Water Mist

This document provides a summary of the control logic diagrams for a water mist fire suppression system on an offshore structure. It includes definitions, reference documents, hardware components, input/output lists, network architecture, descriptions of smoke detectors, flame detectors, digital outputs, inhibit functions, logic, and display screens. The document was issued for review as the first revision with a status of in-force.

Uploaded by

Yasmina Bethy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views20 pages

Water Mist

This document provides a summary of the control logic diagrams for a water mist fire suppression system on an offshore structure. It includes definitions, reference documents, hardware components, input/output lists, network architecture, descriptions of smoke detectors, flame detectors, digital outputs, inhibit functions, logic, and display screens. The document was issued for review as the first revision with a status of in-force.

Uploaded by

Yasmina Bethy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

FPU – AUTOCHIM Document Number

CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 1 of 20

MOHO NORD PROJECT

FPU – AUTOCHIM
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST

Return Status Code by HSHI

The document is:

Code 1 Accepted Without Comments


Code 2 Accepted With Comments
Code 3 Rejected

Signed by HSHI

Date:

Rev. Status Date Revision memo Issued by Checked by Approved by

GD OP
PAD
PA
00 IFR 27-Jun-2014 Issued for Review G.DENIEL O SPITZER
DROSNET
This document has been generated by an Electronic Document Management System. When printed it is considered as a “for information only” copy. The
controlled copy is the screen version and it is the holder’s responsibility that he/she holds the latest valid version
This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 2 of 20

TABLE OF REVISIONS

Revision Modification

00 First issue

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 3 of 20

TABLE OF CONTENT

1 PURPOSE ................................................................................................................................................ 4
2 DEFINITIONS ........................................................................................................................................... 4
3 REFERENCE DOCUMENTS .................................................................................................................... 4
4 HARDWARE ............................................................................................................................................ 5
4.1 PLC ........................................................................................................................................................ 5
4.2 ESA IT 107W ......................................................................................................................................... 5
5 LISTE I/O .................................................................................................................................................. 6
6 NETWORK ARCHITECTURE .................................................................................................................. 8
6.1 READ/WRITE exchange BETWEEN touchscreen hmi and HIMA PLC .................................................. 9
6.2 Download and online functions .............................................................................................................. 9
7 DESCRIPTION ....................................................................................................................................... 10
7.1 Smoke Detectors – ORBIS - RDOS ..................................................................................................... 10
7.2 Flame Detectors – FL4000H - RDIR .................................................................................................... 11
7.3 DIGITAL OUTPUTS ............................................................................................................................. 11
7.3.1 DIGITAL OUTPUTS TO watermist Extinguishing panel(Allen-Bradley PLC) ..................................... 11
7.3.2 DIGITAL OUTPUTS TO FGS ............................................................................................................ 11
7.4 inhibit ................................................................................................................................................... 12
7.5 Logic .................................................................................................................................................... 13
8 DISPLAY ................................................................................................................................................ 15
8.1 system view ......................................................................................................................................... 15
8.2 EVeNTS view ....................................................................................................................................... 16
8.3 fire detection views .............................................................................................................................. 17
8.4 communication fault ............................................................................................................................. 20

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 4 of 20

1 PURPOSE
This document defines operation of fire Detection for Watermist.

2 DEFINITIONS

3 REFERENCE DOCUMENTS

Reference Title

CG-MHN-11-2300-428701 HULL – REQUISITION – FIRE & GAS DETECTION/ALARM SYSTEM

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 5 of 20

4 HARDWARE

4.1 PLC

H41 q ‐ HS

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

F6217 F6217 F6217 F3331 F3331 F3330 F8652 F8652 F7130 F7130

AI AI AI DOM DOM DO CPU CPU ALIM ALIM


‐01 ‐02 ‐03 ‐01 ‐02 ‐01 ‐01 ‐02 ‐01 ‐02

Software HIMA H41q : ELOP II V4.1 build 6134.

