Fuel Conditioning System
Fuel Conditioning System
System Manual
Lit. Code 200001446-1-EN-GB
Manual No. 9013906 02 V. 2
Published by
Alfa Laval SpA
Product Development FCS & Modules
Via Pusiano 2
20900 Monza (MB), Italy
This document and its contents are subject to copyrights and other intellectual property rights owned by Alfa Laval Corporate AB. No part of this document may be copied, re-produced or
transmitted in any form or by any means, or for any purpose, without Alfa Laval Corporate AB’s prior express written permission. Information and services provided in this document are
made as a benefit and service to the user, and no representations or warranties are made about the accuracy or suitability of this information and these services for any purpose. All rights
are reserved.
Contents
1 Operator Panel...........................................................................................................5
1.1 Manual Controls........................................................................................................ 5
1.2 HMI Panel..................................................................................................................6
1.2.1 Overview Matrix........................................................................................... 7
1.2.2 Tab Control...................................................................................................8
1.2.3 Control Bar...................................................................................................9
1.2.4 User Login Dialog...................................................................................... 10
1.2.5 Pop-up Keyboard and Numerical Pad........................................................11
1.2.6 Main Tab 1: FCM One Process..................................................................12
1.2.7 Main Tab 2: Alarms and Events................................................................. 17
1.2.8 Main Tab 3: Trends.................................................................................... 18
1.2.9 Main Tab 4: System Information................................................................ 19
1.2.10 Main Tab 5: Timers and Counters.............................................................. 22
1.2.11 Main Tab 6: Parameters 1..........................................................................23
1.2.12 Main Tab 7: Parameters 2..........................................................................24
1.2.13 Main Tab 8: Parameters 3..........................................................................25
1.2.14 Main Tab 9: Parameters 4..........................................................................26
1.2.15 Main Tab 10: Programmable I/O................................................................ 26
2 Normal Operation...................................................................................................27
2.1 Before Start............................................................................................................. 27
2.2 Manual Start............................................................................................................ 28
2.3 Automatic Start (Recommended)............................................................................ 30
2.4 Stop......................................................................................................................... 32
2.5 Pumps Operation.....................................................................................................33
2.6 Pumps Stand-by Function....................................................................................... 34
2.7 Fuel Operating Modes.............................................................................................35
2.7.1 Fuel Control Type.......................................................................................36
2.7.2 Blending Mode........................................................................................... 37
2.8 Changeover.............................................................................................................38
2.8.1 MGO to HFO..............................................................................................42
2.8.2 HFO to MGO..............................................................................................45
2.9 Automatic Filter........................................................................................................48
2.10 Mixing Tube Aeration...............................................................................................48
2.11 Variable Frequency Drive (VFD)..............................................................................49
2.12 Remote Control....................................................................................................... 49
2.13 Automatic Start-up After Power Failure................................................................... 50
2.14 Regular Checks on the System...............................................................................50
2.15 Emergency Stop......................................................................................................51
2.15.1 Optional External Emergency Stop, EPC Mode........................................ 51
2.15.2 Optional External Emergency Stop, Manual Mode.................................... 51
2.16 Logs Export............................................................................................................. 52
2.17 Standard Log Export................................................................................................53
2.18 Parameters Export and Import................................................................................ 54
3 GPS................................................................................................................................. 55
3.1 Communication Settings..........................................................................................55
3.2 Settings in FCM One............................................................................................... 55
3.3 Transferred Data..................................................................................................... 55
4 Manual Operation...................................................................................................57
4.1 Manual Operation of Main Components..................................................................58
EN
1 Operator Panel
FCM operator panel is placed in the control cabinet upper part and it is
composed of several switches for manual control and by a touchscreen
interface for automation control.
The main component switches are only enabled if the main system switch
is set in manual position.
Pipes heat tracing selector is always enabled and allows to the operator to
select Start (MAN), Stop (OFF) or to leave the control of heat tracing to
EPC (AUTO).
In case that an Automatic/Automatic Alfa Laval Moatti filter has been instal-
led, the automatic filter selector is always enabled and allows to the opera-
tor to select the operating filter.
