Specification
CV3000 Alphaplus Series
Model AGVB / AGVM
Electric Top-Guided Single-Seated Control Valves
OVERVIEW
The CV 3000 Alphaplus range of Top-guided Single-seat Control Valves features a compact valve body with
excellent flow control and minimal pressure loss. Alphaplus valves have large Cv values, high range ability, and
accurate flow control performance.
When securely held in place by a top-guided stem with a long stroke, the valve plug is highly resistant against
vibration and provides flow shutoff performance that fully satisfies IEC standards.
The actuator section performs two-position control or proportional control by directly receiving the signal of 4 to 20
mA DC or 1 to 5 V DC from the electronic-type controller. The provided electric-type actuator offers high accuracy,
compactness, and sturdy structure.
Model AGVB/AGVM control valves are especially suitable for process control applications where high reliability
and tight flow shutoff are essential.
Specifications are subject to change without notice. -1- First issue : Mar. 2001
No.SS2-AGV200-0300
2. Basic Model Numbers
Model AGVB: JIS 10K, ANSI 150, JPI 150
Model AGVM: JIS 16K, JIS 20K, JIS 30K, ANSI 300, JPI 300
3. Optional Specifications
3-1 Body
Figure 2 shows optional specifications of the body.
3-1-1 Flange diameter 3-1-5 Body and Plug Seat Ring Materials
Yamatake manufactures diameters from 1/2 in. to 2 in. as shown For combinations of body and plug seat ring materials and their
in Table 5. applicable temperature ranges, see Table 6. In some ranges the
For other diameters, we recommend a selection from the CV plug seat ring material needs hardening treatment. See Figure 8.
3000 series of control valves. When you select a soft seat, refer to Figure 9.
For materials other than those shown in Table 6, we
3-1-2 Port Diameter and flow Control Characteristics recommend a selection from the CV 3000 series of control
The selection of the port diameter and the rated Cv value falls valves.
within the scope of Table 1 according to the Flange diameter. For
Flange diameters 1inch (25 mm) or less, port diameters are 3-1-6 Valve Seat Leakage
expressed in terms of Cv values. Flow control characteristics For the seat leak performance when the valve is fully
depend on the rated Cv value. closed, select from among the following four classifications, which
Based on the rated Cv value and the calculated necessary conform to IEC 534-4-1986 and JIS B 2007-1993:
Cv value, check the controllability (valve position) using the Class IV: 10-4 X rated Cv value
Flow Control Characteristics in Figures 4, 5, and 6. (0.01% of rated Cv value)
Class VI: 3 X valve differential pressure (MPa)
3-1-3 Flange Standard (Flange Type) X leakage coefficient ml/min shown below
We manufacture JIS 10KRF, ANSI 150RF, JPI 150RF, Table 1. Leakage coefficient value
JIS 16K, JIS 20K, JIS 30K, ANSI 300, and JPI 300. Nominal size 1 1½ 2 2½ 3 4
For other rated pressures and connection types, you are in. (mm) (25) (40) (50) (65) (80) (100)
recommended to consider the CV 3000 series of control Leakage coefficient 0.15 0.30 0.45 0.60 0.90 1.70
valves.
For shutoff valves, choose Class VI (soft seat).
3-1-4 Bonnet
We manufacture bonnets that can be used at fluid temperatures
3-1-7 Inherent Rangeability:
ranging from -45°C to 400°C.
Table 2. Inherent rangeability Vs. Rated CV
For fluid temperatures outside the above temperature
Rated Cv Inherent Rangeability
range, we recommend a selection from the CV 3000series
of control valves. 0.1, 0.16, 0.25, 0.4 20:1
0.63 30:1
1.0 or more than 1.0 50:1
-2-
No.SS2-AGV200-0300
3-1-8 Gland packing
According to your application, select appropriate type of gland packing from among the following:
Table 3. Selection of gland packing
Usage Type Material
General use (oils, solvent PTFE yarn packing Woven PTFE yarn
acids, alkalis, etc.) (NP4519) with carbon fiber core
Waste oil washing V type PTFE packing PTFE molding
V type PTFE packing
Vacuum service PTFE molding
(direct + reverse)mounted
Low-temperature service V type PTFE packing PTFE molding
Graphite yarn packing
High-temperature service Graphite
(P6610CL+P6722)
PTFE: polytetrafluoroethylene resin
For other gland packing materials, please provide closest model No. and Yamatake will take your request under advice.
