Siepc71061752 (1) - 101-200
Siepc71061752 (1) - 101-200
Siepc71061752 (1) - 101-200
Electrical Installation
Sourcing Mode
(PNP)
3
10 kΩ or more 10 V or more
Note:
Use the formula in Figure 3.46 to calculate the necessary load resistance (kΩ) to increase output voltage VMP(V).
A - Load Impedance
Figure 3.46 Wiring to Use Pulse Train Output in Sourcing Mode
• Use in sinking mode
The external power supply changes the voltage level of the pulse train output signal. Keep the voltage from an
external source between 10.8 Vdc to 16.5 Vdc. Adjust the load impedance to keep the current at 16 mA or lower.
External Power Supply (V) Load Impedance (kΩ) Sinking current (mA)
Note:
Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.
Parameter
Terminal Types of Output Signals Jumper S5
No. Signal Level
Voltage output
0: 0 V to 10 V
(Default)
AM H4-07
Current output 2: 4 mA to 20 mA
Electrical Installation
◆ Switch ON Termination Resistor for MEMOBUS/Modbus Communications
When the drive is the last slave in a MEMOBUS/Modbus communications, set DIP switch S2 to the ON position.
This drive has a built-in termination resistor for the RS-485 interface.
◆ Drive ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which Drive Ready [H2-
xx = 6] is set will activate.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
• The drive is de-energized
• During a fault
• There is problem with the control power supply
• There is a parameter setting error that will not let the drive run, although a Run command is entered
• An overvoltage or undervoltage fault occurs when the Run command is entered
• The drive is in Programming Mode.
Electrical Installation
3
Electrical Installation
Figure 3.56 Power Supply Interrupt for Overheat Protection Example
WARNING! Fire Hazard. When you use a braking unit, use a thermal relay on the braking resistors and set a fault contact output for
the braking resistor unit to disconnect drive main power through an input contactor. Incorrect braking circuit protection can cause the
resistors to become too hot and cause serious injury or death.
3
Electrical Installation
A thermal overload relay disconnects the power line to the motor during a motor overload condition to prevent
damage to the motor.
Install a thermal overload relay between the drive and motor in these conditions:
• When you operate more than one motor with one drive
• When you operate the motor directly from the power line with a power line bypass
When you operate one motor with one drive, it is not necessary to install a thermal overload relay. The drive has 3
electronic motor overload protection in the drive software.
Note:
• When you install a thermal overload relay, set parameter L1-01 = 0 [Motor Overload (oL1) Protection = Disabled].
• Set up a sequence that will trip an external fault (coast to stop) for the contacts of the thermal overload relay.
The electronic thermal overload function uses the relation between the speed and heat characteristics in the variable
speed control range to simulate the cooling ability of general-purpose motors and forced-vented motors to prevent
damage to the motor.
When You Operate More than One Motor with One Drive
To disable the overload protection function of the electronic thermal protector of the drive, set L1-01 = 0 [Motor
Overload (oL1) Protection = Disabled].
Note:
If you operate more than one motor from one drive, you cannot use the electronic thermal protection of the drive.
Length of the Motor Cables
If you use long motor cables with a high carrier frequency, the increased leakage current can cause nuisance tripping
of the thermal relay. To prevent this, decrease the carrier frequency or increase the tripping level of the thermal
overload relay.
Nuisance Tripping Because of High Drive Carrier Frequency
High carrier frequency PWM drives make current waveforms that can increase the temperature in overload relays. It
may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.
WARNING! Fire Hazard. Before you increase the detection level of the thermal relay, make sure that a secondary problem is not the
cause of the overload. Make sure that you know the local codes for electrical wiring, then adjust the electrothermal settings.
Incorrect thermal relay adjustment and incorrect wiring can cause serious injury or death.
■ Connect an AC Reactor
Note:
When you connect an AC reactor to the output side (secondary side) of the driver, set C6-02 = 1 [Carrier Frequency Selection = 2.0 kHz].
Electrical Installation
A - Power Supply C - AC reactor
B - MCCB D - Drive
Figure 3.60 Example of Connecting the Noise Filter on the Input Side (Primary Side)
Note:
The input side (primary side) noise filter model is RTEN-5xxx.
Electrical Installation
Drive models GA50CxxxxExx have built-in input noise filters. When you use these drives, make sure that the filter specifications align with
the application and applicable regulations. Refer to European Standards on page 168 for more information.
Figure 3.61 Example of Connecting the Noise Filter on the Output Side (Secondary Side)
Note:
Glossary
• Radio frequency interference:
Electromagnetic waves radiated from the drive and cables make noise through the full radio bandwidth that can have an effect on nearby
devices.
• Inductive noise:
The noise from electromagnetic induction can have an effect on the signal line and can cause the controller to malfunction.
◆ UL Compliance
Install one of the types of short circuit protection devices in Single-Phase 200 V Class on page 115, Three-Phase 200
V Class on page 116, and Three-Phase 400 V Class on page 116 to comply with UL61800-5-1. Yaskawa recommends
connecting semiconductor protective type fuses, but Single-Phase 200 V Class on page 115, Three-Phase 200 V Class
on page 116, and Three-Phase 400 V Class on page 116 also show alternative short circuit protection devices.
When you use MCCBs, RK1, or RK5 fuses, you must mount the drive in a ventilated enclosure according to the
minimum enclosure volume specified in Single-Phase 200 V Class on page 115, Three-Phase 200 V Class on page
116, and Three-Phase 400 V Class on page 116.
Electrical Installation
The maximum SCCR provided by drive and fuse, or drive and MCCB combinations in this document, is 31,000 RMS
symmetrical amps.
• 200 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 31,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 31,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
3
■ Electric Code Compliance
The user must provide short circuit protection to protect input branch circuits as specified by the National Electric
Code (NEC), the Canadian Electric Code, Part 1 (CEC), and local codes.
1 The power supply voltage must be in the input voltage specification range of the drive.
1 • Put the power supply through a molded-case circuit breaker (MCCB) before it gets to the drive input.
• Connect an applicable MCCB.
2 Correctly wire the power supply to drive terminals R/L1, S/L2, and T/L3, or L/L1 and N/L2.
4 Use 600 V heat resistant indoor PVC wire for the power supply and motor lines.
Note:
Wire gauge recommendations assume use of 600 V class 2 heat-resistant indoor PVC wire.
7 Tighten the main circuit and grounding terminal screws of the drive to a correct tightening torque.
8 When operating more than one motor from one drive, set up overload protection circuits.
Electrical Installation
3
A - Power Supply C - oL1, oL2: Thermal overload relay
B - Drive
Note:
Set H1-03 = 25 [Terminal S3 Function Selection = External Fault (NC-Always-Coast)].
9 When you use a braking resistor or a braking resistor unit, install an electromagnetic contactor (MC).
Correctly install the resistor and make sure that overload protection uses the MC to shut off the power supply.
10 Make sure you did not install phase advancing capacitors, input noise filters, or ELCBs, GFCIs, RCM/RCDs on the output side of the drive.
2
Ground the shields of shielded wiring to the ground terminal .