200001446-1-EN-GB 5
EN 1 Operator Panel
The HMI is a 7” touch screen panel with a software program (available option
15”); simply tap the panel with a fingertip to operate on it.
The HMI program includes many different screens. The operator can scroll
and navigate among them via the Overview Matrix or using the Tab Control.
6 200001446-1-EN-GB
Operator Panel 1 EN
In order to get an overview about the available HMI screens, tap the Overview
button in the lower right corner of the screen.
Main tabs are numbered from left to right and sub-tabs are numbered from top
to bottom.
When the operator taps an icon in the overview matrix, the HMI program
automatically goes to that screen viewing the selected menu.
200001446-1-EN-GB 7
EN 1 Operator Panel
In order to navigate through other screens, simply tap a sub-tab or main tab.
8 200001446-1-EN-GB
Operator Panel 1 EN
The following buttons for controlling the FCM One are available in all modules:
Manual button: the button icon is shown when the system switch has been set in manual
position.
The buttons at the right side of the control bar are related to HMI itself:
The Utilities button opens a menu with Backlight and Print screen buttons.
Insert a USB memory stick in the USB port of the HMI panel and then tap the Print button.
This stores a screenshot of the currently displayed screen on the memory stick.
200001446-1-EN-GB 9
EN 1 Operator Panel
Tap the Login button to display or to hide the user login dialog box at the top of the screen.
Tap the Overview button to enter or to leave the screen overview matrix.
Select a user name from the drop down menu then tap the empty password
input field to open the pop-up keyboard.
Type the required password followed by the ‘enter’ key.
There are four user levels to choose from the drop down menu:
Table 1: FCM One User Password
By tapping the Logout button the Login level will be changed to ‘Guest’ that
gives access to the normal system operation.
10 200001446-1-EN-GB
Operator Panel 1 EN
200001446-1-EN-GB 11
EN 1 Operator Panel
12 200001446-1-EN-GB
Operator Panel 1 EN
The overview screen is composed of an upper part showing the process tiles
and by a lower part showing the main sensors and variables.
Process Tiles
Overview process tiles outline indicates the status of a specific process.
The outline flashes green when a process is starting and becomes solid green
when it is correctly running.
The tile outline turns off when a process has been stopped.
200001446-1-EN-GB 13
EN 1 Operator Panel
Main Sensors
The main process sensors are shown in the overview screen together with
heat tracing and mixing tube level switch status.
Manual Release
Manual release button is used to disable all the manual control overrides of
the components.
The button is only enabled if any component manual control has been
activated; tap on the button to release them. A pop-up dialog box will ask for
confirmation.
WARNING
Manual control overrides of components could seriously
compromise the FCM One standard functionality.
14 200001446-1-EN-GB
Operator Panel 1 EN
Animated outline
The outline on the equipment or on the device indicates the status of the
equipment/device.
In the example below the outline flashes when it is starting/stopping or
opening/closing.
Overlay icons
Some of the components show the Faceplate icon in the top left cor-
ner.
Tap the equipment to open the faceplate, which may contain additional information about the equipment or the
manual control function.
The Manual control icon is available at the bottom left corner of the
component when a manual override of the component has been forced.
200001446-1-EN-GB 15
EN 1 Operator Panel
WARNING
Manual control override of components could seriously compromise
the FCM One standard functionality.
The Alarm icon appears at the bottom right corner of a component that is in
fault or of a component that is generating an alarm.
The Warning icon appears, instead, when a component has been disabled.
16 200001446-1-EN-GB
Operator Panel 1 EN
The Main Tab 2 enables the screens related to the system alarms.
Table 3: FCM One Alarms and Events
Event Log List of user interactions with the HMI (audit trail)
Alarm Acknoledge
Before operating the FCM One system, make sure that all active alarms have
been acknowledged by the operator.
The presence of any active alarms is indicated by a red alarm icon at main tab
2.
The red alarm icon flashes until all active alarms have been acknowledged.
