En Quick Start Guide ASIMON Configuration Safe Analog Inputs
En Quick Start Guide ASIMON Configuration Safe Analog Inputs
2.3 Click on "Change adapter 2.4 Open the properties 2.5 Fill in as follows
settings". for the LAN connection (example):
and click on "Internet IP address:
protocol Version 4 192.168.32.3
(TCP/IPv4)". Subnet mask:
255.255.255.0
Standard gateway:
192.168.32.200
3.1 Start ASIMON360, select "New workspace" and 3.2 The hardware configuration opens 3.3 Change in the "Local I/Os" tab the first input 3.4 Select the “Service” tab, activate the global
click on "Create". automatically. Select the ASi 3.0 PROFINET SI1/2 to "Standard input", as there is a rocker error unlock and set the address to SI1 to use the
Gateway with integrated safety monitor switch connected to SI1. Set the terminal pairs rocker switch for this function. Confirm by clicking
(BWU2828). SI3/4 and SI5/6 to "not used". “OK”.
3.5 Click on "Add Slave" on the top menu and 3.6 Select the “General” tab and set the operation 3.7 Click on the "Channel 1" tab and select the 3.8 Click on the arrow under "Settings" and set
select the connected ASi safety analog input module mode to "Two sensors measure the same signal". signal type "Pt100 (2-wire)". Set "Maximum "Lower limit" as 25°C and "Upper limit" as 30°C.
(BW2692). threshold" to 40°C and "Minimum threshold" to Now the safe output shuts off as soon as the
20°C. temperature drops below 25°C or rises above
30°C.
3.9 Select the "Channel 2“ tab and set the signal 3.10 To monitor the safe analog signal drag the 3.11 Start the commissioning wizard to address 3.12 Change the interface of the gateway as
type as "Pt100 (2-wire)". Confirm with "OK" to slave "1-2 analog signal 1 range 1" into the "&- the slaves, and to load the configuration into the follows (example):
finish the hardware configuration. ASIMON360 device" in OSSD1. Drag the "SI1 Standard input" safety gateway (BWU2828) and the ASi safety IP address:192.168.32.123
creates a basis configuration automatically. into the "Monitored start-device", to use the analog input module (BWU2692). Follow the steps Subnet mask: 255.255.255.0
rocker switch on SI1 as a monitored start-device. of the commissioning wizard. Standard gateway: 192.168.32.124
3.13 The download will start once the devices in 3.14 The diagnostic starts automatically. Now you 3.15 A rise in the temperature will be detected by 3.16 Once the temperature returns to the safe
the hardware configuration are properly connected can test the safety configuration. Push the rocker the sensors, shutting off the safety output if the range the OSSD can be restarted and the safety
and recognized. Finally, validate the release pro- switch on SI1 to activate the OSSD and trigger the temperature rises above 30°C. output turned on again by pushing the rocker
tocols and click on “Finish” to finish the monitored start. Detailed information about the switch on SI1.
commissioning. sensors can be obtained by right-clicking on the
safety analog input module. The temperature range
previously defined as safe is marked in green. The
temperature is currently in the safe range.