DOC-00136 - Control - System - Installation - and - Operation - Rev - D - 170618 Print REV3
DOC-00136 - Control - System - Installation - and - Operation - Rev - D - 170618 Print REV3
Note: This manual is relevant only to the Jazz 20 controller and above.
This manual supports all zones (Safe and Ex) and all filters from single to 4 screen units.
Copyright © 2015-2017 Filtersafe®, All rights reserved.
The data contained in this document is proprietary to Filtersafe®. It is disclosed to the receiving party only for
the sole purpose stated herein, and shall not be disclosed by the receiving party to any third party, and shall
not be duplicated, used or disclosed in whole or in part for any purpose other than the purpose specifically
stated.
This publication, or any parts thereof, may not be reproduced in any form without the express written
permission of Filtersafe®.
NOTE
All specifications in this manual are subject to change without notice.
P ublished by Filtersafe ®
M arch 2017
Contact Filtersafe®
To communicate with a Filtersafe® representative, use the following contact information:
Israel
Address: HaElla Street, P.O.B 23, Tefen Ind. Zone 2495900
Phone: +972-4-9873620/1
Fax: +972-4-9873617
Email: [email protected]
Web www.filtersafe.net
Germany
Address: Papenreye 55, Unit 11, 22453 Hamburg
Phone: +49-(0)151 5111 9622
Email: [email protected]
Singapore
Address: 56 Toh Tuck Road, #07-02 Signature Park, Singapore 596746
Phone: +65-8321-3739
Email: [email protected]
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 2 of 60
Authorization
Signature
Revision 02 Approval Name Date approved
Mark X
(HC only)
Revision History
Rev. Description of Revisions Changed by: Date/Sign
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 3 of 60
Table of Contents
1. Preface ..............................................................................................1-6
2. Safety ................................................................................................2-7
2.1 Cautions ....................................................................................................................... 2-7
2.2 General Safety Cautions .............................................................................................. 2-7
3. Introduction ......................................................................................3-8
3.1 System Overview ........................................................................................................ 3-8
3.2 System Purpose ........................................................................................................... 3-8
4. Operating Principles..........................................................................4-9
4.1 Filter Functions.......................................................................................................... 4-10
4.2 Active Components of the Filter ............................................................................... 4-11
4.3 Scanner Movement .................................................................................................... 4-13
4.4 Flushing Cycle ........................................................................................................... 4-13
4.5 Conditions that Initiate an Auto Flushing Cycle ....................................................... 4-14
4.6 Flushing Cycle Options ............................................................................................. 4-14
4.7 Manual Flushing ........................................................................................................ 4-15
4.8 Remote Flushing........................................................................................................ 4-16
5. Control Cabinet Overview .............................................................. 5-17
5.1 Control Panel ............................................................................................................. 5-18
5.2 Controller................................................................................................................... 5-19
5.3 Control Cabinet – Inside View .................................................................................. 5-20
6. Installation ..................................................................................... 6-21
6.1 Mounting ................................................................................................................... 6-21
6.2 Wiring ........................................................................................................................ 6-21
7. Setup .............................................................................................. 7-22
7.1 Introduction ............................................................................................................... 7-23
7.2 Displaying the Setup Menu ....................................................................................... 7-23
7.3 Flushing Parameters .................................................................................................. 7-24
7.4 Optional Flushing Pump Parameters ......................................................................... 7-26
7.5 IP Parameters ............................................................................................................. 7-27
7.6 Controller Name ........................................................................................................ 7-28
7.7 Pressure Transmitter Settings .................................................................................... 7-28
7.8 Analog DPT Settings ................................................................................................. 7-29
7.9 Minimum Flushing Time........................................................................................... 7-30
7.10 Exiting the Setup Menu ............................................................................................. 7-30
8. Service and Testing ........................................................................ 8-31
8.1 Displaying the Service Menu .................................................................................... 8-31
8.2 Returning to the Main Screen .................................................................................... 8-31
8.3 Service Menu Screens ............................................................................................... 8-32
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 4 of 60
8.4 Testing the Scanner Limit Sensors and Motors......................................................... 8-33
8.5 Testing the Pump ....................................................................................................... 8-36
8.6 Testing the Flushing Valve........................................................................................ 8-37
8.7 Testing the MPI Devices ........................................................................................... 8-37
9. Operation ....................................................................................... 9-38
9.1 Power Up ................................................................................................................... 9-39
9.2 Controller Operating Screens .................................................................................... 9-39
9.3 Messages and Indicators ............................................................................................ 9-40
10. Technical Specifications ............................................................... 10-45
10.1 Power Supply .......................................................................................................... 10-45
10.2 Control Panel Components ...................................................................................... 10-45
11. Annex A: Controller Inputs and Outputs ..................................... 11-46
11.1 Inputs ....................................................................................................................... 11-46
11.2 Outputs .................................................................................................................... 11-48
12. Annex B: Modbus Specifications .................................................. 12-49
12.1 Modbus Word Registers .......................................................................................... 12-49
12.2 Word Register Bit Map ........................................................................................... 12-52
13. Annex C: PLC Program Upgrade .................................................. 13-53
14. Annex D: Interface Logic ............................................................. 14-54
14.1 Pump Interface Logic .............................................................................................. 14-54
14.2 Filter Interface Logic ............................................................................................... 14-55
15. Annex: E: Setup Values Form ....................................................... 15-56
16. JAZZ 20 BATTERY REPLACEMENT ................................................ 16-57
17. User Notes .................................................................................... 17-60
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 5 of 60
1. Preface
Manual Purpose
The Filter Control System Installation and Operation Manual is designed for the use of authorized operators
and technicians of the Filter Control System. This manual reviews the most common procedures required
during the operation and maintenance of the Filter Control System.
