TFR Differential Relay Theory and Testing Guide
TFR Differential Relay Theory and Testing Guide
It is easy to understand that transformer differential relay We then calculate the current on both sides of relay's
just compares current on both sides of transformer (balance inputs:
current on both side in healthy condition or external fault)
but actually there are more conditions we have to consider. - On HV side
I Relay HV = I HV / CTRatio
Below are some important points we need to consider: I Relay HV = 0.500 Amp
- On low side
I Relay LV = (I LV Side / CTRatio) 3
I Relay LV = 4.325 Amp
1/12
Subject
How do transformer differential relays correct for Example#2: Using One Side as Reference
the difference in current magnitude?
For this method, the relay fixes one side as reference and
calculate current on other side based the turns ratio of
current transformer and the turns ratio of power
transformer.
We then calculate the per unit current based on these Then we calculate the primary current on the LV Side (in
reference to the HV Side):
formula:
I Cal LV= IMeasCTRatio TRRatio
I Cal LV= 100 Amps
- On high side
I Cal HV = IMeasCTRatio / In TR
Finally, we can use these corrected values to calculate the
IMeas = 0.500 Amp Differential Current:
I Cal HV = 0.500 per unit I Diff = I Cal HV - I Cal LV
2/12
Subject
This method uses tap settings inside the relay to correct for
the magnitude differences at both inputs. Parameter that
will be used for magnitude correction (setting in relay) in
this case are:
For this example, the calculation inside relay will use the
Tap Settings multiply by current on each side.
- On HV Side:
I Cal HV = IMeasTap HV
I Cal HV = 0.500 Amps
- On LV Side:
I Cal LV = IMeasTap LV
3/12
Subject
IaCal = -1 0 1 Ia
IbCal = (1/3)* 1 -1 0 * Ib
IcCal = 0 1 -1 Ic
According Figure7 and Figure8 above have shown the
condition that cause to make different of angle. Some case of vector group we don't need to divide as 3,
1. Vector group of power transformer. for example
2. Connection of CT on secondary side.
Example below will give you an idea and shown you how to
correction different of phase angle by transformer
differential relay.
IaCal = 1 0 1 Ia
IbCal = 1 1 0 * Ib
IcCal = 0 1 -1 Ic
4/12
Subject
5/12
Subject
6/12
Subject
Matrix for eliminate zero sequence components (calculate Total flux = transient flux + steady state flux
from line current):
Steady state flux is relative with voltage that supply to
Ia eliminate I0 = 2 -1 -1 Ia transformer
Ib eliminate I0 = (1/3) * -1 2 -1 * Ib Therefore: e1(t)= N (d/dt)
Ic eliminate I0 = -1 -1 2 Ic
Em sin (t) = N (d/dt)
Matrix for eliminate zero sequence components (measure
from external CT):
steady state= (Em /N) sin (t)
Ia eliminate I0 = 1 0 0 Ix
When m= (Em /N)
Ib eliminate I0 = 0 1 0 - (1/3)* Ix
Ic eliminate I0 = 0 0 1 Ix
Steady state flux: steady state= -mcos (t)
According two matrix above we have seen that both case
When angle on supply voltage during switching at
can eliminate zero sequence components but we loss
time = t
sensibility 1.5 as much for the first case but for second case
total= steady state+ transient
we can improvement so that star point current transformer
total= -mcos (t)+ transient
have to be provided.
Assume switching at time = 0, and switching at angle ()
Conclusion for zero sequence eliminate
= 0 degree
total (t=0)= -m+ transient (t=0)
When power transformer connect as delta/wye or wye/delta
the effect of zero sequence component that cannot transfer
If residual flux at t=0 is zero total (t=0)= 0
between both side (unbalance current on both side) can
made transformer differential relay disoperation in case of
Then transient flux at t=0 transient (t=0) = m
single phase or phase to phase fault is occurred outside
zone protection therefore, filtering zero sequence
Figure16 is shown total flux that occur at t=0. Here we can
components necessary to be considered. Some relay don't
see total flux that occur during switching in this condition
have choice for user to select it's always filter zero
(residual flux is zero and switching at angle 0 degree) will
sequence current but some relay user can decision
get peak as 2*m
therefore for latter case user have to carefully consider.
7/12
Subject
1. Gap detection:
For this method relay will detect gap in each cycle
that current as zero if this gap is larger than some level
then relay determine this current is inrush current and block
trip command from relay.
8/12
Subject
1. Gap detection
2. Fifth Harmonic detection
9/12
Subject
- On low side
I Cal LS = IMeasCTRatio / In TR
IMeas = 4.325 Amp
I Cal LS = 0.500 per unit
4. For setting to compensate error from measurement When load current is increase or external fault is occurred
process or changing of transformer tap position usually any (assume current is changed from 400 amps to 800 amps)
manufacturer call this setting as minimum pick up. This
setting usually must higher than differential current that
occur when change transformer tap position or error from
measurement process. In addition, some relay support
method to get information of tap position then we can
increase sensibility of relay by use only error of
measurement process to consider.
10/12
Subject
11/12
Subject
12/12