200001446-1-EN-GB 17
EN 1 Operator Panel
In order to acknowledge an alarm, select it tapping on alarm line and then tap
Ack Selected button.
Old alarms are stored and they are shown in Alarm History screen 2.2.
Trend Legend
It is possible to toggle the trend legend status between ‘trend legend
displayed’ and ‘trend legend hidden’ by tapping the trend button.
18 200001446-1-EN-GB
Operator Panel 1 EN
2Touch & Controller Info 2Touch & Controller info and software release
PLC Modules
The complete list of installed PLC modules is shown on screen 4.1.
If any PLC module is detecting an error or a fault, or it is not correctly
configured, the Alarm Icon will appear at the bottom of each module.
200001446-1-EN-GB 19
EN 1 Operator Panel
Modbus configuration
Modbus TCP/IP address and Subnet Mask are available on screen 4.2.
In order to change the IP address or Subnet Mask, write the new values and
then tap Update button.
Even Modbus RTU parameters are available in screen 4.2.
Please refer to Parameter list for further details.
NOTE
If HMI and PLC time and date are not synchronized, the log function
will not work correctly.
HMI IP setting
Local and remote HMI IP address can be modified on screen 4.4.
Tap on Edit IP Address button; a pop-up dialog box will appear.
Edit the new IP address and Subnet Mask; then press Ok.
20 200001446-1-EN-GB
Operator Panel 1 EN
Default IP Address
Local HMI 192.168. 250.10
Remote HMI 192.168.250.11
WARNING
Inserting not valid IP address will stop the communication between
HMI and PLC causing FCM system loss of control!
200001446-1-EN-GB 21
EN 1 Operator Panel
Operating Timers 1:
• Machine run time
Operating Timers 1 • Supply pumps run time
• Circulation pumps run time
• Timers for automatic pumps switch
Operating Timers 2:
• Deaerations counter
Operating Timers 2
• Automatic filters run time
• Automatic filter drains counter
All timers and counters are available as Total and Trip counter.
Total counter can only be reset by Alfa Laval Service Engineer; trip counters
can, instead, be reset with any login level.
In order to reset a counter, login with the required login level and tap on the
Reset button.
A pop-up dialog box will appear to ask for confirmation.
22 200001446-1-EN-GB
Operator Panel 1 EN
200001446-1-EN-GB 23
EN 1 Operator Panel
24 200001446-1-EN-GB
Operator Panel 1 EN
200001446-1-EN-GB 25
EN 1 Operator Panel
Alarms delay and pressure limits can be set through Main tab 10.
Table 12: FCM One List of programmable I/O
26 200001446-1-EN-GB
EN
2 Normal Operation
2.1 Before Start
The following procedures assume that the system pipelines and the valves arrangement are set for
operation (open valves and secured pipework). Moreover, they consider that the commissioning
actions described in the Installation System Reference booklet have been successfully performed.
200001446-1-EN-GB 27
EN 2 Normal Operation
28 200001446-1-EN-GB
Normal Operation 2 EN
NOTE
In manual control, the Start button is only
enabled when pumps are in running
mode.
200001446-1-EN-GB 29
EN 2 Normal Operation
30 200001446-1-EN-GB
Normal Operation 2 EN
NOTE
During start-up procedure, low pressure alarms are disabled for the amount of seconds
related to P456/P556 or until the pressure value is above low pressure limits.
200001446-1-EN-GB 31
EN 2 Normal Operation
2.4 Stop
By stopping the system as described in the procedure below, no alarms will be activated.
The system is designed so that the pumps cannot be stopped from EPC controller even if an error
occurs in the controller.
Due to safety reasons, the EPC can only start or switch the pumps but never stop them; this action
has to be performed manually.
32 200001446-1-EN-GB
Normal Operation 2 EN
NOTE
To increase the life-span of the pumps seals, it is recommended to
minimize the number of starts and stops on Heavy Fuel Oil.
The control unit can be set to change pumps (running to stand-by) at preset
intervals during operation according to P451/P551.
Alternatively, the control unit can be set to indicate when the time to change
over pumps is past.
