PM DVRV
PM DVRV
WARNING
Only personnel that have been trained to install, adjust, service
or repair (hereinafter, “service”) the equipment specified in this
manual should service the equipment. The manufacturer will not
be responsible for any injury or property damage arising from
improper service or service procedures. If you service this unit,
you assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require one or
more licenses to service the equipment specified in this manual,
only licensed personnel should servise the equipment.
Improper installation, adjustment, servicing or repair of the
equipment specified in this manual, or attempting to install,
adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property
damage, personal injury or death.
PROP 65 WARNING
FOR CALIFORNIA CONSUMERS
WARNING
Cancer and Reproductive Harm -
www.P65Warnings.ca.gov
0140M00517-A
SYSTEM SELECTION
Indoor Unit Range ...........................................................28
Accessories......................................................................30
Indoor Unit Consideration ...............................................31
Zoning VRV Systems with DZK .......................................35
Hydrobox..........................................................................37
Heat Pump or Heat Recovery? .......................................41
Water-Cooled VRV – Geothermal .................................. 44
Water-Cooled VRV – Design Criteria ..............................45
Solutions For Ventilation .................................................47
VRV Ventilation Methods ................................................49
DESIGN OPTIMIZATION
System Zoning ............................................................... 54
Branch Selector Boxes ....................................................56
Single or Multi BSV Boxes? ............................................60
Optimized Pipe Routes....................................................62
Outdoor Unit Installation Space ......................................63
Heat Pump Changeover ..................................................65
* Complete warranty details are available from your local Daikin manufacturer’s
representative or distributor or online at www.daikinac.com.
6
SYSTEM OVERVIEW
The Features and Benefits of VRV
The benefits of VRV equipment can be categorized by
three core features:
7
Key Points for Selection
System Diversity vs Connection Ratio
Optimizing VRV System Selection
» The most successful users of VRV equipment understand the
importance of a fully optimized design
» A key factor that ensures optimized VRV equipment selection
is to understand the correlation between SYSTEM DIVERSITY
& CONNECTION RATIO
8
Key Points for Selection
System Diversity & Connection Ratio – What's the Difference?
Connection Ratio:
» Both indoor & outdoor units have a Capacity Index number
(e.g. FXMQ30PBVJU indoor unit & RXYQ192TTJU outdoor unit)
Total sum of IDU
index numbers ÷ ODU
index number = CONNECTION RATIO
System Diversity:
System DIVERSITY is the difference between the Maximum System
Load demand and the Maximum Capacity of the outdoor unit,
at design conditions
» In this example, if the maximum load is called for, the outdoor unit
will fall short of demand by 3,954btu – This VRV design has a 2%
system diversity
In Summary:
Connection Ratio does NOT indicate the diversity of a
VRV system. Use of the VRV Xpress selection tool will
indicate clearly if selected VRV equipment has a
system diversity or not.
9
Key Points for Selection
Project Design Criteria
Before selection of any VRV system, a minimum amount of information
is required for accurate equipment selection and to apply an
optimized design.
For an accurate selection of indoor units the following information is required:
PEAK PEAK DESIGN AIR
Cooling Loads Heating Loads Conditions
» Engineers will » Required when » The dry & wet bulb
usually provide either Heating temperature entering
both Total & is the dominant the coil
Sensible loads operation or the » Also known as
which should heating design “air-on” or “mixed air”
be entered condition is conditions
» However it is below 32°F
» Nominal conditions are
possible to select typically 80°F db &
equipment using 67°F wb but rarely
only Total or reflect actual conditions
Sensible load
» Design air-on can also
be given as db/RH%
(e.g. 74°F & 50% RH)
10
Key Points for Selection
When
When using
using at
Indoor only All other
least one All IDU All IDU
Unit FXDQ, FXAQ indoor unit
FXSQ-05, models models
Type FXSQ-07~54 models
FXZQ-05
FXMQ(P)
FXFQ-07/09
Single
Module 180% 200% 130%
Dual
Module 200% 160% 160% 130%
N/A
Triple
Module 130% 130%
Notes:
1. Minimum connection ratio for Class 72 (6 ton) models is 70%
2. Minimum Connection Ratio for all other standard Air-Cooled and
Water-Cooled models: 50%.
3. When systems are designed to >130% connection ratio, indoor units in thermo ON
are set to low fan speed by default. This function can be overridden at commissioning
stage, if desired.
SYSTEM AIR-COOLED
TYPE VRV EMERION VRV AURORA
200%
Single (180%
180% 180% 200%
Module on 14-20
200% TON) 200%
Dual
160% 160% 160% 160%
Module
Note: Minimum Connection Ratio for all VRV AURORA models is 70%
11
Key Points for Selection
Single
150%
Module
Dual 130%
150% 130%
Module (120% on 36 Ton)
Triple 130%
Module (120% on 36 Ton)
12
Key Points for Selection
82 OPTIMAL
80
Cooling Mode
Room Temperature
OVERSIZED
78
SET-POINT
76
74
72
70
68
66
64
82 1 2 3 4 5 6 7 8 9 10 11 12 13
OPTIMAL 14 15
80 Time
Cooling Mode
Room Temperature
OVERSIZED
78
Oversized
76
for heating SET-POINT
In areas
74 of very cold climates, there is a temptation to ‘up-size’ indoor
82
units in the belief that this ensures capacity in extreme conditions below
72
80
design temperature
Room Temperature
70
78 68
The76 reality is correct load calculation and good design ensures
66
74
the64
best performance
72 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
OPTIMAL
In 70heating mode, the expansionTime device never fully closes.
