ATV9 XX
ATV9 XX
ATV930D22N4
Standard Drive Wall Mounting
380...480V/ThreePhase
22kW/30HP
46.3A
ATV930D22N4
V3.8IEXX
3.8.5.0
BFR Motor Standard 50Hz motor frequency 50Hz motor frequency 3015
TFR Max frequency 60 Hz 60 Hz 10 Hz 500 Hz 3103
NPR Nominal motor power 22 kW 22 kW 5.5 kW 37 kW 9613
UNS Nominal motor voltage 400 V 400 V 200 V 500 V 9601
NCR Nominal motor current 41.7 A 41.7 A 11.5 A 69.4 A 9603
FRS Nominal motor frequency 50 Hz 50 Hz 10 Hz 599 Hz 9602
65535
NSP Nominal motor speed 1460 rpm 1460 rpm 0 rpm 9604
rpm
MPC Motor parameter choice Nominal motor power Nominal motor power 9614
COS Motor 1 Cosinus Phi 0.85 0.85 0.5 1 9606
AsyncMotor Stator 6553.5
RSA 0 mOhm 0 mOhm 0 mOhm 9642
resistance mOhm
IDA Magnetizing current 0A 0A 0A 6553.5 A 9652
AsyncMotor Leakage
LFA 0 µH 0 µH 0 µH 65535 µH 9662
inductance
TRA Rotor time constant 0 ms 0 ms 0 ms 65535 ms 9667
Sync motor nominal
NCRS 39.6 A 39.6 A 11.5 A 69.4 A 9670
current
Nominal synchronous 15996
NSPS 2000 rpm 2000 rpm 0 rpm 9671
motor speed rpm
INRT Torque scaling 0.1 0.1 9805
6553.5
TQS Nominal motor torque 105 Nm 105 Nm 0.1 Nm 9684
Nm
PPNS Pole pairs number (sync) 3 3 1 240 9672
Pulse Signal injection - Pulse Signal injection -
AST Auto angle setting type 13925
Optimized Optimized
0 6553.5
PHS Sync. EMF constant 0 mV/rpm 0 mV/rpm 9673
mV/rpm mV/rpm
Calculated SyncMotor 6553.5
RSAS 0 mOhm 0 mOhm 0 mOhm 9682
Stator R mOhm
LDS Sync motor d inductance 0 µH 0 µH 0 µH 65535 µH 9674
LQS Sync motor q inductance 0 µH 0 µH 0 µH 65535 µH 9675
Synchronous motor
FRSS 100 Hz 100 Hz 100 Hz 100 Hz 9679
nominal freq
Maximum current of PSI
MCR Nominal value Nominal value 0% 300 % 15607
alignment
CRTF Filter time of the current Nominal value Nominal value 0 ms 100 ms 9116
Internal currents filter
CRFA 0 ms 0 ms 0 ms 100 ms 9118
time
-3276.7
RDAE Relative d-axis error in % 0% 0% 3276.7 % 9676
%
C:\Users\sesa669719\AppData\Local\Temp\422ffa14-9669-4671-9d12-80b5f237b9bc\Untitled Project.psx 2/34
Untitled Project 06/02/2024 20:02
Number of autotuning
TNBR 1 1 1 3 9831
sequence repetitions
655.35
LA Main inductance 0 mH 0 mH 0 mH 9845
mH
Tangential main 655.35
L0A 0 mH 0 mH 0 mH 9841
inductance mH
655.35
PHI0 Nameplate nominal flux 0 Wb 0 Wb 0 Wb 9851
Wb
655.35
PHIA Rotor nominal flux 0 Wb 0 Wb 0 Wb 9844
Wb
Flux saturation curve -327.67
ALFA 0% 0% 327.67 % 9842
coefficient A %
Flux saturation curve -327.67
BET0 0% 0% 327.67 % 9843
coefficient B %
First Id min current level
IDL1 50 % 50 % 0% 100 % 9836
in rotation
First Id max current level
IDH1 100 % 100 % 50 % 300 % 9837
in rotation
Second Id min current
IDL2 20 % 20 % 0% 120 % 9838
level in rotation
Second Id max current
IDH2 120 % 120 % 20 % 300 % 9839
level in rotation
Autotuning flux
TUNV 0% 0% 0% 65535 % 9835
verification value
Response to thermal
TH4B Ramp stop Ramp stop 13242
error for AI4
Thermal error level for
TH4F 110 °C 110 °C -15 °C 200 °C 13232
AI4
Thermal warning level for
TH4A 90 °C 90 °C -15 °C 200 °C 13222
AI4
TH4V AI4 thermal value 0 °C 0 °C -15 °C 200 °C 13252
Activation of the thermal
TH5S No No 13213
monitoring on AI5
AI5T Configuration of AI5 Current Current 4406
Response to thermal
TH5B Ramp stop Ramp stop 13243
error for AI5
Thermal error level for
TH5F 110 °C 110 °C -15 °C 200 °C 13233
AI5
Thermal warning level for
TH5A 90 °C 90 °C -15 °C 200 °C 13223
AI5
TH5V AI5 thermal value 0 °C 0 °C -15 °C 200 °C 13253
