Protection CT Sizing
Protection CT Sizing
Protection CT Sizing
Maximum Symmetrical Short-circuit Current (HV Side) Issc max 1944.00 A Through Fault Current, limited by Transformer % Z
Selected CT Ratio 800-400/1-1-1-1-1 A CT Ratio 400 A will be used for Transformer Diff.
CT Rated/Nominal Primary Current (Iprimary) Ipn 400 Amp. CT Ratio 400 A will be used for Line Diff.
CT Rated/ Nominal Secondary Current (Isecondary) Isn 1 Amp.
Fault Current at Secondary Side of CT IF 7.88 IF*Isecondary/Iprimary
Full Load / Nominal Current - Secondary ( LV )Side Isec 874.80 A
Maximum Symmetrical Short-circuit Current (LV Side) Issc max 7775.99 A
FOR 132KV
2
Conductor Cross Section 2.5 mm Shall be used for CT & PT connection.
Conductor Material Copper
Number of Runs per Phase 1
Cable Route Length from CT to Relay/Control Panel in MCR L 100 Mtr. Considered Maximum length.
0
Conductor unit Resistance at 75 C R 7.41 ohm/km
Two way Lead Resistance Rl 2 x L x (R/1) / 1000 ohm
RL 1.48 ohm
FOR 33KV
2
Conductor Cross Section 2.5 mm Shall be used for CT & PT connection.
Conductor Material Copper
Number of Runs per Phase 1
Cable Route Length from CT to Relay/Control Panel in MCR L 30 Mtr. Considered Maximum length.
0
Conductor unit Resistance at 75 C R 7.41 ohm/km
RL 0.44 ohm
The resistance of the secondary wire and additional load RL 1.48 ohm
Eal 53.48
Transformer
Purpose
Differential Protection
Selected primary current ratio Ipn 400 A CT Ratio for Line is selected.
Turn Ratio T 1/400
Secondary Current ratio In 1 A
0
Secondary Winding resistance at 75 C at selected ratio RCT 4 ohm
The resistance of the secondary wire and additional load RL 1.48
Full load current IF 218.70 A
Rev-0 4of-9
CURRENT TRANSFORMER SIZING CALCULATION
Class PS Class
Knee Point Voltage Selected Vk ≥1100 Selected
Magnetising Current Imag ≤ 20mA at Vk Current
Required Vk knee point voltage is much lower than knee point voltage of CT (Vk). Hence OK
Transformer backup
Purpose
Protection relay
Selected primary current ratio Ipn 400 A CT Ratio for Line is selected.
Turn Ratio T 1/400
Secondary Current ratio In 1 A
0
Secondary Winding resistance at 75 C at selected ratio RCT 4 ohm
The resistance of the secondary wire and additional load RL 1.48
Full load current IF 218.70 A
Class PS Class
CT Core Number 1
Purpose 7SR11
Selected primary current ratio Ipn 400 A CT Ratio for Line is selected.
Turn Ratio T 1/400
Secondary Current ratio In 1 A
0
Secondary Winding resistance at 75 C at selected ratio RCT 5 ohm
The resistance of the secondary wire and additional load RL 1.48
Full load current IF 218.70 A
Class PS Class
Knee Point Voltage Selected Vk ≥600 Selected
Magnetising Current Imag ≤ 60mA at Vk Current
Required Vk knee point voltage is much lower than knee point voltage of CT (Vk). Hence OK
CT Core Number 1
Purpose 7SR5421
Selected primary current ratio Ipn 1200 A CT Ratio for Line is selected.
Turn Ratio T 1/1200
Secondary Current ratio In 1 A
0 RCT
Secondary Winding resistance at 75 C at selected ratio 6 ohm
Rev-0 4of-9
CURRENT TRANSFORMER SIZING CALCULATION
Class PS Class
Knee Point Voltage Selected Vk ≥15 Selected
Magnetising Current Imag ≤ 60mA at Vk Current
Required Vk knee point voltage is much lower than knee point voltage of CT (Vk). Hence OK
Class PS Class
Knee Point Voltage Selected Vk ≥600 Selected
Magnetising Current Imag ≤ 60mA at Vk Current
Required Vk knee point voltage is much lower than knee point voltage of CT (Vk). Hence OK
Rev-0 4of-9