3 For 3-Wire sequence, set parameters for MFDI terminals and wire control circuits.
6 Tighten the control circuit terminal screws of the drive to a correct tightening torque.
8 Make sure that none of the wires on the terminal block touch other terminals or connections.
9 Make sure that you isolate the control circuit wiring from main circuit wiring in the control panel or in a duct.
10 Make sure that control circuit wiring is not longer than 50 m (164 ft).
11 Make sure that Safe Disable input wiring is not longer than 30 m (98 ft).
Electrical Installation
Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or
particularly long wiring distances. Use an insulated drive motor.
NOTICE: Use an inverter-duty motor or vector-duty motor with reinforced insulation and windings applicable for use with an AC
drive. If the motor does not have the correct insulation, it can cause a short circuit or ground fault from insulation deterioration.
■ High-Speed Operation 3
If you operate a motor more than its rated speed, you can have problems with the motor bearing durability and
dynamic balance of the machine. Contact the motor or machine manufacturer.
■ Torque Characteristics
When you operate a motor with a drive, the torque characteristics are different than when you operate the motor
directly from line power. Make sure that you know about the load torque characteristics for your application.
■ Vibration
Vibrations could occur in the these conditions:
• Resonance with the natural frequency of machinery
Use caution if you add a variable-speed drive to applications that operate the motor from line power at a constant
speed. If resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump
frequency control.
• The motor is not balanced
Use caution if the motor speed is more than the rated motor speed.
• Subsynchronous resonance
Subsynchronous resonance can occur with long motor shafts and in applications such as turbines, blowers, and fans
with high inertia loads.
■ Audible Noise
The audible noise of the motor changes when the carrier frequency setting changes. When you use a high carrier
frequency, audible noise from the motor is equivalent to the motor noise generated when you operate from line power.
If you operate at speeds that are more than the rated rotation speed, the unwanted motor noise increases.
■ Submersible Motors
The rated current of a submersible motor is more than the rated current of a standard motor. Use a sufficiently large
motor cable that will not let voltage drop decrease the maximum torque level.
■ Explosion-Proof Motors
You must test the motor and the drive together for explosion-proof certification. You must also test existing
installations of explosion-proof motors. The drive is not designed for explosion-proof areas. Install the drive in a safe
location.
The encoder used with pressure-resistant explosion-proof motors is intrinsically safe. When wiring between the drive
and encoder, always connect through a specialized pulse coupler.
■ Geared Motors
The continuous speed range is different for different lubricating methods and manufacturers. For oil lubrication,
continuous operation in the low-speed range can cause burnout. Contact the manufacturer for more information about
applications where operating at more than the rated frequency is necessary.
■ Single-Phase Motors
Variable speed drives are not designed to operate with single-phase motors. The drive is for use with three-phase
motors only. If you use capacitors to start the motor, it can cause a high frequency current to flow to the capacitors
and can damage the capacitors. A split-phase start or a repulsion start can burn out the starter coils because the
internal centrifugal switch is not activated.
Electrical Installation
◆ Notes on the Power Transmission Mechanism
For power transmission machinery that uses oil to lubricate gearboxes, transmissions, or reduction gears, make sure
that you use precaution if you operate the machinery continuously at low speed. Oil does not lubricate the system as
well at low speeds. If you operate at frequencies higher than the rated frequency, it can cause problems with the power
transmission mechanism. These problems include audible noise, decreased service life, and decreased durability.
3
WARNING
Electrical Shock Hazard
Do not operate the drive when covers are missing. Replace covers and shields before you operate
the drive. Use the drive only as specified by the instructions.
Some figures in this section include drives without covers or safety shields to more clearly show the inside of the
drive. If covers or safety shields are missing from the drive, it can cause serious injury or death.
Do not remove covers or touch circuit boards while the drive is energized.
If you touch the internal components of an energized drive, it can cause serious injury or death.
Pass-through point to connect a USB cable to the drive to use the DriveWizard PC tool or the DriveWizard Mobile App to program
A USB Terminal Pass-through
the drive. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the drive to a PC, Android smartphone, or tablet.
active at an external Run command source. To disable priority, set o2-02 = 0 [STOP Key Function Selection =
Disabled].
• You pushed on the keypad while the drive is operating in REMOTE Mode.
• The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN
Command].
H /
Switches drive control for the Run command and frequency reference between the keypad (LOCAL) and an external source
(REMOTE).
LO/RE Selection Key Note:
• The LOCAL/REMOTE Selection Key continuously stays enabled after the drive stops in Drive Mode. If the application must
K not switch from REMOTE to LOCAL because it will have a negative effect on system performance, set o2-01 = 0 [LO/RE Key
N RJ-45 Connector Connects to the drive. Use an RJ-45 8-pin straight UTP CAT5e extension cable to install the keypad in a different location than the
drive.
WARNING! Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/REMOTE Run Selection = Accept
Existing RUN Command], the drive can start suddenly. Before you change the control source, remove all personnel from the area
around the drive, motor, and load. Sudden starts can cause serious injury or death.
Drive models GA50Axxxxxxxx-xxxxLx ship from the factory with a blank cover instead of a keypad. To set
parameters on these models, connect an optional keypad or engineering tool to one of the connection ports shown in
Figure 4.2.
Pass-through point to connect a USB cable to the drive to use the DriveWizard PC tool or the DriveWizard Mobile App to program
A USB Terminal Pass-through
the drive. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the drive to a PC, Android smartphone, or tablet.
B RJ-45 Connector Pass-through Connects to the drive. Use an RJ-45 8-pin straight UTP CAT5e extension cable to use the keypad option to program the drive.
Note:
• When you change A1-02 [Control Mode Selection], the settings of some parameters automatically change.
• This manual also shows parameters that are not in Setup Mode. Use to set the parameters not shown in the Setup Mode.
• Display parameters change when the A1-06 [Application Preset] setting changes.
Drive Mode Output current You can monitor the output current.
display -
(Operation of
the motor and
monitoring of Output You can monitor the frequency output from the drive.
operation status) frequency -
display
Forward/reverse
selection : Motor rotates in forward direction
Auto-Tuning The drive automatically calculates and sets the motor parameters. 148
Mode 149
150
Verify Menu Lists all parameters that are not at their default settings.
134
◆ Drive Mode
These operations are available in Drive Mode:
• Operate and stop the drive
• Show the drive status monitors (for example, frequency reference, output frequency, output current, and output
voltage)
• Show the alarm content
• Show the alarm history
Note:
To operate the drive, select Drive Mode. You can switch to other modes when the drive stops, but the drive must be in Drive Mode to start
operation.
These steps show how to set the frequency reference source to LOCAL (keypad) and change the frequency reference
from 0 Hz to 6 Hz.
◆ Programming Mode
In Programming Mode, you can set parameters or do Auto-Tuning. This mode has 4 sub-modes for different
programming requirements:
• Verify Menu: Use this mode to examine and set the parameters that are not at default settings.
• Setup Mode: Use this mode to see and set the minimum parameters necessary for drive operation. Refer to Verify
and Set the Changed Parameters (Verify Menu) on page 134 for more information.
