Dear Partners,
Structural fire protection can save lives and maintain Experience from the construction industry and impul-
infrastructure in the event of a fire. Our comprehensive ses from our close exchange with customers and other
fischer FireStop product portfolio makes an important industry experts are continuously incorporated into the
contribution to this. The solutions effectively prevent further development of our FireStop portfolio. We are
the spread of fire, smoke and toxic gases and thus therefore always happy to receive your suggestions
far-reaching disasters in the event of fire. The assess- and ideas.
ments and approvals of our FireStop products in We hope you enjoy planning and installing our FireStop
accordance with European and international standards products!
give you peace of mind when using them.
For simple and complex applications in construction
projects, the fischer range has the right, easy-to-
assemble and efficient system solution. In this way,
penetrations of any media lines can be effectively
sealed off, curtain walls and VHF (ventilated curtain
walls) can be safely constructed and construction joints Christian Knoll
can be securely sealed. Managing Director fischer SystemTec
From planning and design to training and the installa-
tion of FireStop solutions on site, we also support you
with numerous services. As a strong partner for passive
fire protection, we are at your side with help and advice
in all construction phases until the successful comple-
tion of the project.
For effective sealing against fire, smoke and toxic
gases, the new FireStop catalogue provides you with an
overview of our current products and services. Further
information and details, such as installation instruc-
tions, calculation tables and an index for approvals and
tests, also support you in selecting the most suitable
solution.

3
Brand, safety and sustainability

“Whoever chooses fischer


receives more than a range of
safe products. The aim is to al-
ways develop the best solutions
for our customers across the
globe.” Besides the innovative products, this
predominantly concerns support that is
focused on the customer, and services
designed to improve customer benefit.

A brand and its


promise to perform.
Continious improvement Safety that connects. Decisive quality.
The fischer ProzessSystem (fPS) we ensure that we We don’t make any compromises when it comes to the
are adapting and optimising our processes in line with safety of our products. A whole host of our products are
customer requirements in a flexible manner and on a distinguished by comprehensive, up-to-date and inter-
continuous basis. Thus we are glad having been awar- national approvals. The fischer product range is well-
ded with the 1. place “Excellence in Operations” within positioned in all sectors of fixing technology – Steel,
the challenging contest “Factory of the Year”. Nylon and Chemical fixings. In awardwinning quality
which continues to impress both professional clients
and private customers with equal measure.

Award 2015
Exellence in
Operations

CE
International approvals characterise many of
our products.

4
fischer catalogue FireStop

Always on the pulse of time Our service to you We take responsibility


At fischer, innovation is more than just We are a reliable partner, one that will stand Our active environment management po-
a sum of the patents. We are open to at your side and address your individual licy means that we are helping to maintain
new things and are prepared for change requirements with advice and action: an intact environment for our generation
– always with the aim of off ering our · Our products range from chemical sys- and for those that follow. The environment
customers the greatest possible benefits. tems to steel anchors through to plastic management policy at the Tumlingen site
Over the years, our own development and anchors. has been certified in line with DIN EN ISO
production sites have been developing nu- · Competence and innovation through own 14001.
merous fixing solutions for the most wide- research, development and production. It fills us with particular pride that in 2020
ranging applications. Be it new production · Global presence and active sales service we have received the most important and
procedures or materials, such as renewa- in over 100 countries. largest award in Europe in the field of sus-
ble raw materials: We are carrying out the · Qualified technical consulting for econo- tainability: the German Sustainability Award
research for your safety and will continue to mical and compliant fastening solutions. - category large companies.
do so in the future. This gives us such great Also on-site at the construction site This was in recognition of our holistic
flexibility that we can even develop tailor- requested. approach and the strategic anchoring of
made customer solutions. This power to · Training sessions, some with accredita- our sustainability management. With our
innovate has seen fischer become market tion, at your premises or at the fischer greenline products we have launched the
leader in anchor technology and the fixing academy. first range of fixings on the market that is
industry. · Design and construction software for based on renewable raw materials to more
demanding applications. than 50%.

Deutscher
Nachhaltigkeitspreis 2020

SIEGER
Großunternehmen

Greenline assortment based on German Sustainability


50% regrowing raw materials Award

5
Innovations
that inspire professionals.
Content

Introduction 8 Chapter 1

FireStop Assortment 14 Chapter 2

Basics 64 Chapter 3

Service 74 Chapter 4

7
1
1Introduction 1

FireStop in practice 10

9
1

15

16

3
1

13
6

11

12
10

14

7
fischer catalogue FireStop

FireStop
Applications.

1 2 3

FCPS/FPC/FiAM/FFC RFS 640/FFB-ES FireStop Foam

5 6 7

FiPP/UFS 310/FiGM FiP FiAM (US)/FFRS/FFB-ES/RFS 640/FireStop Foam

9 10 11

RFS 640/UFS 310/FiGM/FCPS FiWS/FiPW/FFSC/FiAM FiWS/FFC

13 14 15

RFS 640/UFS 310/FiGM/FCPS FFB VS/FCFcL FBS/FBB

12
fischer catalogue FireStop

4
FiAM (US) Intumescent Acoustic Mastic 16, 19

FFRS Fire Rated Silicone Sealant 21

RFS 640 Rapid Fire Seal 24

FFB-ES Fire | Barr ElastoSeal 27


UFS 310/FiAM (US)/FiGM

UFS Universal FireStopping Sealant 29


8

FiGM Intumescent Graphite Mastic 32

FBS/FBB Foam Barrier System PLUS 35

FiPW Intumescent Pipe Wrap 38

FFSC/FCPS FiWS Intumescent Wrap Strip 40

12 FFC Fire Collar 43

FCID Plus Cast in Device 45

FiP Intumescent Pillows 47

FiPP Intumescent Putty Pad 49

FCID
FCPS Coated Panel System 51

16
FFSC FireStop Compound 53

FFB-VS VentiStop Cavity Barrier 56

FCFcl Cavity FireStop Clad 59

FireStop Foam 61
FCPS/FiAM/TDW

TDW Thermal Defense Wrap 63

13
2
2 2

FireStop Assortment
Intumescent Acoustic Mastic FiAM 16 Fire Collar FFC 43

Intumescent Acoustic Mastic FiAM US 19 Cast-in Device FCID Plus 45

Fire Rated Silicone Sealant FFRS 21 Intumescent Pillows FiP 47

Rapid Fire Seal RFS 640 24 Intumescent Putty Pad FiPP 49

Fire I Barr ElastoSeal FFB-ES 27 Coated Panel System FCPS 51

Universal FireStopping Sealant UFS 29 FireStop Compound FFSC 53

Intumescent Graphite Mastic FiGM 32 VentiStop Cavity Barrier - FFB-VS 56

Foam Barrier System PLUS 35 Cavity FireStop Clad FCFcl 59

Intumescent Pipe Wraps FiPW 38 FireStop Foam 61

Intumescent Wrap Strip FiWS 40 Thermal Defense Wrap TDW 63

15
Intumescent Acoustic Mastic FiAM · FireStop Assortment

Intumescent Acoustic Mastic FiAM


Flexible fire resistant acoustic mastic

Construction joint application Non combustible pipe application

Applications Advantages

· Metallic pipes: 13“ (325 mm) · Water based · Approved for infinite linear gap length
· Cable trays: 18“ x 2“ (450 x 50 mm) · Low VOC · Halogen and solvent free
· Cable bunches: 4“ (100 mm) · Movement capability ± 25 % · Paintable and excellent slump characte-
· Linear joints: flexible and rigid construc- · Excellent acoustic properties ristics
tion elements
· Joints between FCPS coated panel
system

Certificates Building materials Functioning

· Flexible wall constructions · FiAM is a one-part water-based acrylic

CE ·
·
Rigid floor and wall constructions
Masonry
emulsion.
· It has a fire resistance of up to 5 hours
· Concrete when used in construction joints and
ETA-20/1065 · Timber services in both vertical and horizontal
ETA-20/1064
· Steel applications.
EN ISO 10140
EN 1026 · FCPS System · When exposed to fire, it reacts to form
EN 1366-3 a highly insulative char that slows down
EN 1366-4
ASTM E 84 (UL 723) heat transfer and provides a barrier to
ASTM E 1966 (UL 2079) fire.
· It is suitably compatible in a variety of
materials, and is utilised within the FCPS
which is designed to seal large openings
in fire rated floors and walls.

Installation FiAM

16
Intumescent Acoustic Mastic FiAM · FireStop Assortment

Intumescent Acoustic Mastic FiAM



​ ​ Ap- Languages on the cartridge Contents Adapted for Sales unit
pro-
val
​ ​ ​ ​ ​ ​ ​
​ Item no. ETA ​ [ml] ​ [pcs]
Item ​ ​ ​ ​ ​ ​
FiAM 310 053011 ● DE, FR, EN, IT 310 – 1
FiAM 310 538152 ● DK, FI, SE, NO 310 – 1 2
FiAM 310 538150 ● TR, PT, ES, NL 310 – 1
FiAM 310 538151 ● PL, SK, CZ, HU 310 – 1
FiAM 600 056006 ● – 600 – 1
KPM 2 Plus 053117 – – – FiAM 310, FFRS 310, UFS 310, FiGM 310 1
Applicator gun 600 ml 097967 – – – FIAM 600 ml 1

Technical data

Base material Water-based acrylic


Relative gravity approx. 1.6 g/cm³
Skin-forming time approx. 10 min at 23 °C RH
Curing rate approx. 1.5 mm per 24 hours
Storage temperature + 5 °C to + 25 °C
Movement capability ±25 %
Shelf life 18 month
pH Value 8 - 9.5
Accoustic performance 63 dB
Yield per l/m depending on application
Colour white (grey on request)
European Technical Assessment ETA-20/1064, ETA-20/1065
CE marking 2531-CPR-CXO10321
Curing rate is dependent on substrate, air humidity and weather conditions.

B
A

Application data

Joint width Joint depth ml per linear metres*


A B
[mm] [mm]
60 5 300
50 5 250
30 5 150
15 5 75
5 5 25
*The consumption of the product depends on the application.

17
Intumescent Acoustic Mastic FiAM · FireStop Assortment

Substrate Max. joint width Fire ratings


Integrity rating Insulation rating
[mm] [min] [min]
Concrete/masonry 60 240 240
Concrete or masonry/steel 60 240 60
Concrete or masonry/timber 60 60 60
Concrete/masonry/head detail 60 240 240
For detailed information please refer to listed system.
2
Service type size Fire ratings
Integrity rating Insulation rating
[min] [min]
Copper/steel/metal pipes 35 - 159 mm diameter up to 240 up to 240
Loaded cable try 450 x 50 (tray) cables to 21 mm up to 120 up to 90
Single/bunched cables 21 - 100 mm diameter cables up to 120 up to 120

18
Intumescent Acoustic Mastic FiAM US · FireStop Assortment

Intumescent Acoustic Mastic FiAM US


General purpose fire resistant sealant designed for UL specific applications

Construction joint application Non combustible pipe application

Applications Advantages

· Linear joints: flexible and rigid construc- · Water based · Age resistant
tion elements with dynamic movement · Excellent acoustic properties · Smoke resistant
· Metallic pipes and ducts · Low VOC · Excellent adhesion
· Insulated metallic pipes · Halogen and solvent free · F-rating up to 3 hrs
· Conduits · Various applications with two products · T-rating up to 3 hrs
· Cable and cable bunches only
· Cable trays

Certificates Building materials Functioning

· Flexible wall constructions · The FiAM US is a one-part water based


· Rigid floor and wall constructions fire resistant sealant designed for a wide
· Masonry range of UL listed applications.
· Concrete · The FiAM US can be used in construction
· Steel joint and service penetration applicati-
ASTM E 84 (UL 723) ons.
ASTM E 814 (UL 1479)
ASTM E 1966 (UL 2079)
· The FiAM US can be used in both vertical
and horizontal orientation and can be
used in conjunction with the FiWS for a
wide range of combustible services.

