MV HV Switchgear Gas Insulated RMU System Medium Voltage Ormazabal CGMCOSMOS
MV HV Switchgear Gas Insulated RMU System Medium Voltage Ormazabal CGMCOSMOS
MV HV Switchgear Gas Insulated RMU System Medium Voltage Ormazabal CGMCOSMOS
CGMCOSMOS
Fully gas-insulated modular
and compact (RMU) system
Up to 24 kV
The quality of the products designed, manufactured and
installed by Ormazabal is backed by the implementation
and certification of a quality management system, based
on international standard ISO 9001:2000.
Our commitment to the environment is reaffirmed with
the implementation and certification of an environmental
management system as laid down in international standard
ISO 14001.
Contents
General description 4
Introduction 4
Areas of implementation 4
Applicable standards 4
Main characteristics 5
Design and construction characteristics 6
Safety 7
Quality of electrical supply 8
Types of function 9
Feeder, CGMCOSMOS-L 10
Fuse protection, CGMCOSMOS-P 11
Circuit-breaker protection, CGMCOSMOS-V 12
Busbar switch, CGMCOSMOS-S 14
Busbar switch with earthing, CGMCOSMOS-S-Pt 15
Cable rise, CGMCOSMOS-RC 16
Double cable rise, CGMCOSMOS-R2C 16
Busbar rise, CGMCOSMOS-RB 17
Busbar rise with earthing, CGMCOSMOS-RB-Pt 17
Metering, CGMCOSMOS-M 18
Compact (RMU), CGMCOSMOS-2LP 19
Compact, CGMCOSMOS-RLP 20
Compact, CGMCOSMOS-2L/3L 20
Compact, CGMCOSMOS-3LP/2L2P/3L2P 21
Installation 30
Environmental information 33
Configuration guide 33
3
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
General description
INTRODUCTION
AREAS OF IMPLEMENTATION
APPLICABLE STANDARDS
Public distribution
IEC 62271-1
Common specifications for high voltage switchgear and controlgear
standards.
IEC 62271-200
Alternating current metal-enclosed switchgear and controlgear for
rated voltages above 1 kV and up to and including 52 kV.
IEC 60265-1
High voltage switches. Part 1: High voltage switches for rated
voltages above 1 kV up to and including 52 kV.
IEC 62271-102
Alternating current disconnectors and earthing switches.
IEC 62271-105
High voltage alternating current switch-fuse combinations.
IEC 62271-100
High voltage alternating current circuit-breakers.
IEC 60255
Electrical relays.
IEC 60529
Degrees of protection provided by enclosures.
IEC 61958
Voltage presence indicating systems.
Private distribution
Î The CGMCOSMOS system passes the immersion test at a
pressure of 3 metres of water column, 24 hours at rated
voltage and power frequency insulation test.
4
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
MAIN CHARACTERISTICS
Presentation of ORMALINK Additional safety using ekorSYS units: ekorVPIS, a light voltage
presence indicator; and ekorSAS, an acoustic alarm preventing
earthing.
Accessories and live testing as an option.
Horizontal fuse holders with front access, protected within a gas
tank.
Ease of connecting cables by means of front plug-in or screw-in
terminals.
Commitment to the environment through:
• The use of highly recyclable materials.
• Minimal gas volume per functional unit.
• End-of-life cycle management.
SERVICE CONDITIONS
Type of switchgear Indoors
Maximum ambient temperature + 40 ºC *
Minimum ambient temperature -5 ºC / -30 ºC **
Maximum average ambient temperature, measured over a 24-hour period + 35ºC
Maximum average relative humidity, measured over a 24-hour period < 95%
Maximum average vapour pressure, measured over a 24-hour period 22 mbar
Maximum average vapour pressure, measured over a 1-month period 18 mbar
Maximum height above sea level 2000 m *
Solar radiation Negligible
Environmental air pollution (dust, salinity, etc.) Insignificant
Vibrations (seismicity) Negligible
* For special conditions, please consult our Technical-Commercial Department:
• Maximum ambient temperatures
• Altitudes
• Seismic resistance: non-negligible seismic conditions
** Storage: -40 ºC. Other classes: please, consult.
5
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
Cable compartment
6
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
SAFETY
Internal arc
The CGMCOSMOS cubicles are designed to protect persons and
property against the effects of an internal arc in accordance with the
criteria in Annex A of the IEC 62271-200 standard:
• Internal arc in tank (AF class):16 kA 0.5 s / 20* kA 0.5 s
• Internal arc in tank (AFL class):16 kA 1 s / 20* kA 1 s**
• IAC AFL class:16 kA 1 s / 20* kA 1 s**
Interlocks
These cubicles have internal interlocks fitted as standard to enable
safe and reliable service, in accordance with the requirements of the
IEC 62271-200 standard.