PTEF yarn packing V type PTEF packing V type PTEF (direct+ reverse) Graphite yarn packing
*1 *1 *1 *1
*1: It is a standard practice to use packing glands with O rings to render them dustproof.
Figure 3. Gland packing structure
3-1-9 Gasket
Table 4. Selection of Gaskets
General / Low temp. High temperature Oil free treatment
Metal gasket Metal gasket
Metal gasket
Between bonnet & body (PTFE coating) (PTFE coating)
V543
V543(PTFE) V543 (PTFE)
Metal gasket
Metal gasket
Between seat ring & body Not necessary (PTFE coating)
V564 (Monel)
V563 (PTFE)
-3-
No.SS2-AGV200-0300
Table 5. Models of AGVB and AGVM
1 (25)
Nominal size 1½ 2
In. (mm) 3/4 (20) (40) (50)
1/2 (15)
Port diameter 0.1
0.4 1.0 2.5 8.0 10 1 1¼ 1½ 1¼ 1½ 2
Inch 0.16
0.63 1.6 4.0 6.3 14
Rated Cv value 0.25 14 21 30 21 30 50
Figure 4. Cv values 0.1, 0.16, and 0.25 Figure 5. Cv values 0.4 to 14 Figure 6. Port diameter 1½ to 2inch
(linear model ) (equal percentage model) (equal percentage model)
: Scope of control generally considered feasible *Cv value in percentage and travel in percentage)
Figure 8. Temperature and normal differential Figure 9. Temperature and maximum differen-
pressure ranges that require a stellite tial pressure ranges for soft seats
1) For valves for cavitation/flashing service, oil-proof service, or tight shutoff Note) When there is a possibility of erosion by such fluids as saturated
service, a stellite is recommended regardless of process fluid tempera- steam and heated water please use metal seats.
tures or differential pressures.
2) For valves for cavitation/flashing service for water or for valves for su-
perheated water above 100°C, SUS 440C is recommended.
-4-
No.SS2-AGV200-0300
3-2 Actuator 3-2-2 Tables of Allowable Differential Pressures
3-2-1 Actuator and Valve Actions Ensure the required shut-off differential pressure specified in the
• Actuator equipment design is satisfied by selecting an actuator with an
Table 7. Specification of actuator allowable differential pressure equal to or higher than the shut-off
Type Electronic motor pressure, according to the seat leakage class.
Control action Proposional control or Seat leakage, Class IV (0.01% of rated Cv value)
Two-posiition control • Model AGVB : Table 9, 10.
Power supply AC100 V ± 10% 50/60 Hz • Model AGVM : Table 11, 12.
Single phase
Seat leakage, Class VI (highshutoff model : soft seat)
Input signal AC200 V ± 10% 50/60 Hz
• Model AGVB : Table 13, 14
Single phase
• Model AGVM : Table 15, 16
Action Direct or Reverse
Power failure action Close, Open or Hold
3-2-3 Coating
Input resistance 250Ω
The normal standard coating color for Yamatake control valves is
Demand Opelation 24 VA
blue (Munsell color 10 in. 5/10). Silver is also available as stan-
Non-operation 1.5 VA (AC100 V)
dard.
Insulation resistance Between input terminal and case
With stand voltage Between poser supply terminal and You can specify any other color using the number code of the
Material Case: Aluminium die-casting Standard colors are also used for such optional accessories as
Stem: 303ss positioners, pressure regulator with filter, and solenoid valves.
Yoke: Carbon steel
Type of protection IP65 equivalent
Motor Reversible motor
Coil insulation class E
Rated temperature Continuity (built-in thermal switch)
Position sensor Potentiometer
Protective device Built-in open/close limit switch
Built-in lower tourque limiter
Electrial connection G1/2
Ambient temperature -25 to 55 °C
limits
Ambient humidity limits 10 to 90%RH
Vibration tolerance 2 G 5 to 100 Hz
Travel transmission* 1 to 5 V DC
Manual operation Top handle
*) Travel transmission shall be option for two-position control.