NOTE
Since the pumps shaft seal has to be lubricated, a small amount of
oil will drop from the pump housing. About 10 drops per hours is
considered normal. If the leakage is greater, the shaft seal should be
replaced immediately to avoid additional damages. See Oil Feed
Pumps booklet for details.
200001446-1-EN-GB 33
EN 2 Normal Operation
NOTE
When a stand-by pump is started due to a fault or due to low
pressure alarm, the faulty pump is disabled in parameter P401/P501.
If the pump is disabled, the stand-by function for the set of pump is
disabled. It is necessary to restore stand-by function for the pump
using parameter P401/P501.
NOTE
If power supply is missing for stand-by pump, an alarm is shown and
the stand-by function is temporary disabled. When power supply is
back, the stand-by function is automatically restored.
Automatic switch of pumps always changes the selected running and stand-by
pump in parameter P401/P501.
If a fault occurs in one pump (e.g. one of the supply pumps) the stand-by
function for the other set of pumps (e.g. circulation pumps) continues to be
active.
Stand-by function has two different time delays:
• When a pump failure occurs there is a delay defined by parameter G3
before the stand-by pump contactor closes.
• When a low pressure alarm occurs the time before the stand-by pump
starts is defined by parameter G1.
34 200001446-1-EN-GB
Normal Operation 2 EN
Each fuel, including blend mode, can be configured with dedicated name,
specifications, set points and alarm limits (see Parameter list booklet for
details).
NOTE
Only installed fuels are available for configuration and shown in HMI
control bar.
CAUTION
Wrong settings of density parameter may cause inaccurate viscosity
measurement.
• Temperature set point parameter: the new fuel may be heated to a different
temperature to obtain the same viscosity set point.
NOTE
Wrong temperature set point may cause undesired behaviour during
the changeover process.
200001446-1-EN-GB 35
EN 2 Normal Operation
• Viscosity control: Viscosity set point is used to control heating and cooling
systems.
Even if viscosity control is set, high and low temperature alarms are always
active.
Temperature control is always used during change overs temperature ramp
and during start-up.
NOTE
Wrong temperature set point may generate temperature alarms
when viscosity control is used.
36 200001446-1-EN-GB
Normal Operation 2 EN
WARNING
Blending not compatible fuels may cause system instability and
clogging! Perform a compatibility test before blend fuels.
The blended fuel can be defined specifying the required final sulphur
content or the percentage of each original fuel composing the blend.
The blend definition mode is selected by parameter P310.
NOTE
Set the theoretical sulphur content of each fuel according to bunker
delivery receipt. The theoretical sulphur content must be updated
after a new bunkering.
Fuel percentage of each fuel is calculated measuring mass flow of each fuel
with dedicated mass flow meters.
The actual sulphur content of blended fuel is calculated using measured mass
flow of each fuel and its theoretical sulphur content specified by parameters.
Inlet three way changeover valves are driven according to the measured mass
flow; the valves are moved using a dedicated PID controller.
200001446-1-EN-GB 37
EN 2 Normal Operation
2.8 Changeover
The different properties and working conditions of bunkered fuels, make the
fuel changeover one of the most important and critical function in the booster
systems. Particular attention must be paid to fuel incompatibility, temperature
gradient, changes in viscosity.
The fuel incompatibility
The risk of incompatibility between residual fuel and low-sulphur distillates is
considered higher than what is typically associated with mixing different types
of residual fuel. Introducing distillate may cause the asphaltenes in the
residual fuel to precipitate as heavy sludge. This may result in filter clogging
and, in extreme cases, may cause fuel starvation in the engine and
subsequent engine shutdown. Another associated issue may be sticking of the
injection pump due to deposits between the plunger and the barrel.
Compatibility tests may be carried out either on board during bunkering or via
an independent laboratory.
The temperature gradient
The effect of large and rapid changes in fuel oil temperature on the injection
pumps could result in a seizure of the pump cylinder liner and the plunger due
to the varying thermal expansion properties of the liner and the plunger.