This manual is associated with Safe Zone, Ex d and Ex ia model filters. The Filter Control System is used to
control single filters and multi-filter systems. The images and illustrations are for demonstration only and may
not reflect the exact hardware included in your filter model.
Applicable Documents
BS025-BS200 Operation Manual (P/N 00144)
BS300/BS400 Automatic Screen Filter Operation Manual (P/N DOC- 00142)
Compact Model Operation Manual (P/N DOC- 00157)
Multi-Screen Filter Operation Manual (P/N DOC- 00141)
Safe Zone Data Sheets (P/N DOC 00159)
Ex d Model Operation Manual Appendix (P/N DOC- 00155)
Ex ia-1 Appendix (P/N DOC-0000309)
Ex ia-0 Appendix (P/N DOC-0000310)
Note:
Filtersafe® takes extreme care in packaging the equipment to protect it against damage during shipment.
Upon receipt, inspect all shipment contents and in case of damage, contact Filtersafe® immediately.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 6 of 60
2. Safety
This chapter contains an overview of the Filter Control System safety concerns and includes:
Section 2.1: Cautions
Section 2.2: General Safety Cautions
2.1 Cautions
CAUTION
CAUTION: Filters may flush automatically, without prior warning.
The following instructions and guidelines are necessary to ensure safe operation and long filter life.
Before performing any work on the filter, become familiar with the following safety sections:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 7 of 60
3. Introduction
This manual describes installation and operation of the Filter Control System for Filtersafe automatic single
screen and multi-screen filters.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 8 of 60
4. Operating Principles
This chapter describes operating principles of the filter and control system and includes the following:
Section 4.1: Filter Functions
Section 4.2: Active Components of the Filter
Section 4.3: Scanner Movement
Section 4.4: Flushing Cycle
Section 4.5: Conditions that Initiate an Auto Flushing Cycle
Section 4.6: Flushing Cycle Options
Section 4.7: Manual Flushing
Section 4.8: Remote Flushing
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 9 of 60
4.1 Filter Functions
The Filtersafe Automatic Screen Filter performs two primary functions:
Filtering – raw water flows into the filter and comes out clean
Flushing – the filter screens are cleaned
4.1.1 Filtering
During filtering:
Raw water flows through the filter inlet pipe and through the filter screen.
Solids and dirt particles are caught by the screen.
Clean water exits the system through the filter exit pipe.
4.1.2 Flushing
During flushing:
The Flushing Valve is open.
The Flushing Pump is operating.
The Scanner motor is operating.
The screen is cleaned.
Dirt is flushed from the system.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 10 of 60
4.2 Active Components of the Filter
Note: Components vary according to application.
4.2.1 Scanner
The scanner is a set of nozzles rotated by a Drive Unit that cleans the filter screen during
Flushing.
The scanner moves in a helical motion causing the nozzles to run back and forth across the
screen.
See section 4.3: Scanner Movement.
4.2.2 Drive Unit
The drive unit powers the Scanner operation.
The different filter models have different types of drive units (motor + Gear):
• Safe zone – standard electric motor
• Ex d – Ex d electric motor
• EX ia – air operation motor
4.2.3 Limit Sensor
A Scanner includes two limit sensors that control the Scanner Movement (see section 4.3).
The limit sensors are normally closed (NC).
The different filter models have different types of limit sensors:
• Safe zone – mechanical limit switches or proximity sensors
• Ex models – mechanical limit switches or proximity sensors
4.2.4 Flushing Valve
The flushing valve is a normally closed valve and is opened during Flushing.
The open valve creates a pressure differential between the filter inlet and the atmospheric
pressure at the flushing outlet. This differential creates suction at the scanner nozzles.
4.2.5 Optional Flushing Pump
The flushing pump is connected to the flushing pipe.
The flushing pump helps relieve water pressure head in the downstream flow.
The flushing pump increases the suction pressure at the scanner nozzles.