• Parameter Setting Mode: Use this mode to see and set all parameters.
• Auto-Tuning Mode: Use this mode to automatically set the motor parameters necessary for each control method.
Push and hold to go back to the frequency reference screen from any screen.
Use these steps to change C1-01 [Acceleration Time 1] from 1.0 s (default) to 2.0 s.
Push and hold to return to frequency reference screen from any screen.
Use Verify mode to view all parameters that are not at default settings. This is very useful when you replace a drive.
When there are no changes to parameter settings, the display shows . This lets you quickly access and re-edit
changed parameters. Figure 4.10 shows the procedure.
Note:
The drive will only display A1-02 [Control Method Selection], A1-xx, A2-01 to A2-32 [User Parameter 1 to User Parameter 32], and E5-01
[PM Motor Code Selection].
You can use or MFDI functions (LOCAL/REMOTE Selection) to switch between LOCAL and REMOTE.
Note:
■ Use the LO/RE Selection Key on the Keypad to Switch between LOCAL and REMOTE
Each time you push , the mode switches between LOCAL and REMOTE. The LED illuminates in LOCAL
Mode.
Figure 4.11 Use the LO/RE Selection Key to Switch between LOCAL and REMOTE
■ Use MFDI Terminals (S1 to S7) to Switch between LOCAL and REMOTE
When you set H1-xx = 1 [MFDI Function Selection = LOCAL/REMOTE Selection], you can activate/deactivate the
terminal to switch between LOCAL and REMOTE. Set H1-xx = 1 to disable the LO/RE key on the keypad. For
information about the MFDI functions, refer to the list in H1: Digital Inputs on page 643.
◆ Flowchart A: Connect and Run the Motor with Minimal Setting Changes
Flowchart A shows a basic start-up sequence to connect and run a motor with a minimum of setting changes. Settings
can change when the application changes.
Use the drive default parameter settings for basic applications where high precision is not necessary.
Figure 4.15 Procedure for Test Run of EZ Open Loop Vector Control Method
Correctly wire power supply input terminals R/L1, S/L2, and T/L3, or L and N.
Connection between Drive Output Make sure that you connected drive output terminals U/T1, V/T2, and W/T3 in the correct sequence to align with motor terminals U, V,
Terminals and Motor Terminals and W and tighten the screws to a correct tightening torque.
Make sure that you connected the drive control circuit terminals in the correct sequence to align with devices and switches and tighten the
Control Circuit Terminal Wiring
screws to a correct tightening torque.
Control Circuit Terminal Status Turn OFF the inputs from all devices and switches connected to the drive control circuit terminals.
Connection between Machinery and Motor Disengage all couplings and belts that connect the motor and machinery.
When the The display is different for different faults. Refer to “Troubleshooting” to remove the cause of the fault.
Drive Detects The ALM/ERR LED will illuminate.
a Fault
0 9 I R
1 A J S
2 B K T
3 C L U
4 D M *1 V
5 E N W *1
6 F O X No indication
7 G P Y
8 H Q Z No indication
Push and hold to return to frequency reference screen from any screen.
Use these steps to monitor parameter settings.
Push and hold to return to frequency reference screen from any screen.
Use Verify mode to view all parameters that are not at default settings. This is very useful when you replace a drive.
This lets you quickly access and re-edit changed parameters.
Note:
The drive will only display A1-02 [Control Method Selection], A1-xx, A2-01 to A2-32 [User Parameter 1 to User Parameter 32], and E5-01
[PM Motor Code Selection].
Push and hold to return to frequency reference screen from any screen.
The setup mode shows the parameters set in A2-01 to A2-32 [User Parameter 1 to User Parameter 32]. This lets you
quickly access and change these parameters.
Note:
Continue to change the parameters or press and hold to go back to the frequency reference screen.
Push and hold to go back to the frequency reference screen from any screen.
This example shows how to change C1-01 [Acceleration Time 1]. Set the parameter to the necessary value.
Continue to change parameters or push and hold to go back to the frequency reference screen.
Push and hold to go back to the frequency reference screen from any screen.
Use these steps to save a backup of the drive parameters to the keypad.
Making backups of the parameter settings can save time when setting parameters after replacing a drive. If you set up
more than one drive, you can copy the parameter settings from a drive that completed a test run to the other drives.
Note:
• Make sure that you stop the motor before you back up parameters.
• The drive does not accept Run commands while it is making a backup.
• Set o3-02 = 0 [Copy Allowed Selection = Disabled] to protect the parameters saved in the keypad.
Push and hold to go back to the frequency reference screen from any screen.
Use these steps to write the parameters backed up in the keypad into a different drive.
Note:
• Make sure that you stop the drive before you restore the backed-up parameters.
• The drive does not accept Run commands while it is restoring parameters.
Push and hold to go back to the frequency reference screen from any screen.
This procedure verifies that the parameter setting values that were backed up in the keypad agree with the parameter
setting values in the drive.
Note:
4
• Make sure that you stop the drive before you examine parameters.
• The drive does not accept Run commands while it is restoring parameters.
Push and hold to go back to the frequency reference screen from any screen.
Use these steps to erase the parameters backed up in the keypad.
Press and hold to return to the frequency reference screen from any screen.
Use this procedure to set an application preset.
The drive has application presets to set the necessary parameters for different applications to their best values. Use
to find parameters that were changed automatically by the application preset function in A1-06.
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
4.9 Auto-Tuning
Auto-Tuning uses motor characteristics to automatically set drive parameters for vector control. Think about the type
of motor, drive control method, and the motor installation environment and select the best Auto-Tuning method.
WARNING! Injury to Personnel. Rotational Auto-Tuning rotates the motor at 50% or more of the motor rated frequency. Make sure
that there are no issues related to safety in the area around the drive and motor. Increased motor frequency can cause serious
injury or death.
• When you can decouple the motor and load the motor can rotate
freely while Auto-Tuning.
• When operating motors that have fixed output characteristics.
Rotational Auto-Tuning T1-01 = 0 x x
• When it is necessary to use motors that have high-precision control.
• When you cannot decouple the motor and load, but the motor load is
less than 30%.
• After Auto-Tuning, the wiring distance between the drive and motor
changed by 50 m or more.
Stationary Line-Line Resistance T1-01 = 2 • When the wiring distance is 50 m or more in the V/f Control mode. x x
• When the motor output and drive capacity are different.
Auto-Tuning Mode
(T1-01 Setting)
Input Data Parameter Unit
Rotational Auto-Tuning Stationary Auto-Tuning Stationary Line-Line
1 Resistance
(0)
(1) (2)
*1 Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*2 Input this value when A1-02 = 0 [Control Method Selection = V/f].
*3 If T1-12 = 1 [Test Mode Selection = Yes], when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current].
*4 Input this value when T1-10 [Motor Rated Slip Frequency] = 0 Hz.
*5 Set the same value to No-Load Voltage as T1-03 [Motor Rated Voltage] to get the same characteristics using Yaskawa 1000-Series drives
or other legacy models.
■ KEB Tuning
KEB Tuning automatically sets parameters used for the KEB Ride-Thru function and for the overvoltage suppression
function.
