0% found this document useful (0 votes)
105 views

20 - HW + SW Installation

This document provides instructions for installing hardware and software for an industrial automation application. It includes steps for installing WinCC Runtime on a Panel PC, configuring the Ethernet and PG/PC interfaces, and installing and configuring the DiagAddOn software. The DiagAddOn installation involves creating a new project, setting basic parameters like the project name and PLC IP address, and enabling parameterization mode to modify settings.

Uploaded by

david_gdsbs
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views

20 - HW + SW Installation

This document provides instructions for installing hardware and software for an industrial automation application. It includes steps for installing WinCC Runtime on a Panel PC, configuring the Ethernet and PG/PC interfaces, and installing and configuring the DiagAddOn software. The DiagAddOn installation involves creating a new project, setting basic parameters like the project name and PLC IP address, and enabling parameterization mode to modify settings.

Uploaded by

david_gdsbs
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

2.

HW + SW Installation SICAR@TIA DiagAddOn

Warranty and Liability


The Application Examples are not binding and do not claim to be complete regarding the circuits shown,
equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They
are only intended to provide support for typical applications. You are responsible for ensuring that the
described products are used correctly. These application examples do not relieve you of the responsibility to
use safe practices in application, installation, operation and maintenance. When using these Application
Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause
described. We reserve the right to make changes to these Application Examples at any time without prior
notice. If there are any deviations between the recommendations provided in these application examples and
other Siemens publications – e.g. Catalogs – the contents of the other documents have priority.

We do not accept any liability for the information contained in this document.

Any claims against us – based on whatever legal reason – resulting from the use of the examples,
information, programs, engineering and performance data etc., described in this Application Example shall
be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German
Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or
health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition
which goes to the root of the contract (“wesentliche Vertragspflichten”). The damages for a breach of a
substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of
contract, except in the event of intent or gross negligence or injury to life, body or health. The above
provisions do not imply a change of the burden of proof to your detriment. Any form of duplication or
distribution of these Application Examples or excerpts hereof is prohibited without the expressed consent of
Siemens Industry Sector.

Manual page 1 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

Table of contents

1. Overview Hardware 3

2. Software Installation 3
2.1 IPC277E (Sample) 3
2.2 Installation TIA WinCC Advance RT 3
2.3 Ethernet interface Panel PC 3
2.4 Set PG / PC Interface 4
2.5 Installation DiagAddOn 6
2.5.1 Creating a new project 7
2.5.2 Basic parameterization 9
2.5.3 Stop the application 13
2.5.4 Switch between WinCC RT and DiagAddOn 14
2.6 Autostart WINCC Advanced RT und DiagAddOn 15
2.6.1 WINCC RT Advanced 15
2.6.2 DiagAddOn 15

Manual page 2 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

1. Overview Hardware
PLC:
Each SIMATIC PLC 15xx with a Profinet / Profibus interface can be used.
Size of the PLC depends on the line configuration.

Panel/HMI:
Minimum IPCxx7 (Win7)

2. Software Installation

2.1 IPC277E (Sample)

2.2 Installation TIA WinCC Advance RT

For the installation of WinCC flexible Runtime you need an installation CD with the current Version.
Select only “Runtime / Simulation” (“Licence Manager” will be installed automatically) and “ProSave”.
When the installation is finished you have to restart your computer.
Install the latest update.

2.3 Ethernet interface Panel PC

Open the control panel of your PC (or use the symbol in the taskbar) and choose “Network and Sharing
Center” to change the adapter settings.

Open the properties of your Local Area Connection and set your IP address.
This IP address has to be the same as in your WinCC project.

Manual page 3 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.4 Set PG / PC Interface

Open the control panel of your PC und choose “Set PG/PC interface” to set your access point of the
Application.

Choose the access point of the Application. Make sure you choose the right connection which ends with
“TCPIP”.
For example: S7 Online (Step 7)  Intel(R) 82579LM Gigabit … TCPIP.1

Manual page 4 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

Manual page 5 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5 Installation DiagAddOn

Starting the set_up file “SICAR_Diag_AddOn V2.x.x.exe” as administrator.


The application will be installed to the default path “C:\xxxxx\SICAR_LP_CS”.

Create a shortcut on Desktop


Change settings for Shortcut
Compatibility: Access level: Mark Start Program as Administrator

Settings for all user


Access level: Mark Start Program as Administrator

Manual page 6 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.1 Creating a new project


With the installation of DiagAddOn setup create in folder “LP_Projects” two project folder, “application” and
“sample”

Make a copy of “sample”

Rename the new prject folder to your project specific name. (e.g. “New Project”)

Rename the copied project files (“sample”) with the new project name (e.g. “New Project”), mandatory to use
the same name.

