Lesson Learnt - PH and Mechanical
Lesson Learnt - PH and Mechanical
1 GAS
2 GAS
3 GAS
4 FIRE PROTECTION
COMPRESSED AIR SIZING
5 DRAINAGE
6 GAS
7 WATER SUPPLY
8 DRAINAGE
9 DRAINAGE
10 WATER SUPPLY
11 WATER SUPPLY
12 DRAINAGE
13 DRAINAGE
14 WATER SUPPLY
15 GAS
16 WATER SUPPLY
17 FIRE PROTECTION
24 GAS
25 WATER SUPPLY
26 STORM WATER
27 FIRE PROTECTION
28 FIRE PROTECTION
29 DRAINAGE
30 FIRE PROTECTION
31 FIRE PROTECTION
32 DRAINAGE
33 DRAINAGE
34 DRAINAGE
35 HOT WATER
36 WATER SUPPLY
37 FIRE PROTECTION
HOT WATER
DRAINAGE
38 ALL SERVICES
45 FIRE PROTECTION
46 DRAINAGE
46 EXCEL
47 WATER SUPPLY- BS STANDARD
48 DRAINAGE
FIRE PROTECTION
FIRE PROTECTION
FUEL TANK SIZING
LPG TANKS
Sprinklers in Obstruction
Expansion Vessel on booster PumpSet
Hot Water Expansion Tank Sizing
Sewer Holding Tank (Main One)
General MEP templates and Articles
Fire Pump Selection Online
Drainage technical Guidelines (including siphonic drainage)
Key words
Relative density
Electric Vaporiser
Electric Vaporiser
NOVEC 1230
SIZING
Pump selection
Pump selection
Grease interceptor
CLOSED LOOP
PIPE FRICTION LOSS
LINT INTERCEPTOR
ACID NUTRILISATION
PUMP SIZING
PIPE IN PIPE
TANK FILLING
Tech Street/BSOL
DRAINAGE OVER KITCHEN
RECOVERY RATE
DISTANCE BETWEEN HEATER AND FIXTURE
HOT WATER RECIRCULATION PUMP
PRESSURE LOSS
PERMISSIBLE LOCATION
GRP TANK
RAIN FALL INTENSITY
FHC ON ROOF
WAREHOUSE SPRINKLERS
SUMP PIT
PIPE MATERIAL
PIPE MATERIAL
STORM WATER
VLOOKUP
BS STANDARD PIPE SIZE
Fittings
HEATLOSSES
ASPE
BABBIT FORMULA
OFFICIAL LINK
Fire Protection
Water Supply
Water Supply
Drainage
MEP
Link
Siphonic Drainage
Lesson Learnt
Relative density (s as given in IGEM) is .6 for NG and 1.5 for LPG.
Electric Vaporisers are only used when you are storing the Gas, in Direct infrasturcture connection it is not required.
Power for Electric Vaporiser is not small. Google Algas vaporisers to get the data sheets for the same and google electric sp
Use Sapphire template for NOVEC calculation, it gives plinth dimension and number of nozzles as well.
REFER IOP PAGE 92, THERE IS A GRAPH
Self cleaning velocity for Drainage gravity flow is .75 m/s . Use manning's online calculator, to access how much gravity flo
cleaning velocity is required to be achieved atleast once a day.
Natural has is lighter than air, so it goes up. Venting and Gas detectors to be placed accordingly. LPG is heavier than air so
Use this link and always use advanced selection as it gives plinth dimensions and all that as well in advanced.
https://product-selection.grundfos.com/front-page.html
Use this link and always use advanced selection as it gives plinth dimensions and all that as well in advanced for submersib
https://product-selection.grundfos.com/front-page.html
Use the link below, it provides method to calculate GI sizes based on all three methods shown in BS :1825. BS 1825 availab
http://smartselect.kessel.de/gs.php?mid=6&id1=4&id2=9&check=1
In closed loop system, you do not add static pressure.
Equation to calculate exact pipe friction loss is given in NFPA 13.Section 23.4
Sizing to be done as per ADSSC guidellines . Code saved in your HD
Sizing to be done as per ADSSC guidellines . Code saved in your HD
FOR ANY PUMP SIZING YOU TAKE INDEX RUN ONLY EXCEPT FOR HOT WATER RETURN PUMP WHERE YOU TAKE WHOLE LO
IT IS REQUIRED ONLY WHEN GAS PIPE IS RUNNING IN CONFINED SPACE LIKE ABOVE CEILING . IF IT IS RUNNING EXPOSED N
RAW WATER TO INSIDE BUILDING TANK FILLING SHOULD BE BASED ON 8 HRS.ROOF TANK SHOULD BE BASED ON 1 TO 2 H
AS PER UAE FIRE CODE AND NFPA 13, ONE ACV CAN ONLY SERVE 4830(OR AREAD BASED ON TYPE OF HAZARD), ON ONE F
http://subscriptions.techstreet.comFor BS go to Ecosystem and Search BSOL. Password : Welcome@2020
IN RACK OR ESFR - NFPA 13 SECTION 16. 12 SPRINKLERS CONSIDERED TAKE FLOWRATE BASED ON K FACTOR +ADD HOSE D
THAN LANDING VALVE AND STANDPIPE DEMAND FOR PROJECT.(REFER TABLE 16.2.3.1-FOR ESFR RACK STORAGE WITHOU
DEPTH OF SUMP PIT.