• Valve action
Single-fail-close: actuator action where the valve opens as the
input signal increases
Single-fail-open: actuator action where the valve closes as the
input signal increases
With the Alphaplus, the valve closes as the plug lowers. The
valve action depends, in turn, on whether an single-fail-close
or single-fail-open actuator is chosen.
-5-
No.SS2-AGV200-0300
4. Fluid Conditions
Please clear the Fluid condition as follows.
Name Description
Flow rate Maximum (MAX), normal (NOR), and minimum (MIN) flow rates to be controlled
Upstream pressure Pressure on upstream side of control valve (P1 in Figure 10.)
Downstream pressure Pressure on downstream side of control valve (P2 in Figure 10.)
Differential pressure when fully closed Differential pressure when the valve is fully closed (actuator selection condition)
Weight percentage of flashing to occur on downstream side when pressure is reduced by the
Flashing %
control valve
Yamatake has developed personal computer software to calculate Cv values and expected noise.
Please specify if you require such a PC-based tool.
-6-
No.SS2-AGV200-0300
Valve seat leakage, Class IV: 0.01% of the rated Cv value
Table 9. Model AGVB nominal size 1/2, 3/4, and 1 in.
Note that the permissible differential pressure varies with the rated Cv value you have selected.
Differential pressure (classified by Cv value) kPa {kgf/cm2}
Nominal size 0.1
Actuator 0.4 1.0 2.5 6.3 10
in. 0.16
0.63 1.6 4.0 8.0 14
0.25
1/2
1960
3/4 EA1
{20.0}
1
Note that the maximum permissible differential pressures must not exceed the maximum working pressures specified
by JISB2201-1984, ANSIB16.34-1981, and JPI-7S-65-83.
Table 11. Model AGVM nominal size 1/2, 3/4, and 1 in.
Note that the permissible differential pressure varies with the rated Cv value you have selected.
Differential pressure (classified by Cv value) kPa{kgf/cm2}
Nominal size Actuator 0.1
0.4 1.0 2.5 6.3 10
in. 0.16
0.63 1.6 4.0 8.0 14
0.25
1960
1/2 {20.0}
3/4 EA1
1 5100 4120 3040
{52.0} {42.0} {31.0}
Note
1) Note that the maximum permissible differential pressures must not exceed the maximum working pressures specified by JISB2201-1984, ANSIB16.34-1981,
and JPI-7S-65-83.
2) In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At
your request, we can manufacture control valves with normal pressures exceeding 1960kPa.
1960
1½ {20.0} 1870 1270 760
EA1 —— —— ——
2 {19.0} {12.9} {7.7}
3040
{31.0}
Note:
1) Note that the maximum permissible differential pressures must not exceed the maximum working pressures specified by JISB2201-1984, ANSIB16.34-1981,
and JPI-7S-65-83.
2) In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed. At
your request, we can manufacture control valves with normal pressures exceeding 1960kPa.
-7-
No.SS2-AGV200-0300
Valve seat leakage, Class VI: high shutoff model: soft seat
Table 13. Model AGVB nominal size 1/2, 3/4, and 1 in.
Note that the permissible differential pressure varies with the rated Cv value you have selected.
Differential pressure (classified by Cv value) kPa{kgf/cm2}
Nominal size 0.1
Actuator 0.4 1.0 2.5 6.3 10
in. 0.16
0.63 1.6 4.0 8.0 14
0.25
1/2
1960
3/4 EA1
{20.0}
1
Note that the maximum permissible differential pressures must not exceed the maximum working pressures specified by JISB220-1-1984, ANSIB16.34-1981,
and JPI-7S-65-83.
Table 15. Model AGVM nominal size 1/2, 3/4, and 1 in.
Note that the permissible differential pressure varies with the rated Cv value you have selected.
Differential pressure (classified by Cv value) kPa{kgf/cm2}
Nominal size 0.1
Actuator 0.4 1.0 2.5 6.3 10
in. 0.16
0.63 1.6 4.0 8.0 14
0.25
1/2 1960
{20.0} 1700
3/4 EA1
2940 2070 {17.3}
1 {30.0} {21.1}
Note:
1) Note that the maximum permissible differential pressures must not exceed the maximum working pressures specified
by JISB220-1-1984, ANSIB16.34-1981,and JPI-7S-65-83.