Manual page 7 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

Starting the application “SICAR_lp_CS.exe”

Important: Execution “as Administrator”. Otherwise you´ll get a Run Time Error.

Manual page 8 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.2 Basic parameterization


For the communication between PLC and HMI different parameterizations must be done first.
This setting is done in the mask ‘P_system‘.

Project Declaration of directory and name of the project

Panel number: Input of the panel number


Possible settings: 1 ... 8
There must always be an operator panel No.1.
If there is more then one panel connected to a PLC, these
must be numbered in series.

Path RSS Feed: File path for RSS-files, if there is no entry no Feed is generated

Options RSS Feed & SK – MB - SYS


TopTen evaluation: Send / Generate: Sequences, Messageblocks, System messages

Diagnosis options Display with / without DB-names


Display with absolte address and symbolic or only with symbolic

IP-Adresse: Assign the IP-Adress of the PLC

Language Language choice

Representation of softkeys Choice of softkey representation of the HMI.


Possible settings:
symbol, softkeys are represented by symbols
text, softkeys are represented by text (according to the language choice)

Manual page 9 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.2.1 Parametrization mode ON/Off

In this mode, the data of system setting and movements can be modified.
The parameterization takes place in the same masks as in the “normal operation“.
Additional entry fields, for data inputs are activated in the masks.

With this button parameterization mode will be

enabled

and

disabled.

When the button is pressed, a password question will be activated. The password is “simatico“.

simatico

The change of background color signifies whether “normal operation“ or “parameterization mode“ is
activated:

Normal operation: background color gray Parameterization mode: background color turquoise

Manual page 10 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.2.2 Modification of system setting in normal operation

A requested line can be activated by touch or using a mouse. The selected line will change background color
to blue and a drop down menu will be displayed.

After pressing the disk symbol l the modification will be stored into the project data
base. These setting is available after initial restart of the operator panel software.

In normal operation, only the following parameters can be modified:

 Language
 Representation of softkeys

Manual page 11 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.2.3 Modification of system setting in parameterization mode


The input fields can be activated by using the mouse or touch, they can be modified using the keyboard.
The setting of parameters which showing a menu, can be selected by using the mouse or touch.
The settings can be stored by using the button with the disk symbol.

In parameterization mode, only the following parameters can be modified:

 Project path
 Project
 Panel number
 Path for RSS Feeds
 Options for RSS Feed and TopTen Evaluation
 Options Diagnosis
 IP address of PLC

Note for changing the Project path

The new directory must exist, means DiagAddOn is already installed in the “new” directory.
If his is not the case, input of new path name is not accepted.

Manual page 12 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.3 Stop the application

To close the application press the button with the Stop symbol and the password
dialog will come up

Enter the password “simatico” followed by return.

simatico

Application will be stopped.

Manual page 13 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.5.4 Switch between WinCC RT and DiagAddOn

To switch from WinCC RT to DiagAddOn use the button “Diag AddOn”. With the event “Click” the script
“SwitchToLP” is executed and the DiagAddOn is opened.

Switch to DiagAddOn

To switch back from DiagAddOn to WinCC RT a fixed button in the application is assigned to this function.
This is realized by script „lp_flex.vbs“.

Return to WinCC Runtime

The script is located in the installationfolder of DiagAddOn, e.g.: C:\Program Files (x86)\SICAR_LP_CS.

Manual page 14 / 15 Edition: 2019-01


2. HW + SW Installation SICAR@TIA DiagAddOn

2.6 Autostart WINCC Advanced RT und DiagAddOn

2.6.1 WINCC RT Advanced


Add a link „WinCC RT Loader“ to Windows Startup Folder

2.6.2 DiagAddOn
DiagAddOn has to be started by using the Task Scheduler

Win7:
Start “Control Panel” / Administrative Tools / Task Scheduler
Actions / Create Task
Name of Task: DiagAddOn
Triggers / New / Begin the task: “At Startup”
General / Mark “Run with highest privileges”
General / Cofigure for: “Windows 7, Windows Server 2008 R2”
Actions / New / Action: Start a program
Program / script: Browse to “SICAR_lp_cs.exe”

Win10:
Start “Control Panel” / Administrative Tools / Task Scheduler
Actions / Create Task
Name of Task: DiagAddOn
Triggers / New / Begin the task: “Bei Anmeldung” / “Jeder Benutzer”
General / Mark “Run with highest privileges”
General / Configure for: “Windows 10”
Actions / New / Action: Start a program
Program / script: Browse to “SICAR_lp_cs.exe”
Check under Settings:
Use following rules if Task is already running:
„Start no new instances“

Manual page 15 / 15 Edition: 2019-01