Control Tuning automatically sets the parameters in Table 4.16 to the best values.
Table 4.16 Parameters set in Control Tuning
Parameters Automatically Set Deceleration Rate Tuning KEB Tuning
*1 The drive automatically sets C1-08 [Deceleration Time 4] only when C1-11 [Accel/Decel Time Switchover Freq] ≠ 0.
*2 When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1], the drive will automatically adjust C1-09 [Fast Stop
Time] and will not adjust L2-06 [Kinetic Energy Backup Decel Time]. If you must not change the Fast Stop time, do not do KEB Tuning.
*3 When L2-29 = 1, 2, or 3 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2, System KEB Ride-Thru 1, or System KEB
Ride-Thru 2], the drive will automatically adjust L2-06 [Kinetic Energy Backup Decel Time].
Rotational PM Rotational Auto-tuning T2-01 = 4 Disabled Functions the same as during usual
operation.
High Frequency Injection T2-01 = 5 Disabled Keeps the status at the start of
Auto-Tuning.
*1 When you set a terminal to H2-xx = E [MFDO Function Selection = Fault], it will function the same as during usual operation.
WARNING! Crush Hazard. Wire a sequence that will not let a multi-function output terminal open the holding brake during
Stationary Auto-Tuning. If the holding brake is open during Stationary Auto-Tuning, it can cause serious injury or death.
WARNING! Sudden Movement Hazard. Before you do Rotational Auto-Tuning, disconnect the load from the motor. The load can
move suddenly and cause serious injury or death.
WARNING! Injury to Personnel. Rotational Auto-Tuning rotates the motor at 50% or more of the motor rated frequency. Make sure
that there are no issues related to safety in the area around the drive and motor. Increased motor frequency can cause serious
injury or death.
WARNING! Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
■ Automatically Set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current]
If T1-12 = 1 [Test Mode Selection = Yes] when selecting Stationary Auto-Tuning, the drive will automatically set
motor parameters E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current] after Auto-Tuning is complete 4
when you use the motor for the first time in Drive Mode.
After Stationary Auto-Tuning is complete, use this procedure to do the operation in test mode:
1. Check the E2-02 and E2-03 values on the “Modified Parameters/Fault Log” screen or the “Parameters” screen.
2. Operate the motor in Drive Mode with these conditions:
• Make sure that you connect all wiring between the drive and motor
• Make sure that a mechanical brake on the motor shaft is not locked
• The maximum motor load must be 30% of the rated load.
• Keep a constant speed of 30% of E1-06 [Base Frequency] (default value = maximum frequency) or more for 1
second or longer.
3. After the motor stops, examine the values of E2-02 and E2-03 again in the Verify Menu or Parameter Setting
Mode.
4. Make sure that the input data is correct.
When the settings in E2-02 and E2-03 are different than in step 1, the drive set the values automatically.
2.
4. Push .
The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.
5. Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.
If the drive detects a fault, remove the cause.
A - Forward Rotation of Motor (Counter Clockwise Direction as Seen from Load Shaft)
6. Push to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
7. Each time you increase the setting value, use U1-03 [Output Current] to check the drive output current.
When the output current of the drive is not more than the motor rated current, the status is correct.
Connect the motor and machine, then do the test run with the same procedure that you used for the no-load test run.
4. Push .
The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.
5. Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.
If the drive detects a fault, remove the cause.
6. Push to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
7. Each time you increase the setting value, use U1-03 [Output Current] to check the drive output current.
When the output current of the drive is not more than the motor rated current, the status is correct.
◆ V/f Control
Table 4.18 Parameters for Fine Tuning the Drive (A1-02 = 0 [V/f])
Issue Parameter Number Possible Solutions Default Recommended Setting
*1 The default setting changes when the settings for C6-01 [Normal / Heavy Duty Selection] and o2-04 [Drive Model (KVA) Selection]
change.
*2 The default setting changes when the settings for A1-02 [Control Method Selection] and o2-04 change.
*3 The default setting changes when the settings for A1-02 and E1-03 [V/f Pattern Selection] change.
*4 Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
*1 The default setting changes when the settings for A1-02 [Control Method Selection] and o2-04 [Drive Model (KVA) Selection] change.
*2 The default setting changes when the settings for A1-02 [Control Method Selection] and E1-03 [V/f Pattern Selection] change.
*3 The default setting changes when the settings for C6-01 [Normal / Heavy Duty Selection] and o2-04 change.
*4 Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
50%
Note:
There is too much current during n8-79 [Pull-in Current at When n8-79 = 0, the drive will Decrease in increments of 5%.
Set n8-79 < n8-51.
deceleration. Deceleration] apply the n8-51 setting to the
pull-in current during
deceleration.
n8-47 [Pull-in Current Comp Filter Decrease the setting value in 5.0 s -
Time] increments of 0.2 s.
• Yaskawa motor
• Adjust the setting value. Set the motor code from the
• E5-09 [PM Back-EMF Vpeak
The drive detects STPo [Motor (mV/(rad/s))] • Examine the motor code on the motor nameplate.
Step-Out Detected] fault when the motor nameplate or the data *1 • Motor from another
load is not too high. • E5-24 [PM Back-EMF L-L sheet, then set correct values for manufacturer
Vrms (mV/rpm)]
E5-09 or E5-24. Set the values from the test
report.
*1 The default setting changes when the settings for E5-01 [Motor Code Selection] and o2-04 [Drive Model (KVA) Selection] change.
• High speed
C5-01 [ASR Proportional Gain • If torque or speed response are
slow, increase the setting value
1]
in increments of 5.00. 10.00 5.00 to 30.00 *1
• Low speed
• Unsatisfactory motor torque • If hunting or oscillation occur,
C5-03 [ASR Proportional Gain
and speed response 2] decrease the setting value.
• Hunting or oscillation
• High speed • If torque or speed response are
C5-02 [ASR Integral Time 1] slow, decrease the setting value.
0.500 s 0.300 s to 1.000 s *1
• Low speed • If hunting or oscillation occur,
C5-04 [ASR Integral Time 2] increase the setting value.
The drive cannot find ASR Change the ASR proportional gain
C5-07 [ASR Gain Switchover
proportional gain or integral time Frequency] and ASR integral time to conform 0.0% 0.0% to maximum rotation speed
for low speed or high speed. to the output frequency.
*1 The best values for a no-load operation are different than the best values for actual loading operation.
• High speed
• If torque or speed response are
C5-01 [ASR Proportional Gain
1] slow, increase the setting value
in increments of 5.00. 10.00 10.00 to 50.00 *1
• Low speed
The drive cannot find ASR C5-07 [ASR Gain Switchover Change the ASR proportional gain
proportional gain or integral time and ASR integral time to conform 0.0% 0.0% to maximum rotation speed
for low speed or high speed. Frequency] to the output frequency.
Oscillation when the motor starts. n8-51 [Accel / Decel Pull-In Increase the setting value. 80% Increase in increments of 5%.
Current]
Motor stalls. L7-01 to L7-04 [Torque Limit] Increase the setting value. 200% Increase in increments of 10%.