1. CLEARANCE FOR SUBMERSIBLE PUMP FROM GRUNDFOS.
2.RETENTION VOLUME
3. SECOND PUMP LEVEL 15% HEIGHT OF RETENTION VOLUME.
4. 100 MM FOR ALARM LEVEL
5. INVERT LEVEL OF INLET PIPE
CARBON STILL IS USED ONLY WHEN THE ENVIORNMENT IS NOT CORROSIVE. WHERE IT IS CORROSIVE USE GALVANISED ST
OLD UAE FIRE CODE STATES FIRE PUMP SHOULD ALWAYS BE THERE AT THE LOWEST FLOOR. IT CANNOT SUPPLY BELOW, I
STATES THAT THE FIRE PUMP ROOM CAN BE ANY WHERE BETWEEN GROUND TO LOWEST LEVEL.UAE 2018 PAGE 73.
DRAINAGE SCREED ON THE ROOF SHOULD BE 2%- THIS IS A CODE REQUIREMENT
BS-12056-2 REQUIRES ACCESS ON EVERY 3 FLOOR INTERVAL,HOWEVER DUBAI MUNCIPALITY REQUIRES EVERY FLOOR. RE
Uniform Pluming Code of Abu Dhabi (UPC-ADH) Chapter 11, section 1101.11 mandates sizing the
primary storm water drainage for storm water duration of 60 minutes and a 100 year return period.
FOR SYSTEM VOLUME-50 L / PER PANEL. EX 100 PANEL = 50X100=5000 L/HR FLOW OF SOLAR TO DB PUMP.VELOCITY .55 M
IN PUMP SIZING ONLY THE INDEX RUN MATTERS.
MINIMUM INSTALLATION SIZE FOR ACV INSTALLATION (800x500x800)
HOT WATER RETURN PIPE SIZE BY THUMG RULE IS 2 SIZES DOWN .REFERENCE IOP
YOU CANNOT HAVE DRAINAGE RUNNING INSIDE THE TANKS. ALSO ALWAYS CONSIDER ACCESS TO THE INSIDE OF TANKS F
Water Supply
Cold Water
Hot water
Sanitary
External Drainage
Internal Drainage
Buried in foundation
Storm Water
External
Internal
Buried in Foundation
Irrigation Water
Water feature piping
Condensate Drain Pipe
Fire Protection
Buried Pipe
Above Ground
Clean Agent
Natural Gas
Buried Pipe
Above ground
Compressed Air
Compressed air Piping
Medical Gas
Medical Gas piping
IN FIRE YOU USE PRVA ONLY AND WHERE THE PRESSURE EXCEEDS 12.1 BAR.
REFERENCE UAE FIRE CODE 2018.
Undergroud pipe material can be HDPE, allowed and given in UAE FLS 2018, above ground also CS and GS and Thermoplas
FOR SIDE WALLS DRAINING INTO THE ROOF , SEE UPC ABUDHABI PAGE 110 ,1106.2 APPERENTLY YOU HAVE TO ADD WAL
Vlook up only works if the data you are looking up is in the assending order.
INTERPRETATION OF LU TO FLOWRATE CHART.
CHECK SEAWORLD DETAIL YOU WILL FIND IT . ALSO GOOGLE IT. REFER UPC ABUDHABI PAGE 111, SECTION 909.
NFPA 20 11.4.2
SEPERATION DISTANCE
REFERENCE DOMESTIC WATER HEATING DESIGN MANUAL-ASPE
FIRE PUMP SUCTION FLANGE TO FLANGE OF PUMP SHOULD BE 10 TIMES DISTANCE OF DIAMETER , NFPA 20 FIGURE A.4.1
NFPA 20 11.4.2
75 mm/hr section H
Section 603.3.2.1
CIBSE Guide M , Appendix 13.A.1
https://www.gfps.com/en-ae/downloads-tools/online-tools.html
Every 1 l/s 4 cum of Polystorm . And cell come in depth of 600mm and so on.