The flushing pump is powered and controlled from the Filtersafe control cabinet or the customer
control system.
4.2.6 Optional Flow Switch
The optional flow switch indicates the water flow at the flushing water outlet.
The flow switch sends a signal to the control cabinet.
The flow switch provides pump protection in case of a valve fault.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 11 of 60
4.2.7 DPT
The DPT (Differential Pressure Trigger) indicates the differential pressure between the filter upstream
(incoming) water and the downstream(outgoing) water. Dirt buildup on the screen changes the pressure
differential between the upstream raw water pressure and the downstream clean water pressure.
The filter includes one of the following DPT options:
Differential Pressure Switch – default option
Analog Differential Pressure Transmitter – provides an analog signal
Analog Pressure Transmitters – includes two analog transmitters: one for upstream and one
for downstream
4.2.8 Optional Alert Switches
The following optional switches can be connected to the Controller:
Differential Pressure Switch with Alarms –high DP outputs
Pressure Switch – located in the upstream; alarm options:
• High upstream pressure
• Low upstream pressure (alert on low flushing pressure)
• Contact Filtersafe for additional options
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 12 of 60
4.3 Scanner Movement
Scanner movement proceeds as follows (see Figure 4-1):
1. The Drive Unit starts, causing the Scanner to rotate in a spiral movement.
2. When the Scanner reaches the end of its travel, a disk on the Scanner shaft activates the Limit Sensor.
3. The motor changes direction, causing the Scanner to rotate in the opposite direction.
4. When the Flushing Cycle signal ends, the Scanner moves to the next Limit Sensor and stops.
5. After Remote Flushing the Scanner continues until it reaches the HOME position and then stops.
Note: The description is relevant to automatic mode flushing. In manual flushing (see section 4.7: Manual
Flushing), the Scanner stops moving as soon as the flushing is turned off, even if it did not reach a Limit
Sensor.
Figure 4-1: Scanner M ovem ent
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 13 of 60
4.5 Conditions that Initiate an Auto Flushing Cycle
To configure Flushing Cycle settings, see chapter 7: Setup.
This section describes conditions that initiate an auto Flushing Cycle in filter automatic mode:
4.5.1 DPT Signal
The DPT (see section 4.2.7) indicates pressure
differential that requires a Flushing Cycle. The
Flushing Cycle starts after a predefined delay time.
The Flushing Cycle ends after meeting all of the
following conditions:
DPT is off
DPT Off delay timer exceeds its set point
Minimum flushing time exceeds its set point
Scanner reaches its stop position.
Note: There is a three second delay between reaching the pressure differential set point and initiation of the
Flushing Cycle.
Note: When the system is at rest, timer operation is disabled until one DPT initiated Flushing Cycle occurs.
When performing Remote Flushing (see section 4.8) the timer goes into rest mode until one DPT initiated
Flushing Cycle occurs.
Note: It is recommended to set the timer to initiate a Flushing Cycle every 45 minutes.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 14 of 60
4.6.2 DPS Off Delay
When the DPT turns off, the DPS Off Delay
extends the Flushing Cycle for a preset amount of
time. This is to prevent rapid flushes in very dirty
water. It is recommend to set this delay preset to
half of the scan cycle.
To define the DPS Off Delay time, see DPS Off
Delay screen pg. 7-25.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 15 of 60
4.8 Remote Flushing
Remote flushing is initiated manually using the customer controller. After the controller signal is terminated,
flushing stops when the Scanner reaches the HOME position (see section 4.3: Scanner Movement).
During the remote flushing procedure:
The flushing switch on the Control Panel must be in Auto position.
A command signal is sent from the central control system.
The Timer Operation enters rest mode (see section 4.5.2).
The filter enters Flushing (see section 4.1.2) until the flushing trigger is off.
The Scanner reaches the HOME position.
Flushing Cycle stops.
Note: Remote flushing can be initiated by pressing and holding the 4 button on the Controller or directly
from the I/O in the control cabinet (see electrical diagrams).
Note: Remote flushing must be initiated after each filtration session and after each Manual Flushing.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 16 of 60
5. Control Cabinet Overview
This chapter describes the parts of the control cabinet and includes:
Section 5.1: Control Panel
Section 5.2: Controller
Section 5.3: Control Cabinet – Inside View
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 17 of 60
5.1 Control Panel
The control panel includes:
Main power switch (1) – turns ON and OFF the filter power.
Controller (4)– see section 5.2
Power indicator (6) – lights up when the main power switch is ON and power is present in the
system.
Alarm indicator (5) – indicates alarm events and includes the following states:
• Blinking – alarm (view alarm message on the Controller display screen).
• Constant – attention is required (view alarm message on the Controller display screen).
Flushing control switch (3) – includes the following settings:
• AUTO – Flushing Cycle activation is controlled by the control system.