*1 The best values for a no-load operation are different than the best values for actual loading operation.
3 Set the voltage for the power supply in E1-01 [Input AC Supply Voltage].
Select the best V/f pattern for your application and motor characteristics.
4 Example: For a motor with a rated frequency of 60 Hz, set E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max] as a standard V/f
pattern.
Refer to the information on the motor nameplate and set this data correctly:
• Motor rated power (kW) to T1-02
• Motor rated voltage (V) to T1-03
6 • Motor rated current (A) to T1-04
• Motor base frequency (Hz) to T1-05
• Number of motor poles to T1-06
• Motor base speed (min-1) to T1-07
7 Do Rotational Auto-Tuning.
8 Set E5-01 to E5-24 [PM Motor Settings] according to manufacturer data, or do Rotational Auto-Tuning
9 Set E5-01 to E5-24 [PM Motor Settings] according to manufacturer data, or do Rotational Auto-Tuning
10 Set C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1].
11 Make sure that the keypad shows READY LED before you start to operate the motor.
12 To give the Run command and frequency reference from the keypad, push to set to LOCAL Mode (when in LOCAL Mode, the LO/RE LED
illuminates).
13 If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
14 Set Heavy Duty or Normal Duty Mode with C6-01 [Normal / Heavy Duty Selection] to conform to the load condition.
15 Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload (oL1) Protection] correctly for motor thermal protection.
16 Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the LO/
RE LED turns OFF).
Make sure that the frequency reference gets to the necessary minimum and maximum values.
If drive operation is incorrect, make these adjustments:
• Gain Adjustment
Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference is at the necessary value.
– For terminal A1 input: H3-03
19
– For terminal A2 input: H3-11
• Bias adjustment
Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference is at the necessary value.
– For terminal A1 input: H3-04
– For terminal A2 input: H3-12
WARNING
Electrical Shock Hazard
Do not operate the drive when covers are missing. Replace covers and shields before you operate
the drive. Use the drive only as specified by the instructions.
Some figures in this section include drives without covers or safety shields to more clearly show the inside of the
drive. If covers or safety shields are missing from the drive, it can cause serious injury or death.
Always ground the motor-side grounding terminal.
If you do not ground the equipment correctly, it can cause serious injury or death if you touch the motor case.
Do not remove covers or touch circuit boards while the drive is energized.
If you touch the internal components of an energized drive, it can cause serious injury or death.
Only let approved personnel install, wire, maintain, examine, replace parts, and repair the drive.
If personnel are not approved, it can cause serious injury or death.
Do not wear loose clothing or jewelry when you do work on the drive. Tighten loose clothing and
remove all metal objects, for example watches or rings.
Loose clothing can catch on the drive and jewelry can conduct electricity and cause serious injury or death.
Do not modify the drive body or drive circuitry.
Modifications to drive body and circuitry can cause serious injury or death, will cause damage to the drive, and will
void the warranty. Yaskawa is not responsible for modifications of the product made by the user.
Fire Hazard
Tighten all terminal screws to the correct tightening torque.
Connections that are too loose or too tight can cause incorrect operation and damage to the drive. Incorrect
connections can also cause death or serious injury from fire.
Tighten screws at an angle in the specified range shown in this manual.
If you tighten the screws at an angle not in the specified range, you can have loose connections that can cause
damage to the terminal block or start a fire and cause serious injury or death.
Damage to Equipment
Do not apply incorrect voltage to the main circuit of the drive. Operate the drive in the specified
range of the input voltage on the drive nameplate.
Voltages that are higher than the permitted nameplate tolerance can cause damage to the drive.
Fire Hazard
Do not put flammable or combustible materials on top of the drive and do not install the drive near
flammable or combustible materials. Attach the drive to metal or other noncombustible material.
Flammable and combustible materials can start a fire and cause serious injury or death.
WARNING
Crush Hazard
Wear eye protection when you do work on the drive.
If you do not use correct safety equipment, it can cause serious injury or death.
Electrical Shock Hazard
After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure
that all indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of
the problem. If you do not know the cause of the problem, contact Yaskawa before you energize the
drive or peripheral devices.
If you do not fix the problem before you operate the drive or peripheral devices, it can cause serious injury or death.
NOTICE
Damage to Equipment
When you touch the drive and circuit boards, make sure that you observe correct electrostatic
discharge (ESD) procedures.
If you do not follow procedures, it can cause ESD damage to the drive circuitry.
Do not break the electrical connection between the drive and the motor when the drive is
outputting voltage.
Incorrect equipment sequencing can cause damage to the drive.
Before you connect a dynamic braking option to the drive, make sure that qualified personnel read
and obey the Braking Unit and Braking Resistor Unit Installation Manual (TOBPC72060001).
If you do not read and obey the manual or if personnel are not qualified, it can cause damage to the drive and braking
circuit.
Make sure that all connections are correct after you install the drive and connect peripheral
devices.
Incorrect connections can cause damage to the drive.
Note:
Standards Compliance
Do not use unshielded cable for control wiring. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive.
Unshielded wire can cause electrical interference and unsatisfactory system performance.
EMC Directive
EN 61800-3:2004/A1:2012
2014/30/EU
The customer must display the CE Mark on the final device containing this product. Customers must verify that the
final device complies with EU standards.
◆ EU Declaration of Conformity
Go to www.yaskawa.com and search for “EU Declaration of Conformity” to get an original copy of the EU
Declaration of Conformity.
Yaskawa declares that this product complies with the following directives and standards at our sole responsibility.
■ Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or less as specified in IEC/CE
60664.
■ Electrical Installation
Refer to Figure 5.2 for an example of a drive that is wired to comply with the CE Low Voltage Directive.
Standards Compliance
5
*4 The control circuit is a Safety Extra-Low Voltage circuit. Use reinforced insulation to separate this circuit from other circuits. Make sure
that you connect the Safety Extra-Low Voltage as specified.
*5 Reinforced insulation separates the output terminals from other circuits. You can also connect circuits that are not Safety Extra-Low
Voltage circuits when the drive output is 250 Vac 1 A maximum or 30 VDC 1 A maximum.
WARNING! Electrical Shock Hazard. When you connect the shield wire of the control circuit wiring to the protective ground
terminal, do not connect the protective ground wire. If you connect the shield wire and the protective ground wire to the
protective grounding terminal, it may not comply with the technical standards and local safety regulations and can cause
serious injury or death.
+/-
Slotted (-)
Wire Stripping
Recomm. Gauge Applicable Gauge Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 Size and Shape N∙m (lbf∙in)
mm
0.5 - 0.6
L/L1, N/L2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B001 -, +1 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
L/L1, N/L2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B002 -, +1 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
L/L1, N/L2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B004 -, +1 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2
Standards Compliance
- M3.5 (7.1 - 8.9)
0.5 - 0.6
L/L1, N/L2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B006 -, +1 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
2.5 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
L/L1, N/L2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B010 -, +1 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
2.5 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 mm Size and Shape N∙m (lbf∙in)
1.5 - 1.7
L/L1, N/L2 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
B012 -, +1 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
L/L1, N/L2 6 2.5 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
B018 -, +1 6 2.5 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
2.0 - 2.5
6 *2 4 - 10 *2 - M5 (17.7 - 22.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp.
