Ag2020-07 20200327
Ag2020-07 20200327
PURPOSE
Federal incentives, better technology, and a desire for cleaner power are contributing to Distributed
Energy Resources (DER) becoming more common. DER provide unique scenarios not previously
protected by traditional distribution protection schemes. DER connect to Area Electric Power
Systems (Area EPS) through a point of common coupling (PCC). This application guide explains
how to set an SEL-651R Advanced Recloser Control to protect at the PCC to maintain confor-
mance with your interconnection agreement. In developing this application guide, we used IEEE
1547 as the industry-recognized standard for protection at the PCC. This application guide seeks to
help settings developers adhere to this standard while providing them flexibility to accommodate
future revisions to the standard.
OUTLINE
This application guide explains how to modify the SEL-651R-2 default settings file to implement
typical protection at the PCC. The outline is as follows:
➤ Creating a New Settings File
➤ Global Settings
➤ Group Settings
➢ Identifier and Instrument Transformer Settings
➢ Voltage Element Settings
➢ Frequency Element Settings
➢ Directional Element Settings
➢ Overcurrent Element Settings
➢ Power Element Settings
➢ Synchronism Check Element Settings
➢ Close Logic Equations
➢ Trip Logic Equations
➤ Front-Panel Settings
➤ Report Settings
APPLICATION
Figure 1 shows the example system configuration that serves as the basis for this application
guide.
Global Settings
To fully set the SEL-651R, review the settings this section describes to ensure that the device is
configured correctly.
NFREQ, the nominal frequency of the system, is set to a default value of 60 Hz. It can be changed
to 50 Hz.
PHROT, short for phase rotation, is set to a default value of ABC. It can be changed to ACB for
ACB systems.
Figure 3 shows entry of these settings.
The phasing of the lines going through a recloser can be in any orientation, which causes a
challenge in assigning each CT between the recloser and SEL-651R to the correct phase. The
SEL-651R defines the current terminations as I1, I2, and I3. The SEL-651R allows the user to
label the inputs I1, I2, and I3 from the recloser to the phases connected to the system.
The Global setting IPCONN defines the current pole connection. Table 1 displays the different
connection options with the corresponding IPCONN setting.
Table 1 Current Connection Setting IPCONN
CTPOL is a setting that can mathematically manipulate CT polarity. If the value for this setting is
POS, the SEL-651R maintains the polarity of the CTs on the system. If CTPOL is set to NEG, the
CT polarity is effectively inverted. This is useful in defining the direction of the power, impedance,
and directional overcurrent elements.
VYCONN and VZCONN specify how the SEL-651R voltage connections are connected to the
system. As with the current inputs, the voltage inputs are labeled by pole (i.e., V1Y, V2Y, V3Y and
V1Z, V2Z, V3Z) into the SEL-651R. Table 2 displays the voltage selection options for Terminal Y.
Substitute Z for Y in the table to get the voltage selection options for Terminal Z.
Table 2 Voltage Connection Setting VYCONN
VSELECT determines which voltage input, whether VY or VZ, should be used for protection
functions that require three-phase voltage. It also enables loss-of-potential (LOP) protection.
Group Settings
Identifier and Instrument Transformer Settings
Next, as Figure 5 shows, specify the current transformer ratio, potential transformer ratio, and
nominal system voltage.
NOTE: Consult the SEL-651R-2 instruction manual for guidance in setting PTRY, PTRZ, and VNOM when
using low-energy analog (LEA) inputs.
The clearing time is defined as the time between the start of the abnormal condition and the
operating device disconnecting the DER from the Area EPS. For this example, we assume a 3-
cycle recloser clearing time.
The undervoltage and overvoltage elements in the SEL-651R-2 are set in volts secondary. Time
delays can be implemented through the use of SELOGIC variable and timers. The timers are set in
units of cycles. The delay in Table 3 must therefore be converted to cycles to be set correctly in the
SEL-651R-2. The time-delay conversion shown in Equation 1 assumes a measured 60 Hz
fundamental frequency.