Therefore
68 a unitHeating Mode
that continuously cycles onOVERSIZED
and off will,
in time,
66 see a steady increase in temperature above Set-point
SET-POINT
64
82 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
80 Time
Room Temperature
78
76
74
72
OPTIMAL
70
68 Heating Mode OVERSIZED
66 SET-POINT
64
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Time
13
Application Limits
Refrigerant Piping Limits
AIR-COOLED WATER-COOLED
PIPING VRV
LIMITATIONS VRV VRV VRV VRV VRV VRV
VRV IV-W
Liquid Line EMERION IV IV AURORA IV-S IV-W
IV-S (8, 10 ,
Max (ft) Heat Heat Heat Low (4 & (6 &
(3 Ton) &
Recovery Pump Recovery Ambient 5 Ton) 7 Ton)
12 Ton)
Vertical 164 164 164 164
A 98 98 164 164
Drop (361)4 (295)¹ (295)¹ (295)¹
Linear
E 540 540 540 540 164 230 390 540
Length
Total
3280 3280 3280 1640 820 984 980 980
Network
1
Setting adjustment on condensing unit required.
2
Fan coil distance differentials must be met.
3
When linear length exceeds 390ft, AND when IDU to IDU height differential exceeds 49ft,
an operational setting adjustment is required. An increase in refrigerants noise may occur.
4
When height exceeds 295ft, in addition to setting adjustment, additional conditions may
need to be met. Refer to installation manual.
14
Application Limits
Voltages and Maximum IDU Connections
# of Compressors
# of Compressors
# of Compressors
# of Modules
# of Modules
# of Modules
Max. # IDU
Max. # IDU
Max. # IDU
Voltage
Voltage
Voltage
Capacity
MBH (Tn)
72 (6) 1 1 12 12 12
96 (8) 16 16 1 16
20 1 1 20 1 20
3 Phase: 208-230V ~ 460V ~ 575V
144 (12) 25 25 25
168 (14) 1 2 29 29 29
192 (16) 33 33 2 33
3 Phase: 208-230V ~ 460V
216 (18) 37 37 37
240 (20) 41 41 41
264 (22) 45 2 2 45 2 3 45
288 (24) 49 49 49
312 (26) 54 54 4 54
336 (28) 58 58 58
360 (30) 62 62 3 62
2 4
384 (32) 64 64 3 4 64
230V
408 (34) 64 3 3 64 460V 5 64
230V
432 (36) 64 460V 64
only
456 (38) 64 64
480 (40) 64
15
Application Limits
Capacity Range
VRV AURORA
AIR- WATER- HEAT PUMP &
COOLED HEAT PUMP & COOLED RECOVERY
RECOVERY
# of Compressors
# of Compressors
# of Modules
# of Modules
Max. # IDU
Max. # IDU
Voltage
Voltage
Capacity Capacity
MBH (Tn) MBH (Tn)
72 (6) 12 72 (6)* 12
3 Phase: 208-230V ~
1
460V ~ 575V*
96 (8) 1 16 84 (7)* 14
120 (10) 20 96 (16) 1 1 20
144 (12) 25 120 (20) 25
3 Phase: 208-230V ~ 460V ~ 575V*
288 (24) 61
# of Modules
Max. # IDU
Voltage
16
Application Limits
Wiring Parameters
Communication Wiring should be:
» 18-16 2AWG stranded » (A) to (C), (A) to (E),
» No polarity (A) to (G) or (C) to (G)
» No shielding » Maximum total distance is (A to
F) + (B to C) + (D to E) + (F to G)
» Maximum linear distance = 3280 ft.
» Each local controller (H to C)
» Maximum total distance = 6560 ft.
can run up to a distance of
» Maximum linear distance in the 1640 ft.
example below is the longest
of either
Ambient Limits
Ambient Heat Pump Heat Recovery
122 F 120
113
110
100
95
COOLING
COOLING
75 F 90
Entering Water Temperature (˚F)
60 F
SIMULTANEOUS
AURORA Series Standard Operating Range
80 Standard Range
for Continuous
HEATING
Operation
HEATING
70
23 F Range
60 for
10 F Operation
-4 F 50
*EWT Below 50˚F
Requires Antifreeze
-13 F 40
34
-22 F
VIA technical cooling function
23*
VIA extended capacity tables 20
Cooling operation for VRV IV Heat Pump single 14
module systems (RXYQ72/96/120/144/168T)
can be extended down to 10˚F, from the standard 50 59 70 80 82 90
limitation of 23˚F under defined conditions. Indoor Temperature (˚FWB)
Contact your local Daikin manufacturer’s
representative or distributor for details. * Limited to 27˚ F
(For the PC Series)
17
Nomenclature
How to Read Model Number
Indoor Units
FX M Q 24 P VJ U
Outdoor Units
R EL Q 192 T A YC U
18
Piping Guide
Condensing Unit Pipe Connections
VRV
19
Piping Guide
Branch Selector Box Connections
Single-Port Boxes
Multi-Port Boxes
Single & multi-port box pipe orders differ
All piping on BS boxes are female connectors
HL
DOWNSTREAM
(to IDUs)
L S
Cut first for Connect as is
3/8” 5/8” for 1/4” 1/2”
Local pipe
” ” If connecting pipe is ” ”
If connecting pipe is
CONNECT AS IS CUT THE PIPE
L Liquid S Suction Gas HL Hi/Lo Gas
20
Piping Guide
What constitutes an oil trap?
Most limitations applied to VRV piping are need to ensure adequate oil
return to the compressor. Minimizing potential oil traps is a key component
of a good install. To understand what constitutes an oil trap, different rules
apply to PRIMARY & SECONDARY piping. Primary piping runs from the
ODU to the furthest branch (or multiport box). All other piping is considered
SECONDARY.