Three-Phase 200 V Class
Wire Stripping
Recomm. Gauge Applicable Gauge Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 Size and Shape N∙m (lbf∙in)
mm
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2001 -, +1, +2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2002 -, +1, +2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2004 -, +1, +2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2006 -, +1, +2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
2.5 *2 2.5 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
2010 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
Standards Compliance
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
2012 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
5
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
2021 -, +1, +2 6 4 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.2 - 1.5
6 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 mm Size and Shape N∙m (lbf∙in)
1.5 - 1.7
R/L1, S/L2, T/L3 6 4 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 6 4 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
2030 -, +1, +2 10 2.5 - 16 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
2.0 - 2.5
6 *2 6 - 16 - M5 (17.7 - 22.1)
1.5 - 1.7
R/L1, S/L2, T/L3 10 2.5 - 16 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 10 2.5 - 16 10 M4 (13.5 - 15)
2.3 - 2.5
2042 -, +1, +2 16 4 - 25 18 M5 (19.8 - 22)
1.5 - 1.7
B1, B2 4 2.5 - 6 10 M4 (13.5 - 15)
2.0 - 2.5
10 6 - 16 - M5 (17.7 - 22.1)
2.3 - 2.5
R/L1, S/L2, T/L3 16 4 - 25 18 M5 (19.8 - 22)
2.3 - 2.5
U/T1, V/T2, W/T3 16 4 - 25 18 M5 (19.8 - 22)
• ≤ 25 mm2
2.3 - 2.5
(19.8 - 22)
2056 -, +1, +2 25 6 - 35 18 M5 • 35 mm2 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
B1, B2 10 4 - 16 10 M4 (13.5 - 15)
5.4 - 6.0
10 10 - 25 - M6 (47.8 - 53.1)
5 - 5.5
R/L1, S/L2, T/L3 25 6 - 35 20 M6 (45 - 49)
5 - 5.5
U/T1, V/T2, W/T3 16 6 - 25 20 M6 (45 - 49)
5 - 5.5
2070 -, +1, +2 35 10 - 50 20 M6 (45 - 49)
1.5 - 1.7
B1, B2 10 4 - 16 10 M4 (13.5 - 15)
5.4 - 6.0
16 10 - 25 - M6 (47.8 - 53.1)
5 - 5.5
R/L1, S/L2, T/L3 35 10 - 50 20 M6 (45 - 49)
5 - 5.5
U/T1, V/T2, W/T3 25 10 - 35 20 M6 (45 - 49)
5 - 5.5
2082 -, +1, +2 50 16 - 70 20 M6 (45 - 49)
1.5 - 1.7
B1, B2 16 4 - 16 10 M4 (13.5 - 15)
5.4 - 6.0
16 10 - 25 - M6 (47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp.
Three-Phase 400 V Class
Wire Stripping
Recomm. Gauge Applicable Gauge Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 Size and Shape N∙m (lbf∙in)
mm
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
4001 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
2.5 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
4002 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
2.5 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
Standards Compliance
0.5 - 0.6
4004 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3) 5
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
4005 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
4007 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
4009 -, +1, +2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 2.5 2.5 - 4 8 M3 (4.4 - 5.3)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
4012 -, +1, +2 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.2 - 1.5
4 *2 2.5 - 6 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 2.5 2.5 - 4 10 M4 (13.5 - 15)
1.5 - 1.7
4018 -, +1, +2 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
2.0 - 2.5
4 *2 2.5 - 16 - M5 (17.7 - 22.1)
1.5 - 1.7
R/L1, S/L2, T/L3 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 4 2.5 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
4023 -, +1, +2 4 4-6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
2.0 - 2.5
4 *2 4 - 16 - M5 (17.7 - 22.1)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
mm2 mm2 mm Size and Shape N∙m (lbf∙in)
1.5 - 1.7
R/L1, S/L2, T/L3 6 4 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 6 4 - 10 10 M4 (13.5 - 15)
2.3 - 2.5
4031 -, +1, +2 10 2.5 - 16 18 M5 (19.8 - 22)
1.5 - 1.7
B1, B2 2.5 2.5 - 4 10 M4 (13.5 - 15)
5.4 - 6.0
6 *2 6 - 16 *2 - M6 (47.8 - 53.1)
1.5 - 1.7
R/L1, S/L2, T/L3 10 4 - 16 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 6 2.5 - 10 10 M4 (13.5 - 15)
2.3 - 2.5
4038 -, +1, +2 16 4 - 25 18 M5 (19.8 - 22)
1.5 - 1.7
B1, B2 4 2.5 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
10 6 - 16 - M6 (47.8 - 53.1)
2.3 - 2.5
R/L1, S/L2, T/L3 16 4 - 25 18 M5 (19.8 - 22)
2.3 - 2.5
U/T1, V/T2, W/T3 10 4 - 16 18 M5 (19.8 - 22)
2.3 - 2.5
4044 -, +1, +2 16 6 - 25 18 M5 (19.8 - 22)
1.5 - 1.7
B1, B2 6 4 - 10 10 M4 (13.5 - 15)
5.4 - 6.0
10 6 - 16 - M6 (47.8 - 53.1)
Standards Compliance
• ≤ 25 mm2
2.3 - 2.5
(19.8 - 22)
R/L1, S/L2, T/L3 25 6 - 35 18 M5 • 35 mm2 ≤
4.1 - 4.5
(36 - 40)
2.3 - 2.5
U/T1, V/T2, W/T3 16 4 - 25 18 M5 (19.8 - 22)
• ≤ 25 mm2
4060 2.3 - 2.5
-, +1, +2 25 6 - 35 18
(19.8 - 22) 5
M5 • 35 mm2 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
B1, B2 10 2.5 - 16 10 M4 (13.5 - 15)
5.4 - 6.0
10 6 - 16 - M6 (47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp.
B006 FWH-80B
4012 FWH-90B
Model Model
B006 FWH-80B
Model Model
Standards Compliance
2001 FWH-25A14F 2021 FWH-90B
Model Model
4012 FWH-90B
◆ EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the EMC
Directive.
Drives with built-in EMC filters (models BxxxE, 2xxxE, 4xxxE) were tested in accordance with European standard
EN 61800-3:2004/A1:2012, and comply with the EMC Directive.
Standards Compliance
Figure 5.6 Install a Drive with a Built-in EMC Filter
5. Connect an AC reactor or DC link choke to decrease harmonic distortion. Refer to DC Link Chokes on page
187 to select a DC link choke.
Note:
• To comply with EN 61000-3-2 on drive models 2001 to 2006, and 4001 to 4004, install a DC link choke.
• The terminal block for the drive main circuit and the terminal block for the DC link choke have different shapes. The drive has a
European-style terminal block, and the DC link choke has a round terminal block. Correctly prepare the ends of the wiring.
Ground Wiring 5
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Ground the neutral point on the power supply of drive models BxxxE, 2xxxE, and 4xxxE to
comply with the EMC Directive before you turn on the EMC filter or if there is high resistance grounding. If you turn ON the EMC
filter, but you do not ground the neutral point, it can cause serious injury or death.