Installation FiAM US

19
Intumescent Acoustic Mastic FiAM US · FireStop Assortment

Technical data

​ ​ Languages on the cartridge Contents Adapted for Sales unit
​ ​ ​ ​ ​ ​
​ Item no. ​ [ml] ​ [pcs]
Item ​ ​ ​ ​ ​
FiAM US 546487 DE, EN, ES, TR 310 – 1
FiAM US 19 liter bucket 554934 – – – 1
KPM 2 Plus 053117 – – FiAM 310, FFRS 310, UFS 310, FiGM 310 1
2
Technical data

Base material Water-based elastomeric


Skin-forming time approx. 20 - 30 min
Curing rate 3 to 4 weeks at 25 °C
Storage temperature + 2 °C to + 49 °C
Movement capability up to 33 %
Shelf life up to 36 month
pH Value 7-8
Accoustic performance 65 dB
Surface burning characteristics Flame spread: 10 - Smoke: 10
Colour red

B
A

Application data

Joint width Joint depth ml per linear metres*


A B
[mm] [mm]
1“ (25 mm) 5/8“ (16 mm) 400
1“ (25 mm) 1/2“ (13 mm) 325
2“ (50 mm) 1/4“ (6 mm) 300
3-1/2“ (90 mm) 1/4“ (6 mm) 540
3/4“ (20 mm) 5/8“ (16 mm) 320
*The consumption of the product depends on the application.

20
Fire Rated Silicone Sealant FFRS · FireStop Assortment

Fire Rated Silicone Sealant FFRS


Elastomeric fire resistant sealant

Construction joint application Vertical construction joint application

Applications Advantages

· General construction joints in floor to · Excellent acoustic properties · Halogen and solvent free
floor, wall to wall, floor to wall and head of · Primerless adhesion to most substrates · Excellent slump characteristics
wall up to 2.36‘‘ (60 mm) · Approved for infinite linear gap length · Movement capability ± 7.5 %
· Internal and external applications

Certificates Building materials Functioning


EN ISO 10140 · Concrete · FFRS is a one part silicone based sealant

CE
EN 1026
EN 1366-4 · Masonry that can provide up to 5 hours fire resis-
· Steel tance when used in construction joints.
ETA-20/1102 · Timber · It provides primerless adhesion to a
wide range of porous and non-porous
substrates.

Installation FFRS

21
Fire Rated Silicone Sealant FFRS · FireStop Assortment

Technical data

​ ​ Ap- Languages on the cartridge Contents Adapted for Sales unit
pro-
val
​ ​ ​ ​ ​ ​ ​
​ Item no. ETA ​ [ml] ​ [pcs]
Item ​ ​ ​ ​ ​ ​
FFRS White 310 ml 512374 ● DE, FR, EN, IT 310 – 1
2 FFRS White 310 ml 538140 ● DK, FI, SE, NO 310 – 1
FFRS White 310 ml 538138 ● TR, PT, ES, NL 310 – 1
FFRS White 310 ml 538139 ● PL, SK, CZ, HU 310 – 1
KPM 2 Plus 053117 – – – FiAM 310, FFRS 310, UFS 310, FiGM 310 1

Technical data

Curing system Alcoxy


Relative gravity 1.17 kg/m³
Skin-forming time approx. 5 - 10 min (at 25 °C and 50% relative humidity)
Tack free after approx. 20 min
Curing rate approx. 2 to 3 mm per 24 hours (at 25 °C and 50 % relative humidity)
Shore A hardness 25
Extrudability 55 (standard MNRPS 495A 3 mm/3 bars)
Movement capability ±7.5 %
Shelf life up to 12 month
European Technical Assessment ETA-20/1102
Colour white (grey and black on request)
Elastic recovery > 90 %
Accoustic performance 38 dB
The cured sealant is unaffected by water, dilute acids and alkalis, soap and household detergents. Certain solvents may soften and swell the cured rubber on prolonged contact.

B
A

Application data

Joint width Joint depth ml per linear metres*


A B
[mm] [mm]
60 5 300
50 5 250
30 5 150
15 5 75
5 5 25
*The consumption of the product depends on the application.

22
Fire Rated Silicone Sealant FFRS · FireStop Assortment

Substrate Max. joint width Depth of sealing Fire ratings


Integrity rating Insulation rating
[mm] [mm] [min] [min]
Masonry/masonry 60 5 240 60
Masonry/masonry 12 6 240 120
Masonry/masonry 60 30 240 90
Masonry/masonry 60 5 240 240
Masonry/masonry 50 25 240 240
Masonry/plasterboard 25 20 120 120 2
Steel/masonry 60 5 240 60
Wood/masonry 60 5 180 180
For detailed information please refer to listed system.

23
Rapid Fire Seal RFS 640 · FireStop Assortment

Rapid Fire Seal RFS 640


Rapid fire resistant sealant

Curtain wall application Head of wall application

Applications Advantages

· Curtain wall/slab edge: 8“ (200 mm) · Water based · Spray or brush applied
· Head of wall: 4“ (100 mm) · Flexible set · Excellent smoke seal
· General construction joints: 8“ (200 mm) · Contains mould growth inhibitor · Water resistant
· Cable tray: 24“ x 4“ (600 mm x 100 mm) · Freeze - thaw capabilities · Asbestos and solvent free
· Steel pipes: 8“ (200 mm) · Paintable · Can be used for internal applications and
· Accelerated age and humidity tested for conditions where dynamic movement
· Low VOC may occur.

Certificates Building materials Functioning

· Flexible wall constructions · RFS 640 is a spray grade one-part


· Rigid floor and wall constructions water-based, fire rated sealant, which
· Flexible wall has been designed to provide smoke and
· Masonry fire protection on construction joints and
· Concrete service penetrations in both vertical and
ASTM E 84 (UL 723) horizontal applications.
ASTM E 814 (UL 1479)
· Provides up to 3 hours fire rating (also in
ASTM E 1966 (UL 2079)
ASTM E 2307 accordance with ASTM E 2307).
· Meeting the new requirements of ASTM E
1399, RFS 640 has been cycled tested up
to 500 times.
· Can be used for internal applications and
for conditions where dynamic movement
may occur.
· RFS 640 has also been tested at positive
pressure with a minimum 0.01in. (2.5
mPa) water i.a.w UL 2079 test standards.

24
Rapid Fire Seal RFS 640 · FireStop Assortment

Installation RFS 640 - Joint application

Installation RFS 640 - Penetration application

Installation RFS 640 - Air duct application

Technical data

​ ​ Contents Colour Sales unit
​ ​ ​ ​ ​
​ Item no. [l] ​ [pcs]
Item ​ ​ ​ ​
RFS 640 516539 19 red 1

Technical data

Base material Water-based


Density approx. 1.25 g/cm³
Skin-forming time approx. 30 - 45 min
Curing time approx. 5 - 7 days
Storage temperature + 2 °C to + 49 °C
Movement capability up to 50 %
Water resistant depending on individual system
Shelf life 36 months month
pH Value 7-8
Accoustic performance 65 dB
Surface burning characteristics Flame spread: 0 - Smoke: 0
Skin-forming and curing time is dependant on substrate, air humidity and weather conditions.
Movement capability depends on UL listed system and configuration.
Water resistant in accordance with UL 2079.

25
Rapid Fire Seal RFS 640 · FireStop Assortment

Application data

Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail


[inch] [mm] [mm]
0.25 6 198 1,325 89 404
0.50 13 164 1,099 74 335
0.75 19 141 941 63 287
1.00 25 124 830 56 253
1.25 32 109 731 49 223

2 2.00 51 82 548 37 167


4.00 102 49 328 22 100
6.00 152 35 233 16 71
8.00 203 27 180 12 55
The above table provides an approx. yield for a coverage of 1/16“ (1.5 mm) Wet Film Thickness (WFT) with a 1/2“ (12.5 mm) overlap. Application shall be as per listed system.

26
Fire I Barr ElastoSeal FFB-ES · FireStop Assortment

Fire I Barr ElastoSeal FFB-ES


Elastomeric fire resistant coating for construction joint and assemblies

Elecrtical application Curtain wall application

Applications Advantages

· Linear joints in construction elements up · Openings up to 20“ (500 mm) wide · Air permability
to 20“ (500 mm) wide · Movement capabilities of 25 % · Acoustic performance
· Floor to floor · Working temperature between -10 °C and · 80 kg/m³ stone wool base
· Wall to wall 95 °C · 2.5 mm WFT required
· Head of wall · Can be spray or brush applied
· Bottom of wall
· Curtain wall
· Cabel / cabel trays
· Metallic pipes

Certificates Building materials Functioning

· Flexible wall constructions · FFB-ES is a one-part water-based acrylic

CE ·
·
Rigid floor and wall constructions
Concrete
coating, which has been designed to
provide smoke and fire protection on
· Masonry construction joints in both vertical and
ETA-20/1103 horizontal applications.
ETA-20/1101
· Developed for use on 80 kg/m³ stone
EN ISO 10140
EN 1026 wool base.
EN 1027 · Once applied, it prevents the passage of
EN 1364-4
EN 1366-3 fire and smoke and can contribute to the
EN 1366-4 acoustic value of a structure between fire
rated compartments giving a fire resis-
tance for up to EI 240.

Installation FFB-ES

27
Fire I Barr ElastoSeal FFB-ES · FireStop Assortment

Technical data

​ ​ Ap- Content Sales unit
pro-
val
​ ​ ​ ​ ​
​ Item no. ETA [kg] [pcs]
Item ​ ​ ​ ​
FFB-ES/White 520753 ● 20 1
2 FFB-ES/Grey 520755 ● 20 1
FFB-ES/Red 520756 ● 20 1

Technical data

Description Water-based, flexible acrylic coating


Density 1.25 - 1.3 g/cm³
Coating thickness 2.5 mm nominal, wet film thickness
Sealant coverage 2.8 kg/m², 2.24 l/m²
Fire resistance EN1366-4:2006 120 EI
Accoustic performance -
Air permeability 600 PA positive and negative pressure and tested to EN1026
Water permeability 450 PA positive pressure and tested to EN1027
Spraying guidance -
Storage temperature - 5 °C to +25 °C
Colour -
Shelf life from date of manufacture 18 month
European Technical Assessment ETA-20/1101, ETA-20/1103
CE marking 2531-CPR-CXO10324

Application data

Joint width Joint width Ft/gallon Ft/pail LM/gallon LM/pail


[inch] [mm] [mm]
0.25 6 119 800 54 244
0.50 13 99 683 44 202
0.75 19 85 567 38 173
1.00 25 73 492 33 150
1.25 32 66 443 30 135
2.00 51 49 328 22 100
4.00 102 31 207 14 63
6.00 152 22 148 10 45
8.00 203 16 108 7 33
The above table provides an approx. yield for a coverage of 2.5 mm Wet Film Thickness (WFT) with a 12.5 mm overlap. Application shall be as per listed system.

28
Universal FireStopping Sealant UFS · FireStop Assortment

Universal FireStopping Sealant UFS


Universal firestopping sealant which is suitable for metallic, non-metallic services and construction joints

Electrical application Combustible and non combustible pipes application

Applications Advantages

· Metallic services: steel and cast iron 20“ · Water based · Paintable
(500 mm) - copper 6“ (150 mm) · Flexible set · Accelerated age and humidity tested
· Non metallic service: PVC 2“ (51 mm · Contains mould growth inhibitor · Low VOC
open) 3“ (75 mm closed) · Freeze - thaw capabilities · Excellent acoustic properties
· Insulated service: 20“ (500 mm)
· Construction joints: 4“ (100 mm)
· HVAC 100“ (2500 mm)
· Cable bunches 4“ (100 mm): busway 27“
(686)

Certificates Building materials Functioning

· Wall constructions - linear joints · UFS is a one-part water-based intume-


· Floor constructions - linear joints scent sealant which is used for sealing
· Flexible wall construction joints and service pene-
· Masonry tration in both vertical and horizontal
· Concrete applications.
ASTM E 84 (UL 723) · Up to 4 hours of fire rating can be provi-
ASTM E 814 (UL 1479)
ASTM E 1966 (UL 2079)
ded.
· It exhibits excellent slump characte-
ristics, is easy to apply and cures to a
flexible set. It is suitable for internal ap-
plications and conditions where dynamic
movement may occur.
· UFS can be used for most application
properties.