60 cycles = 1 s
Equation 1
If we assume a nominal secondary voltage of 120 V phase-to-neutral, Table 4 derives the set points
and the applicable time delays from Equation 1. For the time delays in this example, we assume a
3-cycle recloser clearing time.
Table 4 Interconnection System Response Delay to Abnormal Voltages (VNOM = 120 V)
Voltage Range
Delay Setting (Cycles)
(Volts Secondary)
0.45 • VNOM = 54 9.6 – 3 = 6.6
0.70 • VNOM = 84 120 – 3 = 117
1.1 • VNOM = 132 120 – 3 = 117
1.2 • VNOM = 144 9.6 – 3 = 6.6
The SEL-651R-2 has two sets of voltage inputs, one corresponding to a set of Y terminals (load)
and the other to a set of Z terminals (source). For this setting example (refer to Figure 1), we
consider the utility to be the source and connected to the Z terminals. We consider the DER site to
be the load and connected to the Y terminals.
The SEL-651R-2 has voltage-sensing capability on both sides of the recloser, so we can implement
the voltage elements in close logic for hot-source (energized) and dead-load (de-energized)
supervision. An adequate voltage measurement for determining an energized source is 92 percent
of the rated nominal voltage (VNOM). We can use 15 percent of the rated nominal voltage
(VNOM) to determine the presence or absence of voltage.
The Close Logic Equations section reviews the previous voltage set points in more detail. For this
example, we use both the Y and Z terminals. The SEL-651R-2 uses Relay Word bits that assert
(turn on) or deassert (turn off) based on meeting certain criteria related to set points in the recloser
control. Table 5 lists undervoltage and overvoltage settings and the corresponding Relay Word bits.
Additionally, two elements (59YP1P and 59ZP1P) will be used to verify healthy voltage on both
sides of the recloser.
Table 5 Voltage Settings and Corresponding Relay Word Bits
By using the set points derived in Table 4, we can now add the settings into the SEL-651R-2
setting file, as shown in Figure 6.
Set the input for time-delayed voltage protection similarly for both positive-sequence and inverter-
based DER. However, inverters can respond differently in comparison to conventional rotating
positive-sequence sources and could falsely assert LOP during abnormal system events.
Additionally, voltage elements are the primary protection for inverter-based sources; therefore, not
tripping for a blown fuse could compromise protection. For these reasons, remove NOT LOP from
the input logic for applications where the SEL-651R is used on inverter-based DER.
SV03T, SV04T, SV05T, and SV06T are voltage element-driven timers. To trip the PCC for an
abnormal voltage condition, include these Relay Word bits in the trip logic equation.
The SEL-651R is equipped with six frequency elements with independent timers. Each element
can be set as either an overfrequency or an underfrequency element, depending on the set point. If
the set point exceeds the nominal frequency, the element operates as an overfrequency element. If
the set point is lower than the nominal frequency, the element operates as an underfrequency
element.
For the DER to separate from the Area EPS within the specified time shown in Table 6, recloser
tripping time must be subtracted from the overall clearing time.
Beginning with firmware R408, the SEL-651R allows setting of the frequency time delay in units
of cycles or seconds, as defined by setting E81. When E81 = 1–6, cycles will be the applied units.
When E81 = E1–E6, seconds will be the applied units. Equation 2 illustrates how to use the pickup
setting to convert from seconds to cycles.
For this example, the time delay will be applied in seconds. This example assumes, again, that the
recloser will extinguish the arc in 3 cycles, and this time will be subtracted from the time delay. If
we use the default settings from Table 7, four frequency elements will be necessary.