Enable the Internal EMC Filter
On drive models BxxxE, 2xxxE, and 4xxxE, move the screw or screws to turn ON and OFF (enable and disable) the
EMC filter.
Make sure that the symmetric grounding network is applied, and install the screw or screws in the ON position to
enable the built-in EMC filter in compliance with the EMC Directive. The EMC filter switch screw or screws are
installed in the OFF position by default.
WARNING! Electrical Shock Hazard. Disconnect all power to the drive, wait for the time specified on the warning label, and check
the drive for dangerous voltages before you remove covers or touch EMC filter screws. If you touch the screws when there are
dangerous voltages, it will cause serious injury or death.
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Ground the neutral point on the power supply of drive models BxxxE, 2xxxE, and 4xxxE to
comply with the EMC Directive before you turn on the EMC filter or if there is high resistance grounding. If you turn ON the EMC
filter, but you do not ground the neutral point, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Connect the ground cable correctly. If you touch electrical equipment that is not grounded, it
can cause serious injury or death.
NOTICE: To disable the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque. If you fully
remove the screws or tighten the screws to an incorrect torque, it can cause drive failure.
NOTICE: Move the EMC switch screw or screws to the OFF position for networks that are not symmetrically grounded. If the screws
are not in the correct position, it can cause damage to the drive.
B001E - B004E
Figure 5.8
2001E - 2006E
B006E - B012E
2010E - 2021E Figure 5.9
4001E - 4012E
2030E - 2082E
Figure 5.10
4018E - 4060E
A - SW (ON) B - SW (OFF)
Standards Compliance
A - SW (ON) B - SW (OFF)
5
Figure 5.9 EMC Filter Switch Location 2
A - SW (ON) B - SW (OFF)
B006 - B012
0.5 - 0.7
2010 - 2021 M3 × 20
(4.4 - 6.2)
4001 - 4012
3. Ground the wire shielding on the drive side and motor side.
Standards Compliance
B - Metal plate
Figure 5.12 Ground the Shield
*1 When you install an external EMC noise filter, change the terminals or use the junction terminal.
Table 5.14 External EMC Noise Filter (4xxxA)
Drive model EMC Noise Filter Model Quantity Manufacturer
Standards Compliance
4009 FS23639-10-07 1 Schaffner
*1 When you install an external EMC noise filter, change the terminals or use the junction terminal.
■ DC Link Chokes
To comply with EN 61000-3-2 drive models 2001 to 2006, and 4001 to 4004, install a DC link choke when you use
an internal or external EMC filter. Refer to Table 5.15 to select a DC link choke.
Table 5.15 DC Link Chokes for Harmonic Suppression
DC Link Choke
Drive Model
Rating
◆ Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or less as specified in
UL61800-5-1.
• Users can purchase wiring tools from Yaskawa. Contact Yaskawa or your nearest sales representative for more
information.
• Wire gauges on the drive you are replacing may not match the wire gauge ranges on your new drive. Contact
Yaskawa or your nearest sales representative for more information about the connection procedures.
• Do not tighten the terminal screws at an angle of 5 degrees or more. Failure to obey can cause damage to the
terminal screws.
If you damage a terminal screw, contact Yaskawa or your nearest sales representative.
Standards Compliance
5
A - Cable clamp
Figure 5.17 Strain Relief Example
Table 5.16 Recommended Wiring Tools
Bit Torque Driver Model Torque Wrench
Screw
Size Screw Shape Wire Gauge Adapter
Model Manufacturer (Tightening Torque) (Tightening Torque)
TSD-M 1,2NM
M3 - Bit SF-BIT-SL 0,5X3,0-70 PHOENIX CONTACT (0.3 - 1.2 N∙m -
(2.7 - 10.6 lbf∙in))
TSD-M 3NM
M4 - Bit SF-BIT-SL 1,0X4,0-70 PHOENIX CONTACT (1.2 - 3.0 N∙m -
(10.6 - 26.6 lbf∙in))
TSD-M 3NM
≤ 25 mm2
(1.2 - 3.0 N∙m -
(AWG 10) (10.6 - 26.6 lbf∙in))
M5 *1 Bit SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
≥ 30 mm2 4.1 - 4.5 N∙m
-
(AWG 8) (36.3 - 39.8 lbf∙in) *2 *3
5 - 9 N∙m
M6 - Bit SF-BIT-HEX 5-50 PHOENIX CONTACT -
(WAF: 5 mm) (44.3 - 79.7 lbf∙in) *2 *3
*1 When you wire drive models 2042, 2056, 4031, 4038, 4044, and 4060, select the correct tools for the wire gauge.
*2 Use 6.35 mm (0.25 in) bit socket holder.
*3 Use a torque wrench that can apply this torque measurement range.
WARNING! Fire Hazard. Do not connect a braking resistor to terminals +1 or -. Use terminals B1 and B2 for the braking resistor
connections. If you connect a braking resistor to the incorrect terminals, it can cause damage to the drive and braking circuit and
serious injury or death.
Screw Shape
These tables use icons in Table 5.17 to show the shapes of the screw heads.
Table 5.17 Icons to Identify Screw Shapes
Icon Screw Shape
+/-
Slotted (-)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
L/L1, N/L2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B001 -, +1 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
L/L1, N/L2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B002 -, +1 14 14 6.5 M3 (4.4 - 5.3)
Standards Compliance
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
L/L1, N/L2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3) 5
0.5 - 0.6
B004 -, +1 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
L/L1, N/L2 12 14 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B006 -, +1 12 14 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
L/L1, N/L2 10 12 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B010 -, +1 10 12 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
L/L1, N/L2 8 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 12 14 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
B012 -, +1 8 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 14 14 - 12 10 M4 (13.5 - 15)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
L/L1, N/L2 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 10 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
B018 -, +1 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 14 14 - 12 10 M4 (13.5 - 15)
2.0 - 2.5
8 *2 12 - 8 *2 - M5 (17.7 - 22.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp.
