Installation Standard
Installation Standard
Ducts shall be supported every 1500 mm. All joints to be sealed with high
pressure duct sealer.
Openings in ductwork for collars shall be field measured and cut to ensure
proper location of air distribution outlets and inlets in finished construction.
Collars shall be fabricated to properly receive air distribution outlet and inlet for
alignment in finished construction and to accommodate dampers, equalizing
deflectors and shall be in accordance with manufacturer’s printed
recommendations.
We select the copper pipe size as per manufactures standard and thickness of copper
pipe wall as per attached
Wall thickness
➢ Insulating material:
The insulating material should be a suitable thickness and the inner diameter should
match the size of refrigerant pipes
10 314 615
12 314 615
4. Hoisting
Supports must be strong enough. The supports should be full thread booms, and
we are using dia. of rod ≥ 8/10mm. As per unit weight.
5. Branch Joint:
c. From the inlet or outlet of branch joint, there should be straight pipe with
length at least 1 m