2) In the differential pressure column, upper figures show normal differential pressures and lower figures differential pressures when the valve is fully closed.
At your request, we can manufacture control valves with normal pressures exceeding 1960kPa.
-8-
No.SS2- AGV200-0300
MODEL SELECTION
CV3000 ALPHAPLUS Model No, Constraction Table (AGVB Type)
AGVB
1/2 in. 1
3/4 in. 2
Valve Size 1in. 3
1½ in. 4
2 in. 5
Cv=0.1 Linner *1 A
Cv=0.16 Linner *1 B
Cv=0.25 Linner *1 C
Cv=0.4 EQ% D
Cv=0.63 EQ% E
Port Size & Cv=1.0 EQ% F
Plug Flow Cv=1.6 EQ% G Valve Seat ClassIV:0.01% of the rated Cv value 1
Charactur- Cv=2.5 EQ% H Leakage ClassVI:High shutoff model:Soft seat 3
istic Cv=4.0 EQ% J PTFE Yarn (General use) 1
Cv=6.3 EQ% 4 V-typePTFE (For General&Degreasing) 2
*1
Cv=8.0 EQ% K V-typePTFE (D)+(R) (For Vacuum service) 3
Cv=10 EQ% L VTypePTFE (For Low Temp. service) 5
1in. (25 mm),Cv=14 EQ% M Gland Graphite Yarn(For Hi Temp./Water resistant) 4
1¼ in. EQ% N Packing Graphite Yarn(For Hi&Lo Temp./Oil resistant) 6
1½ in. EQ% P Graphite Yarn(For Alkali or Acid service) 7
2in. EQ% R Graphite Yarn(For Solvent service) 8
JIS 10K RF J Others Enter client's requirement
9
Rating ANSI 150 RF A
JPI 150 RF P EA1R (Single to open, Positional control) [Close] 5
Standard Type (-17 to 230 deg.C) 1 EA1R (Single to open, Positional control) [Hold] 6
Upper
Extention Type (230 to 400 deg.C EA1R (Single to open, Positional control) [Open] 7
Bonnet 2
or -45 to -17 deg.C) EA1D (Single to close, Positional control) [Close] 8
SCPH2 1 Actuator and EA1D (Single to close, Positional control) [Hold] L
SCS13A 2 Vlave action EA1D (Single to close, Positional control) [Open] M
SCS14A 3 [Power failure EA1R (Single to open, Two-position control) [Close] N
Body A216WCB A action] EA1R (Single to open, Two-position control) [Hold] P
Material A351CF8 B EA1R (Single to open, Two-position control) [Open] Q
A351CF8M C EA1D (Single to close, Two-position control) [Close] R
Others Enter client's EA1D (Single to close, Two-position control) [Hold] S
9
requirement EA1D (Single to close, Two-position control) [Open] T
SUS316 2 AC 100 V 4-20 mA DC (Positional control ) J
SUS316 Stellite 4 AC 100 V 1-5 V DC (Positional control ) K
SUS440C 5 AC 110 V 4-20 mA DC (Positional control ) L
SUS316 Soft seat 6 AC 110 V 1-5 V DC (Positional control ) M
Plug&Seat SUS316Stellite face *1 7 AC 200 V 4-20 mA DC (Positional control ) N
Material SUS316L 8 Power supply AC 200 V 1-5 V DC (Positional control ) P
SUS316L Stellite A and Input signal AC 220 V 4-20 mA DC (Positional control ) Q
SUS316L Soft seat B AC 220 V 1-5 V DC (Positional control ) R
Others Enter client's AC 100 V (Two-position control ) S
9
requirement AC 110 V (Two-position control ) T
AC 200 V (Two-position control ) U
AC 220 V (Two-position control ) W
Standard :Blue(M10B5/10) 1
Silver 2
Heat resistant Silver 3
Corrosion resistant Silver 4
Finish
Saline-resistant Silver 5
Recommend:Bolt & nut material:SUS304
Others Enter client's requirement 9
Body/ Diaphragm case/ Yoke
(Refer to next page)
-9-
No.SS2- AGV200-0300