Generally, engine manufacturers recommend a gradient of no more than 2 °C
per minute. For this reason, fuel changeover can take considerable time from
initiation to completion.
The changes in viscosity
The optimum operational viscosity of a residual fuel at the engine fuel pump is
usually within the range of 10–20 cSt; to achieve parameter, fuel oil must be
heated up around 130/140 °C. Distillates viscosity is much lower; it is usually
in the range within 2 and 6 cSt at 40 °C and often requires fuel cooling to
achieve it. Engine manufacturer normally require to maintain viscosity above
the minimum viscosity of 2 cSt to avoid both lubrication issues and excessive
leakages within components that can lead to lack of performance and, in same
situation, to seizure.
Changeover time
Another important factor to be considered during a changeover is its duration:
a long changeover time requires a bigger consumption of light fuel.
Anyway there are two sides to the changeover process that must be
considered; one is the practical side to get the correct viscosity into the
engine; the other side is to be in compliance with MARPOL Annex VI with
0.10% maximum sulphur value. Compliance with regulations takes longer than
just changing over from one fuel to the other.
The time needed will depend on:
• Fuel system design, how much oil is within the system
• Sulphur values of the fuels
• Consumption of the engines
38 200001446-1-EN-GB
Normal Operation 2 EN
1. Tap the required fuel button on the HMI; a pop-up dialog box will appear to
ask for confirmation.
2. If manual changeover valve CV1 has been installed, move the valve to the
new fuel. If automatic changeover valve has been installed the valve will
immediately start to move towards the new fuel position.
NOTE
If more than one changeover valve have been installed, the controller
will perform position check on other changeover valves and, if
required, will move them to the required position before starting to
move the valve involved in changeover procedure.
NOTE
If automatic changeover valve has been installed, changeover time
for each valve and for each direction can be set by parameters. The
right time is function of temperature ramp, fuel consumption and
total fuel volume and may vary for each installation and running
conditions.
NOTE
Different engine loads may require different valve changeover times
to ensure the viscosity to stay within specified limits.
As general rule, a longer valve switch over time is required with high
fuel consumption; a shorter valve switch over time is required with
low fuel consumption.
200001446-1-EN-GB 39
EN 2 Normal Operation
NOTE
Temperature high and low limits change together with temperature
ramp. Viscosity high and low limits are fixed during changeover
procedure.
NOTE
If viscosity goes above HFO set point or below MGO set point,
temperature ramp is frozen and the temperature is maintained until
viscosity is again within the acceptable range.
4. After the time set by parameter, changeover valve gets to the new fuel posi-
tion.
If SPV Cooler has been installed, as soon as the changeover valve reaches
MGO position, CV5 moves toward SPV cooler position.
5. If both heating and cooling systems have been installed, EPC is able to auto-
matically switch from heater to cooler and vice versa operating on changeover
valve CV4.
The controller will move the CV4 if the difference between actual temperature
and set point temperature is bigger than P912 (°C) for more than P913 (s)
time.
The valve changeover time is set by parameters P921/P922.
NOTE
If required, the controller is able to switch from heater to cooler and
vice versa even if changeover process is not started.
NOTE
The delay for total fuel replacement in the loop depends on the
engine consumption and the total fuel volume (Mixing tube, FCM
circulation pipes, pipes from FCM to engine and return line from
engine to FCM).
WARNING
Mixing not compatible fuels may cause system instability and
clogging! Perform a compatibility test before a fuel changeover.
40 200001446-1-EN-GB
Normal Operation 2 EN
200001446-1-EN-GB 41
EN 2 Normal Operation
2 Changeover started.
3 Viscosity decreases.
42 200001446-1-EN-GB
Normal Operation 2 EN
6 Changeover ongoing.
7 Changeover ongoing.
200001446-1-EN-GB 43
EN 2 Normal Operation
8 Changeover finished.
Changeover from MGO to HFO. The complete procedure took more than three hours. this is the effect
of the combination of long run time for CV1 and low engine load.