If an application demands, it is possible to run Primary piping vertically up
& down (or down & up) within the maximum standard vertical limitations:
Additional inverted
loop is not
Up to permitted
130’ height between ODU &
for up & down 1st REFNET
≤ 3.3’
Up to Additional inverted
130’ height loop is not
for up & down permitted
between ODU
& 1st REFNET
Up to 164’ Serving multiple floors from
vertical to down secondary piping is
NOT permitted
21
Piping Guide
What constitutes and oil trap?
2 ft
2 ft
2 ft NO oil trap
required
2 ft 6 ft
11 ft
8” oil trap 8” oil trap
required required
NOTE: This section is 10ft long
however it does NOT require a trap
oil traps within as no single horizontal section is
6.5 ft of branch greater than 6.5ft
8 ft
Note: Image above is for illustrative purposes only. VRV-IV = max. 3 x ODU
VRV EMERION = max. 2 x ODU
22
Piping Guide
23
Electrical Wiring
2"
NEC requires all IDU Fan Coils be connected to a 15A fuse breaker by default, though multiple
can be connected. to the same circuit. The chart below can be used to determine the amount
of units that can be strung together.
15 0.3 0.4 0.3 0.4 0.4 0.5 1.2 1.5 1.2 1.4
18 0.5 0.6 0.5 0.6 0.5 0.6 0.4 0.5 1 1.3 1.3 1.6 0.4 0.5 0.5 0.6 3.9 4.9 1.3 1.6
24 0.5 0.7 0.5 0.6 0.5 0.7 1.1 1.4 1.4 1.8 0.5 0.6 0.8 1 0.5 0.6 3.9 4.9 1.4 1.8
30 1 1.3 1.1 1.4 2.2 2.9 3.9 4.9 1.5 1.8
36 1.2 1.5 1.1 1.4 2.3 2.9 1.1 1.4 3.9 4.9 2 2.5
41 5.2 6.5
48 1.4 1.8 2.7 3.4 5.2 6.5 2 2.8
54 2.6 3.4 6.9 8.6 2.6 3.3
60 6.9 8.6
71 7.6 9.5
96 8.6 10.7
24
System
Selection
Indoor Unit Range
Sizes & Accessories Available of all IDU’s
7 9 12 15 18 24 30 36 48
FXZQ-T
VISTA (2’ X 2’) CASSETTE
5 7 9 12 15 18
FXEQ
1 WAY FLOW CASSETTE
7 9 12 15 18 24
FXUQ
4 WAY FLOW UNDER CEILING
18 24 30 36
FXHQ
1 WAY FLOW UNDER CEILING
12 24 36
FXAQ
WALL-MOUNTED
7 9 12 18 24
FXLQ
FLOOR-MOUNTED
7 9 12 18 24
FXNQ
CONCEALED FLOOR-MOUNTED
7 9 12 18 24
28
Indoor Unit Range
Sizes & Accessories Available of all IDU’s
9 12 18 24 30 36 42 48 54 60
FXDQ
LOW STATIC DUCTED
SYSTEM SELECTION
7 9 12 18 24
FXSQ
MID STATIC DUCTED
5 7 9 12 15 18 24 30 36 48 54
FXMQ-T
HIGH STATIC DUCTED
7 9 12 15 18 24 30 36 48 54
FXMQ-M
LARGE CAPACITY DUCTED
72 96
24 36 48 60
FURNACES
GAS FURNACES
40 60 80 100 120
29
Accessories
Example
Options Page
30
Indoor Unit Considerations
12 ft. 3% of unit
FXZQ-T All 11¾"
(per outlet) air flow rate
0 ~ 2¼"
17 ft.
FXUQ All (sits below N/A
(per outlet)
ceiling)
15% of unit
FXEQ All 10" 15ft
air flow rate
Note: Air throws are subjective. The data provided here is for
guideline purposes only.
31
Indoor Unit Considerations
07 ~ 12 0.04" 0.12"
FXDQ 77/8"
18 ~ 24 0.06" 0.17"
05 ~ 48 0.60"
FXSQ 911/16" 0.20" 20% of
54 0.56" units
air flow
15 ~ 48 0.40" 0.80" rate
FXMQ-T 10"
54 0.40" 0.56"
0.96"
FXMQ-M 72 ~ 96 181/8"
1.03"
FXSQ
FXMQ-T Most applications – Multiple room zoning
Application
Examples FXMQ-M Large open plan areas – High ESP requirements
32
Indoor Unit Considerations
Max. Typical
Concealed Model Height
WG O.A.
10%
FXNQ All 24 Minimal air flow
rate*
09 - 36 45"
33
Indoor Unit Considerations
EXPOSED units usually offer the client the most economical installed
cost solution on a VRV system. These types of units are most often
used when there are budget constraints or where an area has no void
space/enclosure to conceal other unit types. None of these units have
integral condensate pumps fitted.
Considerations:
» How big is the space?
» Where can the unit be located?
» Is piping / condensate run clear?
» Is the client accepting of exposed units?
Approx. Air
Exposed Units Model Max. WG Typical O.A.
Throw
Note: Air throws are subjective. The data provided here is for guideline purposes only.
34
Zoning VRV Systems with DZK
VRV Meets VAV - Features & Benefits
DZK - Daikin Zoning Kit
The DZK solution increases the
flexibility of VRV applications by
allowing multiple zones to be served
by one indoor unit fan coil
while still providing individual
temperature control.