Table 7 Default Frequency Settings
The SEL-651R-2 has an undervoltage supervision check for all frequency elements that ensures
frequency elements do not operate for a fault condition. A fault condition creates a transient that
can result in incorrect system frequency measurement. Therefore, set 27B81 to assert for all fault
conditions. For this example, the undervoltage supervision check (27B81P) will be set to
70 percent of VNOM. If the measured voltage is less than 27B81P, the frequency elements will be
blocked until the system voltage recovers above the specified threshold.
The Relay Word bits associated with the frequency element time delays are 81D1T, 81D2T,
81D3T, and 81D4T. To trip the PCC for an abnormal frequency condition, include these Relay
Word bits in the trip equation. Note that frequency measurement can come from either the Y or Z
voltage terminal. To detect abnormal and healthy frequency conditions on the Area EPS, regard-
less of the physical state of the recloser, use the source terminals (FSELECT = VZ) for frequency
protection.
The ORDER setting is contingent on many factors including application, source type, transformer
connections, and protection philosophy. Setting guidelines have been published for conventional
rotating positive-sequence sources in [1]. Existing guidelines may need adjusting for inverter-
based DER. The zero-sequence directional element (ORDER=V) has been popularized in recent
years due to the response of inverter-based DER during a fault. All directional settings should be
carefully reviewed especially for these source types. See the SEL-651R-2 instruction manual for
more information on directional element settings.
This example follows the guidance in [1]. Set ORDER to QV and E32 = AUTO2. Additionally, set
50P32P to assert for all three-phase faults within the zone of protection.
During an LOP condition (e.g., blown PT fuse), the Q and V directional elements are impacted and
can be unreliable. Therefore, if ELOP = Y or Y1, the voltage-polarized directional elements are
disabled and blocked from operation. If ELOP = Y1 and an LOP condition occurs, any directional
element-controlled overcurrent element is disabled entirely. However, if ELOP = Y and an LOP
condition occurs, the overcurrent elements that were controlled in the forward direction remain
enabled. For this example, set ELOP to Y.
A coordination study ordinarily determines the selection of pickups, curves, and time dials. This
application guide uses generic values for illustration. Figure 12 shows how to set the
nondirectional phase overcurrent element.
The setting 51PTC is the logic equation that supervises the 51P1 element. When programmed as
51PTC = 1, the element is always enabled. The second-level phase overcurrent element will be
torque controlled for faults in the forward direction (32PF). The second level is enabled through
use of the single-phase overcurrent elements, so each phase should be set identically with respect
to the associated settings. Figure 13 and Figure 14 demonstrate this.
As with the phase overcurrent elements, the ground overcurrent elements will be set to allow
Level 1 to operate regardless of the fault direction and Level 2 will be torque controlled for
forward faults (32GF). Additionally, LT01 resides within the default logic so you can use PB01 on
the front of the device to enable and disable ground elements. The present example maintains that
default logic and use for PB01 (see the settings for the 51GTC and 51G2TC torque-control
equations in Figure 15).
The SEL-651R-2 should perform no automatic reclosing operations following a protective trip at
the PCC. Figure 16 illustrates how to disable the reclosing function for the recloser control.
In this example, as shown in Figure 1, there is a transformer on the DER of the PCC. When the
PCC recloser closes, the utility distribution feeder supplies magnetizing inrush currents that may
result in a sensitive overcurrent element operating during energization. The second-harmonic
blocking logic can prevent this by blocking the overcurrent elements until inrush currents have
subsided. The second-harmonic blocking should be enabled for the previously discussed condi-
tions. A pickup of 10 percent is the default set point, but this may need adjusting based on the spe-
cific installation. To learn how to empirically measure second-harmonic content, refer to
Mitigation of Undesired Operation of Recloser Controls Due to Distribution Line Inrush available
from the Technical Papers listing on the SEL website. Figure 17 shows the applicable settings.