• MAN – flushing operates continuously (see section 4.7: Manual Flushing).
• 0 – automatic and manual functions are disabled and alarm is reset.
Flushing indicator (2) – includes the following states:
• Constant – the system is ready (standby).
• Blinking – the system is in Flushing.
Pump control switch (8) – controls the Flushing Pump; includes the following states:
• AUTO – pump activation is controlled by the system.
• MAN – pump is activated continuously.
• 0 – pump is OFF.
Pump indicator (7) – indicates the flushing pump status and includes the following states:
• Constant – pump is ready (standby).
• Blinking – pump is operating.
Figure 5-1: Control P anel
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 18 of 60
5.2 Controller
The controller is used to perform Setup (see chapter 7) and Service and Testing (see chapter 8)) and displays
System Information Screens (see section 9.2.2). The controller includes:
Display screen (3) – displays the current system procedure and alarm messages.
Navigation buttons (1) – used to scroll through the controller menus.
Number pad (2) – used to enter numeric settings.
Enter button (4) – used to advance the screens and enter values.
Figure 5-2: Controller
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 19 of 60
5.3 Control Cabinet – Inside View
The control cabinet inside view includes:
Terminal blocks (1)
Contactors (2)
Overload switches (3)
Power supply (4)
Fuses (5)
Relays (6)
Figure 5-3: Control Cabinet – Inside View
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 20 of 60
6. Installation
6.1 Mounting
Install the control cabinet in a dry, secured area.
Fasten the control cabinet to a strong stable wall or other stable installation site.
6.2 Wiring
CAUTION
CAUTION: The control cabinet must be connected by a certified electrician.
CAUTION
CAUTION: The installation must meet or exceed all electrical codes.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 21 of 60
7. Setup
This section describes the tasks associated with using the controller for setting up the filter operation
parameters and includes:
Section 7.1: Introduction
Section 7.2: Displaying the Setup Menu
Section 7.3: Flushing Parameters
Section 7.4: Optional Flushing Pump Parameters
Section 7.5: IP Parameters
Section 7.6: Controller Name
Section 7.7: Pressure Transmitter Settings
Section 7.8: Analog DPT Settings
Section 7.9: Minimum Flushing Time
Section 7.10: Exiting the Setup Menu
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 22 of 60
7.1 Introduction
7.1.1 Instruction Tables
The following sections contain tables that illustrate how to use the controller menus:
The first column contains a Description of the function of the relevant controller screen.
The second column contains an image of the screen as it appears on the controller and
Instructions for using the controller buttons for the relevant screen.
7.1.2 Entering Numeric Values
To enter a numeric value for one of the controller menus:
2. Press the _ button to enter edit mode.
3. Use the number pad to enter a value.
4. Press the button _ to set the value.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 23 of 60
7.3 Flushing Parameters
The following table shows cycle times for different filter models.
Description Instructions
Number of Screens – define the amount of
screen units used in the filter.
Note: The number is selectable only in controller Enter a value from 1 – 4 to define the
application version M5-4A-00. In version M5-1-00 number of filter screens.
only 1 screen is available.
Operation Mode Selection – select how many
screen units operate at one time during Flushing.
In multi-screen filters, Scanners can operate
sequentially. Each Scanner operates until it 1 – 1 Group Flush: all scanners
reaches the Limit Sensor (see section 4.3: operate together
Scanner Movement), and then the next Scanner in 2 – 2 Group Flush: the filter is divided
the sequence operates. into 2 groups –
Default setting: Safe Zone - 1 Group Flush In filters with 2 screens, one
Exd - 1 Group Flush screen unit operates at a time.
Ex ia - 2 Group Flush In filters with 4 screens, 2
screen units operate at a
Note: This mode is selectable only with a multi time: first scanners 1 and 2,
controller with application version M5-4A-00. In then scanners 3 and 4.
version M5-1-00 only 1 group is available. 3 – Sequential Flush: one screen unit
operates at a time
Cycle Time – define the time it takes the Scanner
to move from one Limit Sensor to another (see
section 4.3: Scanner Movement).
This setting is required to measure Limit Sensor _ – press once to edit the value; use
error. An error is a greater than 20% delay of a the press again to set the value
stroke.
Default setting: according to the filter model (see
above table).
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 24 of 60
Description Instructions
MPI 0 (Multi-Purpose Input 0) Function
Several optional devices can be connected to the
controller input # 0 (on single filter system) or input
#2 (on multi filter). 0 – Not Used: Function not used.
This option defines what is connected to this input 1 – Flow Switch: Flow Switch output
and enables the function of the selected device. contact.
Default setting: Not Used (0). 2 – High PR Alarm: connected to the
For more details, refer to the electrical drawings. Pressure Switch.
3 – High DP Alarm: connected to the
Differential Pressure Switch with
Alarms.
4 – Low Inlet Pressure Alarm:
connected to the Pressure Switch.