The interlock assembly prevents unsafe operations:
• It makes it impossible to close the switch-disconnector and the
earthing switch at the same time
• It permits the opening of the access cover to the Medium Voltage
cables only if the earthing switch is connected
• It conditions access to the cable / fuse holder area
The cubicles in the CGMCOSMOS system independently admit the
locking of operations with a padlock from the switch and from the
earthing switch.
Optionally, lock devices for locking operations are available.
Environmental resistance
The making and breaking elements are inside a stainless steel,
hermetically sealed, SF6 gas-insulated tank.
The full gas insulation provides resistance to harsh environmental
conditions (humidity, salinity, dust, pollution, etc.) and protection
against indirect contacts.
The tank enclosure has been designed and tested to withstand the
effects of internal arcs, thereby protecting persons and property. The
sealing maintains the optimum operating conditions throughout the
cubicle's service life, in accordance with standard IEC 62271-1.
The position of the switch is reliably displayed on the mimic diagram,
and validated by the kinematic chain test in accordance with current
standards (IEC 62271-102).
* Tests performed at 21 kA
** Except in CGMCOSMOS-V with RAV/RAMV driving mechanism
7
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
8
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
Types of function
MODULAR UNITS
CGMCOSMOS-L CGMCOSMOS-S CGMCOSMOS-RB
CGMCOSMOS-P CGMCOSMOS-RC
COMPACT UNITS
CGMCOSMOS-2LP CGMCOSMOS-RLP CGMCOSMOS-2L
(RMU)
Fuse protection and Fuse protection, Feeder functions
feeder functions feeder and busbar
rise functions
(other versions: 3LP,
2L2P or 3L2P)
TECHNICAL CHARACTERISTICS
L P V (AV) V (RAV) S S-Pt RC RB RB-Pt M
Rated current
General busbar and cubicle Ir [A] 400/630 400/630 400/630 630 400/630 400/630 400/630
interconnection
in output to
Ir [A] - 200 - - - - -
transformer
Dimensions
* See detailed information for 12 kV on the pages below. Available with Ur= 7.2 kV on request.
** Tests conducted at 21 kA / 54.6 kA
# See dimensions reduced under specifications on the following pages
## The weight refers to the enclosure, with no transformer inside
9
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
CGMCOSMOS-L
Feeder function
Modular cubicle with feeder function, equipped with three-position
switch-disconnector (closed, open or earthing).
Extensibility: right, left and both sides.
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630 400/630
interconnection
feeder Ir [A] 400/630 400/630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50 APPLICATIONS
Across isolating distance Ud [kV] 32 60
Input or output of the Medium Voltage
Rated lightning impulse withstand voltage cables, enabling communication with the
phase-to-earth and between phases Up [kV] 75 125 busbar in the general cubicle assembly.