In a distribution system, it is typical for inrush currents to remain above minimum pickups for as
long as 10 cycles. Therefore, a SELOGIC variable and timer could be used to block the overcurrent
elements when the second harmonic content exceeds the threshold. However, the SELOGIC
variable will unblock the element after 10 cycles. Additionally, there can be measurable
second-harmonic content during fault conditions. If second-harmonic content exceeds the
threshold, therefore, the overcurrent element is only delayed by the specified time and not blocked
continuously. It may be desirable to adjust the timer to another value based on the system
configuration.
Figure 18 shows the SELOGIC variable and time configured for this condition.
Figure 18 SELOGIC Variable Settings for Dropout Time Using Harmonic Blocking
Note that we add the logic NOT(HBL2T AND SV10T), as shown in Figure 27, to supervise the
overcurrent elements for inrush conditions, so coordination studies with upstream protection must
use the time-overcurrent settings with a 10-cycle minimum trip response to model this device.
R1
Customer
PCC
Load
VZ VY
SEL-651R-2
Three-phase power elements can be set to operate for power export violations. If the
interconnection agreement includes this constraint, the SEL-651R can be set to detect a power
flow in the reverse direction. For power export violations, set the power element (PWRnT, where
n = 1, 2, 3, or 4) to –WATTS. For other applications that require forward direction power elements,
set the recloser control power element to +WATTS.
Use Equation 3 to calculate the reverse three-phase power element pickup.
WATTs
3PWR1P = -----------------------------
CTR PTR
Equation 3
where:
3PWR1P is the three-phase power element pickup in secondary Watts
WATTs is the desired three-phase power set point in primary Watts
CTR is the current transformer ratio, (xxx/1)
PTR is the potential transformer ratio, (xxx/1)
Through the use of Equation 3, we can calculate the SEL-651R power element pickup setting for
an example primary threshold of 100 kW. Note that a higher PT ratio results in a smaller secondary
power element pickup. For this reason, if you need sensitive power element pickups (such as in a
no-export contract), you may need to use traditional wire-wound PTs rather than the capacitive or
resistive voltage dividers commonly available with the attached recloser.
CTR: 500/1
PTR: 120/1
100 kW
3PWR1P = -------------------- = 3.34 VA
60 500
Equation 4
A minimum time delay of 5 cycles prevents the power elements from operating during system
transients. In some cases, it may be desirable to use the NOT of an overcurrent element (51P) to
supervise the power element. This can prevent lack of coordination with other protection elements.
For this example, a 10-cycle delay provides added security. Figure 20 shows how to specify these
settings into QuickSet.
Additional three-phase power elements are available and can be used for additional
interconnection guidelines such as satisfying minimum import criteria. The Relay Word bit
3PWR1 may be used in the TR logic equation to trip the recloser through use of the power
element.
The Relay Word bit 25A1 asserts once the two sources are synchronized within the voltage,
frequency, and angle windows, and the bit may now be used to supervise a close command in the
close logic equation of the SEL-651R.
When you issue either a local or remote close, it is possible that the supervision logic is not
immediately satisfied. It may therefore be desirable to add a timer that allows a close within a
specified time window. If that window expires prior to a close, it would be necessary to reinitialize
the close logic. If the supervision logic evaluates as a true condition anytime during the specified
time window, the SEL-651R-2 issues the close. The logic in Figure 22 illustrates the close
permissive and timer logic.
where:
PB11_PUL is the front-panel CLOSE pushbutton
LT05 is the front-panel PUSH BUTTONS LOCKED pushbutton (and thus is in the unlocked
state)
CC3 is the remote close
LT03 is remote functions enabled
SV01 is the close permissive and timer
The default SEL-651R-2 includes several unused AUX pushbuttons that can be programmed for
custom functions. Pushbutton 10, for example, can be used to enable and disable automatic
restoration close permissive logic. Figure 23 shows the logic to enable and disable the automatic
restoration feature.