Installation UFS - Cabel application

29
Universal FireStopping Sealant UFS · FireStop Assortment

Installation UFS - Pipe application

Installation UFS - Penetration application

Installation UFS - Air duct application

Technical data

​ ​ Languages on the cartridge Contents Contents Adapted for Sales unit
​ ​ ​ ​ ​ ​ ​
​ Item no. ​ [ml] [l] ​ [pcs]
Item ​ ​ ​ ​ ​ ​
UFS 310 5165381) DE, FR, EN, NL 310 – – 12
UFS 19 liter bucket 533889 – – 19 – 1
KPM 2 Plus 053117 – – – FiAM 310, FFRS 310, UFS 310, FiGM 310 1
1) Curing rate is dependant on substrate, air humidity and weather conditions.Movement capability depends on UL listed system and configuration.

Technical data

Base material Water-based elastomeric


Density approx. 1.31 g/cm³
Skin-forming time approx. 20 - 30 min
Curing rate approx. 4 mm in 72 hours
Storage temperature + 2 °C to + 49 °C
Movement capability up to 50 %
Intumescent activation 190 °C to 593 °C °C
Shelf life up to 36 month
pH Value 6.5 - 7
Surface burning characteristics Flame spread: 0 - Smoke: 0
Colour red
Curing rate is dependant on substrate, air humidity and weather conditions.
Movement capability depends on UL listed system and configuration.

30
Universal FireStopping Sealant UFS · FireStop Assortment

Application data

Services Fire ratings (minutes)


Types Sizes Integrated rating Insulation rating
PVC/CPVC closed pipe systems 3" (75 mm) 120 120
PVC/CPVC open pipe systems 2" (50 mm) 120 120
Steel and cast iron pipes 20" (508 mm) 180 0
Copper pipes 6" (152 mm) 180 0
Insulated services 20" (508 mm) 120 120 2
Construction joints 4" (100 mm) 120 120
HVAC 100" (2,500 mm) 120 120
Cable bunches 4" (100 mm) 120 120
Cable tray/ladder 24" (600 mm) 120 45
Bus tar 27" (686 mm) 120 45
For detailed information please refer to listed system.

31
Intumescent Graphite Mastic FiGM · FireStop Assortment

Intumescent Graphite Mastic FiGM


High performance intumescent graphite fire resistant mastic

Electrical application Application of metallic pipes

Applications Advantages

· Metallic pipes: 6“ (159 mm) · Low VOC · Halogen and solvent free
· Non-metallic pipes: 5“ (125 mm) · Excellent acoustic properties · Excellent slump characteristics
· Cable bunches: 1“ (21 mm)
· Insulated service: 6“ (159 mm)
· Construction joints: 1“ (25 mm)
· Mixed services

Certificates Building materials Functioning

· Concrete · FiGM is a one-part water-based flexib-

CE ·
·
Masonry
Steel
le acrylic emulsion containing a high
pressure intumescent graphite, which is
· Timber used to seal service penetrations in both
ETA-20/1105 vertical and horizontal applications.
EN ISO 10140 · It can expand up to 20 times its own volu-
EN 1026
EN 1366-3
me and cures to form a resilient, flexible
fire seal.

Installation FiGM - Cabel application

32
Intumescent Graphite Mastic FiGM · FireStop Assortment

Installation FIGM - Pipe application

Installation FIGM - Penetration application

Technical data

​ ​ Ap- Languages on the cartridge Contents Adapted for Sales unit
pro-
val
​ ​ ​ ​ ​ ​ ​
​ Item no. ETA ​ [ml] ​ [pcs]
Item ​ ​ ​ ​ ​ ​
FiGM 310 ml 508765 ● DE, FR, EN, IT 310 – 1
FIGM 310 ml 538147 ● TR, PT, ES, NL 310 – 1
FiGM 310 ml 538148 ● PL, SK, CZ, HU 310 – 1
FiGM 310 ml 538149 ● DK, FI, SE, NO 310 – 1
KPM 2 Plus 053117 – – – FiAM 310, FFRS 310, UFS 310, FiGM 310 1

Technical data

Base material Aqueous thixotropic paste


Density approx. 1.3 g/cm³
Curing rate 1.7 mm per 24 hours dependent on conditions
Storage temperature + 5 °C to + 30 °C
Tack free after 30 min
Curing system Water-based
UV resistance good
Expansion up to 20 times
Skin-forming time 15 min (at 25 °C and 50% relative humidity)
Accoustic performance 64 dB
Shelf life up to 12 month
European Technical Assessment ETA-20/1105
CE marking 2531-CPR-CXO10327
Chemical and water resistant -
Colour black

33
Intumescent Graphite Mastic FiGM · FireStop Assortment

Application data

Services Fire ratings (minutes)


Types Sizes Integrated rating Insulation rating
PVC pipe Up to 125 mm diameter 120 120
HDPE pipe Up to 90 mm diameter 120 120
ABS pipe Up to 90 mm diameter 120 120
Insulated copper pipe Up to 159 mm diameter + up to 32 mm insulation 120 120
2 Cables Up to 21 mm diameter x bunches 10 max. 120 120
Mixed Up to 63 mm diameter HDPE + 21 mm diameter cables x 10 120 120
For detailed information please refer to listed system.

34
Foam Barrier System PLUS · FireStop Assortment

Foam Barrier System PLUS


FireStop Foam and FireStop Block for use in a System. Or individually. ETA approved and UL listed applications.

Electrical application Mixed penetration application

Applications Advantages

· Metallic pipes up to 8“ (203 mm) · Easy access for difficult to reach ope- · Resistant to damp
· Insulated metallic pipes nings · Re-enterable and repairable
· Conduits · Low VOC · Excellent adhesion
· Cable and cable bunches · Various applications with two products · No backing material required
· Cable trays only · F-rating / E-Integrity rating up to 2 hours
· Mixed multiple penetrations · Age resistant · T-rating / EI-Insulation rating up to 2
· Smoke resistant hours

Certificates Building materials Functioning

· Concrete (wall and floors) · FBS is a two component polyurethane

CE · Masonry
· Flexible wall
expanding sound, smoke and firestop-
ping seal for hard to reach locations
which expands to up to 5 times of its
ETA-17/0845 volume.
EN 1366-3 · FBB are highly elastic mouldable blocks.
ASTM E 84 (UL 723)
· FIB is a glass fiber reinforced intume-
ASTM E 814 (UL 1479)
EN 13501-1 scent wrap to enhance the insulation
value of ETA applications.
· Tested in accordance with ASTM E 814
(UL 1479), ASTM E84 (UL 723) as well as
EN 1366-3, EN 13501 the Barrier System
PLUS allows an easy application which
saves time and costs on site.

35
Foam Barrier System PLUS · FireStop Assortment

Installation FBS

FIRE STOP
2

Installation FBB

Technical data

​ ​ Ap- Languages on the cartridge Contents Dimensions Sales unit
pro-
val
​ ​ ​ ​ ​ ​ ​
​ Item no. ETA ​ [ml] [mm] [pcs]
Item ​ ​ ​ ​ ​ ​
FBS-UL 544079 – – 380 – 6
FBB-UL FireStop Block 544083 – – – 200 x 130 x 60 12
FBS-EN 544084 ● DE, FR, EN, IT 380 – 6
FBS-EN 544085 ● DK, FI, SE, NO 380 – 1
FBS-EN 544086 ● PL, SK, CZ, HU 380 – 1
FBS-EN 544087 ● TR, PT, ES, NL 380 – 1
FBB-EN FireStop Block 544088 ● – – 200 x 144 x 60 4
FIB Insulating Bandage 544089 – – – 5000 x 150 1
FFBD Foam Barrier Dispenser 544090 – – – – 1

Technical data FBS-UL

Temperature resistance ≤ 80 °C
Yield ≤ 1.9 l
Curing time approx. 90 s
Shelf life 12 month
Storage temperature + 5 °C to + 30 °C
Colour reddish brown

Technical data FBS-EN

Density ≥ 215 kg/m³


Temperature resistance ≤ 80 °C
Construction material class B2 as per DIN 4102
Yield ≤ 2.1 l
Curing time approx. 90 s
Shelf life 12 month
Storage temperature + 5 °C to + 30 °C
Accoustic performance 43.5 - 66 dB
Colour reddish brown

36
Foam Barrier System PLUS · FireStop Assortment

Technical data FBB-EN

Temperature resistance ≤ 80 °C
Construction material class B2 as per DIN 4102
Accoustic performance 45.5 - 68
Colour reddish brown

Technical data FBB-UL


2
Temperature resistance ≤ 80 °C
Colour reddish brown

Application data - UL

Blank opening Metallic pipes and conduits Cables/Cable trays Insulated metall pipes Mixed penetrations
Max. possible sizes of Max 32 x 32 inch Max 8 inch (203 mm) Max 24 inch (610 mm) wide Max 8 inch (203 mm) dia- see listed system
penetrations (813 x 813 mm) diameter by max. 6 inch (152 mm) meter with 1 inch (25 mm)
deep cable tray insulation
Barrier System PLUS UL C-AJ-0158, W-L-0052 C-AJ-1669 C-AJ-3341, C-AJ-4110, C-AJ-5383 C-AJ-8260, C-AJ-8261
W-L-4091

Application data - ETA

Seal thickness 144 mm Seal thickness 200 mm


Cable / Cable Trays and Ladders Sheated electrical cables up t o 80 mm Wall: E120/EI60 - Floor: EI60 Wall/Floor: E120/EI90
Tied cable bundles up t o 100mm Wall: E120/EI60 - Floor: EI60 Wall/Floor: E120/EI90
Non-sheated electrical cables Wall: E120/EI45 - Floor: E60/EI30 Wall/Floor: E120/EI60
Condiuts Conduits/pipes of plas tic up to a max. diameter of 40 mm Wall: E120/EI60 - Floor: E60/EI30 Wall/Floor: EI120
Pipes Insulated metal pipes with max. diameter of 54 mm Wall: E120/EI90 - Floor: EI60 Wall/Floor: E120/EI90
Non-insulated metal pipes with max. diameter of 28 mm Wall: E120/EI60 - Floor: EI60 Wall/Floor: E120/EI90
Insulated metal pipes with AF/Armaflex insulation up to 88.9 mm diameter Wall: E120/EI90 - Floor: EI60 Wall/Floor: EI120
Combustible pipes with max. 50 mm diameter Wall: EI120 - Floor: EI60 Wall/Floor: EI120
For detailled information please refer to ETA 17/0845. Remaining space around penetrants can be filled with FBB FireStop Block.

37
Intumescent Pipe Wraps FiPW · FireStop Assortment

Intumescent Pipe Wraps FiPW


An intumescent single or endless wrap for sealing flammable pipes

Combustible pipes floor application Combustible pipe wall application

Applications Advantages

· Non-metallic pipes · Efficient and effective for sealing of pipe · Economical solution
· Polyvinyl Chloride PVC openings in floors and walls · Up to 2 hours fire resistance
· Chlorinated Polyvinyl Chloride cPVC · Easy to fit · Asbestos and halogen free
· Medium-density Polyethylene MDPE · Moisture resistant · Available on a roll for more flexibility in
· High-density Polyethylene HDPE · No mechanical fixing required pipe diameters
· Acrylonitrile Butadiene ABS

Certificates Building materials Functioning

Test Building Materials Print · FiPW is a flexible composite strip, which

CE is composed of thermoplastic compo-


nent containing intumescent graphite in a
synthetic compound and enclosed in an
ETA-21/1061 outer polyethylene cover.
EN 1366-3 · Can also be used as a cast-in solution.
For large openings, use in conjunction
with FCPS or FFSC.