Up to 6 separate dampers supply variable air flow to the zones in
response to individual zone thermostats.
Zoning Box
The zoning box is a plenum with motorized dampers
that constantly modulate the conditioned air flow
into each zone through standard ductwork, in
response to the demand from the individual zone
thermostat.
Wired Thermostat
The main thermostat is a wired color touch display
master unit used to configure the DZK system.
It can also be used as the thermostat for one or
all of the zones.
Wireless Thermostat
The Wireless thermostat is a battery powered, touch
display unit that is used for one zone. Each zone
thermostat monitors and allows the user to select a
comfortable room temperature, and program or adjust
the control functions for the room.
35
Zoning VRV Systems with DZK
Advantages
» Reduces system hardware cost - fewer Indoor units required
» Increases comfort levels by allowing more individual zone control
» Reduces installation expense and maintenance costs
» Reduces the amount of refrigerant required in the installation
» Increases the flexibility of the VRV application design
DZKS Zoning Box Range for FXSQ Units
Product
DZKS015E-4 DZKS015E-4 DZKS030E-4 DZKS030E-4 DZKS048E-4 DZKS048E-4
Reference
Compatible
FXSQ15TA FXSQ18 ~ 30TA FXSQ36 ~ 48TA
Ducted Unit
No. of
Air Duct 3 x ø8" 4 x ø6" 4 x ø8" 5 x ø6" 4 x ø8" 6 x ø6"
Outlets
Number
2 to 3 2 to 4 2 to 4 2 to 5 2 to 4 2 to 6
of Zones
36
Hydrobox
Model Reference
HXY 48 TA VJU
Radiant
Heating/Cooling
Low Temp
Radiators
Fan Coils
37
Hydrobox
VRV ODU Tonnage 6 8 10 12 14
Minimum VRV IDU Connection Ratio ≥50%
Max Hydro Units 1 2
Total Connection Ratio Range 50~130%
68 / 61 122
Outdoor Temperature
Outdoor Temperature
Continuous Operation
Continuous Operation
Pull-Down Operation
Warm-up Operation
˚FDB / ˚FWB
˚FDB
41
50
-4 / -4 50 / 46
41 68 77 113 50 68 77
Leaving Water Temperature (˚F) Leaving Water Temperature (˚F)
38
Hydrobox
G
F Build and Components
A Expansion Tank H EEV
E
B Water Strainer I Refrigerant
C Safety Relief Valve Filters
A
D Inverter Water
J Water connections
Supply with NPT thread
H Pipe Adaptors
E Brazed Plate
Refrigerant to K Pressure Gauge
I C Water Heat L Hydrobox
B Exchanger Controller
F Flow Switch (User Interface)
J
K L
G Auto Air Vent
Piping Limitations
Some standard VRV-IV X piping limitations are restricted when a
Hydrobox is installed.
Equivalent piping length between indoor unit and outdoor unit. 525
Maximum vertical height (when the ODU is installed above the IDU’s 164
39
Hydrobox
Expansion Tank:
» Volume: 2.6 gal (10 liter)
» Factory Default Pre-pressure: 14.5 psi
* This is the height difference (m) between the highest point of the water circuit
and the indoor unit. If the indoor unit is at the highest point of the installation,
the installation height is 0 m.
40
Heat Pump or Heat Recovery?
The Various Heat/Cool Changeover Options
Heat Pump (HP)
» The 2-pipe Heat Pump system is the equivalent of a 2-pipe chilled
water system
» A Heat Pump system provides the means of heating OR cooling
at any given time
» Multiple Heat Pump systems can be zoned and will work
independently of each other
» When demand is met by an indoor unit the unit will work on fan
only or the fan will cycle on/off until demand returns or mode
change occurs
41
Heat Pump or Heat Recovery?
Subarctic / Arctic
Very Cold
Marine
Cold
Mixed-Humid
Mixed-Dry
Hot-Humid
Hot-Dry
GEOGRAPHY
The location or the project will often dictate what type of system will
be required. Projects in temperate climates tend to use Heat Recovery
due to the changeable load demands that can occur through the course
of a day. However areas with defined seasons or little demand for
simultaneous heating or cooling throughout the year will usually utilize
Heat Pump.
42
Heat Pump or Heat Recovery?
BUILDING LAYOUT
Sites with open plan areas and/or similar orientation will often be
satisfied by a Heat Pump system, irrespective of geography. On the
other hand, if the site has many aspects, individual rooms and/or heat
loads, this may define the client requirement toward Heat Recovery.
Differing internal room load demands may see the need for cooling for
longer periods of the year.
OCCUPANCY
The type of end user will often trump any other consideration. Typically
a multi-tenanted site will require a heat recovery system as the ability for
individual mode control is paramount. Typical examples of this include
hotels, assisted living, condos as well as offices. It is always important to
establish from the outset if an office application is to have multiple tenants.
Heating Heating Cooling Cooling Cooling Cooling Heating Heating Cooling Heating
43
Water-Cooled VRV – Geothermal
44
Water-Cooled VRV – Geothermal
45
Water Cooled VRV – Design Criteria
Design Criteria:
Water loop design is the responsibility of the engineer. However, two
facts are needed from Daikin:
The minimum & maximum entering water temperatures:
» 50°F - 113°F for Cooling
» 23°F - 113°F for Cooling on a Geothermal System*
» 50°F - 113°F for Heating
» 14°F - 95°F for Heating on a Geothermal System*
A suitable water flow rate:
» 13.2 gpm to 39 gpm per module Boiler & Tower System
» 21 gpm to 39 gpm per module with glycol use
* (Be aware that conditions need to be met when EWT for heating is
required below 50°F – seek assistance for these applications)
Other consideration:
» When VRV is to be applied with an open loop system, a 3rd party
heat exchanger is required to ensure the plate heat exchanger of
the VRV condensing unit operates in a closed loop system.