Figure 23 Setting Latch 10 Using Pushbutton 10 for Automatic Restoration Close Permissive
Logic
where:
PB10_PUL is the front-panel automatic restore enable and disable
LT10 is the automatic restore logic enable
Automatic restore logic can be applied when the PCC recloser control (SEL-651R-2) detects that
the utility has islanded and tripped. After the utility source is reconnected to the feeder, and all
three-phases remain healthy for a specified time, the automatic restore logic issues a close permis-
sive. Figure 24 shows this logic.
Figure 24 Setting SELOGIC Variable 09 for Automatic Restoration Close Permissive Logic
where:
SV09T is the restore close permissive
The close permissive, which incorporates the Relay Word bits SV08 and SV09T, can be included
(as shown in Figure 25) in equations CL3P and ULCL3P.
To alert the user of a forthcoming close, use another SELOGIC variable as an oscillator that will
flash both RECLOSER OPEN and RECLOSER CLOSED LEDs. Figure 26 displays this oscillator logic.
SV07T will be incorporated in control LED settings PB11_LED and PB12_LED, as shown in
Figure 34.
Close Logic Equations on page 21 explains how to achieve this. As suggested by the automatic
restore logic timer, it is necessary to wait some time to verify that the system is stable. Five
minutes is typical and was used in the example.
SYS
IFAULT FAULT
ISYS
EPS
SEL-651R
PCC IFAULT
MIRRORED BITS ® SEL-651R
Communications
DER
The utility recloser control in this example is also an SEL-651R, but it could be any feeder
protective recloser control. The SEL-651R at the breaker sends a DTT over MIRRORED BITS
communications to the PCC SEL-651R. Once the upstream breaker recloses and holds closed for a
set time, the reclose reset (79RS) Relay Word bit asserts. The PCC SEL-651R uses the VZ
terminals to measure the utility voltage and begins a 5-minute timer. During these 5 minutes, the
recloser control analyzes system voltages and frequency to verify that they are healthy. If they
remain healthy for 5 minutes and the two systems are synchronized, the PCC SEL-651R closes the
recloser. For the MIRRORED BITS communications, transmitted bits include TMB1A–TMB8A
(Channel A) and TMB1B–TMB8B (Channel B). The received bits in the PCC SEL-651R are
RMB1A–RMB8A and RMB1B–RMB8B.
If the PCC SEL-651R receives DTT via transmit MIRRORED BITS from the upstream SEL-651R
and the recloser is closed, the recloser should trip. The trip logic shown in Figure 29 contains the
elements necessary for such a trip.
The upstream device begins its reclosing cycle. If it recloses and the fault has cleared, the device
enters the reset state after a specified delay. As described by the automatic restore close logic, if
the utility remains closed in on the line and the voltage is healthy for the specified time, the PCC
issues a close permissive to restore the PCC connection.
Front-Panel Settings
Targeting on the front of the recloser control is an initial visual of the type of event that occurred.
Consider Figure 30. Note that the LED targeting on the recloser control front panel includes
phases, ground, voltage elements, frequency elements, reclosing state, and other elements. You can
program and relabel these LEDs as you want.
It is necessary to program only a few of these LEDs in the RDB file to other than what exists in the
default settings. Notice that Trip Latch T_LED is set to Y for these elements. If setting
TxxLEDL = Y, and a trip occurs while the individual LED equation is true, the Txx_LED remains
latched in.
Figure 31 displays the logic added to LEDs 11 and 12 for frequency and voltage, respectively.
Add the Level 1 power element to LED 18, as shown in Figure 32.
Apply the logic in Figure 33 to illuminate LEDs 22–24 for healthy voltages on the Z terminals.
Within the Close Logic Equations, PB10 was programmed to enable and disable the automation
restoration close logic. If you use this logic, also program the PB10_LED to display the status.
Figure 34 includes the logic necessary for you to use this feature to view automation restoration
close status from the front panel. Additionally, SELOGIC Variable 07 is added to equations
PB11_LED and PB12_LED. This logic alerts the user by flashing both the RECLOSER CLOSED and
RECLOSER OPEN pushbutton LEDs when an imminent close is possible (SV08 or SV09 are asserted).