Across isolating distance Up [kV] 85 145
Internal arc classification IAC AFL 16 kA 1 s/20** kA 1 s
IP rating IP IP3X
Switch-disconnector acc. IEC 60265-1 + IEC 62271-102
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
Peak value Ip [kA] 40/52**/62.5# 40/52**
Mainly active load-breaking current I1 [A] 400/630
Cable charging-breaking current I4a [A] 50/1,5
Closed-loop breaking current I2a [A] 400/630
Earth fault breaking current I6a [A] 300
Cable- & line-charging breaking
I6b [A] 100
current under earth fault conditions
Main switch making capacity
Ima [kA] 40/52**/62.5# 40/52**
(peak value)
Switch category
1000-M1 (manual)
Mechanical endurance
5000-M2 (motor)
Cycles of operations
5-E3
(Short-circuit making current)- class
Earthing Switch acc. IEC 62271-102
Rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
#
Peak value Ip [kA] 40/52**/62.5 40/52**
DIMENSIONS
Earthing switch making capacity #
Ima [kA] 40/52**/62.5 40/52**
(peak value)
Height [mm] 1740 1300
Earthing Switch Category
Mechanical endurance (manual) 1000-M0 Depth [mm] 735 735
10
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CGMCOSMOS-P
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630 400/630
interconnection
output to transformer Ir [A] 200 200
Rated short-duration power frequency withstand voltage (1 min)
APPLICATIONS phase-to-earth and between phases Ud [kV] 28 50
11
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
CGMCOSMOS-V
ELECTRICAL CHARACTERISTICS
Rated voltage Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 630 630
interconnection
feeder Ir [A] 630 630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50
Across isolating distance Ud [kV] 38 60
Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 75 125
Across isolating distance Up [kV] 85 145
Internal arc classification AFL 20* kA 1 s
IP rating IP IP33 + IPX7
Circuit-breaker acc. IEC 62271-100
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 20*
Peak value Ip [kA] 50*
Rated breaking capacity and making capacity
Mainly active current rated breaking
I1 [A] 630
capacity
Short-circuit breaking capacity Isc [kA] 20*
Main switch making capacity
Ima [kA] 50*
(peak value)
Rated making and breaking capacities of capacitive currents (50 Hz)
Capacitor banks [A] 400
Capacitor banks in parallel [A] 400
DIMENSIONS
Rated operating sequence O - 0.3 s - CO - 15 s - CO
Circuit-breaker category
Mechanical endurance (operations-class) 10 000-M2 Height [mm] 1740
Electrical endurance (class) 10 000 Depth [mm] 845
Disconnector and Earthing Switch acc. IEC 62271-102
Width [mm] 480
Rated short-time withstand current (main and earthing circuits)
Value tk = 1 s or 3 s Ik [kA] 20* Weight [kg] 240
12
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
AV/AMV circuit-breaker
ELECTRICAL CHARACTERISTICS
Rated voltage Ur [kV] 24
Rated frequency fr [Hz] 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630
interconnection
feeder Ir [A] 400/630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 50
Across isolating distance Ud [kV] 60
Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 125
Across isolating distance Up [kV] 145
Internal arc classification IAC AFL 16 kA 1 s/20* kA 1 s
IP rating IP IP3X
Circuit-breaker acc. IEC 62271-100
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20*
Peak value Ip [kA] 40/50*
Rated breaking capacity and making capacity
Mainly active current rated breaking
I1 [A] 400/630
capacity
Short-circuit breaking capacity Isc [kA] 16/20*
Main switch making
Ima [kA] 40/50*
capacity (peak value)
Rated operating sequence CO - 15 s - CO
Circuit-breaker category
Mechanical endurance (operations-class) 2000-M1
Electrical endurance (class) 2000
Switch-disconnector acc. IEC 60265-1 + IEC 62271-102
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20*
Peak value Ip [kA] 40/50*
Mainly active current rated
I1 [A] 400/630
breaking capacity
Main switch making capacity
Ima [kA] 40/52*
(peak value)
Switch-disconnector Category
Mechanical endurance 1000-M1
Cycles of operations
5-E3
(Short-circuit making current) - class
DIMENSIONS
Earthing Switch acc. IEC 62271-102
Rated short-time withstand current (earthing circuit)
Height [mm] 1740
Value tk = 1 s or 3 s Ik [kA] 16/20*
Depth [mm] 845 Peak value Ip [kA] 40/50*
Width [mm] 480 Earthing Switch making capacity
Ima [kA] 40/50*
(peak value)
Weight [kg] 240
Earthing Switch Category
Mechanical endurance 2000-M1
Cycles of operations
5-E2
(Short-circuit making current) - class
* Tests conducted at 21 kA/52.5 kA.
** More breaking values: see table CGMCOSMOS-L
13
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
CGMCOSMOS-S
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630 400/630
interconnection
feeder Ir [A] 400/630 400/630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50
Across isolating distance Ud [kV] 32 60
APPLICATIONS
Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 75 125 Interruption in main busbar load
Across isolating distance Up [kV] 85 145 of the transformer substation.