4.2 ESA IT 107W

Software Touchscreen operator Terminal ESA IT 107 : ESAPOLYMATH V2.21.2013

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 6 of 20

5 LISTE I/O

Module
Tag Detectors Detector Type Reference Localisation
Type
13‐RDOS‐03007A31 Smoke Detector LEVEL 0 Em DG ROOM Orbis

11‐RDOS‐03203B31 Smoke Detector LEVEL ‐2 Ess DG ROOM 1 Orbis

11‐RDOS‐03204B31 Smoke Detector LEVEL ‐2 Ess DG ROOM 2 Orbis


8 Analog
11‐RDOS‐03312B31 Smoke Detector LEVEL ‐3 DO TREATMENT ROOM Orbis
Inputs
F6217
11‐RDOS‐03310B31 Smoke Detector LEVEL ‐3 HPU ROOM 1 Orbis
Z7128/
11‐RDOS‐03311B31 Smoke Detector LEVEL ‐3 HPU ROOM 2 Orbis

Spare

Spare

11‐RDOS‐03310B33 Smoke Detector LEVEL ‐3 HPU ROOM 1 Orbis

11‐RDOS‐03311B33 Smoke Detector LEVEL ‐3 HPU ROOM 2 Orbis

11‐RDIR‐03310B34 IR3 FLAME DETECTOR LEVEL ‐3 HPU ROOM 1 FL4000H


8 Analog
11‐RDIR‐03311B34 IR3 FLAME DETECTOR LEVEL ‐3 HPU ROOM 2 FL4000H
Inputs
F6217
11‐RDOS‐03312B33 Smoke Detector LEVEL ‐3 DO TREATMENT ROOM Orbis
Z7128/
11‐RDIR‐03312B34 IR3 FLAME DETECTOR LEVEL ‐3 DO TREATMENT ROOM FL4000H

Mode Inhibition KEY Switch

Spare

13‐RDIR‐03007A32 IR3 FLAME DETECTOR LEVEL 0 Em DG ROOM FL4000H

11‐RDIR‐03203B32 IR3 FLAME DETECTOR LEVEL ‐2 Ess DG ROOM 1 FL4000H

11‐RDIR‐03204B32 IR3 FLAME DETECTOR LEVEL ‐2 Ess DG ROOM 2 FL4000H


8 Analog
11‐RDIR‐03312B32 IR3 FLAME DETECTOR LEVEL ‐3 DO TREATMENT ROOM FL4000H
Inputs
F6217
11‐RDIR‐03310B32 IR3 FLAME DETECTOR LEVEL ‐3 HPU ROOM 1 FL4000H
Z7128/
11‐RDIR‐03311B32 IR3 FLAME DETECTOR LEVEL ‐3 HPU ROOM 2 FL4000H

Spare

Spare

11‐RDWM‐011001 CONFIRMED FIRE To FGS Em DG ROOM 2oo2

11‐RDWM‐011002 CONFIRMED FIRE To FGS Ess DG ROOM 1 2oo2

2oo2 8 Digital
11‐RDWM‐011003 CONFIRMED FIRE To FGS Ess DG ROOM 2
Outputs
2oo2 F3331/
11‐RDWM‐011005 CONFIRMED FIRE To FGS DO TREATMENT ROOM
Z7138
11‐RDWM‐011006 CONFIRMED FIRE To FGS HPU ROOM 1 2oo4

11‐RDWM‐011007 CONFIRMED FIRE To FGS HPU ROOM 2 2oo4

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 7 of 20

Module
Tag Detectors Detector Type Reference Localisation
Type
System Fault To PCS

Spare

CONFIRMED FIRE To WM Em DG ROOM 2oo2

CONFIRMED FIRE To WM Ess DG ROOM 1 2oo2

CONFIRMED FIRE To WM Ess DG ROOM 2 2oo2

2oo4 8 Digital
CONFIRMED FIRE To WM DO TREATMENT ROOM Outputs
CONFIRMED FIRE To WM HPU ROOM 1 2oo4 F3331/
Z7138
CONFIRMED FIRE To WM HPU ROOM 2 2oo4

