0% found this document useful (0 votes)
49 views4 pages

S Mod Modules - 3 1

The document describes plug-in I/O and communication modules for MOD 30ML, MODCELL, RetroPAK, and SteamPAK series controllers. The modules include analog inputs and outputs, current output, discrete inputs and outputs, relay outputs, and communication modules. All analog and digital I/O modules provide isolation between channels and from ground. The modules have features like short-circuit detection, failsafe settings, and maintaining signal values on CPU failure.

Uploaded by

Julián Camargo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views4 pages

S Mod Modules - 3 1

The document describes plug-in I/O and communication modules for MOD 30ML, MODCELL, RetroPAK, and SteamPAK series controllers. The modules include analog inputs and outputs, current output, discrete inputs and outputs, relay outputs, and communication modules. All analog and digital I/O modules provide isolation between channels and from ground. The modules have features like short-circuit detection, failsafe settings, and maintaining signal values on CPU failure.

Uploaded by

Julián Camargo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

MOD Series

Plug-In I/O and Communication Modules


• For MOD 30ML, MODCELL, RetroPAK,
and SteamPAK Series controllers
• Single-point input, output &
communication modules
• Individual point isolation
• Short-circuit & cut wire detection
• Microprocessor-based analog modules
hold failsafe settings & last good values
• Maintain signal value on main CPU
failure

The 2000 series plug-in modules are used with the Analog Modules
MOD 30ML 1800, MODCELL 2000, SLC RetroPAK,
• Multifunction current module, switch-
353 RetroPAK, MOD 30 RetroPAK, and the
SteamPAK family of controllers. The series includes selectable for current input with or without
analog inputs, current output, discrete input and transmitter power, or current output
output, relay output, and communication modules. • 3-wire, 100 ohm RTD or 2-wire, 1000 ohm
RTD input with upscale burnout detection
All analog and solid-state digital I/O modules are
fully isolated, both channel-to-channel and channel- • Thermocouple input with upscale burnout
to ground. This helps eliminate propagation of detection (Supports all standard thermocouple
noise and spikes on signal and power lines, and types; cold junction compensation provided)
protects the main board and adjacent I/O, when the • Volt/millivolt input
controller is properly installed. Each I/O module
includes short-circuit and cut-wire detection with Discrete Modules
associated diagnostics, and a digital flag that can be • Isolated discrete input (2.5-28Vdc, 4-16Vdc,
used to initiate alternate control logic such as safe 10-32Vdc, 12-32Vac, 35 to 60V ac/dc, 90 to
shutdown. Out-of-range and quality diagnostics are 140V ac/dc, 180 to 280V ac/dc)
also associated with each module. The RS-232 and
RS-485 Modbus modules provide address switches • Non isolated (contact sense) discrete input
and pull-up/pull-down bus resistor switches. The 2.2V to 24V dc
Instrument Communication Network (ICN) module • Isolated discrete output (5 to 60V dc, 5 to
provides address switches. The Ethernet Interface 200V dc, 12 to 140V ac, SPST, NO, 24 to
modules provide Modbus TCP using standard RJ45 280V ac, SPST, NO, 24 to 280V ac, SPST,
connectors. NC)
• Non isolated discrete output 25V, 50mA TTL
MOD 30ML accepts up to 11 plug-in modules to
complement its built-in I/O. MODCELL accepts • Dual Mechanical relay output
up to 32 plug-in modules. Modules can be a mix
of analog, discrete, and communication. The only Communication Modules
restriction on placement is the communication • Instrument Communications Network (ICN)
modules, which must be installed in dedicated
positions. If these postiions are not used for • RS-232 Modbus RTU
communications they may be used for inputs or • RS-485 Modbus RTU (4-wire)
outputs. • Ethernet Modbus TCP Interface

Specification Sheet
S-MOD-MODULES_3
Plug-In I/O and Communication Modules S-MOD-MODULES_3

Analog Input / Output Modules


Voltage 2001AZ, Model C Current 2014AZ
Range (0-100%) ±10V dc, ±100 mV dc Range (0-100%) 4 to 20mA
Low limit -10V, -110mV Low limit 0 mA
High limit +10V, +110 mV High limit 22 MA
Input resistance 1 Megohm Input resistance 100 ohms
Noise filter 3db at 15hz on 10 volt range Noise filter 3db a 5 Hz
3db at 1.5hz on 100mv range
Resolution 16 bits Resolution 13 bits
Sensitivity 0.4mv on 10 volt range Sensitivity 1.6µA
4µv on 100mv range
Accuracy 0.1% of range Accuracy 0.2%
Isolation 250V rms Isolation 250V rms
Maximum survivable ±300V dc / 250V ac Maximum survivable 50 mA dc
differential input differential input
Common mode rejection 100 db a 60 Hz minimum
Normal mode rejection 40 db a 60 Hz minimum