Wire Stripping
Recomm. Gauge Applicable Gauge Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil Size and Shape N∙m (lbf∙in)
mm
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2001 -, +1, +2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2002 -, +1, +2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2004 -, +1, +2 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 6.5 M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2
Standards Compliance
- M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 6.5 M3 (4.4 - 5.3)
0.5 - 0.6
2006 -, +1, +2 14 14 6.5 M3 (4.4 - 5.3)
B1, B2 14 14 6.5
0.5 - 0.6 5
M3 (4.4 - 5.3)
0.8 - 1.0
14 *2 14 *2 - M3.5 (7.1 - 8.9)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
2010 -, +1, +2 12 14 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
R/L1, S/L2, T/L3 12 14 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 12 14 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
2012 -, +1, +2 10 12 - 10 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 8 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 10 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
2021 -, +1, +2 8 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 14 14 - 10 10 M4 (13.5 - 15)
1.2 - 1.5
8 14 - 8 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
2030 -, +1, +2 6 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 12 12 - 8 10 M4 (13.5 - 15)
2.0 - 2.5
8 10 - 6 - M5 (17.7 - 22.1)
1.5 - 1.7
R/L1, S/L2, T/L3 6 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 6 12 - 6 10 M4 (13.5 - 15)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
2042 -, +1, +2 4 10 - 2 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
B1, B2 10 14 - 6 10 M4 (13.5 - 15)
2.0 - 2.5
6 10 - 6 - M5 (17.7 - 22.1)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
4.1 - 4.5
R/L1, S/L2, T/L3 4 10 - 2 18 M5 (36 - 40)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3 4 10 - 2 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
2056
4.1 - 4.5
-, +1, +2 2 8-2 18 M5 (36 - 40)
1.5 - 1.7
B1, B2 8 12 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
6 8-4 - M6 (47.8 - 53.1)
5 - 5.5
R/L1, S/L2, T/L3 2 6-1 20 M6 (45 - 49)
5 - 5.5
U/T1, V/T2, W/T3 2 8-1 20 M6 (45 - 49)
5 - 5.5
2070 -, +1, +2 1 6 - 1/0 20 M6 (45 - 49)
1.5 - 1.7
B1, B2 8 12 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
4 6-4 - M6 (47.8 - 53.1)
5 - 5.5
R/L1, S/L2, T/L3 1 6 - 1/0 20 M6 (45 - 49)
5 - 5.5
U/T1, V/T2, W/T3 2 6-1 20 M6 (45 - 49)
5 - 5.5
2082 -, +1, +2 2/0 2 - 2/0 20 M6 (45 - 49)
1.5 - 1.7
B1, B2 6 10 - 6 10 M4 (13.5 - 15)
Standards Compliance
5.4 - 6.0
4 6-4 - M6 (47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp. 5
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2
Three-Phase 400 V Class
Wire Stripping
Recomm. Gauge Applicable Gauge Length *1 Terminal Screw Tightening Torque
Model Terminal
AWG, kcmil AWG, kcmil Size and Shape N∙m (lbf∙in)
mm
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4001 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
14 *2 14 - 10 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4002 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
14 *2 14 - 10 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4004 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4005 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4007 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
0.5 - 0.6
R/L1, S/L2, T/L3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
U/T1, V/T2, W/T3 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
4009 -, +1, +2 14 14 - 12 8 M3 (4.4 - 5.3)
0.5 - 0.6
B1, B2 14 14 - 12 8 M3 (4.4 - 5.3)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 12 14 - 10 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 14 14 - 12 10 M4 (13.5 - 15)
1.5 - 1.7
4012 -, +1, +2 10 12 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 14 14 - 12 10 M4 (13.5 - 15)
1.2 - 1.5
10 *2 14 - 10 *2 - M4 (10.6 - 13.3)
1.5 - 1.7
R/L1, S/L2, T/L3 10 12 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 10 12 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
4018 -, +1, +2 10 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 14 14 - 12 10 M4 (13.5 - 15)
2.0 - 2.5
10 *2 14 - 6 *2 - M5 (17.7 - 22.1)
Standards Compliance
1.5 - 1.7
R/L1, S/L2, T/L3 8 14 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 10 14 - 8 10 M4 (13.5 - 15)
1.5 - 1.7
4023 -, +1, +2 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
B1, B2 12 14 - 10 10 M4 (13.5 - 15)
5
2.0 - 2.5
10 *2 10 - 6 *2 - M5 (17.7 - 22.1)
1.5 - 1.7
R/L1, S/L2, T/L3 8 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 8 12 - 6 10 M4 (13.5 - 15)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
4031 -, +1, +2 6 12 - 4 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
B1, B2 10 12 - 8 10 M4 (13.5 - 15)
5.4 - 6.0
8 10 - 6 - M6 (47.8 - 53.1)
Recomm. Gauge Applicable Gauge Wire Stripping Terminal Screw Tightening Torque
Model Terminal Length *1
AWG, kcmil AWG, kcmil mm Size and Shape N∙m (lbf∙in)
1.5 - 1.7
R/L1, S/L2, T/L3 6 12 - 6 10 M4 (13.5 - 15)
1.5 - 1.7
U/T1, V/T2, W/T3 8 12 - 6 10 M4 (13.5 - 15)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
4038 -, +1, +2 4 10 - 2 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
1.5 - 1.7
B1, B2 10 14 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
6 10 - 6 - M6 (47.8 - 53.1)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
R/L1, S/L2, T/L3 4 10 - 2 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3 6 12 - 4 18 M5 • AWG 8 ≤
4044 4.1 - 4.5
(36 - 40)
4.1 - 4.5
-, +1, +2 2 8-2 18 M5 (36 - 40)
1.5 - 1.7
B1, B2 8 12 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
6 10 - 6 - M6 (47.8 - 53.1)
4.1 - 4.5
R/L1, S/L2, T/L3 2 8-2 18 M5 (36 - 40)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3 4 10 - 2 18 M5 • AWG 8 ≤
4.1 - 4.5
(36 - 40)
4060
4.1 - 4.5
-, +1, +2 2 6-2 18 M5 (36 - 40)
1.5 - 1.7
B1, B2 8 12 - 6 10 M4 (13.5 - 15)
5.4 - 6.0
6 10 - 6 - M6 (47.8 - 53.1)
*1 Remove insulation from the ends of wires to expose the length of wire shown.
*2 If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp terminals or
equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm2 (copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
• P10-8R from PANDUIT Corp.
When you use MCCBs, RK1, or RK5 fuses, you must mount the drive in a ventilated enclosure according to the
minimum enclosure volume specified in Single-Phase 200 V Class on page 199, Three-Phase 200 V Class on page
199, and Three-Phase 400 V Class on page 200.
Molded Case Circuit Breaker (MCCB) Ratings
• Maximum MCCB rating is 200% of the Normal Duty drive full load output amp (FLA) rating.
• When you use MCCBs, install the drive into a ventilated enclosure with a minimum enclosure volume.
Note:
When you use MCCBs, current limiting type are recommended, but not required.
Non-Semiconductor Fuse Ratings
• Maximum CC, J, T, RK1 or RK5 fuse rating is 175% of the Normal Duty drive full load output amp (FLA) rating.
Short Circuit Current Ratings (SCCR)
The maximum SCCR provided by drive and fuse, or drive and MCCB combinations in this document, is 31,000 RMS
symmetrical amps.
• 200 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 31,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 31,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
Electric Code Compliance
The user must provide short circuit protection to protect input branch circuits as specified by the National Electric
Code (NEC), the Canadian Electric Code, Part 1 (CEC), and local codes.
Single-Phase 200 V Class
Table 5.18 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Ventilated Protected Enclosure Not Required Ventilated Protected Enclosure Required
Drive Model Semiconductor Fuse Class J, CC, and T Fuse MCCB Class RK1 or RK5 Fuse Minimum Enclosure
Manufacturer: EATON/ Volume
Maximum Amps Maximum Amps Maximum Amps
Bussmann (in3)
Standards Compliance
B006 FWH-80B 20 25 20 600
Analog output AM, AC Uses the LVLC power supply in the drive.