Installation FiPW

38
Intumescent Pipe Wraps FiPW · FireStop Assortment

Installation FiPW with FCPS

FIRE STOP
2

Technical data

​ ​ Ap- Fits pipe-Ø Fire rating Sales unit
pro-
val
​ ​ ​ [mm] [hours] ​
​ Item no. ETA ​ ​ [pcs]
Item ​ ​ ​ ​ ​
FiPW E / 2 mm (25 meter roll) 539608 ● 30 - 250 up to 2 1

Technical data

State solid
Colour black inner component in outer foil carrier
Odour odourless
Density 1.3 kg/m³
Expansion ratio 1 : 25
Significant expansion occurs at temperature > 180 °C
Storage temperature + 5 °C to + 35 °C
Thickness 2 mm
European Technical Assessment ETA-21/1061
CE marking 2531-CPR-CXO10326

Application data

Configuration for up to 120 min.


Outer pipe diameter No. wraps Thickness Length per stacks
[mm] [mm]
40 1 2 138
55 2 4 383
63 2 4 434
75 2 4 509
82 2 4 553
90 3 6 923
110 3 6 1112
125 4 8 1696
160 4 8 2136
200 5 10 3331
250 7 14 5846

39
Intumescent Wrap Strip FiWS · FireStop Assortment

Intumescent Wrap Strip FiWS


Universal intumescent wrap strip for sealing combustible services

Universal Collar 2 Combustible pipe application

Applications Advantages

· Non-metallic service: PVC 14“ (355 mm), · Efficient and effective for sealing of pipe · No mechanical fixing required
cPVC 8“ (203 mm), ABS 6“ (152 mm), openings in floors and walls · Economical solution
FRPP 4“ (102 mm) · Easy to fit · Up to 4 hours fire resistance
· Insulated service: Steel 10“ (254 mm), · Moisture resistant · Asbestos and halogen free
Iron 10“ (254 mm), Copper 4“ (102 mm), · Freeze-thaw characteristics
Glass fibre 3“ (75 mm), AB/PVC flexible
foam 1“ (25 mm)
· Cable bunches: 3“ (76 mm)

Certificates Functioning

· FiWS is a flexible, intumescent graphite-


based synthetic compound strip, which
has been designed to be installed in both
vertical and horizontal applications.
· FiWS has been developed as a PRE or
ASTM E 814 (UL 1479) cast-in FireStop solution, and has been
ASTM E 84 (UL 723)
designed to work with the fischer Uni-
versal Collar for retro fitting or surface
mounted applications.
· For large openings, the FiWS can be used
in conjunction with the FFSC.

40
Intumescent Wrap Strip FiWS · FireStop Assortment

Installation FiWS with FFSC

FIRE STOP

Technical data

​ ​ Dimensions Sales unit
​ ​ BxLxH ​
​ Item no. ​ [pcs]
Item ​ ​ ​
FiWS-2 531397 50 mm x 6 mm x 5.48 m / 2˝x 1/4˝ x 18˝ 1
Universal Collar 2 536053 51 mm x 15 m / 2“ x 50 ft 1

Technical data

State solid
Odour odourless
Density approx. 1.3 kg/m³
Expansion ratio 1 : 40
Significant expansion occurs at temperature > 190 °C
Max. recom. pipe-Ø < 355 mm
Flame spread (ASTM E 84 - UL723) 5
Smoke index (ASTM E 84 - UL723) 5
Colour black

41
Intumescent Wrap Strip FiWS · FireStop Assortment

2
Both sides of the wall

Botttom of floor

Application data

FiWS - typical configuration


Pipe diameter No. of layers Length per stacks
[mm] [mm]
50 1 200
75 2 580
100 2 740
150 3 1640
200 4 2890
305 4 4210

42
Fire Collar FFC · FireStop Assortment

Fire Collar FFC


Collar for sealing a wide range of combustible pipes where passing through fire rated walls and floors

Combustible pipe floor application Combustible pipe wall application

Applications Advantages

· Non-metallic pipes like PVC, HDPE, · Easy retrofit at any time · Pre-fixed attachment lugs
MDPE, ABS of various sizes through fire · Water resistant · Fold back tag for secure fixture around
rated walls and floor assemblies · No minimum annular service required pipe

Certificates Building materials Functioning

· Flexible and rigid wall constructions · FFC is a powder coated cylindrical steel

CE · Solid concrete floors


· Hollow precast floors
sleeve, which contains a heat reactive
graphite-based intumescent material
that expands during fire.
ETA-20/1066 · Designed to be securely fitted around the
EN 1366-3 pipe and held in position with a retaining
bolt.
· Any gaps up to 10 mm around FFC should
be backfilled with FiAM or larger annular
space should be closed with FCPS or
FFSC.

Installation FFC with FCPS

43
Fire Collar FFC · FireStop Assortment

Technical data

​ ​ Ap- Fits pipe-Ø Sales unit
pro-
val
​ ​ ​ [mm] ​
​ Item no. ETA ​ [pcs]
Item ​ ​ ​ ​
FFC 2/30-32 052456 ● 30 - 250 1
FFC 2/38-40 052480 ● 38 - 40 1
FFC 2/55 052481 ● 55 1
FFC 2/63 052482 ● 63 1
FFC 2/75 052483 ● 75 1
FFC 2/82 052486 ● 82 1
FFC 2/90 052487 ● 90 1
FFC 2/110 052488 ● 110 1
FFC 2/125 052489 ● 125 1
FFC 2/160 052500 ● 160 1
FFC 2/200 052501 ● 200 1

Technical data

State solid
Odour odourless
Fire resistance up to 4 hours
Available sizes > 30 mm and max up to 200 mm
Significant expansion occurs at temperature > 180 °C
Storage temperature N/a
Shelf life N/a month
Colour black inner component in outer foil carrier
European Technical Assessment ETA-20/1063
CE marking 2531-CPR-CXO10320

44
Cast-in Device FCID Plus · FireStop Assortment

Cast-in Device FCID Plus


Fast and efficient solution for forming service penetrations through concrete floors

FCID Plus within reinforced concrete floor Installed pipe through FCID Plus device

Applications Advantages

· Sealing and firestopping PVC and HDPE · Quick installation · Cost saving
pipes up to 6˝ (150 mm) · Watertight seal · Reduced foot plate
· Forms holes up to 8˝ (200mm) thick · Higher tolerance · Eco-friendly extension tube
concrete floors. In combination with · Easily extendable · Closer proximity positioning
extension pieces up to additional 4“ · Wider base for further connections · Free of asbestos, solvents and any hazar-
(100mm) possible. · No further collars or wraps required dous ingredients.
· FCID Plus creates recesses in slabs for · Reduce working at heights
lower positioning of soil
· Manifold units in wet room applications

Certificates Building materials Functioning


ASTM E 814 (UL 1479) · Reinforced cast concrete slabs · FCID Plus is a pass through system,
· Some prefabricated slab systems (sub- which is constructed from a highly resi-
ject to design) lient polypropylene material and contains
a powerful intumescent graphite band.
· The FCID Plus is rugged enough to with-
stand the force and load of a concrete
pour, yet lightweight enough to permit
easy placement and handling.

Installation FCID Plus

45
Cast-in Device FCID Plus · FireStop Assortment

Technical data

​ ​ Fits pipe-Ø Height H Sales unit
​ ​ [mm] H ​
​ Item no. ​ [mm] [pcs]
Item ​ ​ ​ ​
FCiD Plus 50 566285 50/2“ 200/8“ 12
FCiD Plus 75 566286 75/3“ 200/8“ 12
FCiD Plus 100 566287 100/4“ 200/8“ 12
2
FICD Plus 150 566288 150/6“ 200/8“ 6
FCiD Plus 50 extension 566289 50/2“ 100/4“ 6
FCiD Plus 75 extension 566290 75/3“ 100/4“ 6
FCiD Plus 100 extension 566291 100/4“ 100/4“ 6
FCiD Plus 150 extension 566292 150/6“ 100/4“ 6
FCiD Plus 50 Deck adapter 566293 50/2“ – 6
FCiD Plus 75 Deck adapter 566294 75/3“ – 6
FCiD Plus 100 Deck adapter 566295 100/4“ – 6
FCiD Plus 150 Deck adapter 566296 150/6“ – 6

Technical data

State solid
Odour odourless
Shell material Polyethylene
Fire resistance up to 4 hours - BS 476: Part 20 and AS 1530: Part 4
Extension or reduction in height possible Yes
Standard flange width min 154 mm and max 254 mm
Significant expansion occurs at temperature > 190 °C
Shelf life N/a month
Colour black

46
Intumescent Pillows FiP · FireStop Assortment

Intumescent Pillows FiP


FireStop solution for temporary and permanent service penetrations in vertical and horizontal applications

Electrical floor application Electrical wall application

Applications Advantages

· Metal pipes · Approved as permanent fire barrier · No shelf life


· Cables/cable trays · Reusable · Moisture resistant
· Electrical trunking · Dry installation · Up to 2 hours fire protection
· Electrical trunking: for conformance with · Quick and easy installation
the 17th Edition of the IEE Wiring Regula-
tions (BS 7671:2008)

Certificates Functioning

· FiP is an intumescent graphite and mi-

CE neral fibre blend covered in a glass fibre


PVC coated cloth bag.
· FiP is suitable for applications where
ETA-20/1063 temporary and permanent fire barriers
EN 1366-3 are required.
EN ISO 10140-3:1995

Installation FIP - Wall application

47
Intumescent Pillows FiP · FireStop Assortment

Installation FIP - Floor application

Technical data

​ ​ Ap- Dimensions Weight per pillow Sales unit
pro-
val
​ ​ ​ ​ ​ ​
​ Item no. ETA [mm] [g] [pcs]
Item ​ ​ ​ ​ ​
FiP/S 516960 ● 330 x 50 x 20 80 1
FiP/Std 533890 ● 330 x 100 x 20 120 1
FiP/M 516959 ● 330 x 200 x 25 230 1
FiP/L 516958 ● 330 x 200 x 45 420 1

Technical data

State solid
Odour -
Expansion -
Significant expansion occurs at temperature > 140
European Technical Assessment ETA-20/1063
CE marking 2531-CPR-CXO10320
Colour black

Estimation quantities

Width Length [mm]


Size Large Medium Large Medium Large Medium Large Medium Large Medium Large Medium
[mm] Seal type 100 100 300 300 500 500 700 700 900 900 1,000 1,000
200 Wall 3 5 7 13 12 22 17 31 21 39 24 47
Floor 2 3 4 7 6 12 9 17 11 22 12 27
400 Wall 5 9 14 26 24 44 33 61 42 78 47 95
Floor 3 5 7 15 12 24 17 34 22 43 24 52
600 Wall 7 13 21 39 35 65 49 91 63 117 70 143
Floor 4 7 11 22 18 36 25 51 33 65 36 79
800 Wall 9 18 28 52 47 87 66 122 84 157 94 192
Floor 5 10 15 29 24 48 34 67 33 87 48 107
1000 Wall 10 22 35 65 59 109 82 152 105 196 117 217
Floor 6 12 18 36 30 60 42 84 54 108 60 120

48
Intumescent Putty Pad FiPP · FireStop Assortment

Intumescent Putty Pad FiPP


Intumescent Putty Pad FiPP

Internal application External application

Applications Advantages

· Most flexible partition assemblies · Excellent acoustic properties · No electrical conductivity


· Fire and insulation resistance · Internal and external versions available · Air permeability
· Acoustic sealing · Primerless adhesion to most substrates · Quick and simple installation
· Air permeability · Robust detail part E handbook accepted
· Plastic and metal electrical outlets

Certificates Building materials Functioning


EN ISO 10140 · Most flexible wall partitions constructed · Can maintain the fire resistance and
EN 1026
EN 1366-3 from plasterboard/gypsum board, timber insulation of flexible wall partitions, where
and steel studs they are penetrated by plastic or metal
electrical outlets and cables.
· FiPP can also be used for upgrading
the acoustic performance of flexible
partitions.