Current with 2-wire transmitter power 2014AZ Thermocouple 2013AZ, Model C1


Range 4 to 20mA Types B,E,J,K,N,R,S,T
Low limit 0 mA Range ±100 mVd dc
High limit 22 mA Low limit -10V, -110mV
Input resistance 100 ohms High limit +10V, +110 mV
Noise filter 3db a 5 Hz Input resistance 1 Megohm
Resolution 14 bits Noise filter 3db at 1.5hz
Sensitivity 1µA Resolution 16 bits
Accuracy 0.2% Sensitivity 4µV
Isolation 250V rms Accuracy 0.1% of range
Normal mode rejection 40 db a 60 Hz minimum Isolation 250V rms
Normal mode rejection 40 db a 60 Hz typical
RTD 2009AZ
Range Low Limit High Limit
2 wire 0-4000 ohms (1000 ohms nominal) 0 ohms 4200 ohms
3 wire 0-400 ohms (100 ohms nominal) 0 ohms 400 ohms
Input Resistance 100 ohms each wire
Noise Filter 3 db a 5 Hz
Resolution 2 wire: 0.08 ohms/count
3-wire: 0.008 ohms/count
Accuracy (absolute) 2 wire: ±2 ohms
3-wire: ±0.2 ohms
Isolation 250 V rms
Common Mode Rejection 100 db a 60 Hz minimum
Normal Mode Rejection 40 db a 60 Hz minimum
1
Note: if built-in analog input 1 on MOD 30ML is configured for thermocouple with cold junction compensation, the CJC value can be
used for any other thermocouples on the instrument.

Current Output 2014AZ


Range (0-100%) 4 to 20 mA
Low Limit 0 mA
High Limit 22 mA
Open Circuit Voltage 26 volts maximum
Isolation 250V rms
Resolution 12 bits
Sensitivity 5 uA
Accuracy ±0.2%
Load Limit 0 - 800 ohms
Fault Output user defined between 0 and 100%, or last value

2
Plug-In I/O and Communication Modules S-MOD-MODULES_3

Digital Input / Output Modules

Isolated Digital Inputs 2004AP


2004AP10… …100A …110A …120A …130A …140A …150A
10-32V dc
Input Voltage Range 2.5-28V dc 4-16V dc 35-60V ac/dc 90-140V ac/dc 180-280V ac/dc
12-32V ac
Low logic input 1V 1V 3V 9V 45V 80V
Maximum input current 30mA 45mA 25mA 6mA 11mA 6.5mA
Response time 1.5 ms 0.1 ms 5 ms 10 ms 20 ms 20 ms
1000 ohms dc
Input resistance 900 ohms 300 ohms 10K ohms 14K ohms 43K ohms
1500 ohms ac

Non-isolated Digital Inputs 2006AZ


Contact sense 5V/ 0.5 mA dc typical
Low logic input 0 a 0.65V dc to 50K ohms minimum
High logic input 2.2 a 24V dc to 50 ohms maximum
Maximum input current 2.5 mA dc
Response time 1 ms

Isolated Digital Output 2005AP


2005AP21… …100A …110A …120A …130A/140A
Output voltage range 5-60V dc 5-200V dc 12-140V ac 24-280V ac
Maximum output current 1A 0.55A 1A 1A
Response time 0.75 ms 0.75 ms 1/2 cycle 1/2 cycle

Non-isolated Digital Output 2007AZ


Output Voltage Range +5 a +24V dc
Maximum output current 100 mA dc
Maximum leakage current 100 µA dc
Response time 100 µs

Mechanical Relay Output 2011AZ


Types Two independent relays (NO/NO, NC/NC, NO/NC)
Contact load 3A a 250Vac or 30V dc per relay
Contact resistance 0.10 ohms maximum
Isolation 250V rms (contact to coil)
Response time 10ms
! IMPORTANT NOTE:
Communication Modules Care must be taken not to exceed maximum
ICN 2030NZ power consumption when adding I/O and
BAUD Rate 31.25K BAUD communication modules. See Ordering
Addresses 0 - 15 Information for individual module power
consumption.
Modbus RTU RS-232 2033NZ
BAUD Rate 300 to 38.4K BAUD MOD 30ML
Addresses 1 - 247 5 amps maximum
Output Swing ± 9V with ± 5V supply 1220mA used for base instrument
Receiver Input Levels ± 30V
Built-in outputs:
20mA output: 140mA
Modbus RTU RS-485 (4-wire) 2034NZ
50mA output: 410mA
BAUD Rate 300 to 38.4K BAUD
Transmitter power: 150mA
Addresses 1 - 247