Internal arc classification IAC AFL 16 kA 1 s/20** kA 1 s
IP rating IP IP33 + IPX7
Switch-disconnector acc. IEC 60265-1 + IEC 62271-102
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
#
Peak value Ip [kA] 40/52**/62.5 40/52**
Mainly active load-breaking current I1 [A] 400/630
Cable charging-breaking current I4a [A] 50/1,5
Rated closed loop
I2a [A] 400/630
breaking capacity
Earth fault breaking current I6a [A] 300
Cable- & line-charging breaking
I6b [A] 100
current under earth fault conditions
Main switch making
Ima [kA] 40/52**/62.5# 40/52**
capacity (peak value)
Switch category
1000-M1 (manual)
Mechanical endurance
5000-M2 (motor)
Cycles of operations
5-E3
(Short-circuit making current)- class
DIMENSIONS
14
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CGMCOSMOS-S-Pt
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630 400/630
interconnection
feeder Ir [A] 400/630 400/630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50
Across isolating distance Ud [kV] 32 60
APPLICATIONS Rated lightning impulse withstand voltage
Interruption in main busbar load phase-to-earth and between phases Up [kV] 75 125
of the transformer substation and Across isolating distance Up [kV] 85 145
its earthing on the right (Ptd) or Internal arc classification IAC AFL 16 kA 1 s/20** kA 1 s
left (Pti) of the break.
IP rating IP IP3X
Switch-disconnector acc. IEC 60265-1 + IEC 62271-102
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
Peak value Ip [kA] 40/52**/62.5# 40/52**
Mainly active load-breaking current I1 [A] 400/630
Cable charging-breaking current I4a [A] 50/1,5
Rated closed loop
I2a [A] 400/630
breaking capacity
Earth fault breaking current I6a [A] 300
Cable- & line-charging breaking
I6b [A] 100
current under earth fault conditions
Main switch making
Ima [kA] 40/52**/62,5 40/52**
capacity (peak value)
Switch category
Mechanical endurance (manual) 1000-M1
Cycles of operations
5-E3
(Short-circuit making current)- class
Earthing Switch acc. IEC 62271-102
Rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
#
Peak value Ip [kA] 40/52**/62.5 40/52**
Earthing switch making
Ima [kA] 40/52**/62.5# 40/52**
DIMENSIONS capacity (peak value)
Earthing Switch Category
Height [mm] 1740 1300 Mechanical endurance (manual) 1000-M0
Cycles of operations
Depth [mm] 735 735 5-E2
(Short-circuit making current)- class
Width [mm] 450 450 * Also available with Ur= 7.2 kV on request.
** Tests conducted at 21 kA/52.5 kA.
Weight [kg] 115 110 # Value only valid for tk = 1 s
15
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
CGMCOSMOS-RC
APPLICATIONS DIMENSIONS
Housing of feeder cables to
busbar in the general cubicle Height [mm] 1740
assembly, on the right (RCd) or on
Depth [mm] 735
the left (RCi).
Width [mm] 365
Weight [kg] 40
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
feeder Ir [A] 400/630 400/630
* Also available with Ur= 7.2 kV on request.
CGMCOSMOS-R2C
APPLICATIONS DIMENSIONS
Housing of feeder cables to
busbar in the general cubicle Height [mm] 1740
assembly, on the right (R2Cd) or
Depth [mm] 735
on the left (R2Ci).
Width [mm] 550
Weight [kg] 60
16
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CGMCOSMOS-RB
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
APPLICATIONS Ir [A] 400/630 400/630
interconnection
Input or output of Medium Voltage cables, feeder Ir [A] 400/630 400/630
enabling communication with the busbar in Rated short-duration power frequency withstand voltage (1 min)
the general cubicle assembly, on the right phase-to-earth and between phases Ud [kV] 28 50
(RBd) or on both sides (RBa). Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 75 125
DIMENSIONS Internal arc classification IAC AFL 16 kA 1 s/20* kA 1 s
* Also available with Ur= 7.2 kV on request.
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24
Rated frequency fr [Hz] 50/60 50/60
Rated current
General busbar and cubicle
Ir [A] 400/630 400/630
interconnection
feeder Ir [A] 400/630 400/630
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50
Rated lightning impulse withstand voltage
APPLICATIONS
phase-to-earth and between phases Up [kV] 75 125
Input or output of Medium Voltage cables, Internal arc classification IAC AFL 16 kA 1 s/20* kA 1 s
on the right (RBd-Pt) or on both sides (RBa- Earthing Switch acc. IEC 62271-102
Pt) and the earthing of the cables and of the Rated short-time withstand current (earthing circuit)
busbar in the general cubicle assembly. Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20**
Peak value Ip [kA] 40/52**/62.5# 40/52**
DIMENSIONS Earthing switch making
Ima [kA] 40/52**/62.5# 40/52**
capacity (peak value)
Earthing Switch Category
Height [mm] 1740 1300
Mechanical endurance (manual) 1000-M0
Depth [mm] 735 735
Cycles of operations
5-E2
Width [mm] 365 365 (Short-circuit making current)- class
* Also available with Ur= 7.2 kV on request.
