1056 1056 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 4
Outlet plant temperature chiller 5
A 1057 A1057 1057 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 5
Outlet plant temperature chiller 6
A 1058 A1058 1058 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 6
Outlet plant temperature chiller 7
A 1059 A1059 1059 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 7
A 1060 A1060 1060 Outlet plant temperature chiller 8 °C ‐999.9 999.9 R
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
Temperatura uscita impianto chiller 8
Outlet plant temperature chiller 9
A 1061 A1061 1061 °C ‐999.9 999.9 R
Temperatura uscita impianto chiller 9
Outler recovery (2/4 pipes) temperature chiller 1
A 1068 A1068 1068 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 1
Outler recovery (2/4 pipes) temperature chiller 2
A 1069 A1069 1069 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 2
Outler recovery (2/4 pipes) temperature chiller 3
A 1070 A1070 1070 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 3
Outler recovery (2/4 pipes) temperature chiller 4
A 1071 A1071 1071 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 4
Outler recovery (2/4 pipes) temperature chiller 5
A 1072 A1072 1072 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 5
Outler recovery (2/4 pipes) temperature chiller 6
A 1073 A1073 1073 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 6
Outler recovery (2/4 pipes) temperature chiller 7
A 1074 A1074 1074 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 7
Outler recovery (2/4 pipes) temperature chiller 8
A 1075 A1075 1075 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 8
Outler recovery (2/4 pipes) temperature chiller 9
A 1076 A1076 1076 °C ‐999.9 999.9 R
Temperatura uscita recupero (2/4 tubi) chiller 9
Integer variables
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
State chiller 1 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 13 I0013 5014 ‐ 0 99 R
Stato chiller 1 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 2 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 14 I0014 5015 ‐ 0 99 R
Stato chiller 2 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 3 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 15 I0015 5016 ‐ 0 99 R
Stato chiller 3 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 4 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 16 I0016 5017 ‐ 0 99 R
Stato chiller 4 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 5 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 17 I0017 5018 ‐ 0 99 R
Stato chiller 5 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 6 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 18 I0018 5019 ‐ 0 99 R
Stato chiller 6 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 7 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 19 I0019 5020 ‐ 0 99 R
Stato chiller 7 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 8 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 20 I0020 5021 ‐ 0 99 R
Stato chiller 8 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
State chiller 9 (0=not present, 1=ON, 2=OFF,
3=alarm, 4=alarm serious, 5=offline)
I 21 I0021 5022 ‐ 0 99 R
Stato chiller 9 (0=non presente, 1=ON,
2=OFF, 3=allarme, 4=allarme grave, 5=offline)
Power plant request 1
I 1061 I1061 6062 ‐ 0.0 100.0 R
Potenza impianto richiesta 1
Power plant request 2
I 1062 I1062 6063 ‐ 0.0 100.0 R
Potenza impianto richiesta 2
Power plant request 3
I 1063 I1063 6064 ‐ 0.0 100.0 R
Potenza impianto richiesta 3
Power plant request 4
I 1064 I1064 6065 ‐ 0.0 100.0 R
Potenza impianto richiesta 4
Power plant request 5
I 1065 I1065 6066 ‐ 0.0 100.0 R
Potenza impianto richiesta 5
Power plant request 6
I 1066 I1066 6067 ‐ 0.0 100.0 R
Potenza impianto richiesta 6
Power plant request 7
I 1067 I1067 6068 ‐ 0.0 100.0 R
Potenza impianto richiesta 7
Power plant request 8
I 1068 I1068 6069 ‐ 0.0 100.0 R
Potenza impianto richiesta 8
Power plant request 9
I 1069 I1069 6070 ‐ 0.0 100.0 R
Potenza impianto richiesta 9
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
Power recovery (2/4 pipes) request 1
I 1343 I1343 6344 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 1
Power recovery (2/4 pipes) request 2
I 1344 I1344 6345 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 2
Power recovery (2/4 pipes) request 3
I 1345 I1345 6346 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 3
Power recovery (2/4 pipes) request 4
I 1346 I1346 6347 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 4
Power recovery (2/4 pipes) request 5