Installation FiPP - Internal application

Installation FiPP - External application

49
Intumescent Putty Pad FiPP · FireStop Assortment

Technical data

​ ​ Dimensions Fire rating Sales unit
​ ​ ​ [hours] ​
​ Item no. [mm] ​ [pcs]
Item ​ ​ ​ ​
FiPP/I-S 053578 170 x 170 2 1
FiPP/I-D 054757 230 x 170 2 1
FiPP/E-S 506261 155 x 155 2 1
2
FiPP/E-D 506262 210 x 180 2 1

Technical data

Base material Drywall


Specific grafity 1.55 kg/m³
Accoustic performance 66 dB
Colour red

50
Coated Panel System FCPS · FireStop Assortment

Coated Panel System FCPS


FireStop coated panel system for multiple service penetrations

Mixed penetration through the floor Mixed penetration through the wall

Applications Advantages

· Small and large openings · Approved for light partition walls · Excellent acoustic properties
· Cables/cable trays · Can be installed dry · Asbestos and halogen free
· Air ducts with dampers · No coatback required for services
· Metallic or non-metallic pipes

Certificates Functioning
ISO 10140 · FCPS is a rock fibre core coated with ab-

CE
EN 1366-3
lative sealant FPC for use in both vertical
and horizontal applications.
ETA-20/1062 · It maintains the sound reduction index of
ETA-20/1067 a structure.
· The FCPS will allow additional services to
be added or removed and will accommo-
date thermal and mechanical movement
of services.
· FPC can be used to adhere sections of
FCPS board when jigsaw assembly is re-
quired and can also be used to enhances
smoke and acoustic performance.

Installation FCPS
FIRE STOP

51
Coated Panel System FCPS · FireStop Assortment

Technical data

​ ​ Ap- Dimensions Content Contents Adapted for Sales unit
pro-
val
​ ​ ​ ​ ​ ​ ​ ​
​ Item no. ETA [mm] [kg] [ml] ​ [pcs]
Item ​ ​ ​ ​ ​ ​ ​
FCPS/50 053252 ● 1200 x 600 x 50 – – – 1
2 FPC/5kg 053253 ● – 5 – – 1
FiAM 310 053011 ● – – 310 – 1
KPM 2 Plus 053117 – – – – FiAM 310, FFRS 310, UFS 310, 1
FiGM 310

Technical data

Density 140 kg/m³


Coating thickness 1 mm WTF
Fire resistance depending on application
Accoustic performance 27 dB
Thermal conductivity 0,034 W/mK at 10 °C
Maximum size of seal Wall 6,76 m², floor 1,65 m²
Maximum size unsupported 1.2 x 1.2 m
Density of panel coating FPC 1.25 - 1.375 g/cm³
Panel coating FPC coverage ca. 1,6 kg/m² l/m²
Shelf life of panel coating FPC Art.-No. 53253 12 month
European Technical Assessment ETA-20/1062, ETA-20/1067
CE marking 2531-CPR-CXO10319, 2531-CPR-CXO10329

Application data

Services Rigid partition walls Flexible partition walls Concrete floors


[Fire rating - hours] [Fire rating - hours] [Fire rating - hours]
Cable ladder/tray/basket Up to 2 Up to 2 Up to 2
Cables up to 26 mm diameter Up to 2 Up to 2 Up to 2
Cables up to 80 mm diameter Up to 2 Up to 2 Up to 2
Steel/Copper pipes up to 159 mm diameter Up to 2 Up to 2 n/a
PVC pipes* up to 110 mm diameter Up to 1 Up to 1 n/a
Blank seals Up to 2 Up to 2 Up to 2
* PVC Pipes must be protected in conjunction wit h FiPW, which must be securely sealed in place wit hin the FCPS.

52
FireStop Compound FFSC · FireStop Assortment

FireStop Compound FFSC


Structural fire resistant seal for floors and walls

Mixed penetration through the floor Mixed penetration through the floor

Applications Advantages

· Metallic services with steel and cast iron · Water based · Excellent acoustic proper-ties
pipes · Low VOC · Both vertical and horizontal applications
· Non-metallic services with FiPW intume- · Load bearing · Halogen and asbestos free
scent pipe wrap or FFC pipe collar
· Voids or cavities in floors or walls
· Cable bunches

Certificates Functioning

· FFSC is a specially formulated gypsum

CE based compound, which when mixed


with water can be trowelled or poured.
· FFSC can provide up to 4 hours integrity
ETA-21/0678 and insulation.
EN ISO 10140 · Set within 45 min depending on ambient
EN 1366-3
ASTM E 814 (UL 1479)
temperature.
· Capable of accommodating foot traffic
within 72 hours.

53
FireStop Compound FFSC · FireStop Assortment

Installation FFSC - Floor application

Installation FFSC - Wall application

FIRE STOP
Technical data

​ ​ Ap- Content Sales unit
pro-
val
​ ​ ​ ​ ​
​ Item no. ETA [kg] [pcs]
Item ​ ​ ​ ​
FFSC/20 kg 533247 ● 20 1

Technical data

Base material Gypsum


Bulk density 950 kg/m³
Wet density 1850
Setting time 20 min
Storage temperature + 5 °C to + 25 °C
Accoustic performance 59 dB
Reaction to fire (EN13501-1) Class F
Shelf life 12 months month
European Technical Assessment ETA-21/0678
Tensile strength 30 N/mm²
Thermal conductivity 0.57 W/mK at 50 %, 0.65 W/mK at 90 %
Colour off white

Application data

By volume
Powder to water ratio
Pourable grade 2.5 : 1
Trowelable grade 3:1
* These are approximate calculations based on 20 kg bags. The coverage does not take into account the percentage of the hole filled with services.
** As a further safety margin, we would recommend that all floor seals with clear areas greater than 1,100 mm x 1,100 mm mus t be reinforced.
Load bearing note: the open area free of services: Thickness of seal ratios for non-reinforced seals given above allow an ample safety margin for normal foot traffic, e.g., loads of two men
plus equipment with a combined weight up to 200 kg.

54
VentiStop Cavity Barrier - FFB-VS · FireStop Assortment

VentiStop Cavity Barrier - FFB-VS


Effective ventilated fire barrier designed to close the void between the inner and outer construction elements

FFB-VS Ventistop installed with Multi-Purpose FFB-VS Ventistop installed with DHM Anchor
Bracket

Applications Advantages

· Horizontal cavities between the inner and · Tested up to 120 minutes integrity and gap
outer construction elements 90 minutes insulation (120 min insulation · Voids up to 450 mm wide
with FFB-VS HP80) utilising the heating · Free of halogens, asbestos, fi bres and
and pressure conditions of EN 1363-1: silica and is non-toxic
2017 and ASFP TGD19: 2014 - Open State · Long life expectancy
Cavity Barriers. · Contributes to green building
· Suitable to close 25 & 50 mm ventilation

Certificates Building materials Functioning


BS 8414 · Concrete slabs, columns and walls · FFB-VS a foil-faced stone wool pre-cut
EN 1363-1-TGD19
NFPA 285 unit, which has a powerful intumescent
graphite strip bonded to the exposed
face. The intumescent graphite strip is
pre-wrapped with a durable polythene
adhesive sheet to prevent water ingress.
· FFB-VS has been designed to provide a
25 & 50 mm ventilation gap, that allows
air fl ow and moisture to pass down the
back of the cladding. Under fire conditi-
ons, the powerful intumescent along the
front edge expands horizontally to close
the gap and prevent the passage of fire.

Installation FFB-VS with DHM

55
VentiStop Cavity Barrier - FFB-VS · FireStop Assortment

Installation FFB-VS with Multi Purpose Bracket

Technical data

​ ​ To suit cavity void width Sales unit
​ ​ ​ ​
​ Item no. [mm] [pcs]
Item ​ ​ ​
FFB-VS/25-50 521520 25 - 50 1
FFB-VS/51-100 521521 51 - 100 1
FFB-VS/101-150 521522 101 - 150 1
FFB-VS/151-200 521523 151 - 200 1
FFB-VS/201-250 521524 201 - 250 1
FFB-VS/251-300 521525 251 - 300 1
FFB-VS/301-350 521526 301 - 350 1
FFB-VS/351-400 521527 351 - 400 1
FFB-VS/401-450 521528 401 - 450 1

IMPORTANT: Please provide TOTAL cavity width for your application, excluding an y insulation there might be.

Technical data

​ ​ To suit cavity void width Sales unit
​ ​ ​ ​
​ Item no. [mm] [pcs]
Item ​ ​ ​
FFB-VS50/51-100 545628 51 - 100 1
FFB-VS50/101-150 545629 101 - 150 1
FFB-VS50/151-200 545630 151 - 200 1
FFB-VS50/201-250 545631 201 - 250 1
FFB-VS50/251-300 545632 251 - 300 1
FFB-VS50/301-350 545633 301 - 350 1
FFB-VS50/351-400 545634 351 - 400 1
FFB-VS50/401-450 545635 401 - 450 1

IMPORTANT: Please provide TOTAL cavity width for your application, excluding an y insulation there might be.

Technical data

Description Foil faced stone wool with a black intumescent leading edge
Fire resistance up to 120 min
Closure time - FFB-VS < 5 min
Activation approx. 180 °C
Expansion pressure approx. 7 N/mm²
Density Stone wool - 90 kg/m³, intumescent 1.3 g/cm ³
Weather resistance Yes
Sag 0%
Open void size 25 - 50 mm
Dimensions 80 mm thick, 1000 mm long mm
Width 30 - 450 mm
Fixing points (brackets or anchor DHM) 300 mm
Colour White/red/silver/black

56
VentiStop Cavity Barrier - FFB-VS · FireStop Assortment

Technical data

​ ​ To suit cavity void width Colour Fire rating Sales unit
​ ​ ​ ​ [hours] ​
​ Item no. [mm] ​ ​ [pcs]
Item ​ ​ ​ ​ ​
Multi Purpose Bracket 563201 230 x 25 x 1 (A2) silver N/a 250
Multi Purpose Bracket 551868 390 x 25 x 1 (A2) silver N/a 1
Multi Purpose Bracket 551954 500 x 25 x 1 (A2) silver N/a 1
2
FCI Cassette tray cavity barrier 554125 1200 x 100 x 50 silver N/a 1

57
Cavity FireStop Clad FCFcl · FireStop Assortment

Cavity FireStop Clad FCFcl


Designed to protect the building void between the inner and outer construction elements

FCFcl Cavity Clad - Vertical application FCFcl Cavity Clad - Horizontal application

Applications Advantages

· Horizontal and vertical cavities bet- · Tested to EN 1366-4 & BS 476 · Superior Level of Sustainability
ween the inner and outer construction · Classification to EN 13501-2, EN 13501-1 · Encased Fibre Migration for Air Plenum
elements · Air Permeability to EN 1026 to 600Pa Use
· Ceiling Cavity Barriers · Acoustic Isolation to EN 10140 to 31dB · Floor & Wall voids up to 590 mm wide
· Under Floor Cavity Barriers
· Slab Edge Barriers

Certificates Building materials Functioning


BS 8414 · Concrete slabs, columns and walls · FCFcl Cavity Clad comprises of a one

CE
EN ISO 10140
EN 1026
· Curtain wall assemblies piece closed dimension stone wool core.
EN 1366-4 · The product is encased with an alumi-
NFPA 285
num foil face which provides class ‚O‘
ETA-21/1062
rating and exhibits excellent resistance
to smoke.
· The FCFcl Cavity Clad provides a resilient
lateral compression which is required to
ensure a tight fit.