Weight [kg] 100 90 ** Tests conducted at 21 kA/52.5 kA.
# Value only valid for tk = 1 s
17
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
CGMCOSMOS-M
Metering function
Modular cubicle with metering function.
ELECTRICAL CHARACTERISTICS
Rated voltage* Ur [kV] 12 24 APPLICATIONS
Rated frequency fr [Hz] 50/60 50/60
Voltage and current metering
Rated current
transformer housing, enabling
General busbar and cubicle
interconnection
Ir [A] 400/630 400/630 communication with the busbar in
the general cubicle assembly, via
Rated short-duration power frequency withstand voltage (1 min)
a dry cable.
phase-to-earth and between phases Ud [kV] 28 50
Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 75 125
* Also available with Ur= 7.2 kV on request.
DIMENSIONS
18
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CGMCOSMOS-2LP
ELECTRICAL CHARACTERISTICS L P
Rated voltage* Ur [kV] 12 24 12 24
Rated frequency fr [Hz] 50/60 50/60 50/60 50/60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 400/630 400/630 400/630
feeder Ir [A] 400/630 400/630 - -
output to transformer Ir [A] - - 200 200
Rated short-duration power frequency withstand voltage (1 min)
phase-to-earth and between phases Ud [kV] 28 50 28 50
Across isolating distance Ud [kV] 32 60 32 60
Rated lightning impulse withstand voltage
phase-to-earth and between phases Up [kV] 75 125 75 125
Across isolating distance Up [kV] 85 145 85 145
Internal arc classification IAC AFL 16 kA 1 s/20** kA 1 s
IP rating IP IP33 + IPX7
Switch-disconnector acc. IEC 60265-1 + IEC 62271-102 L P
Rated short-time withstand current (main circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20** 16/20**/25# 16/20**
# #
Peak value Ip [kA] 40/52**/62.5 40/52** 40/52**/62.5 40/52**
Mainly active current rated breaking capacity I1 [A] 400/630 200
Rated no-load cable-charging breaking capacity I4a [A] 50/1.5 - -
Closed-loop breaking current I2a [A] 400/630 - -
Rated breaking capacity in the event of fault to earth I6a [A] 300 - -
Rated breaking capacity of no-load cables/lines
I6b [A] 100 - -
in the event of fault to earth
Main switch making capacity (peak value) Ima [kA] 40/52**/62.5# 40/52** 40/52**/62.5# 40/52**
Switch category
Mechanical endurance 1000-M1 (manual) / 5000-M2 (motor)
Cycles of operations (Short-circuit making current)- class 5-E3
Combined switch-relay (ekorRPT) take-over current
Breaking Imax acc. TDito IEC 62271-105 [A] - - 1250 1250
Switch-fuse combination transfer current
Breaking Imax acc. TDitransfer IEC 62271-105 [A] - - 1500 1300
Earthing Switch acc. IEC 62271-102 L P
Rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 16/20**/25# 16/20** 1/3
Peak value Ip [kA] 40/52**/62.5# 40/52** 2.5/7.5
Earthing switch making capacity (peak value) Ima [kA] 40/52**/62.5# 40/52** 2.5/7.5
Earthing Switch Category
Mechanical endurance (manual) 1000-M0
Cycles of operations (Short-circuit making current)- class 5-E2
* Also available with Ur= 7.2 kV on request.
** Tests conducted at 21 kA/52.5 kA.
# Value only valid for tk = 1 s
CGMCOSMOS-2LP DIMENSIONS
CGMCOSMOS-RLP
DIMENSIONS
CGMCOSMOS-2L DIMENSIONS
CGMCOSMOS-2L
Feeder functions* Height [mm] 1740 1300
Compact cubicle with two or three feeder functions, which includes Depth [mm] 735 735
the features of the feeder cubicles, in one single tank.
Width [mm] 730 730
Extensibility: right, left, both sides.
Weight [kg] 210 210
CGMCOSMOS-3L configuration via module grouping.