Flow Error Delay – when the flow switch is
connected to I2, the function delays activation of
the flow error alarm.
See section 4.2.6: Optional Flow Switch. _ – press once to enter a value; press
Default setting: 10 again to set the value
MPI 1 (Multi-Purpose Input 1) Function
Several optional devices can be connected to the
controller input # 1 (on single filter) or input #0 (on
multi filter). 0 – Function not used.
This option defines what is connected to this input 1 – Flushing DPS: DPT output.
and enables the function of the selected device.
2 – High DP Alarm: connected to the
Default setting: Flushing DPS (1).
Differential Pressure Switch with
For more details, refer to the electrical drawings.
Alarms.
3 – High PR Alarm: connected to the
Pressure Switch
DPS Off Delay – defines the time that delays the
DPS output when it switches Off.
See section 4.6.2: DPS Off Delay.
Default setting: 20. _ – press once to enter a value; press
again to set the value
Timer Operation – when activated, a maximum
time between Flushing Cycles can be defined (see
section 4.5.2: Timer Operation and next control).
Default setting: Not Used (0). 0 – Timer Operation is not used
1 – Timer Operation is used
Timer Interval – defines the maximum allowed
time without screen flushing. The Flushing Cycle is
initiated automatically after the interval has
passed. _ – press once to enter a value; press
See section 4.5.2: Timer Operation. again to set the value
Default setting: 45
Timer Cycle Interval – defines the number of
Scanner Movement cycles for each flushing
initiated by a Timer Interval.
Default setting: 1 Enter a value from 1 – 9 .
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 25 of 60
7.4 Optional Flushing Pump Parameters
Description Instructions
Pump Enabling – defines if the Flushing Pump is
used in the system.
Default setting: Used (1).
0 – flushing pump is not used
1 – flushing pump is used
Pump Ready Signal – defines if the Controller
receives a Flushing Pump ready signal input and
activates an alarm if this input is not received.
Default setting: Enabled (1) 0 – pump ready signal is disabled
1 – pump ready signal is enabled
Pump Run Signal – defines if the Controller
receives a Flushing Pump run signal input and
activates an alarm this such input is not received.
Default setting: Enabled (1) 0 – signal disabled
1 – signal enabled
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 26 of 60
7.5 IP Parameters
7.5.1 Setting IP Parameters
Define the IP settings by selecting the relevant segment and editing the numbers in the selected segment.
The X represents the segment to be edited.
Note:
Each IP segment value must be between 000 and 255.
To define an IP setting:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 27 of 60
7.5.2 IP Parameters
The following table describes the different IP parameters.
Description Instructions
Local IP – defines in four segments the controller
IP address. Each segment is defined on a different
screen.
Sub Net Mask – defines the IP mask in four
segments.
Each segment is defined on a different screen.
Gateway IP – defines in four segments the
network gateway address.
Each segment is defined on a different screen.
ModBus Loc Port – defines the Local ModBus
TCP communication port.
(See chapter 12: Annex B: Modbus
Specifications.)
Default setting: 502
Description Instructions
PT0/PT1 Zero Set – type the zero set value found
on the Analog Pressure Transmitters label at 4ma.
Default setting: 0
1. Define the value for PT0.
2. Advance to the next screen to
define the value for PT1.
PT0/PT1 Span Set – type the span set value
found on the Analog Pressure Transmitters label at
20ma.
Default setting: 0 1. Define the value for PT0.
2. Advance to the next screen to
define the value for PT1.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 28 of 60
7.8 Analog DPT Settings
The following settings are associated with the DPT and optional alert switches with analog output.
All values are in millibar.
Description Instructions
Upstream Low Pressure Set Point – defines the
set point for the upstream low pressure alarm.
Default setting: 1600
Upstream High Pressure Set Point – defines the
set point for the upstream high pressure alarm.
Default setting: 6000
Differential Pressure Flush – defines the DPT set
point for initiating flushing.
Default setting: 400
Differential Pressure Hysteresis – defines the
defines the set point for stopping the DPT flushing
signal.
Example: if the Differential Pressure Flush is set
to 400 mb and the Hysteresis is set to 150 mb,
the request for flush starts when DP reaches 550
mb and will remain until DP falls below 250 mb.
Default setting: 150
Alarm Set Point – defines the high alarm set point
for the Differential Pressure Switch with Alarms.
Default setting: 1000
Zero 4ma – set the reading for the zero level of the
analog inputs. This setting is performed when all
analog inputs are at zero level only.
Note: Do not perform this function if the readings Press 1 to zero analog readings.
are accurate.
Sel. AN. (Select Analog) – defines analog
sensors used in the system.