A display point message can also be programmed to provide additional clarification that an
imminent close is in progress. Display Point 01 (DP01) provides indication that the close
permissive logic is initiated and timing is as defined by SV08. Also, SV09 is assigned to Display
Point 02 (DP02) to provide indication that the automatic restoration close logic is initiated and
timing.
Report Settings
The report settings are essential for troubleshooting and verifying the intended behavior of the
control. To ensure that the SEL-651R archives relevant data for these purposes, map elements in
which you are interested to the SER and ER equations.
For this example, we incorporated additional elements into equations SER3 and SER4, as shown in
Figure 36 and Figure 37, respectively.
For this example, as shown in Figure 38, we incorporated additional elements into the ER
equation.
CONCLUSION
The SEL-651R Recloser Control offers comprehensive protection at the PCC that includes the
voltage and frequency-tripping requirements established by the industry-recognized standard,
IEEE 1547. This application guide demonstrates how to take a default SEL-651R-2 settings file
and configure SELOGIC to apply IEEE 1547 setting guidelines in addition to common protection
and control used at the PCC.
SELOGIC Equations
SV04PU := 6.50
SV04DO := 0.00
SV04 := 27ZA2 OR 27ZB2 OR 27ZC2 #Undervoltage Level 2 (Inverter-Based Source)
SV04 := (27ZA2 OR 27ZB2 OR 27ZC2) AND NOT LOP #Undervoltage Level 2
(Positive-Sequence Sources)
SV05PU := 117.00
SV05DO := 0.00
SV05 := 59ZA2 OR 59ZB2 OR 59ZC2 #Overvoltage Level 1
SV06PU := 6.50
SV06DO := 0.00
SV06 := 59ZA3 OR 59ZB3 OR 59ZC3 #Overvoltage Level 2
SV07PU := 30.00
SV07DO := 30.00
SV07 := (SV08 OR SV09) AND NOT SV07T #IMMINENT CLOSE OSCILLATOR
SV08PU := 3600.00
SV08DO := 0.00
SV08 := (PB11_PUL AND LT05 OR CC3 AND LT03) AND NOT TRIP3P OR SV08
AND NOT SV08T AND NOT TRIP3P AND NOT CLOSE3P # CLOSE PERMISSIVE
AND TIMER
SV09PU := 18000.00
SV09DO := 0.00
SV09 := 3P59Z AND NOT TRIP3P AND NOT CLOSE3P AND NOT 52A3P AND
LT06 AND LT10 #AUTOMATIC RESTORE CLOSE PERMISSIVE
SV10PU := 0.00
SV10DO := 10.00
SV10 := R_TRIG HBL2T
Latch Bits Set/Reset SET10 := PB10_PUL AND NOT LT10 AND LT05 #AUTO RESTORE ENABLED
SELOGIC Equations RST10 := PB10_PUL AND LT10 AND LT05 #AUTO RESTORE DISABLED
SELOGIC Equations
CL3P := (SV08 OR SV09T) AND (3P59Z AND 3P27Y OR 25A1) AND FREQOK
AND NOT 81D5 AND NOT 81D6 AND LT06 AND TCCAP # CLOSE FROM
PUSHBUTTON SUPERVISED BY LOCK. ALL CLOSING SUPERVISED BY HOT
Close Logic Equations LINE TAG (LT06) AND TRIP/CLOSE CAPACITOR (TCCAP)
Operator Control
PB11_LED := 52A3P # RECLOSER CLOSED
LED Settings
REFERENCES
[1] K. Zimmerman and D. Costello, “Fundamentals and Improvements for Directional Relays,”
presented at the 37th Annual Western Protective Relay Conference, October 2010. Available:
selinc.com.
TECHNICAL SUPPORT
We appreciate your interest in SEL products and services. If you have questions or comments,
please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.338.3838
Fax: +1.509.332.7990
Internet: selinc.com/support
Email: [email protected]