» The VRV condensing units have a heat output into the adjacent
mechanical room (see table). Where multiple units are placed in
an enclosed area, any potential heat buildup must be addressed
(either with adequate ventilation or even a fan coil unit). RWEQ_TA
series units have the ability to configure the unit to reject this heat
to the refrigerant circuit. See Installation manual for further details.
» From the CU pipe connection to the fan coils, the equipment,
controls & selection process is identical to Air-Cooled VRV.
46
Solutions for Ventilation
Range & Limitations of our Ventilation Options
CFM 300 1000 1500 2000 2500 3000 5000 7500 10000+
VAM -300-1200
Energy Recovery
Ventilator
FXMQ_MF OA
Processing
630 – 1230
Unit
Daikin
Maverick II Rooftop
(DOAS) 15-75 ton
or 4500 - 23,000 cfm
47
Solutions for Ventilation
Allowable Ventilation Air %
Typically Daikin equipment has been applied using a standard rule of
thumb that a maximum of 20% OA can be incorporated into a ducted
fan coil unit (FXMQ, FXSQ, FXDQ, FXTQ and FXNQ). However, this
practice is not always applicable as this rule of thumb is based upon
introducing OA at nominal conditions.
Basic Rules
1. COOLING: Any percentage of OA can be used as long
as the resulting mixed air is between 57 and 77˚F WB
and 80% RH or lower.
2. HEATING: Any percentage of OA can be used as long
as the resulting mixed air is between 59 and 80˚F DB
and 80% RH or lower.
Note: Space temperature sensing should be done via the room zone controller or
remote sensor kit if a “mixed air” approach is taken.
48
VRV Ventilation Methods
Direct Method
Untreated outside air is mixed with return air either in the return
air ductwork or enters the VRV IDU directly
Application Consideration
» IDU must be sized for both space and ventilation loads
» IDU fan speed varies with the different modes, affecting the amount
of entering OA. A fixed speed is available through a field setting.
» OA should always be pre-filtered
Return Air
Supply Air
Return Air
Pros Cons
» Lowest cost » Indoor fans must operate continuously to provide
ventilation during scheduled occupancy
» Limited OA (Mixed air limitation)
» Indoor unit must be sized to handle the entire
ventilation and internal load
49
VRV Ventilation Methods
Integrated Method
The OA is conditioned by mechanical means before being supplied to
the VRV indoor unit for distribution.
Application Consideration
» Allows the ventilation air unit (100% OA Unit, DOAS, HRV or
ERV) to handle all or part of the OA load. The IDU is sized for
the internal space load, and possibly part of the OA load.
OA EA
FXMQ-MF
RA SA SA RA
Pros Cons
» Less ductwork and diffuser » IDU fan must run constant
» Opportunity for plenum condensation » Difficult to balance
is reduced since OA is not introduced
into IDU mix air plenum
» IDU capacity is not de-rated since
they are handling only warm
return air
50
VRV Ventilation Methods
Integrated Method
OA EA
FXMQ-MF
SA RA RA SA
Pros Cons
» Less ductwork » IDU Fan must run constant
and diffusers » Risk for condensation in the mixing plenum
» Indoor Unit capacity de-rate due to cool
mix air temp
2. Small to
medium
Std Config: Std Config: 50-100%
applications 23°F DB (FXMQ-MF <=30%)
Combined***
3. Suitable for
all climates Heating
4. Allows for
Enhanced Enhanced Config:
sharing load Config: 50-130%
between 59 (50*)°F DB (FXMQ-MF <=50%)
ventilation
system and
VRV system EKEQDCBAVEUS 122°F DB /
Cooling
89°F WB
90-110%
Heating 23°F DB
51
VRV Ventilation Methods
Separate Method (Decoupled)
OA is supplied directly to the space being conditioned.
A separate ventilation system using conventional technology
and a Daikin VRV system can both be installed where the
VRV system function is to maintain comfort.
»
Application Consideration
» Allows the DOAS to
handle the entire OA
oad. IDUs sized only for
the internal space load. RA
SA SA
RA
Pros Cons
» Opportunity to cycle off the local IDU fan » Requires installation of
» Allows the OA unit to operate during additional ductwork and
unoccupied periods (for after hours humidity separated diffuser
control or pre-occupancy purge) » Many require multiple
» Flexible layout diffusers to ensure that
OA is adequately dispersed
» Can meet strict filtration requirement through-out the zone
» Larger OA volume
52
Design
Optimization
System Zoning
Guideline to Optimized Zoning of Systems
Typical Zoning of Heat Pump
When more than one system is required, it is good practice to zone units
that are positioned on the same orientation or are subject to common
load profiles. This maximizes the scope for correct heating/cooling
demands to be met.
HP HP
HR HR
54
System Zoning
MULTIPLE MODULE Design
There are some advantages to linking VRV condensing units together: Less
piping & total refrigerant needs and a greater likelihood of heat recovery to
occur (on 3-pipe) due to increase in varying zones on the systems.
Note: This design option can be pushed back at design stage due to
refrigerant limitations in small spaces, set by ASRAE Std 15.
DESIGN OPTIMIZATION
The OPTIMIZED Design
It is important to avoid defining a project as a ‘heat recovery job’ or
‘heat pump job’. There are often applications where a mixture of both
types is the best design practice — and can reduce costs to the client.