Default setting: No analog sensors (0)
Enter on of the following values:
0 – no analog sensors
1 – PT0: upstream, PT1: disabled
2 – PT0: upstream, PT1: downstream
3 – PT0 is disabled, PT1 is connected
to the Analog Differential Pressure
Transmitter
4 – PT0 is upstream, PT1 is connected
to the Analog Differential Pressure
Transmitter
5 (for version 3.1) – Current - the
Flushing Pump motor current.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 29 of 60
7.9 Minimum Flushing Time
Description Instructions
Minimum Flushing Time – the minimum amount
of time to sustain a Flushing Cycle regardless of
the DPT signal.
See section 4.6.1: Minimum Flushing Time).
Default setting: 0
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 30 of 60
8. Service and Testing
This section describes the controls for servicing and testing the system.
Note: The tasks in this section must be performed by an authorized Filtersafe technician.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 31 of 60
8.3 Service Menu Screens
Description Instructions
Ethernet Status – displays the connection status
of the Ethernet connection.
Three possible states:
Not Attached – no module installed
Attached – module installed and working
Connected – client connected to PLC
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 32 of 60
Description Instructions
Valve Test Results – tests the Flushing Valve
For full test instructions, see section 8.6: Testing
the Flushing Valve.
View the following values: 1 – test V1
FS – flow switch status 2 – test V2
V1 – flushing valve 1
V2 – flushing valve 2
Multi-Purpose Input A Staus – displays the
status of the optional device or function that is
connected to MPI . The top line of the screen
shows the name of the connected device or
function.
See section 8.7: Testing the MPI Devices
Multi-Purpose Input B Status – displays the
status of the optional device or function that is
connected to MPI . The top line of the screen
shows the name of the connected device or
function.
See section 8.7: Testing the MPI Devices
Analog Readings – view DPS readings for:
Upstream pressure
Downstream pressure
Press the button to scroll through the
Pressure Differential different readings.
Current pump reading (for ver. 3.1)
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 33 of 60
8.4.2 Testing the Limit Sensors
To test the proper functioning of the Scanner Limit Sensors:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 34 of 60
8.4.3 Testing the Scanner Motors
To test the proper functioning of the Scanner motors:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 35 of 60
8.5 Testing the Pump
Note: The Pump Test screen is only displayed when the Flushing Pump is enabled (see section 7.4: Optional
Flushing Pump Parameters).
To test the proper functioning of the Flushing Pump:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 36 of 60
8.6 Testing the Flushing Valve
This section describes testing the proper functioning of the Flushing Valve and the Flow Switch. 0 indicates
the output is OFF and 1 indicates that the output is ON.
To test the proper functioning of the Flushing Valve and the Flow Switch:
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 37 of 60
9. Operation
This section describes filter startup and operation. For more information, refer to the Startup and First
Operation section in the relevant filter operation manual.
Section 9.1: Power Up
Section 9.2: Controller Operating Screens
Section 9.3: Messages and Indicators
For more information, refer to the Startup and First Operation section in the relevant filter operation manual.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 38 of 60
9.1 Power Up
To power up the filter in automatic mode:
Description Instructions
When in operating mode, the controller screen
displays:
Filter Status (1) – displays the operating
status of the filter (see section 9.3.1: Filter
Status Messages and Indicators).
Alarm Messages (2) – displays specific
information about alarm events (see section
9.3.2: Alarm Event Messages and Indicators).
Description Instructions
Flushing Cycle History – displays how long ago
the last flushing cycle occurred and how many
flushing cycle have occurred since the filter was
installed. Press the button to display this
screen.
The display returns to the main screen
after a few seconds.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 39 of 60
Description Instructions
Analog Readings – view DPS readings for:
Upstream pressure
Downstream pressure
Press the button to display this
Pressure Differential screen.
Current pump reading (for ver. 3.1) Press the button to scroll through the
different readings.
Flushing Relay
Status Relay
Green Pump
Description/
Red Alarm
Controller
DP Relay
Indicator
Indicator
Indicator
Display
Action
Couse
Signal
Alarm
Relay
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 40 of 60
9.3.2 Alarm Event Messages and Indicators
The following table contains messages that are associated with alarm events and are displayed on the lower
line of the controller Main Screen.
Description/
DP Relay
Indicator
Indicator
Indicator
Flushing
Flushing
Display
Action
Status
Couse
Signal
Green
Green
Alarm
Alarm
Pump
Relay
Relay
Relay
Red
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 41 of 60
Description/
DP Relay
Indicator
Indicator
Indicator
Flushing
Flushing
Display
Action
Status
Couse
Signal
Green
Green
Alarm
Alarm
Pump
Relay
Relay
Relay
FLOW Red
Const Blink OFF ON OFF N/R N/R Warning Pump is on Check flow,
ERROR alarm, and Flow Flushing
pump Switch mode valve, pump,
shutdown. is “ON” Flow Switch
(Setup (if no flow
Menu). After switch is
preset used, make
seconds sure it is
(Setup “OFF” in the
Menu), the setup menu).
flow signal
remains
OFF.