I 1347 I1347 6348 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 5
Power recovery (2/4 pipes) request 6
I 1348 I1348 6349 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 6
Power recovery (2/4 pipes) request 7
I 1349 I1349 6350 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 7
Power recovery (2/4 pipes) request 8
I 1350 I1350 6351 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 8
Power recovery (2/4 pipes) request 9
I 1351 I1351 6352 ‐ 0.0 100.0 R
Potenza recupero (2/4 tubi) richiesta 9
Digital variables
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
Reset alarm chiller 1
D 53 D0053 53 ‐ 0 1 RW
Reset allarme chiller 1
Reset alarm chiller 2
D 54 D0054 54 ‐ 0 1 RW
Reset allarme chiller 2
Reset alarm chiller 3
D 55 D0055 55 ‐ 0 1 RW
Reset allarme chiller 3
Reset alarm chiller 4
D 56 D0056 56 ‐ 0 1 RW
Reset allarme chiller 4
Reset alarm chiller 5
D 57 D0057 57 ‐ 0 1 RW
Reset allarme chiller 5
Reset alarm chiller 6
D 58 D0058 58 ‐ 0 1 RW
Reset allarme chiller 6
Reset alarm chiller 7
D 59 D0059 59 ‐ 0 1 RW
Reset allarme chiller 7
Reset alarm chiller 8
D 60 D0060 60 ‐ 0 1 RW
Reset allarme chiller 8
Reset alarm chiller 9
D 61 D0061 61 ‐ 0 1 RW
Reset allarme chiller 9
Disable/enable chiller 1
D 62 D0062 62 ‐ 0 1 RW
Disabilita/abilita chiller 1
Disable/enable chiller 2
D 63 D0063 63 ‐ 0 1 RW
Disabilita/abilita chiller 2
Disable/enable chiller 3
D 64 D0064 64 ‐ 0 1 RW
Disabilita/abilita chiller 3
Disable/enable chiller 4
D 65 D0065 65 ‐ 0 1 RW
Disabilita/abilita chiller 4
Disable/enable chiller 5
D 66 D0066 66 ‐ 0 1 RW
Disabilita/abilita chiller 5
Disable/enable chiller 6
D 67 D0067 67 ‐ 0 1 RW
Disabilita/abilita chiller 6
Disable/enable chiller 7
D 68 D0068 68 ‐ 0 1 RW
Disabilita/abilita chiller 7
Disable/enable chiller 8
D 69 D0069 69 ‐ 0 1 RW
Disabilita/abilita chiller 8
Disable/enable chiller 9
D 70 D0070 70 ‐ 0 1 RW
Disabilita/abilita chiller 9
Cooling / heating command
D 80 D0080 80 ‐ 0 1 RW
Raffreddamento / riscaldamento comando
Alarm active multichiller
D 101 D0101 101 ‐ 0 1 R
Riassunto allarmi multichiller
Plant side multichiller state
D 102 D0102 102 ‐ 0 1 R
Stato impianto multichiller
Reset alarms multichiller
D 103 D0103 103 ‐ 0 1 RW
Reset allarmi multichiller
Off on plant from BMS multichiller enable/disable
D 104 D0104 104 ‐ 0 1 RW
Off on impianto da BMS multichiller Multichiller-Evo
Off on recovery (2/4 pipes) from BMS multichiller
D 105 D0105 105 ‐ 0 1 RW
Off on recupero (2/4 tubi) da BMS multichiller
Recovery (2/4 pipes) side multichiller state
D 106 D0106 106 ‐ 0 1 R
Stato recupero (2/4 tubi) multichiller
AL001 U1 broken or disconnected
D 201 D0201 201 ‐ 0 1 R
AL001 U1 rotta o disconnessa
D 202 D0202 202 AL002 U2 broken or disconnected ‐ 0 1 R
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
AL002 U2 rotta o disconnessa
AL003 U3 broken or disconnected
D 203 D0203 203 ‐ 0 1 R
AL003 U3 rotta o disconnessa
AL004 U4 broken or disconnected
D 204 D0204 204 ‐ 0 1 R
AL004 U4 rotta o disconnessa
AL005 U5 broken or disconnected
D 205 D0205 205 ‐ 0 1 R
AL005 U5 rotta o disconnessa
AL006
D 206 D0206 206 ‐ 0 1 R
AL006
AL007
D 207 D0207 207 ‐ 0 1 R
AL007
AL008
D 208 D0208 208 ‐ 0 1 R
AL008
AL009
D 209 D0209 209 ‐ 0 1 R
AL009
AL010
D 210 D0210 210 ‐ 0 1 R
AL010
AL011 1B1 broken or disconnected
D 211 D0211 211 ‐ 0 1 R
AL011 1B1 rotta o disconnessa
AL012 1B2 broken or disconnected
D 212 D0212 212 ‐ 0 1 R
AL012 1B2 rotta o disconnessa
AL013 1B3 broken or disconnected
D 213 D0213 213 ‐ 0 1 R
AL013 1B3 rotta o disconnessa
AL014 1B4 broken or disconnected
D 214 D0214 214 ‐ 0 1 R
AL014 1B4 rotta o disconnessa
AL015
D 215 D0215 215 ‐ 0 1 R
AL015
AL016
D 216 D0216 216 ‐ 0 1 R
AL016
AL017
D 217 D0217 217 ‐ 0 1 R
AL017
AL018
D 218 D0218 218 ‐ 0 1 R
AL018
AL019 pCOe1 offline
D 219 D0219 219 ‐ 0 1 R
AL019 pCOe1 offline
AL020
D 220 D0220 220 ‐ 0 1 R
AL020
AL021 Chiller1 offline
D 221 D0221 221 ‐ 0 1 R
AL021 Chiller1 offline
AL022 Chiller2 offline
D 222 D0222 222 ‐ 0 1 R
AL022 Chiller2 offline
AL023 Chiller3 offline
D 223 D0223 223 ‐ 0 1 R
AL023 Chiller3 offline
AL024 Chiller4 offline
D 224 D0224 224 ‐ 0 1 R
AL024 Chiller4 offline
AL025 Chiller5 offline
D 225 D0225 225 ‐ 0 1 R
AL025 Chiller5 offline
AL026 Chiller6 offline
D 226 D0226 226 ‐ 0 1 R
AL026 Chiller6 offline
AL027 Chiller7 offline
D 227 D0227 227 ‐ 0 1 R
AL027 Chiller7 offline
AL028 Chiller8 offline
D 228 D0228 228 ‐ 0 1 R
AL028 Chiller8 offline
D 229 D0229 229 AL029 Chiller9 offline ‐ 0 1 R
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
AL029 Chiller9 offline
AL030 Initializ. Completed, reboot PLC!