DIMENSIONS
CGMCOSMOS-3L
Î * Please see ELECTRICAL CHARACTERISTICS tables for the RB, L and P functions on previous pages.
20
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CGMCOSMOS-3LP/2L2P/3L2P
CGMCOSMOS-3LP
CGMCOSMOS-2L2P
CGMCOSMOS-3L2P CGMCOSMOS-2L2P
DIMENSIONS
3LP 2L2P 3L2P
1740/ 1740/ 1740/
Height [mm] 1300* 1300* 1300*
Depth [mm] 735 735 735
* Under specifications
CGMCOSMOS-3L2P
Î * Please see ELECTRICAL CHARACTERISTICS tables for the L and P functions on previous pages.
21
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
OPERATION SAFETY
Driving mechanisms
The front layout of the driving mechanisms and the use of anti-reflex
levers permits safe, comfortable, simple operations with a minimum
of effort. The position is reliably indicated, and it complies with the
kinematic chain test.
Depending on the operating mechanism (3-position switch or circuit-
breaker), there are different models.
Three-position
Circuit-breaker
switch-disconnector
AV and AMV
B and BM
Spring loaded driving
Basic driving mechanism mechanism for circuit-
with independent manual breaker function.
operation (B) or motorised
(BM).
This mechanism is installed
in series with a B type
Local or remote controlled
mecanishm.
operations.
The mechanical endurance of the driving mechanisms of The driving mechanisms of the automatic switch receive
the 3-position switch is class M1 for manual mechanisms the classification M1 (AV/AMV) and M2 (RAV/RAMV),
and class M2 for mechanisms with frequent operations conforming to the IEC 62271-100 standard, giving them
(IEC 60265–IEC 62271-102). These may be replaced live the maximum features in applications with or without
in any of the positions (closed, open or earthed). reclosing.
22
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
ELECTRICAL CHARACTERISTICS
THREE-POSITION SWITCH-DISCONNECTOR
Driving mechanism B BM BR AR ARM
Internal insulation [kV] 2 2 10 10 2
Tripping coil (opening)
[Vcc] - - 24 / 48 / 110 / 125 / 230
Rated voltage*
[Vca] - - 125 / 230
Maximum consumption [W] - - 80
Motorised units
24 / 48 / 24 / 48 /
[Vcc] -
110 / 125 / 230
- - 110 / 125 / 230
Rated voltage*
[Vca] - 125 / 230 - - 230
Motor operation time [s] - <3 - - <3
Peak current [A] - <5 - - <5
Indicating contact
1 NOC + 2NO /
Switch 2 NO + 2 NC 2 NO + 2 NC
2 NO + 2 NC
Earthing 1 NO + 1 NC
Rated voltage* [Vca] 250
Rated current [A] 16
* According to IEC 62271-1 chapter 4.8.2
ELECTRICAL CHARACTERISTICS
CIRCUIT-BREAKER
Driving mechanism AV AMV RAV RAMV
Internal insulation [kV] 2 2 2 2
Tripping coil (opening). Máximum of 2
[Vcc] 24 / 48 / 110 / 125 / 230
Rated voltage
[Vca] 230
Maximum consumption [W] 130 80 60 60
Closing coil
24 / 48 / 24 / 48 /
[Vcc] -
110 / 125 / 230
-
110 / 125 / 230
Rated voltage
[Vca] - 230 - 230
Maximum consumption [W] - 80 - 60
Undervoltage coil
[Vcc] 24 / 48 / 110-125 / 230
Rated voltage
[Vca] 230
Maximum consumption [W] 150
Motorised units
[Vcc] - 24 / 48 / 110 / 125 - 24 / 48 / 110 / 125
Rated voltage
[Vca] - 230 - 230
Motor operation time [s] - <15 - <15
Peak current [A] - <9,6 - <9,6
Indicating contact
Switch 2 NO + 2 NC
Earthing 1 NO + 1 NC
Circuit-breaker 4 NO + 5 NC 5 NO + 6 NC
Spring loading - 1 NO + 1 NC - 1 NO
Rated voltage [Vca] 250 250 250 250
Rated current [A] 16 / 20 16 / 20 20 20
23
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
PROTECTION
With fuses
Protection against short circuits in the Medium Voltage network is
made by means of the fuse protection functions.
The fuse holder tubes reach a uniform temperature all along the
tube when they are placed horizontally inside the gas tank. When
the cover is closed, they are fully sealed against floods and external
pollution.