PUMP IS Const N/R Off Off Off Off N/R Warning Remote Start Not
OFF alarm, Auto Pump Possible.
operation selected check Pump,
not (Setup connection or
possible. Menu) and change
pump switch selections
on the (pump switch
Control must be on
Cabinet is Auto)
not on “0”
MOTOR Const N/R N/R On Off N/R N/R Warning Filter Motor Check
OVERLOAD overload Motors and
protection drive
device goes mechanism/
OFF. Wiring. Reset
Mechanical and start the
overload, system
Defective
Motor,
Defective
Wiring
M1/M2/M3/ Const N/R N/R ON/ Off. N/R N/R Alarm + Relevant Check Limit
M4 Failed OFF relevant motor works, Sensors and
(Dir) Filter stops Limit Disk wiring.
when
all moves away If necessary,
motor from Limit switch
Sensor but connection
fail
the LS between 2
signal does phases, to
not change. change the
Also used to relevant
check the motor’s
relevant direction.
motor
connection/d
irection on
startup.
M1/M2/M3/M Const N/R N/R ON/ Off. N/R N/R Alarm + Relevant Check Limit
4 Failed (LS) OFF relevant motor’s Limit Sensors and
Filter stops Sensors wiring. Reset
when
all broke, or & Start
motor have wiring
fail problems.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 42 of 60
Description/
DP Relay
Indicator
Indicator
Indicator
Flushing
Flushing
Display
Action
Status
Couse
Signal
Green
Green
Alarm
Alarm
Pump
Relay
Relay
Relay
M1/M2/M3/M Red
Const N/R N/R ON/ Off. N/R N/R Alarm + It takes the Check Limit
4 Failed OFF relevant Limit Disk Sensors and
(RunT) Filter stops more than Drive system.
when
all 15% longer Reset & Start
motor to reach a
Limit
fail
Sensor, than
the selected
Run Time
(Setup
Menu)
Low PLC Blink N/R N/R On Off. N/R N/R Warning Controller Change the
Battery backup backup
battery is battery
running low
Pump Not Blink N/R On On Off. On N/R Warning Ready Check pump
Ready Signal not functionality
received and wiring
from pump
controller.
Pump Not Const Const Off. Off. Off. N/R N/R Warning Run Signal Check pump
Run not received functionality
from pump and wiring
controller.
PT0/PT1 Out Blink N/R N/R Off. Off. N/R N/R Warning Relevant Check wiring
of Range analog or replace
pressure device.
transmitter
(see Analog
Pressure
Transmitters
)
malfunctioni
ng – output
is less than
4ma or
greater than
20ma.
US.PR. Too Const Blink N/R On Off. On On Warning Upstream
Low! pressure is
lower than
optimal
flushing
pressure.
US.PR.Too Const N/R N/R On Off. N/R N/R Warning Upstream
High!! pressure is
greater than
maximum
plate stated
working
pressure.
DP. Too Const N/R N/R On Off. N/R On Warning Differential
High!!! (ver. pressure is
3.1 Off) too high.
The filter
may become
damaged.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 43 of 60
Description/
DP Relay
Indicator
Indicator
Indicator
Flushing
Flushing
Display
Action
Status
Couse
Signal
Green
Green
Alarm
Alarm
Pump
Relay
Relay
Relay
High Red
Const N/R N/R On Off. N/R N/R Warning Pressure in
Pressure!!! the filter is
greater than
maximum
plate stated
working
pressure.
No DPT Const Off N/R Off Off. N/R N/R Fatal Error No
selected! Filter differential
operation pressure
trigger
Not
(DPT)device
possible
selected at
setup.
Leakage Const N/R N/R On Off. N/R N/R Warning Flow Switch
Detected detected
flow while
flushing
valve
closed.
Replace
Flushing
Valve or
faulty Flow
Switch.
Err. Power Blink Off Off Off Off Off Off Fatal Error All Setup Check PLC
Down Filter parameters battery;
Run Setup operation have been replace if
first Not lost. PLC faulty and run
battery low Setup.
possible
OR no setup
done during
installation.
Pump N/R N/R Blink N/R N/R N/R N/R Indication Pump run
Run Ext from
V3.2
Cab external
pump
cabinet.