Model No. AGVB
T X X X
- 10 -
No. SS2-AGV200-0300
AGVM
1/2 in. 1
3/4 in. 2
Valve Size 1in. 3
1½ in. 4
2 in. 5
Cv=0.1 Linner *1 A
Cv=0.16 Linner *1 B
Cv=0.25 Linner *1 C
Cv=0.4 EQ% D
Cv=0.63 EQ% E
Port Size & Cv=1.0 EQ% F
Plug Flow Cv=1.6 EQ% G ClassIV:0.01% of the rated Cv value 1
Charactur- Cv=2.5 EQ% H ClassVI:High shutoff model:Soft seat 3
istic Cv=4.0 EQ% J PTFE Yarn (General use) 1
Cv=6.3 EQ% 4 V-typePTFE (For General&Degreasing) 2
*1 Cv=8.0 EQ% K V-typePTFE (D)+(R) (For Vacuum service) 3
Cv=10 EQ% L VTypePTFE (For Low Temp. service) 5
1in. (25 mm),Cv=14 EQ% M Gland Graphite Yarn(For Hi Temp./Water resistant) 4
1¼ in. EQ% N Packing Graphite Yarn(For Hi&Lo Temp./Oil resistant) 6
1½ in. EQ% P Graphite Yarn(For Alkali or Acid service) 7
2 in. EQ% R Graphite Yarn(For Solvent service) 8
JIS 16K RF B Others Enter client's requirement
9
JIS 20K RF C
Rating JIS 30K RF D EA1R (Single to open, Positional control) [Close] 5
ANSI 300RF E EA1R (Single to open, Positional control) [Hold] 6
JPI 300RF F EA1R (Single to open, Positional control) [Open] 7
Standard Type (-17 to 230 deg.C) 1 EA1D (Single to close, Positional control) [Close] 8
Upper
Extention Type (230 to 400 deg.C, Actuator and EA1D (Single to close, Positional control) [Hold] L
Bonnet 2
or -45 to -17 deg.C) Vlave action EA1D (Single to close, Positional control) [Open] M
SCPH2 1 [Power failure EA1R (Single to open, Two-position control) [Close] N
SCS13A 2 action] EA1R (Single to open, Two-position control) [Hold] P
SCS14A 3 EA1R (Single to open, Two-position control) [Open] Q
Body A216WCB A EA1D (Single to close, Two-position control) [Close] R
Material A351CF8 B EA1D (Single to close, Two-position control) [Hold] S
A351CF8M C EA1D (Single to close, Two-position control) [Open] T
Others Enter client's AC 100 V 4-20 mA DC (Positional control ) J
9
requirement AC 100 V 1-5 V DC (Positional control ) K
SUS316 2 AC 110 V 4-20 mA DC (Positional control ) L
SUS316 Stellite 4 AC 110 V 1-5 V DC (Positional control ) M
SUS440C 5 AC 200 V 4-20 mA DC (Positional control ) N
SUS316 Soft seat 6 Power supply AC 200 V 1-5 V DC (Positional control ) P
Plug&Seat SUS316Stellite face *1 7 and Input signal AC 220 V 4-20 mA DC (Positional control ) Q
Material SUS316L 8 AC 220 V 1-5 V DC (Positional control ) R
SUS316L Stellite A AC 100 V (Two-position control ) S
SUS316L Soft seat B AC 110 V (Two-position control ) T
Others Enter client's AC 200 V (Two-position control ) U
9
requirement AC 220 V (Two-position control ) W
Standard :Blue(M10B5/10) 1
Silver 2
Heat resistant Silver 3
Corrosion resistant Silver 4
Finish
Saline-resistant Silver 5
Recommend:Bolt & nut material:SUS304
Others Enter client's requirement 9
Body/ Diaphragm case/ Yoke
(Refer to next page)
- 11 -
No. SS2-AGV200-0300
T X X X
- 12 -
No.SS2-AGV200-0300
DIMENSIONS
Table 17, 18 shown the dimensions and weight of the control valves. Note that the addition of any optional
specifications will change their installed dimensions and weights.
3/4 13 14 13 14 15 16
1 14 15 14 15 16 17
1½ 21 25 21 25 26 30
2 24 28 24 28 27 31
-13-