In accordance with the IEC 62271-105 standard, the switch-fuse
combination may be either the “associated” or “combined” type.
In the latter case, the operation of each of the fuses is indicated on
the front mimic diagram of the cubicle. The fuse-switch assembly
has been temperature-rise tested under normal service conditions
according to IEC 62271-1.
25 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
Ur Ur Ur
Net- Cubicle Fuse Rated Fuse Current IEC 60282-1
work
Î Remarks:
• Fuses recommended: SIBA brand with medium type striker,
conforming to IEC 60282-1 (low power loss fuses).
• The values for combined fuses are given in blue.
• The fuse-switch assembly has been temperature-rise tested
under normal service conditions in accordance with IEC
62271-1.
• A fuse holder carriage adapted for 292 mm 6/12 kV fuses is
available.
• For ratings marked in bold the measurement is 442 mm.
• If any of the fuses blow, we recommend changing all three.
• For overload conditions in the transformer or use of other
brands of fuse, please consult Ormazabal's Technical-
Commercial Department.
24
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
25
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
ekorSYS FAMILY
Ormazabal supplies complete Medium Voltage installations that
include protection, control and automation functions.
Ormazabal, as specialists in Medium Voltage, have a wide
portfolio of applications and services to respond to the needs of the
distribution network.
The units of the ekorSYS family, patented by Ormazabal and
integrated in the cubicle, are the ideal solution for use in the
most demanding installations because they offer high levels of
performance compared to conventional systems.
Protection
• Supply to Medium Voltage customers
• ekorRPG
• ekorRPT
• Protection of switching substations and industrial customers ekorRPG
• ekorRPS
• ekorRPGci
• ekorRPTci
• Protection of rural transformer substations (CTR)
• ekorRPT-K
• Generator set protection unit
• ekorUPG
• Substation protection
• ekorRPS-TCP
Dispatching center
Software
• ekorSOFT
CGMCOSMOS-2LPT + ekorGID
Î For further information, please refer to our Technical-Commercial
department or visit www.ormazabal.es
26
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
CABLE CONNECTIONS
Î For the option of ANSI (IEE 396) compatible bushings, please refer
to our Technical-Commercial department.
Connectors
• Direct connection to the bushings located in the cable compartment
or on the side via plug-in or screw-in connectors (rated current
greater than 400 A or short-circuit current equal to or higher than
16 kA).
• 250 A plug-in connectors (straight or elbow type for rear exit of
cable) in outputs to transformer (cable compartment) for fuse
protection functions.
• Shielded connectors for circuit-breaker protection functions.
27
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
ACCESSORIES
Up to 24 kV
Plug-in shunt in T 250 A
Plug-in shunt in cross formation 250 A
Insulating plugs 250 A
Reducers 250 A
Connection terminals 250 A
Surge arresters 5 kA
Bushing height
Connection.
EUROMOLD straight
plug-in terminal (K-152SR)
28
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
29
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
Installation
a
c
MINIMUM DISTANCES
Side wall a [mm] 100
Ceiling b [mm] 500
Front aisle c [mm] ≤ 1000*
Rear wall d [mm] > 100**
30
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
1 2
MAXIMUM TRENCH DIMENSIONS FOR CUBICLES WITH INTERNAL ARC IN GASTANK (AF) UP TO 20 kA* - 0.5 s
Function type Cable input or output
1 Front and Rear 2 Side
The depth of the trench, suitable for all cable types, is 800 mm.
31
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
Fuse protection
ORMALINK with capacitive output
• 12 kV fuse holder carriage.
for detection of voltage
• 24 kV fuse holder carriage.
Metal enclosure
• Driving mechanism cover.
• Cable compartment cover.
• Mimic diagram.
• Auxiliary profiles: recommended for premises with uneven floor
surfaces.
• Lateral incoming box.
Interlocks/locks
• Open/close operation closing device.
Lateral incoming box
CGMCOSMOS-CL
32
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
Environmental information
The Ormazabal production centres have introduced the corresponding
environmental management systems, conforming to the requirements
of the international ISO 14001 standard and endorsed by the
Environmental Management Certificate AENOR CGM-00/38 among
others.
At the end of the product life cycle, the SF6 gas content must not be
released into the atmosphere. It is recovered and treated for reuse, in
accordance with the instructions given in standards IEC 62271-303,
IEC 60480 and the CIGRE 117 guide.