In addition, Heat recovery does not always mean a branch selector PORT for each
unit — even when those units are serving different rooms. The benefits of Heat
Recovery can still be realized at a reduced cost
55
Branch Selector Boxes
» Heat Recovery (HR) systems require branch selector boxes to provide
simultaneous heating and cooling zones
» Daikin HR gives the project designer several options: Single-port (1),
Multi-port (4 to 12 ports), and Flex Branch Selector box (4 to 8 ports)
Single-
port type
Multi-port type
Single unit Grouped unit Single units Grouped units No BSV box
56
Branch Selector Boxes
Overview of BSQ Box Range & Features
216 MBH
BSF6Q54 5 54 MBH
(162)*
290 MBH
BSF8Q54 5 54 MBH
(162)*
57
Branch Selector Boxes
Flex Branch Selector Box Features
OR
Left and Right and
From Left From Right
Pass Thru Pass Thru
Corridor
40”
Corridor
40”
CLOSED
58 1
Refer to engineering manuals for design rules
Branch Selector Boxes
Flex Branch Selector Box Features
4
15-3/4
(minimum)
11-3/4
9-1/2 9-1/2
OR
59
Single or Multi BSQ Boxes?
Optimized Selection of BSQ Boxes
» HEAT RECOVERY systems using single BSQ boxes generally require much
less piping & refrigerant than a multi-port box application.
» In addition noise levels of single port boxes are a lot less – this allows
flexibility of location
TOTAL PIPING
REQUIRED 726 ft
................. . . . . . . . . . . . . . . .
REFNET JOINT 2' 2' 2' 2' 2' 2'
SETS 11
................. . . . . . . . . . . . . . . . 50' 16' 16' 16' 16' 16'
16'
BRAZED
CONNECTIONS 186
................. . . . . . . . . . . . . . . .
BSQ BOX
HANGING RODS 48
................. . . . . . . . . . . . . . . .
» HEAT RECOVERY systems using multi BSQ boxes will often demonstrate a
reduction on installation costs
TOTAL PIPING
REQUIRED 1164 ft
................................
52' 36' 20' 20' 36' 52'
REFNET JOINT
SETS 0
................................ 100'
12 port
BRAZED
CONNECTIONS 54
................................ 52' 36' 20' 20' 36' 52'
BSQ BOX
HANGING RODS 4
................................
60
Single or Multi BSQ Boxes?
Optimized Selection of BSQ Boxes
TOTAL PIPING
REQUIRED 714 ft
............... . . . . . . . . . . . . . . . . .
10' 10' 10' 12' 28' 44'
REFNET JOINT
SETS 8
............... . . . . . . . . . . . . . . . . . 50' 16' 2' 16' 2'
4 port
BRAZED
CONNECTIONS 102
............... . . . . . . . . . . . . . . . . . 8' 32' 12' 32'
BSQ BOX
HANGING RODS 20
............... . . . . . . . . . . . . . . . . .
61
Optimized Pipe Routes
MAIN LINE
PIPING
30 30 JOINT SIZES
(ODU to
07
Last REFNET)
30 30
5 x Large
07 07 70 ft of 11⁄ 8
(size 72)
2 x Med
36 20 ft of 7⁄ 8
07 (size 33)
1 x Small
4 ft of ¾
36 12 (size 22)
(NO 5 ⁄ 8)
12
30 30 TOTAL REFRIGERANT:
37.5 lbs.
7
30
Example 1 – LINEAR
30
PIPE ROUTE
7
30
30
07 MAIN LINE
30
PIPING JOINT
30 (ODU to SIZES
0707
Last REFNET)
36 3 x Large
07 32 ft of 11⁄ 8
(size 72)
1 x Med
36 12 2 ft of 7⁄ 8
(size 33)
4 x Small
19 ft of ¾
12 (size 22)
30 30
48 ft of 5 ⁄ 8
7
30 30 TOTAL REFRIGERANT:
34.6 lbs.
7
62
Outdoor Unit Installation Space
Minimum Space Requirements
At concept stage one of the most common requirements, especially
in built up areas, is to establish that there is space to fit the outdoor
equipment. The ‘decentralized’ nature of VRV provides a great deal
of flexibility however the multitude of service space combinations
in the engineering book still do not cover fully the bespoke nature of
project application. Therefore it is important to have a grasp of minimum
space requirements.
The 3 criteria to overcome are:
AIR STARVATION • SHORT CIRCUITING • SERVICE SPACE
There are two constants regardless of the application, system type
or series:
» VRV ODU’s require a minimum of 11.75" (300mm)
at the Rear (or air side) of the unit
» VRV ODU’s require a minimum of 19.625" (500mm)
at the Front (or service side) of the unit
*Note: Local code may require a greater distance
16" 16"
63
Outdoor Unit Installation Space
Minimum Space Requirements
The complexity of design comes in to play when multiple units are to
be installed into a restrictive area. The space between units in scenario
1 above are minimal and is only required to avoid any possible issues
of vibration.
However when wall heights exceed those shown in the data book (as they
usually do) rather than move units away from the wall, the better practice
(if the space allows) is to move the units further apart from each other.
The distance can vary according to a number of factors however 16"
between units will cover most all scenario’s.
Therefore, a great rule of thumb to ensure that a space is
suitable for VRV equipment is: 12" x 16" x 20"
Think of the service engineer!
» The minimum service space (20") allows for the removal of a
compressor however if rows of units are to be located in one
area then place the units front to front and allow 40" between
each row (24" air side to air side).
» The minimum space between units of 0.75" can make removing
the top plate awkward. If space allows, always leave at least 4"
between units (although this is not a necessity).