Installation FCFcl

58
Cavity FireStop Clad FCFcl · FireStop Assortment

Installation FCFcl

Technical data

​ ​ Ap- To suit cavity void width Sales unit
pro-
val
​ ​ ​ ​ ​
​ Item no. ETA [mm] [pcs]
Item ​ ​ ​ ​
FCFcl 75 546210 ● 1200 x 600 x 75 1
FCFcl 100 053046 ● 1200 x 1000 x 100 1
FCFcl 1200 546209 ● 1200 x 1200 x 100 1

IMPORTANT: Please provide TOTAL cavity width for your application, excluding any insulation there might be. FCFcl Cavity Clad shall be cut 5 mm (1/5 in.) or 10 mm (3/8 in.) oversize. * Depen-
ding on design & configuration of the FCFcl Cavity Clad.

Technical data

​ ​ To suit cavity void width Fire rating Sales unit
​ ​ ​ [hours] ​
​ Item no. [mm] ​ [pcs]
Item ​ ​ ​ ​
Multi Purpose Bracket 563201 230 x 25 x 1 (A2) N/a 250
Multi Purpose Bracket 551868 390 x 25 x 1 (A2) N/a 1
Multi Purpose Bracket 551954 500 x 25 x 1 (A2) N/a 1

Technical data

Description Foil faced structural stone wool composite


Fire resistance EN1366-4 up t o 120 minutes
Thermal conductivity 0.35 bis 0.36 W/mK
Density 80 kg/m³
Base material Stone wool
Accoustic performance 31 dB
Air permeability 600 pa - 100 pa 2.6/4.2 m ³/h/m²
Thickness 75 and 100 mm
Bracket Required cavity ≥ 150 mm (2 per meter)
Compression 5 or 10 mm
Colour inside yellow, outside silver
European Technical Assessment ETA-21/1062
CE marking 2531-CPR-CXO10328

59
FireStop Foam · FireStop Assortment

FireStop Foam
A single component filler foam with effective fire resistance

Back filling material Construction joint application

Applications Advantages

· Construction joints in walls and floors · High foam yield · High bond strength
· Insulating and sealing doors and win- · No post shrinkage or expansion · Good adhesion to most building mate-
dows: non-fire rated application · CFC free propellant rials
· Backfilling material only for service · Effective seal against smoke · Excellant acoustic and thermal proper-
penetrations · Rendered, cut, painted or sanded ties
· Filling general voids and cavities: nonfire
rated application

Certificates Building materials Functioning


EN ISO 10140 · Concrete · FireStop Foam is a single component,

CE
EN 1366-4
· Masonry self expanding polyurethane foam, which
· Steel as backing material has been designed to be self curing
ETA-20/0770 · Timber as backing material via the absorption of moisture from the
atmosphere.
· The foam has excellent adhesion pro-
perties and can adhere to most building
materials. When the foam sets it cures to
a semi-rigid structure, which accommo-
dates low movement and vibration.

Installation FireStop Foam

60
FireStop Foam · FireStop Assortment

Technical data

​ ​ Ap- Contents Sales unit
pro-
val
​ ​ ​ ​ ​
​ Item no. ETA [ml] [pcs]
Item ​ ​ ​ ​
FireStop Foam Hand 042757 ● 750 1
FireStop Foam Gun 043712 ● 750 1 2

Technical data

Base material Polyurethane


Consistency stabile foam
Curing system Moisture-cure
Yield 1,000 ml yields 35 - 40 l cured foam when extruded in beads
Specific grafity extruded, fully cured approx. 27 kg/m³
Skin-forming time 10 min (at 23 °C and 65% relative humidity)
Drying time Non tacky after approx. 8 min
Shrinkage No
Storage temperature + 5 °C to + 25 °C
Shelf life up to 12 months when stored in unopened cartridges under cool, dry conditions month
Construction material class B1 as per DIN 4102
STC rating 56 dB
Colour red
European Technical Assessment ETA-20/0770

61
Thermal Defense Wrap TDW · FireStop Assortment

Thermal Defense Wrap TDW


Thermal defense wrap for high insulation and temperature stability

Electrical floor application Electrical wall application

Applications Advantages

· Metallic services with steel and cast iron · Remains flexible -10 to +160 · Pre-formed 300 mm roll
pipes · Low VOC · Fast and efficient installation
· General construction joints: wall to floor · High insulation and temperature stability · Remains flexible without aging
to head of wall
· Drywall partitions, connections
· FCPS joints

Certificates Functioning
EN ISO 10140 · TDW is ceramic-based technology of
EN 1366-3
bio-soluble vitreous fibres and flexible
organic builders, and has been designed
to maintain the compartmentalisation of
a fire-rated assembly.
· The unique design of the TDW allows
for movement of services, maintain the
necessary insulation of the services
and prevents temperature, rise of the
services at the cold face. At normal
temperature the TDW remains flexible
and permits thermal and mechanical
movement.
· It provides up to 2 hours integrity and
insulation.

Installation TDW with FCPS


FIRE STOP

62
Thermal Defense Wrap TDW · FireStop Assortment

Technical data

​ ​ Dimensions Sales unit
​ ​ ​ ​
​ Item no. [mm] [pcs]
Item ​ ​ ​
TDW 1 531398 300 x 1000 1

Technical data 2
Apperarance white, fibrous material with aluminium foil face
Base material Calcium magnesium silicate fibres
Water solubility N/a
Alufoil thickness 0.25 mm
Storage temperature + 5 °C to + 25 °C

63
fischer catalogue FireStop

64
3
Basics – good to know. 3

Fire prevention 66

Advanced product selection guide 68

Approvals and markings 68

Calculation of consumption guide 70

fischer training certification 71

Engineering judgement request form 73

65
Fire prevention
Fire prevention is a critical consideration for those who are through a combination of active and passive FireStop sys-
responsible for creating the design, specification and con- tems and, when used in conjunction with each other, provide
struction of new buildings, with consideration in the ongoing a balanced fire protection strategy.
maintenance of occupied premises. Active fire prevention systems are designed to react to the
As the causes of fire vary and are often unpredictable, outbreak of a fire, which is then suppressed with the help of
construction measures are being designed to influence the sprinkler systems, halogen installations, fire extinguishers
formation and spread of fire, smoke and toxic gases, by min- or other proactive mechanical systems. The effects of the
3
imising the available factors needed to create a fire or to limit fire may also be lessened by the removal of smoke from the
the spread of fire once it has started. equation. By including alarms and emergency lighting, active
Effective fire fighting within a building is generally achieved systems also serve to provide escape paths for people inside
through a combination of active and passive FireStop sys- the building.
tems and, when used in conjunction with each other, provide
a balanced fire protection strategy. Passive fire prevention systems
Passive fire prevention is an integral component, which is
Active FireStop systems designed and built in to the fabric of the structure. It is also
Fire prevention is a critical consideration for those who are an essential element of the fire safety of a building. The risk
responsible for creating the design, specification and con- of fire can be minimised by dividing the building into a series
struction of new buildings, with consideration in the ongoing of compartment/cells bounded by fire rated walls and floors.
maintenance of occupied premises. To maintain the firestopping integrity of a compartment/cells,
As the causes of fire vary and are often unpredictable, any gaps, openings, void or channels within the fire rated
construction measures are being designed to influence the walls or floors must be sealed with an approved or certfied
formation and spread of fire, smoke and toxic gases, by min- system to prevent the passage of fire, smoke and toxic
imising the available factors needed to create a fire or to limit gases.
the spread of fire once it has started.
Effective fire fighting within a building is generally achieved

Building codes and national


regulations.
Most model building codes have very clear requirements on separating element should be: Kept as few in number as
passive fire protection. possible and kept as small as practical fire-stopped (which in
“Fire investigation reports have consistently shown that the case of a pipe or duct, should allow for thermal move-
unprotected or improperly protected penetrations and joints ment).”
cause millions in property damage and contribute to the
loss of life and injuries due to the uncontrolled migration of
fire, smoke and toxic gases.” In order to promote life safety BS 7671: 2008: United Kingdom
and property protection, the national building codes include The 17th edition of the IEE Wiring Regulations (BS 7671:2008)
fire testing and performance requirements for penetration is the national standard in the United Kingdom for all com-
firestop and fire resistive joint systems. mercial, domestic and industrial wiring installations. Section
The following regulations are published as statutory instru- 527-02-01 states: “Where a wiring system passes through
ments by Parliament with respect to life safety purposes: elements of building construction such as floors, walls, roofs,
ceilings, partitions or cavity barriers the openings remaining
England and Wales 1991 after passage of the wiring systems shall be sealed accord-
Section 11.2 of Approved Document B3 states: “If a fire ing to the degree of fire resistance required of the element
separating element is to be effective, then every joint, or im- concerned.” Section 527-02-02 states: “where a wiring sys-
perfection of fit, or opening to allow services to pass through tem such as conduit, cable ducting, cable tr unking, busbar
the element, should be adequately protected by sealing or or busbar trunking penetrates an element of building cons
fire stopping so that the fire resistance of the element is truction having specified fire resistance it shall be internally
not impaired.” Section 11.12 adds, under the heading of ‘Fire sealed so as to maintain the degree of fire resistance of the
stopping’, a requirement that: “Joints between fire separating respective element as well as being externally sealed to
elements should be fire stopped; and all openings for pipes, maintain the required fire resistance.”
ducts, conduits or cables to pass through any part of a fire

66
Germany: Federal Building Order of extensive research and development, the first edition of
In Germany, the Federal State Building Order is regulated the International Building Code was published in 1997.
at the level of the federal states. Therefore, there are 16 The code was patterned on three legacy codes previously
regional state building codes with their own regulations and developed by the organizations (BOCA, SBCCI, ICBO) that
guidelines. The 2002 Directive Building Code and the 2005 constitute IBC. By the year 2000, ICC had completed the
Directive Guidelines for conduit and ventilation systems form International Codes series. Relevant firestop requirements
the basis for further consideration. The list of the Technical can be found in below mentioned references:
Building Regulations – M-ETB, includes other codes, such as 702 Definitions
the MLAR and the German Ventilation Systems Directive – 704.9 Separation of Vertical Openings - Sprinkler Exception
MLüAR. Once guidelines are adopted into the list at regional 708 Fire Partitions 1 Hour Rating
state level List of Technical Building Regulations–LTB, the 709 Smoke Barriers 1 Hour Rating 3
guidelines become legally binding. 710 Horizontal Assemblies
NFPA 101 Life Safety code: United States 711 Penetrations (General)
Life Safety Code addresses those construction, protection, 711.3.2 Sprinkler Heads Electrical Boxes
and occupancy features necessary to minimise danger to 711.4.1.2 „F“ & „T“ Rating Requirements
life from the effects of fire, including smoke, heat, and toxic 712 Fire-Resistant Joint Systems
gases created during a fire. The Code establishes minimum 712.4 Curtain Wall to Edge of Slab
criteria for the designs of egress facilities, so as to allow
prompt escape of occupants from buildings or, where desira- Other relevant codes from IBC: United States
ble, into safe areas within buildings. The Code also address- The International Building Code and International Residential
es protective features and systems, building services, oper- Code are just a few of the comprehensive I-Codes the Code
ating features, maintenance activities, and other provisions in Council has created. The publications of the codes allow for
recognition of the fact that achieving an acceptable degree easier following from members and allow them to observe
of life safety depends on additional safeguards to provide and study the model code. Some of these codes have spe-
adequate egress time or protection for people exposed to cific practices, such as the International Fire Code and the
fire. Relevant firestop requirements can be found in below International Green Construction Code, or the IGCC. Here is
mentioned references: the current list of I-Codes developed and published by the
8.2.2 Compartmentation Continuity Code Council:
8.2.3.2.4 Penetrations and Openings In Fire barriers International Building Code
8.2.4.4 Penetrations and Openings In Smoke Partitions International Residential Code
8.3.2 Continuity of Smoke Barriers International Fire Code
International Plumbing Code
NFPA 5000 Building Construction and Safety- International Mechanical Code
code International Fuel Gas Code
NFPA 5000 – Building Construction and Safety Code is a International Energy Conservation Code
model building code developed by the National Fire Pro- IBC Performance Code
tection Association. For the most part, the requirements International Wildland Urban Interface Code
for fire stops are the same in NFPA 5000 as they are in the International Existing Building Code
IBC. It also addresses joints between assemblies in a similar International Property Maintenance Code
manner to the IBC. NFPA 5000 states openings must be International Private Sewage Disposal Code
protected by „a system or material capable of restricting the International Zoning Code
transfer of smoke“. It addresses protection for through-pene- International Green Construction Code
trations and membrane penetrations in Section 8.8 using the
same test methods as the IBC. The requirements for F and T Other relevant code
ratings are also the same. Joint systems, including perimeter NFPA is responsible for 300 codes and standards that are
joints at cur tain walls, are addressed in the same manner as designed to minimize the risk and effects of fire by establish-
the IBC. ing criteria for building, processing, design, service, and
installation. Some of the other widely used NFPA codes are:
IBC International Building Code: United States NFPA 70 NEC – National Electrical Code NFPA 96 - Standard
In the Past: The Regional Model codes developed by the for Ventilation Control and Fire Protection of Commercial
Building Officials Code Administrators International (BOCA) Cooking Operations. NFPA 221 - Standard for High Challenge
were used on the East Coast and throughout the Midwest Fire Walls, Fire Walls, and Fire Barrier Walls
of the United States, while the codes from the Southern
Building Code Congress International (SBCCI) were used in
the Southeast and the codes published by the International
Conference of Building Officials (ICBO) covered the West
Coast and across to most of the Midwest. After three years