D 230 D0230 230 ‐ 0 1 R
AL030 Inizializ. Completata, reboot PLC!
AL031 Slave1 Chiller1 offline
D 231 D0231 231 ‐ 0 1 R
AL031 Slave1 Chiller1 offline
AL032 Slave2 Chiller1 offline
D 232 D0232 232 ‐ 0 1 R
AL032 Slave2 Chiller1 offline
AL033 Slave3 Chiller1 offline
D 233 D0233 233 ‐ 0 1 R
AL033 Slave3 Chiller1 offline
AL034 Slave1 Chiller2 offline
D 234 D0234 234 ‐ 0 1 R
AL034 Slave1 Chiller2 offline
AL035 Slave2 Chiller2 offline
D 235 D0235 235 ‐ 0 1 R
AL035 Slave2 Chiller2 offline
AL036 Slave3 Chiller2 offline
D 236 D0236 236 ‐ 0 1 R
AL036 Slave3 Chiller2 offline
AL037 Slave1 Chiller3 offline
D 237 D0237 237 ‐ 0 1 R
AL037 Slave1 Chiller3 offline
AL038 Slave2 Chiller3 offline
D 238 D0238 238 ‐ 0 1 R
AL038 Slave2 Chiller3 offline
AL039 Slave3 Chiller3 offline
D 239 D0239 239 ‐ 0 1 R
AL039 Slave3 Chiller3 offline
AL040 Slave1 Chiller4 offline
D 240 D0240 240 ‐ 0 1 R
AL040 Slave1 Chiller4 offline
AL041 Slave2 Chiller4 offline
D 241 D0241 241 ‐ 0 1 R
AL041 Slave2 Chiller4 offline
AL042 Slave3 Chiller4 offline
D 242 D0242 242 ‐ 0 1 R
AL042 Slave3 Chiller4 offline
AL043 Slave1 Chiller5 offline
D 243 D0243 243 ‐ 0 1 R
AL043 Slave1 Chiller5 offline
AL044 Slave2 Chiller5 offline
D 244 D0244 244 ‐ 0 1 R
AL044 Slave2 Chiller5 offline
AL045 Slave3 Chiller5 offline
D 245 D0245 245 ‐ 0 1 R
AL045 Slave3 Chiller5 offline
AL046 Slave1 Chiller6 offline
D 246 D0246 246 ‐ 0 1 R
AL046 Slave1 Chiller6 offline
AL047 Slave2 Chiller6 offline
D 247 D0247 247 ‐ 0 1 R
AL047 Slave2 Chiller6 offline
AL048 Slave3 Chiller6 offline
D 248 D0248 248 ‐ 0 1 R
AL048 Slave3 Chiller6 offline
AL049 Slave1 Chiller7 offline
D 249 D0249 249 ‐ 0 1 R
AL049 Slave1 Chiller7 offline
AL050 Slave2 Chiller7 offline
D 250 D0250 250 ‐ 0 1 R
AL050 Slave2 Chiller7 offline
AL051 Slave3 Chiller7 offline
D 251 D0251 251 ‐ 0 1 R
AL051 Slave3 Chiller7 offline
AL052 Slave1 Chiller8 offline
D 252 D0252 252 ‐ 0 1 R
AL052 Slave1 Chiller8 offline
AL053 Slave2 Chiller8 offline
D 253 D0253 253 ‐ 0 1 R
AL053 Slave2 Chiller8 offline
AL054 Slave3 Chiller8 offline
D 254 D0254 254 ‐ 0 1 R
AL054 Slave3 Chiller8 offline
AL055 Slave1 Chiller9 offline
D 255 D0255 255 ‐ 0 1 R
AL055 Slave1 Chiller9 offline
D 256 D0256 256 AL056 Slave2 Chiller9 offline ‐ 0 1 R
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
AL056 Slave2 Chiller9 offline
AL057 Slave3 Chiller9 offline
D 257 D0257 257 ‐ 0 1 R
AL057 Slave3 Chiller9 offline
AL058 Alarm from digital input 8
D 258 D0258 258 ‐ 0 1 R
AL058 Allarme da ingresso digitale 8
AL059
D 259 D0259 259 ‐ 0 1 R
AL059
AL060 Permanent Memory pCO5+
D 260 D0260 260 ‐ 0 1 R
AL060 Permanent Memory pCO5+
AL061 Chiller1 alarm
D 261 D0261 261 ‐ 0 1 R
AL061 Chiller1 allarme
AL062 Chiller2 alarm
D 262 D0262 262 ‐ 0 1 R
AL062 Chiller2 allarme
AL063 Chiller3 alarm