Ormazabal will provide the additional information required to carry
out this task correctly, out of respect for the safety of individuals and
that of the environment.
Configuration guide
Rated voltage Ur Frequency Rated current Short-time current Internal arc [kA - s]
[kV] fr [Hz] Ir [A] Ik [kA - s] 16 - 1
12 50 400 12 kV 25 - 1 IAC AFL
20 -1
24 60 630 12.5 - 1 16 - 0.5
16 - 1 In tank: AF
20 - 0.5
24 kV 16 - 3 16 - 1
21 - 1 In tank: AFL
20 - 1
21 - 3
33
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
Up to 24 kV MV Switchgear
Secondary Distribution Networks
SPECIFIC DATA
CGMCOSMOS L/2L P V RB/ S/
2LP V (AV) V (RAV) RB-Pt S-Pt
(A) + (B) (C)
Driving mechanism
Manual B BR/AR AV B RAV B (RB-Pt) B
Motorized BM -/ARM AMV BM RAMV - BM
Actuating levers (S) (S) (S) (S) (S) (S) (S)
Coils
Tripping coil - YES/NO YES/NO - YES/NO - -
Bistable - - YES/NO - YES/NO - -
2ª tripping coil - - YES/NO - YES/NO - -
Closing coil - - YES/NO - YES/NO - -
Undervoltage coil - - YES/NO - YES/NO - -
Connectivity
Front bushing (S) (S) (S) (S) (S) -
Side connection
Blind (non extensible) YES/NO (2LP) - - - -
Extensible (one side) Left/ Left/ Left/Right Left/ Right -
Right Right Right
Extensible (both sides) YES/NO YES/NO YES/NO YES/NO YES/NO (S)
Additional elements
Lateral incoming box
Left feeder YES/NO YES/NO YES/NO YES/NO - -
Right feeder YES/NO YES/NO YES/NO YES/NO - -
Extended base for double connection YES/NO YES/NO YES/NO YES/NO - -
Safety
Voltage indicator
ekorVPIS YES/NO YES/NO YES/NO YES/NO YES/NO* YES/NO*
ekorIVDS YES/NO YES/NO YES/NO YES/NO YES/NO* YES/NO*
Acoustic alarm, ekorSAS (S) YES/NO YES/NO YES/NO YES/NO YES/NO
Phase comaprator, ekorSPC YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO
Manometer (S) (S) (S) (S) (S) -
Protection and control
Trip - (1)/(2) - - - -
Fuses - YES/NO - - - -
Integrated control and YES/NO - - - -
monitoring unit, ekorRCI
Protection unit, ekorRPG - - YES/NO YES/NO - YES/NO
Protection unit, ekorRPT - YES/NO - - - -
Voltage detection unit, ekorRTK YES/NO - YES/NO YES/NO - YES/NO
(A) Circuit-breaker (1) Combined (S) Standard
(B) Switch-disconnector (2) Associated
(C) Circuit-breaker + disconnector * With earthing
34
Focus on Medium Voltage
CGMCOSMOS Fully gas-insulated
modular and compact (RMU) system
MV Switchgear Up to 24 kV
Secondary Distribution Networks
SPECIFIC DATA
CGMCOSMOS L/2L P V RB/ S/
2LP V (AV) V (RAV) RB-Pt S-Pt
(A) + (B) (C)
Interlocks
Internal (S) (S) (S) (S) (S) (S)
Additional lock YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO
(A) Circuit-breaker (1) Combined (S) Standard
(B) Switch-disconnector (2) Associated
(C) Circuit-breaker + disconnector * With earthing
SPECIFIC DATA
CGMCOSMOS RC/R2C M
Connectivity
Side connection
Extensible (one side) Left/Right
Safety
Voltage indicator
ekorVPIS YES/NO
ekorIVDS YES/NO
Diagram type
Bottom input / Top right output
Bottom input / Top left output
Top input / Top output
Busbar voltage metering
Interlocks
Installed current transformers (3 CTs) YES/NO
Installed voltage transformers (3 VTs) YES/NO
Heater YES/NO
Protection mesh YES/NO
35
Focus on Medium Voltage
Focus on Medium Voltage
TECHNICAL-COMMERCIAL DEPARTMENT
www.ormazabal.com