The bus interface may only be installed and commissioned by qualified electricians. An electrician is a
person who, because of their technical training and experience, has sufficient knowledge with regard to
• Switching on, switching off, isolating, earthing and marking power circuits and devices,
• Proper maintenance and use of protective devices in accordance with defined safety standards.
DANGER
Danger of electric shock
The frequency inverter carries hazardous voltage for up to 5 minutes after being switched off.
• Work must not be carried out unless the frequency inverter has been disconnected from the
voltage and at least 5 minutes has elapsed since the mains was switched off.
Validity of document
This document is only valid in conjunction with the operating instructions of the respective frequency
inverter and the bus communication manual for this bus interface ( See overview at end of document).
These documents contain all of the information that is required for safe commissioning of the bus
interface module and the frequency inverter.
Scope of delivery
1x Bus interface SK TU4-EIP-C
4x Hexagonal socket screw M4 x 40 mm
Accessories required:
1x Bus connection unit SK TI4-TU-BUS-C
TI 275280500 (Part No.: 275 280 500)
Usage area
External technology unit for connecting a distributed frequency inverter (NORDAC BASE,
NORDAC FLEX) to an EtherNet/IP field bus. The bus interface can be mounted on, or in the immediate
vicinity of the frequency inverter. This is connected to the inverter via the system bus, and can directly
access up to 4 frequency inverters. 8 digital inputs and 2 digital outputs are available.
Technical Data
Bus interface
Temperature range -25 °C...50 °C Vibration resistance 3M7
Temperature class Class 3K4 Protection class IP66
Supply voltage 24 V ± 20 %, ≈ 100 mA Dimensions [mm]* H x W x D:
Reverse polarity protected 95 x 136 x 99
* bus interface fitted to bus connection unit
Depth: 108 mm with cover caps on M12connection
Bus specification
Ethernet/IP max. 100 MBaud Cable Min. Ethernet CAT-5
electrical isolation 500 Veff Max. cable length 100 m between two bus
interfaces
Bus connection 2 x M12 sockets Shield via M12 direct to PE
Bus termination performed automatically PE connection via PE screw cap
Status display 8 LEDs in the terminal box
Topology* Star*, ring, linear bus
* additional switch for "star" topology required
Power
Update interval for process data between bus interface and frequency inverter ≥ 5 ms
Parameter read access on the frequency inverter ≈ 15 ms
Parameter write access with storage in EEPROM ≈ 25 ms
Cycle times ≥ 1 ms
Installation
The bus interface must be attached to a suitable connection unit (SK TI4-TU…) and connected using
the 4 provided M4 x 40 mm hexagon socket collar screws (Tightening torque 2 Nm). Installation details
can be found in the data sheet for the relevant connection units.
Connections
The two Ethernet lines are connected exclusively via the two M12 sockets on the front. If the bus
interface is the final subscriber on the line, one M12 socket can remain unoccupied. The use of EMC
cable glands is recommended.
PIN Signal Description
1 TX+ Transmission Data +
2 RX+ Receive Data +
3 TX- Transmission Data -
4 RX- Receive Data -
PIN assignment
M12-4 socket
("D"- coded)
The connection to other signal and control lines takes place via the bus connection unit
SK TI4-TU-BUS(-C).
Terminals Double-sprung 2 x 18 contacts
terminal bar
Cable cross section AWG 14-26 rigid: 0,14 … 2,5 mm
flexible: 0.14 … 1.5 mm with wire end sleeves
PE connection Via housing
RJ12 RJ45 - socket Interface for connecting a parameterisation tool
NOTICE
Short circuit possible
Attention must be paid to the fact that the GND connection (terminals 7 and 8) on the blue block is
basically not short-circuit protected. In case of a short circuit between the 24 V connection (terminals 9
and 10) and the GND connection, the module may become defective.
• To remain short-circuit protected, the GND connection of the grey block must be used, even if the
remaining connections are applied to the blue block.
Connection examples
Connection of voltage supply and
Brown
VI 24V 24 V DC
Blue
Systembus
GND/0V GND/0V
Black
SYS+ Systembus +
Grey
SYS- Systembus-
Configuration
The basic configuration of the module is primarily carried out via its DIP switches. The DIP switch
settings are read after a "Power On" of the bus interface.
DIP switch Meaning
12 11 10 9 8 7 6 5 4 3 2 1 Address
X X X 0 0 0 0 0 0 0 0 X 0
X X X 0 0 0 0 0 0 0 1 X 1
X X X 0 0 0 0 0 0 1 0 X 2
X X X 0 - - - - - - - X -
X X X 1 1 1 1 1 1 1 1 X 255
0 System bus terminating resistor not set.
1 System bus terminating resistor set.
Access rights for remote maintenance
0 Only read access to parameters possible.
1 Read and write access to parameters possible.
0 No control possible.
1 Control is possible.
0 TCP/IP open connection.
1 Secure TCP/IP connection.
The final byte of the IP address can be set via this switch
…
LED indicators
The operating statuses of the bus interface are visualised using LED indicators.
EtherNet/IP-specific LEDs
MS Meaning NS Meaning
(Module State) (Network State)
OFF No operating voltage OFF No operating voltage
Flashing green Bus interface not configured Flashing green IP address configured but no CIP
connection available
Green Bus interface working correctly Green CIP connection(s) available
Flashing red Minor error, faulty configuration Flashing red Time-out, an "exclusive owner connection"
has a time-out error
Red Unrecoverable error Red Dual IP whose IP address is already being
used by the bus interface
Flashing Power up, self test Flashing Power up, self test
red/green red/green
NORD-specific LEDs
Meaning
DS EN
long flashing = 0.5 s on / 1 s off
(Device State) (Device Error)
short flashing = 0.25 s on / 1 s off
OFF OFF Bus interface not ready, no control voltage
ON OFF Bus interface ready, no error, at least one frequency inverter is communicating via the system bus
ON Short flashing Bus interface ready, but
• One or more of the connected frequency inverters has fault status
Long flashing OFF Bus interface ready and at least one other subscriber is connected to the system bus, but
• No frequency inverter on the system bus (or connection interrupted)
• One or more system bus subscriber has an address error
• Software incompatible (bus interface software and FI software incompatible - update required)
Long flashing Short flashing System bus is in status "Bus Warning"
Flash interval • Communication on system bus disrupted
1 x - 1s pause • No other subscribers present on system bus
• Module not inserted correctly or no connection to system bus
• Frequency inverter has no supply voltage
Long flashing Short flashing System bus is in status "Bus Off"
Flash interval • The system bus 24 V power supply has been interrupted during operation
2 x - 1s pause
Long flashing Short flashing System bus is in status "Bus Off"
Flash interval • The 24V voltage supply of the system bus is missing
3 x - 1s pause
Long flashing Short flashing Bus interface error
Flash interval • See parameter P170
4 x - 1s pause
OFF Short flashing System error, internal program sequence interrupted
Flash interval • EMC interference (observe the wiring guidelines!)
1…7 - 1s pause • Bus interface defective