Encoder thermal sensor
THET None None 5661
type
Response to thermal
THEB Ramp stop Ramp stop 5666
error for encoder
Thermal error level for -3276.8
THEF 110 °C 110 °C 3276.7 °C 5665
encoder °C
Thermal warning level for -3276.8
THEA 90 °C 90 °C 3276.7 °C 5664
encoder °C
-3276.7
THEV Encoder thermal value 0 °C 0 °C 3276.7 °C 5663
°C
LFF Fall back speed 0 Hz 0 Hz 0 Hz 599 Hz 7080
Configuration reference
FR1 AI1 Analog input AI1 Analog input 8413
frequency 1
FR1B Configuration ref. 1B Not configured Not configured 8415
Reference frequency Reference frequency
RCB Select switching (1 to 1B) 8412
channel 1 channel 1
RIN Reverse direction disable No No 3108
Control mode Combined channel Combined channel
CHCF 8401
configuration mode mode
C:\Users\sesa669719\AppData\Local\Temp\422ffa14-9669-4671-9d12-80b5f237b9bc\Untitled Project.psx 6/34
Untitled Project 06/02/2024 20:02
MSMC M/S mechanical coupling type Rigid coupling Rigid coupling 16820
Direct torque Direct torque
MSCT M/S control type 16821
control control
TRF Torque filter activation No No 9236
TRW Torque filter bandwidth 20 Hz 20 Hz 1 Hz 1000 Hz 9237
M/S Master torque reference entry Before advanced Before advanced
MSIT 16826
in control chain filter filter
M/S output torque reference Before advanced Before advanced
MSOT 16827
selection filter filter
M/S Master speed reference entry
MSIS After ramp After ramp 16824
in control chain
M/S output speed reference
MSOS After ramp After ramp 16825
selection
RFT Power backup input assignment Not assigned Not assigned 13831
RSU Power backup voltage 220 V 220 V 220 V 415 V 13832
Power backup reference 6553.5
RSP 5 Hz 5 Hz 0 Hz 13833
frequency Hz
LAF Stop forward limit assignment Not assigned Not assigned 11601
LAR Stop reverse limit assignment Not assigned Not assigned 11602
LAS Stop type on limit switch Freewheel stop Freewheel stop 11603
SAF Fwd stop limit input assig Not assigned Not assigned 12501
SAR RV stop limit input assign Not assigned Not assigned 12502
DAF Forward slowdown limit Not assigned Not assigned 12503
DAR Reverse slowdown limit Not assigned Not assigned 12504
CLS Disable limit switch Not assigned Not assigned 12507
PAS Stop type On ramp On ramp 12506
DSF Deceleration type Standard Standard 12505
STD Stop distance No No 0m 10 m 12521
NLS Rated linear speed 1 m/s 1 m/s 0.2 m/s 5 m/s 12511
SFD Distance stop corrector 100 % 100 % 50 % 200 % 12522
MSTP Memo stop Yes Yes 12523
PRST Priority restart No No 12524
MSLO Memo slowdown Yes Yes 12525
Torque/Speed switching
TSS Not assigned Not assigned 9220
control mode
TR1 Channel for torque reference Not configured Not configured 9221
PI7A DI7 pulse input assignment Not assigned Not assigned 4877
PI8A DI8 pulse input assignment Not assigned Not assigned 4878
PTGA Encoder pulse assignment Not assigned Not assigned 4873
Reference frequency Reference frequency
AI1A AI1 assignment 4821
1 1
AI2A AI2 assignment Not assigned Not assigned 4822
AI3A AI3 assignment Not assigned Not assigned 4823
AI4A AI4 assignment Not assigned Not assigned 4824
AI5A AI5 functions assignment Not assigned Not assigned 4825
AV1A AIV1 assignment Not assigned Not assigned 4861
PI7A DI7 pulse input assignment Not assigned Not assigned 4877
30000
PIL7 DI7 pulseInput low frequency 0 Hz 0 Hz 0 Hz 13360
Hz
PIH7 DI7 pulseInput high frequency 30 kHz 30 kHz 0 kHz 30 kHz 13362
1000