Spare

Spare
Panel FD
13‐RDR‐03007A31 RESET LOOP LEVEL 0 Em DG ROOM
System
Panel FD
11‐RDR‐03203B31 RESET LOOP LEVEL ‐2 Ess DG ROOM 1
System
Panel FD
11‐RDR‐03204B31 RESET LOOP LEVEL ‐2 Ess DG ROOM 2
System
Panel FD 8 Digital
11‐RDR‐03312B31 RESET LOOP LEVEL ‐3 DO TREATMENT ROOM
System Outputs
Panel FD F3330/
11‐RDR‐03310B31 RESET LOOP LEVEL ‐3 HPU ROOM 1
System Z7138
Panel FD
11‐RDR‐03311B31 RESET LOOP LEVEL ‐3 HPU ROOM 2
System
Panel FD
Inhibition status
System
Panel FD
System

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 8 of 20

6 NETWORK ARCHITECTURE

The controller communicates with remote through two serial links equipment.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 9 of 20

6.1 READ/WRITE EXCHANGE BETWEEN TOUCHSCREEN HMI AND HIMA PLC

Slave Address : 1 (configured on the switch cpu by removing the rack off)
Speed : 57600 Bit/Sec
Parity : Even
Stop Bits : 1
Data Bits : 8

6.2 DOWNLOAD AND ONLINE FUNCTIONS

Port dedicated to the HMI Station 1 will be used by the programmer to connect online.
Thus, the data display will not be available during PLC settings.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 10 of 20

7 DESCRIPTION

System monitoring fire is composed of various detection sensors:


18 Orbis – Smoke detectors (RDOS)
9 FL4000H - Flame Detectors (RDIR).
The system manages Fire Detection in 6 room.

7.1 SMOKE DETECTORS – ORBIS - RDOS

The measurement is considered invalid in the 2 following cases:


- Input card channel faulty
- Signal lower than a “low invalidity” threshold (Open loop)

The open-loop monitoring is assumed by the software typical.


In case of invalidity, an invalidity alarm is generated, latched till the loop is valid again and the
alarm is acknowledged by the operator.

The detection threshold is an input parameter of the typical, named DET_THRESH (value
expressed in mA). The detection alarm, which has a trip action, is latched till acknowledgement by
the operator.

Loop reset management

An operator’s reset command (only on local HMI) is available for the reset of the loop.
It can be set by the operator in the following condition:
 Raw detection activated

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 11 of 20

7.2 FLAME DETECTORS – FL4000H - RDIR

To each specific state corresponds a range of the 4-20mA input signal (not filtered signal).

-Here below the correspondence table:

Type of Confirmed
detector Test mode Dirty optic Ready mode Flame detection detection
1.3 to 1.7 mA 1.8 to 2.3 mA 4.1 to 4.5 mA 15.8 to 16.2 mA 19.8 to 20.2 mA
RDI (> and <=) (> and <=) (> and <=) (> and <=) (> and <=)

Ranges (mA) are hardcoded inside the typical (same ranges for all typical of a same category)

The Confirmed Detection alarm is latched till acknowledgement by the operator.


inhibition key switch placed in the cabinet allows us to inhibit sensor.

7.3 DIGITAL OUTPUTS

Reset Relay outputs are controlled by zone to 1 each time you press the “Reset Detect” buttons on
the display. It leads to the opening of the loop detectors Orbis heat for 5 seconds and allows them
initialization.

7.3.1 DIGITAL OUTPUTS TO watermist Extinguishing panel(Allen-Bradley PLC)

All informations exchanged with the Watermist are failsafe and needed to be managed with an
analog input to treat short and open-circuited.

Fire Confirmed Status outputs indicate the detection of a confirmed fire per Room.