67
fischer catalogue FireStop

Advanced product selection guide.


Product Approved to
EN EN EN ASTM ASTM ASTM EN ISO EN 1026 EN 1027 TGD19 EN NFPA
1364-4 1366-3 1366-4 E 814 E 84 E 1966 10140 13501-1 285
(UL 1479) (UL 723) (UL 2079)
Intumescent Acoustic Mastic FiAM – ● ● – ● ● ● ● – – – –
Intumescent Acoustic Mastic – – – ● ● ● – – – – – –
3 FiAM US

Fire Rated Silicone Sealant – – ● – – – ● ● – – – –


FFRS

Rapid Fire Seal RFS 640 – – – ● ● ● – – – – – –


Fire | Barr ElastoSeal FFB-ES ● ● ● – – – ● ● ● – – –
Universal FireStopping – – – ● ● ● – – – – – –
Sealant UFS 310

Intumescent Graphite Mastic – ● – – – – ● ● – – – –


FiGM

Foam Barrier System PLUS – ● – ● ● – – – – – ● –


Intumescent Pipe Wrap FiPW – ● – – – – – – – – – –
Intumescent Wrap Strip FiWS – – – ● ● – – – – – – –
Fire Collar FFC – ● – – – – – – – – – –
Cast in Device FCID – – – ● – – – – – – – –
Intumescent Pillows FiP – ● – – – – ● – – – – –
Intumescent Putty Pad FiPP – ● – – – – ● ● – – – –
Coated Panel System FCPS – ● – – – – ● – – – – –
FireStop Compound FFSC – ● – ● – – ● – – – – –
VentiStop Cavity Barrier – – – – – – – – – ● – ●
FFB VS

Cavity FireStop Clad FCFcl – – ● – – – ● ● – – – ●


FireStop Foam – – ● – – – ● – – – – –
Thermal Defense Wrap TDW – ● – – – – – – – – – –

Approvals, markings and


their importance.
Britisch European American
Standard Norm Standard

BS 8414:2020 EN 13501-1:2019 EN 1366-4:2021 ASTM E 84 (UL 723) ASTM E 1966 (UL 2079) ASTM E 814 (UL 1479)
Fire performance of Fire classification of Fire resistance tests for Test method for Surface Test method for Test method for Fire
external cladding sys- construction products service installations - Burning Characteristics Fire-Resistive Joint Sys- Tests of Through Pene-
tems. Test method for and building elements. Linear joint seals. of Building materials. tems. This test is used trations Fire Stops. This
non-loadbearing exter- Reaction to Fire. The test evaluates to evaluate the perfor- test is used to evaluate
nal cladding systems EN ISO 10140:2021 the spread of flame mance of a joint af ter the performance of
EN 13501-2:2016 The laboratory meas- along the surface of a cyclic movement test a firestop system,
Fire classification of urement of airborne the material. It is no t a and fire exposure test. following fire exposure
construction products sound insulation of resistance test. UL 2079 - equivalent. a hose s tream test is
and building elements. buildng elements. conducted. UL 1479 -
Resistance to Fire. equivalent.
EN 1026: 2016
EN 1366-3:2020 Air permeability test
Fire resistance tests for method.
service installations –
Penetration seals. EN 1027: 2016
Water permeability test
EN 1364-4:2014 method.
Fire resistance tests
for non-loadbearing
elements – Curtain wall-
ing-Part Configuration.

68
fischer catalogue FireStop

Marks Application Page


BS ASTM CE UL UL FBC FM Construction Perimeter Metallic Insulated Non-metallic Cable and Air ducts Insulated Rainscreen
8414 E 2307 Marking EU US joint joints pipes pipes pipes cable trays air ducts cavity barrier

– – ● ● ● – – ● – ● – – ● – – – 4
– – – – ● ● – ● – ● ● ● ● ● ● – 6
3
– – ● ● – – – ● – – – – – – – – 8

– ● – – ● – ● ● ● ● – – ● ● – – 11
– – ● ● – – – ● ● 14
– – – – ● ● ● ● – ● ● ● ● ● ● – 16

– – ● ● – ● – – – ● ● ● ● – – – 19

– – ● – ● – – – – – – – – – – – 21
– – ● ● – – – – – – ● ● – – – – 24
– – – – ● ● ● – – ● ● ● – – – – 26
– – ● ● – – – – – – ● ● – – – – 29
– – – ● – – – – – – – ● – – – – 31
– – ● ● – – – – – ● – – ● – – – 33
– – – – – – – – – – – – ● – – – 35
– – ● ● – – – – – ● ● ● ● ● – – 37
– – ● – ● – – – – ● ● ● ● ● – – 39
● – – – – – – – ● – – – – – – ● 42

● – ● – – – – ● – – – – – – – ● 45
– – ● – – – – ● – – – – – – – – 47
– – – – – – – – – – – – ● – – – 49

DIN

DIN 4102:Part1 FM Approvals is an UL-EU Mark is intended UL is an abbreviation for Underwriters NFPA 285
Fire behaviour of international leader in for use on products Laboratories Inc. which is an Sandard Fire Test Method for Evalua-
building material and el- third-party certification destined for the independant, not for profit product tion of fire propagation characterisitcs
ements - Part 1: Building and approval of European marketplace. safety testing and cer tification of exterior wall assemblies containing
materials, concepts. commercial and organisation. combustible components
industrial products.

CE
European Technical Approval/Assessment Issued by a European FBC™ System Compatible indicates
approval authority (e. g. DIBt) on the basis of the guidelines for that this product has been tested, and
European technical approvals (ETAG). ETA (English): European is monitored on an ongoing basis,
Technical Approval/Assessment. CE: The CE marks the conformity to assure its chemical compatibility
of the product to all applicable legal provisions in which their instal- with FlowGuard Gold®, BlazeMaster®
lation is intended. This means that the CE mark only certifies that and Corzan® pipe and fittings. FBC™,
the requirements determined in the relevant harmonisation legal FlowGuard Gold®, BlazeMaster® and
provisions of the union have been complied with. Products with the Corzan® are licensed trademarks of
CE mark can be freely traded in the European Economic Market. The Lubrizol Corporation.

69
fischer catalogue FireStop

Calculation of
consumption guide.
Calculation for mastic/sealant Professional App
a = Hole diameter in mm The Mobile Guide to Fixing Solutions for
b = Depth of sealant in mm/wet film thickness for spray material (see recommendations) Professionals.
3
c = Pipe or bunched cables diameter in mm The Firestop module in the app offers the
d = Annular space in mm (see r ecommendations) possibility to calculate the quantity
l = Length of square opening/joint (Calculation of consumption) automatically.
w = Width of square opening/joint
h = Cartridge or spray bucket size in ml
n = Number of holes
e = Area of hole in mm2 = π(a ÷ 2)2
f = area of pipe in mm2 = π (a ÷ 2)2
g = Amount of mastic needed per hole in ml = ((e-f) x b) ÷ 1,000

Round holes
No. of cartridges needed = n x (g ÷ h) Example: e = 3.14 x 452 = 6,361.73 mm2
Area of hole e = π x (a ÷ 2)2 mm2 a = 90 mm, b = 40 mm, c = 50 mm, h = f = 3.14 x 252 = 1,963.50 mm2
Area of pipe f = π x (c ÷ 2)2 mm2 310 ml, n = 20 g = ((6,361.73 - 1,963.50) x 40) ÷ 1,000 =
Mastic volume = g = ((e-f) x b) ÷ 1,000 ml 175.92 ml

No. of cartridges = 20 x (175.92 ÷ 310) = 11.35 cartridges

Square holes
No. of cartridges needed = n x (g ÷ h) Example: e = 90 x 100 = 9,000 mm2
Area of hole e = l x w mm2 l = 90 mm, w = 100 mm, b = 40 mm, c = 50 f = 3.14 x 252 = 1,963.50 mm2
Area of pipe f = π x (c ÷ 2)2 mm2 ml, h = 310 ml, n = 20 g = ((9,000 - 1,963.50) x 40) ÷ 1,000
Mastic volume = g = ((e-f) x b) ÷ 1,000 ml = 281.46 ml

No. of cartridges = 20 x (281.46 ÷ 310) = 18.1 cartridges

Linear joints
No. of cartridgesbuckets =(g ÷ h) Example for mastic/sealant: e = 20 x 30,000 = 60,000 mm2
Area of joint = e = l x w mm2 w = 20 mm, l = 30m = 30,000 mm b = 10 g = (60,000 x 10) ÷ 1,000 = 6,000 ml
Mastic volume = ((e-f) x b) ÷ 1000 ml = g mm, h = 310 ml

No. of cartridges = (6,000 ÷ 310) = 19.4 cartridges

Example of joint Spray: e = 125 x 300,000 = 37,500,000 mm2


w = 100 mm, w1 = 125 mm (with overspray) g = (37,500,000 x 1.5) ÷ 1,000 = 56,250 ml
l = 300 m = 300,000 mm
b = 1.5 mm
h = 19 litres = 19,000 ml

No. of buckets = (56,250 ÷ 19,000) = 2.96 buckets

70
fischer catalogue FireStop

fischer Training
certification.
fischer Training
Fire protection seminars with certificate for
professionals. Show your competence.
3
Become a trusted specialist of your work!
· Do the right thing quickly and safely
· Competently assess legal issues and
resolve them

We will show you the options for the indivi-


dual systems, tips and tricks for handling,
and give you a clear, competitive advan-
Certificate.
tage.
We will bring you and your employees up-
to-speed in preventative fire protection. 01th November 2022, Waldachtal

· Basic introduction to fire protection


· Model building codes
· Fire testing standards
· Product selection criteria
has successfully demonstrated a level of ceompetence in:
· Trade and a Application areas
· Practical installations „The correct installation of fischer
FireStop products“
Locations and dates
Content of the course:
Please contact your fischer representative · FCPS Coated Panel & FiAM Acoustic Mastic
· FiPW Pipe Wrapp
for further details on course dates. The · FFC Collar
· FFRS Silicone Sealent
entire range of knowledge is shared with · FFFC Compound
· FIP Pillow
you by fischer fire protection experts. · PBB FireStop Block
· FBS Graphite Foam

And agrees to adhere to the fischer FireStop Professional Ethics (FFPE).*


fZE/2022/FS/001

Marion Leipersberger
Product Manager
FireStop

*This certificate is valid for one year from the date of issue.