D 263 D0263 263 ‐ 0 1 R
AL063 Chiller3 allarme
AL064 Chiller4 alarm
D 264 D0264 264 ‐ 0 1 R
AL064 Chiller4 allarme
AL065 Chiller5 alarm
D 265 D0265 265 ‐ 0 1 R
AL065 Chiller5 allarme
AL066 Chiller6 alarm
D 266 D0266 266 ‐ 0 1 R
AL066 Chiller6 allarme
AL067 Chiller7 alarm
D 267 D0267 267 ‐ 0 1 R
AL067 Chiller7 allarme
AL068 Chiller8 alarm
D 268 D0268 268 ‐ 0 1 R
AL068 Chiller8 allarme
AL069 Chiller9 alarm
D 269 D0269 269 ‐ 0 1 R
AL069 Chiller9 allarme
AL070
D 270 D0270 270 ‐ 0 1 R
AL070
AL071
D 271 D0271 271 ‐ 0 1 R
AL071
Off on global plant chiller 1
D 1022 D1022 1022 ‐ 0 1 R
Off on generale impianto chiller 1
Off on global plant chiller 2
D 1023 D1023 1023 ‐ 0 1 R
Off on generale impianto chiller 2
Off on global plant chiller 3
D 1024 D1024 1024 ‐ 0 1 R
Off on generale impianto chiller 3
Off on global plant chiller 4
D 1025 D1025 1025 ‐ 0 1 R
Off on generale impianto chiller 4
Off on global plant chiller 5
D 1026 D1026 1026 ‐ 0 1 R
Off on generale impianto chiller 5
Off on global plant chiller 6
D 1027 D1027 1027 ‐ 0 1 R
Off on generale impianto chiller 6
Off on global plant chiller 7
D 1028 D1028 1028 ‐ 0 1 R
Off on generale impianto chiller 7
Off on global plant chiller 8
D 1029 D1029 1029 ‐ 0 1 R
Off on generale impianto chiller 8
Off on global plant chiller 9
D 1030 D1030 1030 ‐ 0 1 R
Off on generale impianto chiller 9
Cooling / heating
D 1031 D1031 1031 ‐ 0 1 R
Raffreddamento / riscaldamento
Off on global recovery (2/4 pipes) chiller 1
D 1155 D1155 1155 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 1
D 1156 D1156 1156 Off on global recovery (2/4 pipes) chiller 2 ‐ 0 1 R
Carel Carel BACnet Modbus
Description EN/IT UM Min Max RW NOTE
Type Addr. Obj.name Addr.
Off on generale recupero (2/4 tubi) chiller 2
Off on global recovery (2/4 pipes) chiller 3
D 1157 D1157 1157 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 3
Off on global recovery (2/4 pipes) chiller 4
D 1158 D1158 1158 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 4
Off on global recovery (2/4 pipes) chiller 5
D 1159 D1159 1159 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 5
Off on global recovery (2/4 pipes) chiller 6
D 1160 D1160 1160 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 6
Off on global recovery (2/4 pipes) chiller 7
D 1161 D1161 1161 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 7
Off on global recovery (2/4 pipes) chiller 8
D 1162 D1162 1162 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 8
Off on global recovery (2/4 pipes) chiller 9
D 1163 D1163 1163 ‐ 0 1 R
Off on generale recupero (2/4 tubi) chiller 9
How the Instance number and BACnet
Example BACnet software tools Object number varies on BMS

YABE
BACEYE

Analog Value

Integer Value

Digital variables
/BV

1=ON and
0=OFF