Ethernet Interface 2040NZ and 2041NZ* MODCELL


Protocol Serial MODBUS RTU Slave AC Power 4.5 amps
Modbus Address 1 DC Power 3.0 amps
BAUD Rate up to 38400 BAUD

*2040NZ is used with MOD 30ML with Ethernet-style termination.


2041NZ is used with MODCELL and has a built-in Ethernet port for
an RJ45 cable connection.

3
Plug-In I/O and Communication Modules S-MOD-MODULES_3

ORDERING INFORMATION
Some modules require two positions on the MODCELL or MOD 30ML.
Maximum available positions:
MOD 30ML - 11
MODCELL - 32 (at least 2 positions must be used for a communication network for downloading and monitoring)
Positions Power Model No.
Analog Input & Output - isolated
Voltage Input (+/- 100mv, +/- 10V)1 1 80mA 2001AZ10101C
RTD Input (2-wire, 1000 ohm nominal resistance) 1 80mA 2009AZ10220B
RTD Input (3-wire, 100 ohm nominal resistance) Limited availability 2 80mA 2009AZ10130B
Thermocouple Input (supports type B,E,J,K,N,R,S,T and calibrated)1 1 80mA 2013AZ10101C
Current Input/Output - switch selectable (4-20mA / 0-20mA)1 1 2014AZ10101A
Selected as current input non-2 wire 75mA
Selected as current input 2-wire transmitter OR current output 250mA
Digital Input - Isolated
2.5 to 28V dc 1 12mA 2004AP10100A
4 to 16V dc 1 12mA 2004AP10110A
10 to 32V dc, 12 to 32V ac 1 12mA 2004AP10120A
35 to 60V ac/dc 1 12mA 2004AP10130A
90 to 140V ac/dc 1 12mA 2004AP10140A
180 to 280V ac/dc 1 12mA 2004AP10150A
Digital Output - Isolated
5 to 60V dc 1 12mA 2005AP21100A
5 to 200V dc 1 12mA 2005AP21110A
12 to 140V ac, SPST, NO 1 12mA 2005AP21120A
24 to 280V ac, SPST, NO 1 12mA 2005AP21130A
24 to 280V ac, SPST, NC 1 12mA 2005AP21140A
Digital Input - Nonisolated
2.2V to 24V dc (contains internal 5V supply for direct hardwire connection) 1 10mA 2006AZ10100A
Digital Output - Nonisolated
25V, 50mA TTL (open collector switch supports 5V TTL) 1 20mA 2007AZ10100A
Mechanical Relay Output - isolated
Dual SPST, NO/NO (2 outputs) 2 140mA 2011AZ10100A
Dual SPST, NC/NC (2 outputs) 2 140mA 2011AZ10110A
Dual SPST, NO/NC (2 outputs) 2 140mA 2011AZ10120A

COMMUNICATION MODULES
One maximum per MOD 30ML; up to 3 per MODCELL
Instrument Communications Network (ICN) 2 300mA 2030NZ10000B
ICN Termination Assembly for Flushmount MODCELL (1 per ICN network) 200mA 2030FZ00002A
ICN Termination Assembly for MOD 30ML (1 per ICN network) 200mA 2030FZ00001A
Serial Communications for Modbus RTU:
RS-232 2 180mA 2033NZ10000A
RS-485, 4-wire 2 180mA 2034NZ10000A
Ethernet Interface Module for MOD 30ML** 2 275mA 2040NZ10000A
Ethernet Interface Module for MODCELL 2 275mA 2041NZ10000A
**The MOD 30ML with Ethernet termination is shipped with the 2040NZ factory-installed. The module is listed here as a spare/
replacement part only.
Note 1: 2001AZ10101C is a direct replacement for 2001AZ10101B.
2013AZ10101C is a direct replacement for 2013AZ10101B.
2014AZ10101A is a direct replacement for 2002AZ10101B, 2012AZ10101B, and 2003AZ10101A.

The Company’s policy is one of continuous product


improvement and the right is reserved to modify the information
contained herein without notice.