The ANN-RLY relay module provides 10 programmable relays that can be used for various functions like alarms, troubles, AC loss when connected to a compatible fire alarm control panel over an ANN-Bus communication circuit. It can be powered by the host FACP or a separate power supply and mounted on the FACP board or remotely in an enclosure. Up to eight ANN-RLY modules can be connected to each FACP to expand relay capabilities.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views2 pages

DF 52431

The ANN-RLY relay module provides 10 programmable relays that can be used for various functions like alarms, troubles, AC loss when connected to a compatible fire alarm control panel over an ANN-Bus communication circuit. It can be powered by the host FACP or a separate power supply and mounted on the FACP board or remotely in an enclosure. Up to eight ANN-RLY modules can be connected to each FACP to expand relay capabilities.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DF-52431:C • B-200

ANN-RLY
Relay Module

Annunciators

General
The ANN-RLY relay module provides 10 programmable Form-C
relays when used with a compatible FACP (Fire Alarm Control
Panel). The ANN-RLY module may be mounted inside the FACP
main circuit board chassis or in the battery area of the enclosure
using optional mounting bracket P/N: ANN-MBRLY. Reference
Installation Instructions document #53033.
The ANN-RLY and the FACP communicate over a two-wire serial
interface employing the ANN-Bus communication format. An addi-
tional two wires are used for 24-volt DC power. A single four-con-
ductor unshielded cable may be used for both power and data
communications.
Up to eight ANN-Bus devices may be connected to the ANN-Bus of
each FACP.

Features
• ANN-RLY connects to the ANN-Bus terminal on the FACP and
requires minimal programming
• Provides 10 programmable Form-C relays
• Ten Form-C relays can be programmed for various functions;
Alarm, Trouble, Supervisory, AC Loss, Waterflow Delay, Input
Zones and Silenceable Alarm.
• Compatible with the ES-200X, ES-50X, MS9600(UD)LS,
MS-9200UDLS, MS-9050UD, MRP-2001, MRP-2002, MS-10UD,
and MS-5UD
Ordering Information
• May be powered by 24 VDC from the host FACP or by remote
power supply (requires 24 VDC) • ANN-RLY: Relay Module provides 10 programmable Form C
• Up to eight ANN-Bus devices may be connected to the ANN-Bus relays
of each FACP • ANN-MBRLY: Optional mounting bracket; required for
• Listed to UL Standard 864, 9th Edition MS-9200UDLS applications
• ROME: Relay Option Module Enclosure, includes one ANN-RLY
Specifications Relay module and one ANN-MBRLY bracket installed

• Maximum ANN-BUS Voltage: 24 VDC Agency Listings and Approvals


• Maximum Current: The listings and approvals below apply to the FeaturedProduct. In
– Alarm: 75 mA Standby: 15 mA some cases, certain modules may not be listed by certain approval
agencies, or listing may be in process. Consult factory for latest list-
• Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC)
ing status.
• Relative Humidity: 93% ± 2% RH (non-condensing) at 32ºC ± 2ºC
(90ºF ± 3ºF) • UL:S2424
• For use indoors in a dry location • FM Approved
• Connections to FACP are power-limited and supervised. • Fire Dept. of New York: #COA 6177
• Relay Contact Ratings: 2 Amps @ 30VDC (Resistive) 0.5 Amps • CSFM: 7120-0075:0222
@ 30VAC (Resistive) • MEA: 333-07-E

The ANN-Bus
POWERING THE DEVICES ON THE ANN-BUS FROM AUXIL-
IARY POWER SUPPLY
ANN-Bus devices can be powered by an auxiliary power supply
when available panel power is exceeded. See FACP manual for
information.
ANN-BUS DEVICE ADDRESSING
Each ANN-Bus device requires a unique address (ID Number) in
order to communicate with the FACP. A maximum of eight devices
can be connected to the FACP ANN-Bus communication circuit. See
the FACP manual for more information.

DF-52431:C • 3/15/2018 — Page 1 of 2


Fire•Lite® Alarms is a registered trademark of Honeywell International Inc.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. Country of Origin: USA
www.firelite.com

Page 2 of 2 — DF-52431:C • 3/15/2018