PG Spec 12V4000DS2000 2080kVA 3D FC 50Hz
PG Spec 12V4000DS2000 2080kVA 3D FC 50Hz
PG Spec 12V4000DS2000 2080kVA 3D FC 50Hz
Product highlights
Bene�ts Performance assurance certi�cation (PAC)
— Low fuel consumption — Engine-generator set tested to ISO 8528-5 for transient response
— Optimized system integration ability — 85% load factor
— High reliability — Verified product design, quality and performance integrity
— High availability of power — All engine systems are prototype and factory tested
— Long maintenance intervals
Complete range of accessories available
Support — Control panel
— Global product support offered — Power panel
— Circuit breaker/power distribution
Standards — Fuel system
— Engine-generator set is designed and manufactured in — Fuel connections with shut-off valve mounted to base frame
facilities certified to standards ISO 2008:9001 and — Starting/charging system
ISO 2004:14001 — Exhaust system
— Generator set complies to ISO 8528 — Mechanical and electrical driven radiators
— Generator meets NEMA MG1, BS 5000, ISO, DIN EN and — Medium and oversized voltage alternators
IEC standards
— NFPA 110 Emissions
— Fuel consumption optimized
Power rating
— System ratings: 1970 kVA - 2080 kVA Certi�cations
— Accepts rated load in one step per NFPA 110* — CE certification option
— Generator set complies to G3 according to ISO 8528-5 — Unit certificate acc. to VDE-AR-N 4110
— Generator set exceeds load steps according to ISO 8528-5*
Marathon 1020FDH7096
11 kV 1656 2070 109 1608 2010 105
(Medium volt. marathon)
Leroy Somer LSA53.2 VL7
11 kV 1664 2080 109 1624 2030 107
(Medium volt. Leroy Somer)
1 All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2 Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. All fuel consumption values refer to rated engine power.
Standard and optional features
Engine
Generator
4 pole three-phase synchronous Insulation class H, utilization acc. to H Meets NEMA MG-1, BS 5000, IEC 60034-1,
generator Radio suppression EN 55011, group 1, cl. B VDE 0530, DIN EN 12601, AS 1359 and
Brushless, self-excited, self-regulating, Short circuit capability 3xIn for 10sec ISO 8528-3 requirements
self-ventilated Winding and bearing RTDs Leroy Somer low voltage generator
Digital voltage regulator (without monitoring) Marathon low voltage generator
Anti condensation heater Excitation by AREP Oversized generator
Stator winding Y-connected, accessible Mounting of CT´s: 2 core CT´s Medium voltage generator
neutral (brought out) Winding pitch: 2/3 winding Engine output optimized generator
Protection IP23 Voltage setpoint adjustment ± 10%
Cooling system
Control panel
Unit cabling with coded plugs for Mains parallel operation of Event recording
easy connection of customer-specific a single genset (V6) IP 54 front panel rating with
controls (V0) Mains parallel operation of integrated gasket
Pre-wired control cabinet for easy multiple gensets (V7) Different expansion modules
application of customized controller (V1+) Basler controller Remote annunciator
Island operation (V2) Deif controller Daytank control
Automatic mains failure operation with Complete system metering Generator winding temperature
ATS (V3a) Digital metering monitoring
Automatic mains failure operation Engine parameters Generator bearing temperature
incl. control of generator and mains Generator protection functions monitoring
breaker (V3b) Engine protection Modbus TCP-IP
Island parallel operation of multiple SAE J1939 engine ECU communications
gensets (V4) Parametrization software
Automatic mains failure operation with Multilingual capability
short (< 10s) mains parallel Multiple programmable contact inputs
overlap synchronization (V5) Multiple contact outputs
Connectivity
The engine system automatically collects and development and improvement as well as
transfers engine data to the manufacturer service optimization. Users can log in or
from time to time. The data is used by the register via https://mtu-go.com and also gain
manufacturer for the purposes of product insight into the data.
Power panel
3-pole circuit breaker Electrical-actuated circuit breaker Base frame mounted GCB, pre-wired with
4-pole circuit breaker generator, ready for commissioning
Fuel system
Flexible fuel connectors mounted to Switchable fuel filter with water separator Fuel cooler integrated into cooling
base frame Switchable fuel filter with water separator equipment
Fuel filter with water separator heavy-duty
Fuel filter with water separator heavy-duty Seperate fuel cooler
Starting/charging system
Mounting system
Welded base frame Resilient engine and generator mounting Base frame mounting on foundation/base
Modular base frame design plate with using clamping brackets
Exhaust system
Exhaust bellows with connection flange Exhaust silencer with Exhaust silencer with
Exhaust silencer with 30 dB(A) sound attenuation 40 dB(A) sound attenuation
10 dB(A) sound attenuation Y-connection-pipe
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation
design. See website for unit specific template drawings.
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
Rolls-Royce Group
www.mtu-solutions.com/powergen