71
fischer catalogue FireStop

fischer Professional.
3
The mobile fixing expert.
www.fischer-international.com

72
fischer catalogue FireStop

Engineering judgement request form.


Project name: Requested by:

Consultant: Company:

Contractor: E-Mail:
3
Contact: Phone:

Email: Supplier:

Phone: fischer Engineer:

Fire rating requirements

F - Rating (HR): T - Rating (HR): Approval type: (BS, ETA, UL)

Through penetration
Assembly details: Wall Floor

Base material: Concrete Masonry/Blocks Drywall


Thickness

Opening details: Sleeved: Yes No Sleeve type: PVC Steel


Size:

Penetration details:
Insulation

Size Material/Type Insulation

Size Material/Type Insulation

Size Material/Type Insulation

Size Material/Type Insulation

Size Material/Type Insulation

Others

Joints
Joint type: Head of wall Blocks Concrete Blocks Wall to wall Perimeter joint

Base material: Concrete Blocks Steeldeck Drywall

Doint details: Static Dynamic Width:

Movement required: Curtain wall details:

Special conditions/comments/drawings/standards

For questions please contact: [email protected]

73
fischer catalogue FireStop

74
4
Service 4

Content

Portfolio 78

fischer subsidiaries 80

75
Service · Portfolio

Main catalogue fixing systems.


Products for use in fixing technology.

The fixing catalogue offers many facts and helps with quick
and safe product selection, e.g.:

· Produktbeschreibungen mit Vorteile/Nutzen im Überblick


4 · Tips for installation
· Application aids
· Detailed technical data and drawings
· Basics of fastening technology
· All you need to know about professional fixing

Order now: [email protected]

Main catalogue Façade Systems.


All facts about the fischer façade range and its applications.

The Façade Systems catalogue offers many facts and helps with
quick and safe product selection, e.g.:

· Presentation of Zykon panel anchor, machine technology, drill bits,


subframes, general fixing products and accessories with detailed
technical data and illustrations.
· Application support.
· Basic knowledge about undercut anchors and subframe systems.
· Available design software

Order now: [email protected]

76
Service · Portfolio

Main catalogue Installation Systems.


Products for use in installation technology.

Many facts about the products and everything you need to know
about fischer installation systems, e.g.:

· Product- and system introductions


· Plugs and anchors for fixing the system components 4
· Application aids
· Detailed technical data and drawings
· Basics of installation technology

Order now: [email protected]

Catalogue Cast-in Channels.


Products and applications of the fischer Cast-in Channel systems.

The Cast-in Channel catalogue shows innovative and secure


solutions, offers comprehensive information and helps with a quick
selection of system components.

· Presentation of the bolt and rail types and their possible combinati-
ons, with detailed technical data and illustrations
· Application support and references
· Basic knowledge on applications, processing and services
· Available design software

Order now: [email protected]

77
Service · fischer subsidiaries

Germany Czech Republic Indien


fischer Deutschland Vertriebs GmbH fischer international s.r.o. fischer Building Materials India PVT Ltd.
Klaus-Fischer-Straße 1 Prùmyslová 1833 Unit 101, First Level, No. 3 (Old 4),
72178 Waldachtal 25001 Brandýs nad Labem Prestige Sigma, Vittal Mallya Road,
P +49 7443 12 - 6000 P +42 03 26 90 46 01 Ward No. 76, Richmond Town
F +49 7443 12 - 4500 F +42 03 26 90 46 00 560001 Bangalore, Karnataka
[email protected] [email protected] P +91 0804 1511 991 92 93
www.fischer.de www.fischer-cz.cz F +91 0804 1511 989
[email protected]
4 www.fischer.in

Argentina Denmark Italy


fischer Argentina s.a. fischer a/s fischer italia S.R.L
Armenia 3044 Sandvadsvej 17 A Corso Stati Uniti, 25, Casella Postale 391
1605 Munro Ra-PCIA Buenos Aires 4600 Køge 35127 Padova Z.I. Sud
P +54 1147 62 27 78 P +45 46 32 02 20 P +39 049 8 06 31 11
F +54 1147 56 13 11 F +45 46 32 50 52 F +39 049 8 06 34 01
[email protected] [email protected] [email protected]
www.fischer.com.ar www.fischerdanmark.dk www.fischeritalia.it

Austria Finland Japan


fischer Austria GmbH fischer Finland Oy fischer Japan K.K.
Wiener Straße 95 Suomalaistentie 7 B Seishin Kudan Building 3rd Floor 3-4-15
2514 Traiskirchen 02270 Espoo Kudan Minami Chiyoda-ku, 102-0074 Tokyo
P +43 2252 53730 0 P +358 20 741 46 60 P +81 33 26 34 49 1
F +43 2252 53730 70 F +358 20 741 46 69 F +81 36 27 29 93 5
[email protected] [email protected] [email protected]
www.fischer.at www.fischerfinland.fi www.fischerjapan.co.jp

Belgium France Korea, Republic


fischer Cobemabel snc fischer S. A. S. fischer Korea Co., Ltd (fikr)
Schaliënhoevedreef 20 D 12, rue Livio, P. O. Box 10182 Room 601/602, Kolon Digital Billant 30,
2800 Mechelen 67022 Strasbourg-Cedex 1 Digitalro 32-Gil, Guro-Gu, Seoul,
P +32 152 8 47 00 P +33 388 39 18 67 Korea 08390
F +32 152 8 47 10 F +33 388 39 80 44 P +82 1544 89 55
[email protected] [email protected] F +82 1544 89 03
www.fischer.be www.fischer.fr [email protected]
www.fischerkorea.com

Brazil Greece Mexico


fischer brasil Industria e Comercio Ltda. fischer Hellas fischer Sistemas de Fijación, S.A. de C.V.
Estrada do Dende, 300 Ilha do Governador Kalavriton 2 & Kaiafa Blvd. Manuel Avila Camacho 3130-400B
21920-001 Rio de Janeiro-RJ 14564 Kifissia, Athens 54020 Col. Valle Dorado, Tlalnepantla
P +55 21 2467 11 30 P +30 21 02 83 81 67 P +52 55 55 72 08 83
F +55 21 2467 01 44 F +30 21 02 83 81 69 F +52 55 55 72 15 90
[email protected] [email protected] [email protected]
www.fischerbrasil.com.br www.fischer.gr www.fischermex.com.mx

China Hungary Netherlands


fischer (Taicang) fixings Co. Ltd. fischer Hungária Bt. fischer Benelux B.V.
No. 17, Lane 166, Guchuan Road, 14th Szerémi út 7/b Gooimeer 14
Floor, Building 2, Zhongjun Tianyue Center 1117 Budapest 1411 DE Naarden
200333 Shanghai P +36 1 347 97 55 P +31 35 6 95 66 66
P +86 21 51 00 16 68 F +36 1 347 97 66 F +31 35 6 95 66 99
F +86 21 65 97 96 22 [email protected] [email protected]
[email protected] www.fischerhungary.hu www.fischer.nl
www.fischer.com.cn

78
Service · fischer subsidiaries

Norway Russian Federation United Arab Emirates


fischer Norge AS OOO fischer Befestigungssysteme Rus fischer FZE
Oluf Onsumsvei 9 Leningradskoe shosse, 47, Bldg. 2, 2nd R/A 07, BA - 04, Jebel Ali Free Zone
0680 Oslo floor, apt. VI, 125195 Moscow Dubai
P +47 23 24 27 10 P +7 495 223 61 62 P +97 14 8 83 74 77
F +47 23 24 27 13 F +7 495 223 03 34 F +97 14 8 83 74 76
[email protected] [email protected] [email protected]
www.fischernorge.no www.fischerfixing.ru www.fischer.ae

Philippines Singapore United Kingdom


fischer PH Asia, Inc. fischer systems Asia Pte. Ltd. fischer fixings UK Ltd.
No 100 Congressional Avenue, Project 8 4 Kaki Bukit Avenue 1, #01-06 Whitely Road
1106 Quezon City 417939 Singapore Oxon OX10 9AT Wallingford
P +63 2426 0888 217 P +65 6741 0480 P +44 1491 82 79 00
F +63 2880 3256 F +65 6741 0481 F +44 1491 82 79 53
[email protected] [email protected] [email protected]
www.fischer.ph www.fischer.sg www.fischer.co.uk

Poland Slovakia United States


fischerpolska Sp.z o.o fischer S.K. s.r.o. fischer fixings LLC (fius)
ul. Albatrosow 2 Nová Rožňavská 134 A 205 US HWY 46, Suite 4 07512 Totowa,
30-716 Kraków 831 04 Bratislava New Jersey
P +48 12 2 90 08 80 P +421 2 4920 60 46 P +1 973 256 30 45
F +48 12 2 90 08 88 F +421 2 4920 60 44 F +1 845 625 26 66
[email protected] [email protected] [email protected]
www.fischerpolska.pl www.fischer-sk.sk www.fischerfixings.com

Portugal Spain Vietnam


fischerwerke Portugal, Lda. fischer Ibérica S.A.U. fischer production Company Limited –
Rua das Musas, Passeio dos Cruzados Klaus Fischer 1 Tay Ninh Branch
Lote 2.01 (Bloco3), Loja 8 (01.D) / Parque 43300 Mont-Roig del Camp Tarragona Lot 36-23-B, 36-24, D14A Road, Phuoc
das Nações, 1990-171 Lisboa P +34 977 83 87 11 Dong Industrial Park, Phuoc Dong
P +351 218 954 180 F +34 977 83 87 70 Commune, Go Dau District, Tay Ninh
F +351 218 967 066 [email protected] Province
[email protected] www.fischer.es [email protected]
www.fischer.pt

Qatar Sweden
fischer fasteners QD Trading LLC fischer Sverige AB
HUB Business Center, Barwa Commercial Nygatan 93
Avenue, Arkan Building, Block No. 4, Office 602 34 Norrköping
No. 56, Building No 115, Street 964, Zone P +46 11 31 44 50
56, P. O. Box – 35190 Doha [email protected]
[email protected] www.fischersverige.se
www.fischer.qa

Romania Turkey
fischer fixings Romania S.R.L. fischer Metal Sanayi Ve Ticaret Ltd Sti
Strada Oradiei, Nr. 1-3-5-7 Cevizli Mahallesi, Mustafa Kemal Paşa Cad.
400220 Cluj Napoca, Judetul Cluj Seyit Gazi Sok. No 66, Hukukçular Towers A
P +40 264 455 166 Blok, 34865 Kartal İstanbul
F +40 264 403 060 P +90 216 326 00 66
[email protected] F +90 216 326 00 18
www.fischer.com.ro [email protected]
www.fischer.com.tr

79
fischer catalogue FireStop

80
fischer catalogue FireStop

The information in this catalogue is intended for general guidance only and
is given without engagement. Additional information and advice on specific
applications is available from our Technical Support Team. For this however, we
require a precise description of your particular application.
All the data in this catalogue concerning work with our fixing elements must be
adapted to suit local conditions and the type of materials in use.
If no detailed performance specifications are given for certain articles and
types, please contact our Technical Service Department for advice.

fischerwerke GmbH & Co. KG


72178 Waldachtal
Germany

We cannot be responsible for any errors, and we reserve the right to make
technical and range modifications without notice.
No liability is accepted for printing errors and omissions.

81

You might also like