Sprinkler distribution cannot happen if the pressure is more than 12.1 bar . Same case for FHC capped off as well . This is w
Always connect using Back flow preventer.(BFP) there are like double check valve
HWS and CWS should always have similar pressure to enable efficient mixing. Location of PRV should be such that dead lea
https://www.aco.co.uk/quad-hydraulic-design-2.0
https://www.dewa.gov.ae/en/builder/useful-tools/dewa-circulars
Water Supply
PPR Under ground (4 inch and smaller)
Sanitary
Storm Water
uPVC Class E Above ground Piping
HDPE Underground Storm
PVC Sch 80
uPVC class E
uPVC Class E
Fire Protection
Black Steel ASTM A53 Sch 40 Underground under road way
Natural Gas
MDPE Buried Pipe Outdoor
Seamless black steel sch 40 Above ground Outdoor
Compressed Air
Compressed Air Between Air
Stainless Steel
compressor and Receivers
Drain Piping
Medical Gas
Seamless Copper NA
100 YEARS , 60 MINS GIVES 29MM/HR
taken prior to PRV.
1.09504132231405
SWAD-EXP
Soft copper ASTM B 88
Ductile Iron
CPVC
Galvanized steel
Black steel
Galvainzed Steel
Steel Pipe
Sch 40 Galvanized steel/Type L copper
tube/Aluminium Piping /PE-AL-PE
NA
Neom Data
SWAD -Recommendation
Water Supply
Cold Water PPR + Insulation
Sanitary
Storm Water
External Buried HDPE
Internal Buried HDPE
Condensate
Condensate Drain Pipe uPVC Class E with Insulation
Condensate Drain Pipe UG HDPE
Fire Protection
Buried Pipe HDPE
Above Ground , Sprinkler and Wet
Galvanized steel
riser
Dry Pipe System/ Deluge/ Pre
Galvanized steel
action
Clean Agent Black Steel ASTM A53 Sch 40
Sprinkler Drain pipe Galvanised Steel Sch 40
Natural Gas
Buried Pipe HDPE - PE-100
Above Ground Seamless black steel sch 40
Compressed Air
Compressed Air Between Air
Sch 40 Galvanized steel
compressor and Receivers
Medical Gas
Medical Gas piping Seamless Copper
2 Sprinkler Protection-Stairs
Sprinkler Protection-Above
3
false ceiling
Sprinkler Protection-
4
Elevator Shaft
Sprinkler Protection-
5
Bathrooms
Sprinkler Protection-
6
laundry/Storage
Sprinkler Protection-
7
Pantries
Sprinkler Protection-
8
Garbage Chute
Sprinkler Protection-High
9
Ceiling areas
Sprinkler Protection-
10
Terrace/Balcony
13 Generator room
14 Portable Extinguishers
5 Hydrant required if
the area exceeds 3600
sq m for warehouses
and 20000 sqm fir
other buildings
6 Balcony sprinklers are i. Exterior balconies having
recommended. combustible materials and
façade shall be provided
with
automatic sprinkler system
as per Section 3.5. of UAE
Fire code.
The stair top (top of the shaft) and first accessible landing above
the bottom of the shaft shall be provided with sprinkler system as
per Section 3.5 of UAE Fire Code.
i. UAE Fire code 2018, States in Chapter -01 , Table 1.9, 47.
(concealed Spaces)," Any concealed spaces more than 800mm
accomodating services such as no fire rated ventilation ducting,
exposed cables, wiring, fuel gas piping, shall be provided with
automatic sprinkler system.Sprinklers shall be provided where
ever the above suffice.
The sidewall spray sprinklers in accordance with Section 3.5 of No impact on cost as in the
UAE Fire Code shall be installed at the bottom of each elevator absence of guidelines in UAE
hoistway (shaft) not more than 600mm above the floor of the pit. fire code 2011, NFPA 13 and
other industry practice were
followed.
Cost reduction
i. Laundry and storage rooms of residential buildings, residential No impact on cost as in the
apartment buildings and hotel apartment buildings shall be absence of guidelines in UAE
provided with sprinkler system as per Section 3.5. fire code 2011, NFPA 13 and
other industry practice were
followed.
Pantries in business occupancies and commercial buildings shall No impact on cost as in the
be provided with a sprinkler system as per Section 3.5. absence of guidelines in UAE
fire code 2011, NFPA 13 and
other industry practice were
followed.
i. A garbage chute shaft shall be provided with one sprinkler head No impact on cost as in the
at the top of the absence of guidelines in UAE
shaft, one sprinkler head at alternating floors and one sprinkler fire code 2011, NFPA 13 and
head at the lowest other industry practice were
level, as per Section 3.5. followed.
i.Where building ceiling height exceeds 10m in height, sprinklers Increase in cost as thelatest
shall be provided code specifies extended
in accordance with Section 3.5 and Table 9.29.A of UAE Fire coverage , early response type
Code. sprinklers.