F0131 How To Upgrade LCD Color Annunciator
F0131 How To Upgrade LCD Color Annunciator
IMPORTANT: The annunciator and panel software versions are not required to match.
You may install the Color Touchscreen LCD Annunciator if the Simplex 4007ES panel is at Rev. 3.02.07 or higher.
The Fire Alarm System Job-specific files (i.e. CFIG) are automatically updated on the annunciator.
INSTRUCTIONS:
In order to install the annunciator, the 4007ES Fire Alarm Panel system software must be at Rev. 3.02.07 or higher.
If upgrade is required, the How to Upgrade a 4007ES Panel job aid shows how to determine current panel software
versions and upgrade the panel software.
Prepare to install the annunciator by following instructions in the 4007ES Color Touch Screen Annunciator
Installation Manual (579-1172). Connect all ground, power and communication wiring, and set the address.
Keep in mind: The BOOTLOADER, KERNEL, and FILESYSTEM annunciator system software files can
ONLY be upgraded via USB memory stick. UPDATES TO THESE FILES ARE RARELY REQUIRED.
The REMOTEUI file may be upgraded via USB memory stick OR from the Main Panel via RUI.
Updating the REMOTEUI via USB takes about 1 minute, and through RUI it takes approximately 20 minutes.
During the update the annunciator is disabled.
Note: Job-specific files (i.e. CFIG) are automatically updated on the annunciator.
Follow the instructions in the How to Upgrade a 4007ES Panel job aid to download the current program to a USB memory stick.
Related documents:
Installation Manual: Color Touchscreen LCD Annunciator (579-1172)
4007ES and 4007ES Hybrid Fire Alarm Systems Programmer’s Manual (579-1167)
4007ES Operator’s Manual (579-1165)
More information: www.Simplex-fire.com and the Tyco LMS.