The system fault status is information indicating that the fire detection system is not fully
operational:

- Fault Detectors
- HMI Fault Communication
- HIMA system Not Normal

7.3.2 DIGITAL OUTPUTS TO FGS

All informations exchanged with the Watermist are failsafe and needed to be managed with an
analog input to treat short and open-circuited.
Fire Confirmed Status outputs indicate the detection of a confirmed fire per Room.
This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 12 of 20

7.4 INHIBIT

Inhibition of sensors is possible after 2 actions:


Place the inhibit switch in inhibition position and enter the keypad code.
This code is valid 15 minutes. It disables the inhibited authorization and imposes new code entry
after this timer. Reset the switch inhibit in initial position removes all inhibitions after 30 seconds if
there is an alarm still active or inhibit. A message appear on the display.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 13 of 20

7.5 LOGIC

Level 0 Em DG ROOM
13-RDOS-03007A31 Voting
2/2 Fire Confirmed Em DG
13-RDIR-03007A32 ROOM

Level 3 DO TREATMENT

11-RDOS-03312B31 Voting
2/4
11-RDIR-03312B32 Fire Confirmed DO
Treatment ROOM
11-RDOS-03312B33

11-RDIR-03312B34

Level 2 Ess DG ROOM 1

11-RDOS-03203B31 Voting
2/2 Fire Confirmed
11-RDIR-03203B32 Ess DG ROOM 1

Level 2 Ess DG ROOM 2

11-RDOS-03204B31 Voting Fire Confirmed Ess


2/2 DG ROOM 2
11-RDIR-03204B32

Level 3 HPU ROOM 1

11-RDOS-03310B31 Voting
2/4
11-RDOS-03310B33
Fire Confirmed HPU
11-RDIR-03310B32 ROOM 1

11-RDIR-03310B34

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 14 of 20

Level 3 HPU ROOM 2

11-RDOS-03311B31 Voting
2/4
11-RDOS-03311B33
Fire Confirmed HPU
11-RDIR-03311B32 ROOM 2

11-RDIR-03311B34

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 15 of 20

8 DISPLAY

The display type ESA 107T is composed of a navigation bar in the upper portion of the screen and
different views:

- An EmDG view
- A DO Treatment view
- A Essential DG Room 1 & 2 view
- An HPU Room 1 view
- An HPU Room 2 view
- An events view
- A System view

8.1 SYSTEM VIEW

(for information without any contractual value)

This view displays the PLC status with or without default.


An EXIT button allows to exit application through a password.
This password is "manager" in lowercase.
After exiting, you can set time or download parameters and then restart application.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 16 of 20

8.2 EVENTS VIEW

(for information without any contractual value)

It displays events with the event time and the disappearance time.
The Page Up and Page Down buttons allows to navigating through events.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 17 of 20

8.3 FIRE DETECTION VIEWS

(for information without any contractual value)

Inhibited and yellow color indicates a sensor inhibited.


Orange color indicates a fault status
Red color indicates Alarm
Red Label “OPT” indicates Optical fault
The remove inhibit button allows you to remove sensor inhibit

The inhibit code appear if inhibit selector is in inhibition position.


It allows you to enter a code : “3579” to allow inhibition.

At this time the keyboard disappear and the text” allowed to inhibit” appear.
After 15 minutes this code is invalid and must be reentered.

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 18 of 20

(for information without any contractual value)

(for information without any contractual value)

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 19 of 20

(for information without any contractual value)

(for information without any contractual value)

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
FPU – AUTOCHIM Document Number
CG-MHN-11-2310-401037
E707HIA
CONTROL LOGIC DIAGRAMS FOR WATER MIST
Revision:00 Status: IFR

Document Type: LPD System : 03 Family Equip. : XG Discipline: INS Class: 2 Date: 27-Jun-2014

VENDOR Document Number and Revision:D43325-37 Page 20 of 20

8.4 COMMUNICATION FAULT

(for information without any contractual value)

Purple color indicates fault communication with PLC.


Text

This document is the property of TOTAL. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.