Man. Const Off. Off. Off. Off. Off. N/R Warning Power Up Reset -
Power while filter In Change
V3.3
Up Manual Flushing
Restart Mode. Selector to 0.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 44 of 60
10. Technical Specifications
10.1 Power Supply
10.1.1 Line voltage
Type A – 190 ÷ 220 V 50/60Hz (3~)
Type B – 380 ÷ 480 V 50/60Hz (3~)
10.1.2 Control voltage
24 VDC
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 45 of 60
11. Annex A: Controller Inputs and Outputs
11.1 Inputs
11.1.1 Analog Inputs
11.1.3 Multi-Filter
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 47 of 60
11.2 Outputs
11.2.1 Single Filter
11.2.2 Multi-Filter
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 48 of 60
12. Annex B: Modbus Specifications
12.1 Modbus Word Registers
Register Access Name Limits Units Data Function
number Type Code
40210 Read Only Motor Alarms bit high = in alarm Bit Mask signed 03
16-bit
integer
40211 Read Only System Alarms bit high = in alarm Bit Mask signed 03
16-bit
integer
40212 Read Only System Status bit high = active Bit Mask signed 03
16-bit
integer
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 50 of 60
Register Access Name Limits Units Data Function
number Type Code
233 Read Only PT0 Out Off Range bit high = in alarm None Bit 01
234 Read Only PT 1 Out Off Range bit high = in alarm None Bit 01
235 Read Only Upstream Pressure bit high = in alarm None Bit 01
Too Low
236 Read Only Upstream Pressure bit high = in alarm None Bit 01
Too High
237 Read Only High Pressure Alarm bit high = in alarm None Bit 01
238 Read Only Differential Pressure bit high = in alarm None Bit 01
To High
239 Read Only PLC Battery LOW bit high = in alarm None Bit 01
240 Read Only Reserved bit high = in alarm None Bit 01
241 Read Only 1 Second Blink Bit Not applicable None Bit 01
System Status Bits
242 Read Only Pump Status bit high = ON None Bit 01
243 Read Only System Ready bit high = Ready None Bit 01
244 Read Only System Alram bit high = Alarm None Bit 01
245 Read Only Flushing Relay bit high = Flushing None Bit 01
246 Read Only High DP Relay bit high = OK None Bit 01
247 Read Only Valve 1 bit high = Open None Bit 01
248 Read Only Valve 2 bit high = Open None Bit 01
249 Read Only Home Return bit high = None Bit 01
Returning
250 Read Only Remote Flushing bit high = Flushing None Bit 01
251 Read Only DP Flushing bit high = Flushing None Bit 01
252 Read Only Timer Flushing bit high = Flushing None Bit 01
253 Read Only Run To Home bit high = Flushing None Bit 01
254 Read Only Scanner Home bit high = Home None Bit 01
255 Read Only 1 Second Blink Bit Not applicable None Bit 01
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 51 of 60
1 Second Blink Bit 1 Second Blink Bit
Bit 15
Motor OverLoad Reserved
Bit 14
Page 52 of 60
Reserved PLC Battery LOW 1 Second Blink Bit
Bit 13
Reserved Differential Pressure Fliter Home
Bit 12 To High
Motor 4 Run Time High Pressure Alarm Run To Home
Bit 11 Error
Motor 4 Direction Error Upstream Pressure Timer Flushing
Bit 10 Too High
Motor 4 Limit Switch Upstream Pressure DP Flushing
Bit 9 Error Too Low
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017
Motor 3 Run Time PT 1 Out Off Range Remote Flushing
Bit 8 Error
Motor 3 Direction Error PT0 Out Off Range Home Return
Bit 7
Motor 3 Limit Switch Check DPS Or Valves Valve 2
Bit 6 Error
Motor 2 Run Time Heavy Dirt Load Valve 1
Bit 5 Error Warning
Motor 2 Direction Error Leakege Detected High DP Relay
Bit 4
Motor 2 Limit Switch Flow Error Flushing Relay
Bit 3
Word Register Bit Map
Error
Motor 1 Run Time No Ready Signal From System Alram
Bit 2 Error Pump
Motor 1 Direction Error No Run Signal From System Status
Bit 1 Pump
Motor 1 Limit Switch Pump Switch Is Off Pump Status
Bit 0 Error
Register Number
40210
40211
40212
12.2
13. Annex C: PLC Program Upgrade
1. Open the side cover of the controller and push in the PLC programmer (CLONER) until it snaps into place.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 53 of 60
14. Annex D: Interface Logic
14.1 Pump Interface Logic
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 54 of 60
14.2 Filter Interface Logic
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 55 of 60
15. Annex: E: Setup Values Form
The following form is used by the client to define setup values for the controller.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 56 of 60
16. JAZZ 20 BATTERY REPLACEMENT
Note:
Once the battery is disconnected, all setup values will be lost. It is highly important to copy (or
photo) all setup values, for setup process see Chapter 7.
Disconnect all plugs from the OPLC.
Make sure to replace the battery with battery model CR2032.
Before opening the controller, touch a grounded object to discharge any electronic charge.
Avoid touching the PCB board directly by holding the PCB board by its connectors.
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 57 of 60
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 58 of 60
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 59 of 60
17. User Notes
Unclassified | Commercial Confidential |Document P/N DOC-00136 | Rev D Printed 18 July 2017 Page 60 of 60