PFI7 DI7 frequency filter 0 ms 0 ms 0 ms 13364
ms
PI8A DI8 pulse input assignment Not assigned Not assigned 4878
30000
PIL8 DI8 pulseInput low frequency 0 Hz 0 Hz 0 Hz 13380
Hz
PIH8 DI8 pulseInput high frequency 30 kHz 30 kHz 0 kHz 30 kHz 13382
1000
PFI8 DI8 frequency filter 0 ms 0 ms 0 ms 13384
ms
-300 300
PEFR Frequency max value 300 kHz 300 kHz 17072
kHz kHz
1000
EFI Frequency signal filter 0 ms 0 ms 0 ms 13312
ms
60000
R6D R6 activation delay time 0 ms 0 ms 0 ms 4246
ms
R6S R6 active level High level High level 4206
9999
R6H R6 holding delay time 0 ms 0 ms 0 ms 4226
ms
R6F Enable relay 6 fallback No No 17603
RSF Fault reset input assignment Digital input 4 Digital input 4 7124
RPA Product restart assignment Not assigned Not assigned 7129
HRFC Extended fault reset activation No No 7150
IPL Input Phase Loss assignment Freewheel stop Freewheel stop 7002
OHL Drive overtemp error response Freewheel stop Freewheel stop 7008
THA Device thermal state warning 100 % 100 % 0% 118 % 11009
TLOL Drive overload monitoring activation Disabled Disabled 7031
Lifecycle warning
LCAC Yes Yes 13720
configuration
LCAD Life cycle Date 0 0 0 65535 13721
No warning No warning
CAR Customer warning clearing 16280
clearing clearing
Configuration of customer
CCA1 Not Configured Not Configured 16200
warning 1
4294967295
CCL1 Configuration counter limit 1 0s 0s 0s 16240
s
Configuration counter Source Drive in running Drive in running
CCS1 16210
1 State State
4294967295
CC1 Time counter 1 0s 0s 0s 16260
s
Configuration of customer
CCA2 Not Configured Not Configured 16201
warning 2
4294967295
CCL2 Configuration counter limit 2 0s 0s 0s 16242
s
Configuration counter Source Drive in running Drive in running
CCS2 16211
2 State State
4294967295
CC2 Time counter 2 0s 0s 0s 16262
s
Configuration of customer
CCA3 Not Configured Not Configured 16202
warning 3
4294967295
CCL3 Configuration counter limit 3 0s 0s 0s 16244
s
Configuration counter Source Drive in running Drive in running
CCS3 16212
3 State State
4294967295
CC3 Time counter 3 0s 0s 0s 16264
s
Configuration of customer
CCA4 Not Configured Not Configured 16203
warning 4
4294967295
CCL4 Configuration counter limit 4 0s 0s 0s 16246
s
Configuration counter Source Drive in running Drive in running
CCS4 16213
4 State State
4294967295
CC4 Time counter 4 0s 0s 0s 16266
s
Configuration of customer
CCA5 Not Configured Not Configured 16204
warning 5
4294967295
CCL5 Configuration counter limit 5 0s 0s 0s 16248
s
Configuration counter Source Drive in running Drive in running
CCS5 16214
5 State State
4294967295
CC5 Time counter 5 0s 0s 0s 16268
s
Device name
IP assignment mode DHCP
IP Address 0.0.0.0
Subnet mask 0.0.0.0
Gateway address 0.0.0.0
Rate setting port 1 Auto detected
Rate setting port 2 Auto detected
Storm Protection 1 (Highest)
Swap word order Modbus Word Order ON
RPI (ms) 10
Input Size (bytes) 4
Input Priority Schedule
Input Type Fixed
Input Mode Multicast
Input Trigger Cyclic
RPI (ms) 10
Output Size (bytes) 4
Output Priority Schedule
Output Type Fixed
Output Mode Point to Point
C:\Users\sesa669719\AppData\Local\Temp\422ffa14-9669-4671-9d12-80b5f237b9bc\Untitled Project.psx 32/34
Untitled Project 06/02/2024 20:02
SNTP Enable
Server 1 IP Address 0.0.0.0
Server 2 IP Address 0.0.0.0
Polling Interval (minute) 1
Manager 1 0.0.0.0
Manager 2 0.0.0.0
System Name
System Location
System Contact
Get public
Set private
Trap Trap