The HFO takes a lot of time to reach the circulation side; if temperature starts to increase, the
viscosity will be too close to the low limit. For this reason the temperature ramp starts some minutes
later than the procedure.
It is even possible to see that CV4 moves too fast, creating some turbulence in temperature and
viscosity during the transition. A longer run time can give smoother results.
44 200001446-1-EN-GB
Normal Operation 2 EN
2 Changeover started.
3 Viscosity increases.
200001446-1-EN-GB 45
EN 2 Normal Operation
6 Changeover ongoing.
7 Changeover ongoing.
46 200001446-1-EN-GB
Normal Operation 2 EN
8 Changeover finished.
200001446-1-EN-GB 47
EN 2 Normal Operation
NOTE
If Automatic-Automatic filter has been installed,
choose the filter in operation through automatic filter
selector.
NOTE
After a differential pressure drain has been activated,
at least one hour is required before the system starts
the next drain.
48 200001446-1-EN-GB
Normal Operation 2 EN
NOTE
Remote control button is only enabled in automatic mode and after
the first start-up of the system.
200001446-1-EN-GB 49
EN 2 Normal Operation
Tap again the remote button on local HMI to disable the remote control.
NOTE
If system switch is moved to manual position, remote control will be
automatically disabled.
50 200001446-1-EN-GB
Normal Operation 2 EN
CAUTION
When the emergency stop button is released in manual mode, the
pumps will start again.
200001446-1-EN-GB 51
EN 2 Normal Operation
NOTE
Before connecting USB drive in PLC, check that CF led on CPU is green. Never insert USB if
the CF led is red (CF card Failure)!
52 200001446-1-EN-GB
Normal Operation 2 EN
200001446-1-EN-GB 53
EN 2 Normal Operation
NOTE
54 200001446-1-EN-GB
EN
3 GPS
With a GPS receiver providing the data, vessel position and UTC/GMT-time
can be logged into the PLC.
The GPS receiver is not part of Alfa Laval scope of supply.
The GPS receiver must comply with protocol NMEA-0183, ver. 4.00. it should
be connected to PLC on dedicated I/O module.
Connection example is shown in the wiring diagram. Max cable length allowed
between PLC and the GPS receiver is 1200 m.
200001446-1-EN-GB 55
EN 3 GPS
56 200001446-1-EN-GB
EN
4 Manual Operation
The manual operation is provided in the unlikely event that the EPC is out of
order.
System components can be manually operated under the direct supervision of
the operator.
WARNING
No automatic regulation is available in manual operation: wrong
system handling may damage component or generate dangerous
events!
If EPC is still available, tap start button on HMI to enable system alarms.
NOTE
In manual control, start button is only enabled when pumps are in
running mode.
200001446-1-EN-GB 57
EN 4 Manual Operation
NOTE
In manual operation, automatic stand-by function is only used in
case of pump failure.
WARNING
Even if EPC is switched off or stop working during automatic
operation, the running pumps will continue to run but stand-by
function is not available. Once EPC is restored, it will take control
again.
In case it is not possible to immediately restore EPC, it is
recommended to switch the system in manual mode.
Temperature Control
Heating media regulation valve can be controlled di-
rectly using the SRV switch.
A hand lever is also available on valve actuator.
Electric heater can have up to four different steps (it depends by heater size).
To increase or decrease heating power, modify the number of active steps.
58 200001446-1-EN-GB
Manual Operation 4 EN
NOTE
Even if the number of steps can vary according to electric heater
size, the selector always expected four steps. Only the available
steps will be activated.
Cooling media control valve must be operated using the hand lever available
on valve actuator.
Automatic Filter
The Alfa Laval Moatti automatic filter can be
operated moving the Automatic Filter switch to
ON position.
The filter can also be manually drained by using the by-pass valve.
Perform a daily check of the pressure drop visual indicator available on the
filter: if pressure drop exceeds 0.2 bar higher than standard operation, a
manual discharge should be performed.
See Operation chapter in the filter component booklet for further information.
The change over valves can be managed with hand lever available on valves
actuator.
200001446-1-EN-GB 59