Mechanical Rooms & Acoustic Enclosures
» The same space rules apply in enclosed areas however the air
side of a unit can be positioned closer than 12" to a louvered wall.
Each unit has a maximum static pressure of 0.32"
» Short circuiting and air
starvation must also be Exhaust Duct
addressed. This is specially
so when units are to be
Louver
situated behind acoustic Suction
louvers and when multiple
units are to be positioned
together in a single enclosure.
64
Heat Pump Changeover
The Various Heat/Cool Changeover Options
There are no less than six ways to provide heat/cool changeover on a
heat pump system. Most of these also apply to heat recovery FCU’s
grouped on a single port of a BS Box (think of the BS box as a mini heat
pump system).
MASTER
Sensor
MANUAL CHANGEOVER
VIA Master Indoor Unit
Note: A common pitfall is to elect an area that is not in constant use or has no easy
access (e.g. managers office). If the unit isn’t running then mode change is not possible
without the intervention of some form of central control.
65
Heat Pump Changeover
The Various Heat/Cool Changeover Options
CENTRAL Sensor
AUTO CHANGEOVER
VIA Ambient Sensor
VRV
HP
MANUAL CHANGEOVER
66
Heat Pump Changeover
GROUP ITM
WEIGHT
1 ZONE A VRV
HP
3 ZONE B
1 ZONE C
Weighted Original
Demand Size Demand Size
Averaging Changeover:
Takes an average of the room temperature and set-point of all
connected indoor units. Uses the averaged values to determine the
system operation mode.
Voting Changeover:
The most flexible auto change over is the voting changeover.
Changeover operates by continually calculating the demand load of each
room by measuring the temperature differential of the Set-point against
the room temperature. Modes are regularly changed accordingly.
This method can be tailored on each application by ‘weighting’
the demand of a room based on it’s importance. Note that this method
can be used for units grouped together on a single port of a heat
recovery system.
Note: Both "Fixed", "Averaging", and "Vote" changeover methods require a
Daikin i-Touch Manager to operate.
In Summary:
With ALL changeover options, when a system mode is changed,
the indoor units on the system are not forced into heating or cooling.
If there is no demand in the room for the mode that has been
selected, the unit(s) will be in thermo-off and the fan may or may
not be running based upon the indoor unit configuration.
67
22 Floor Air- Cooled VRV / California
Controls &
Standards
Controls Portfolio
Range of Zone and Centralized Controllers
Scalable controls offering to match a building’s requirement
DSE40A71
HERO Cloud
HERO Simple Edge
Connection (Compatible with VRV EMERION)
DMS502B71
BACnet Interface
(Shown with optional DAM411B51)
DCM601B71+ DCM014A51
BACnet™ BACnet Server option
Open Protocol Up to 128 IDU connection
DTA118A71
BACnet MSTP Adaptor
LonWorks®
DMS504C71
Open LonWorks Interface
Protocol
DTA116A51
Modbus®
Modbus Adaptor
Open Protocol (home automation/Modus)
Advanced DCM601B71
intelligent Touch Manager
Multi-Zone (Shown with Optional
Control iTM Plus Adaptor)
Groups =
Indoor Unit Groups 1 16 64 128 256 512 1024 Individual Zone Controllers
70
Controls Portfolio
Range of Zone and Centralized Controllers
Scalable controls offering to match a building’s requirement
DTST-ONE-ADA-A
Daikin One+ Smart Thermostat
BRC1H71W
Daikin Madoka Room Controller
Individual
BACRC-T-P01
Zone Control BACRC-TH-P01
BACRC-THO-P01
BACRC-THOC-P01
Daikin Adaptive Touch Controller (ATC)
BRC1E73
Navigation Remote Controller
AZAI6WSCDKA
DKN Cloud Wi-Fi Adaptor
Individual
Wi-Fi Control
AZAI6WSPDKC
DKN Plus Interface
Groups =
Indoor Unit Groups 1 16 64 128 256 512 1024 Individual Zone Controllers
71
Project requirements drive the controls selection process
Project
Requirements BRC1H71W Daikin Daikin
BRC1E73 Daikin One+ AZAI6WSCDKA AZAI6WSPDKC Adaptive
Navigation Madoka Smart DKN Cloud DKN Plus Touch
Remote Room Thermostat Wi-Fi Interface Controller
Controller Controller Adaptor (ATC)
Minimum Set-point
• • • • • •
Control
differential
Individual fan speed for
cooling and heating • • • • •
Programmable schedule • • • • •
Humidity control with
humidity Set-point •2 •3
CO 2 control with Set-point • • • • • •3
Configurable occupancy
sensor logic •3
Secondary heater control •1 •1 • •1 • •
Auxiliary
• •
Control
Heater
• •
Option
BACnet™ MS/TP
Modbus ® • •
Third-party thermostat •
Bluetooth®
configuration app • • •
Smartphone control
• • •
Connectivity
through Wi-Fi
Voice Control by Amazon
Alexa and Google Assistant • • •
Dealer Web portal •
Geo-fencing •
Over-the-air (OTA)
Software update • • •
1. With KRP1C74/KRP1C75 adaptor only
2. Dehumidification with overcooling function
3. Depends on controller model or external sensor connection
72
Project requirements drive the controls selection process (cont.)
73
Project requirements drive the controls selection process (cont.)
74
Project requirements drive the controls selection process (cont.)
Automatic cooling/heating
changeover for heat pump • • • • •
systems
75
Local Control Options
Features & Benefits of the Room Controller
BRC1E73 –Navigation Room Controller
Daikin room controllers offer a vast array of features that provide the
ultimate in flexibility and benefits that many other manufacturers’ are
unable to offer.
