The Siemens XDLC device loop card interfaces addressable fire detection devices to the Desigo fire safety system. It supports up to 252 devices on 4 Class A or 8 Class B circuits. The XDLC initializes, operates, and maintains connected devices, communicating alarm, trouble and supervisory signals to the control panel. It has diagnostic LEDs and supports intelligent detectors, input/output modules, and other addressable devices.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
188 views2 pages
XDLC - Data Sheet - 7312
The Siemens XDLC device loop card interfaces addressable fire detection devices to the Desigo fire safety system. It supports up to 252 devices on 4 Class A or 8 Class B circuits. The XDLC initializes, operates, and maintains connected devices, communicating alarm, trouble and supervisory signals to the control panel. It has diagnostic LEDs and supports intelligent detectors, input/output modules, and other addressable devices.
Supports up to 252 addressable points The Siemens – Fire Safety `Class X’ Device Loop Card (Model XDLC) is the interface used for connecting Siemens addressable, intelligent `X’ as well as `H’-series Operates and maintains all devices devices. residing on up to four (4) `Class A’, eight (8) `Class B’ addressable circuits Each Model XDLC plugs into one (1) slot of the Model CC-2 or Model CC-5 card cage. Compatible with Siemens intelligent, Programming for Model XDLC is accomplished via the Desigo Fire Safety Modular addressable ‘X’ and ‘H’-series devices: system custom-configuration tool, Zeus-D. Model XDLC takes one (1) address on - Multi-criteria / Carbon Monoxide (CO) the network, communicating up to a total 252 detectors and devices. Model XDLC Detector with ASAtechnologyTM has 16 LEDs for diagnostic purposes, and provides ground-fault detection and zone- - Multi-criteria Detector isolation circuitry. with ASAtechnologyTM - Multi-criteria Detector Specifications - Thermal (Heat) Detector The `Class X’ Device Loop Card (Model XDLC) initializes, operates and maintains all - Input / Output Interface Module devices residing on up to four (4) `Class A’, eight (8) `Class B’ addressable circuits. Polarity insensitive (in non-isolation Model XDLC communicates all relevant device and event data (`Alarm’, `Trouble’ and mode) via SureWireTM technology: `Supervisory’ commands) to a Desigo Fire Safety Modular (Desigo Modular) fire- - Modern technology supports alarm control panel (FACP), and supervises the device loop circuit. comprehensive system and interface communication Model XDLC is polarity insensitive via SureWire technology, which greatly reduces commissioning time normally spent tracing down crossed-field wiring. Model XDLC Quantity 16 diagnostic light-emitting communicates detector data, such as sensitivity of intelligent fire detectors and diodes (LEDs) for easy circuit diagnosis logic-function information, to the Desigo Modular Operating Unit (Model FCM2041- Microchip controls on-board isolators U2), which is located within a given Desigo Modular system. Device Programmer / Tester Each device loop card supports four (4) `Class A’, eight (8) `Class B’ circuits for up to (Model DPU) programs and verifies a total of 252 addressable devices – as well as relay and audible bases, remote lamps device’s address: and duct-detector housings in any combination. - programming capabilities include testing a duct detector, as well as The microprocessor in a Model XDLC controls the other Siemens addressable devices on-board isolation, in case there is a fault (short) in Supports `Class B’ | `Class A’ | `Class X’ any of the circuits, thus allowing the other circuit wiring to continue operating. For continuous protection, Supports T-Tapping the on-board microprocessor continues to operate even in the event of a CPU failure. Degrade mode UL864 | CAN / ULC Listed NOTE: Refer to installation manual: P/N – A6V101040156 to ensure Model XDLC compatibility with the Siemens FACPs intended for use in the given application.
Model XDLC d
Side View Model XDLC
d
Front View
Siemens Data Sheet 7312
Smart Infrastructure – Building Products usa.siemens.com/fire Model XDLC- Diagram of an `Class X’ Device Loop Card mounted to a Siemens Card Cage
Temperature and Humidity Range
`Class X’ Device Loop Cards are UL Listed | ULC Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).
Technical Data Details for Ordering
24V CURRENT DRAW: MODEL PART [Back Plane] 0 PRODUCT OR TYPE NUMBER 24V CURRENT DRAW: 100mA + 1.4mA `Class X’ [Screw Terminal] per device XDLC S54430-B8-A1 Device Loop Card 6.2V CURRENT DRAW: 1mA, max. [Back Plane] 24V CURRENT DRAW: 100mA + 1.4mA [Standby] per device
DEVICE LOOP: 500mA, max.
[@ 30 VDC Max.] (power limited) xx
NOTICE – The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice. The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information. Copies of install-type, instruction sheets – as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product, and are available from the Manufacturer. Data contained in the aforesaid type of documentation should be consulted with a fire-safety professional before specifying or using the product.