In addition to the basic functions
Fan
Operation
Mode
Room
that meet the zone control
Speed Temp Current
Date/Time
requirement of all VRV indoor
units, the Navigation Remote
Set-point
Controller will provide advanced
Backlit control functions that historically
Display
require a central controller
On/Off
to administer:
Menu/OK
» 7 day Schedule
Cancel
» Temperature Limiting
Operation Menu
Mode Navigation » Control Lockout
Selector Control
Fan Speed » Dual set-points
Control
» Auto cool/heat changeover
» Automatic adjustment for
Daylight Saving Time (DST)
The controllers operate on the » Temperature sensor with
basis of last command priority. configurable offset
76
Local Control Options
Features & Benefits of the Room Controller
BRC1H71W – Madoka Room Controller
Daikin is pleased to introduce the Madoka remote controller for the
North American VRV, SkyAir, and Single and Multi-zone systems. The
Madoka features a sleek and stylish design with an intuitive interface
including touch button control. It retains advanced functions for indoor
unit control. It can be commissioned and managed with ease through
a Bluetooth® configuration app or via the onboard menus. The Madoka
provides 3 configurable display modes: Text (default), Icon, and Scale to
help meet project and occupant needs.
Award-winning
design. Madoka On/Off Button.
earned an IF
design award and
Red Dot Product
Design Award for its
innovative design.
77
Local Control Options
Features & Benefits of the Room Controller
4 A thin LED light bar sits flush within the bottom surface and runs from
edge to edge, delicately illuminating the wall beneath. Emitting a soft
emotive glow, the light bar indicates the current system mode: red for
heating, blue for cooling.
78
A number of screen Turning the dial
1 savers are available, 2 changes the
including this temperature
analog clock. set-point.
4
5
79
Local Control Options
Features & Benefits of the Room Controller
AZAIGWSPDKC – DKN Plus Interface
The DKN Plus Interface (AZAI6WSPDKC)
enables the energy-efficient control of Daikin
air conditioners by a third-party thermostat
or an automation system. With this interface,
third-party devices or systems can control
the VRV, SkyAir, and Daikin Single/Multi-Zone
indoor units through Cloud API, Modbus®,
BACnet™ MS/TP, or thermostat relay contacts.
This interface can be commissioned with ease
through the DKN Cloud North America (NA) app
via Bluetooth® Low Energy (BLE).
80
Local Control Options
Features & Benefits of the Room Controller
81
Featured Controllers
82
Featured Controllers
83
Featured Controllers
84
Codes & Standards
Some Key Considerations
Key Codes/
Category Situation for VRV
Standards
UL 1995 Daikin systems are UL 1995 certified.
Nat’l Electric Code Install per NEC guidelines.
Safety and NFPA 90A, 90B Daikin systems comply via UL 1995.
Electrical Std is applicable for APPLICATION,
Not equipment.
ASHRAE Std 15 RcL not to exceed 26lbs/1000cuft (13lbs
Canada: B52 in restricted/institutional occupancies).
85
Where to find Official Information?
Handbook
Submittal
Eng. Data
Bulletin
Design
Option
Product Detail
Guide
Sales
SVM
IOM
Features Summary ◆ ◆ ◆
Summary Table ◆ ◆ ◆ ◆
Specification
Electrical ◆ ◆ ◆ ◆
Dimension ◆ ◆ ◆
Drawings Piping ◆ ◆ ◆
Wiring ◆ ◆
Capacity
Correction
◆ ◆
Performance Piping ◆ ◆
Airflow / ESP ◆ ◆
Sound Level ◆ ◆
Piping ◆ ◆
Wiring ◆ ◆
Installation Fundamentals ◆ ◆
How to use ◆
Operation
Controls ◆ ◆ ◆ ◆
Specification ◆ ◆ ◆
Accessories
Installation ◆ ◆
Characteristics Functions ◆ ◆
Test Operation ◆ ◆
Set-up, Troubleshooting ◆
Commissioning
& Service Flow Charts ◆
Replace Procedure ◆
86
VRV Application — Document Portfolio
Further information for the application of VRV is available in form of
Best Practice Guides. Hard copies are available and can also be obtained
online via daikincity.com
Best Practice Guides
Outdoor Unit Layout Guide Codes and Standards Daikin Zoning Kit
BPG-VRV4OD BPG-CS BPG-DZKAPP
Reference Guides
87
Regional training offered by Daikin Applications Engineering
ADVANCED LEVEL
» 2D FLOORPLAN ON WEBXPRESS » OUTSIDE AIR INTEGRATION
A live demonstration and practical Understanding the various methods
application of the 2D Floorplan of outside air integration with
function on WEBXpress and its VRV equipment
ability to integrate with AutoCAD » WATER-COOLED
» LCXPRESS SELECTION TOOL All aspects of W-VRV and water
A live demonstration and hands-on loop integration to ensure
selection of Rooftop Packaged units optimized design
plus an in-depth look at the various » AHU INTEGRATION
optional accessories available Correct application of the Daikin
» COLD CLIMATE EEV/Control boxes created to
Covers all the methods of integrate 3rd party AHU’s onto
supplemental heating used with VRV equipment
VRV in colder climates
88
About Daikin:
A WORLD LEADING
MANUFACTURER
OF HVAC PRODUCTS
FOUNDED
I N 1 9 2 4
OVER 100,000 DAIKIN VRV SYSTEMS
OPERATING
THROUGHOUT NORTH AMERICA
RESEARCH
DEVELOPMENT
DEDICATED TO INNOVATIVE TECHNOLOGIES
www.daikincity.com
PM-DVRV_09-22