Lecture 17 - Building Managment System
Lecture 17 - Building Managment System
Lecture 17 - Building Managment System
Lecture 17
Its core function is to manage the environment within the building and may control
temperature, carbon dioxide levels and humidity within a building. As a core function in
most BMS systems, it controls heating and cooling, manages the systems that distribute this
air throughout the building (for example by operating fans or opening/closing dampers), and
then locally controls the mixture of heating and cooling to achieve the desired room
temperature. A secondary function sometimes is to monitor the level of human-generated
CO2, mixing in outside air with waste air to increase the amount of oxygen while also
minimizing heat/cooling losses.
Systems linked to a BMS typically represent 40% of a building's energy usage; if lighting
is included, this number approaches 70%. BMS systems are a critical component to
managing energy demand. Improperly configured BMS systems are believed to account for
20% of building energy usage. As well as controlling the building's internal
environment, BMS systems are sometimes linked to access control (turnstiles and access
doors controlling who is allowed access and egress to the building) or other security
systems such as closed-circuit television (CCTV) and motion detectors. Fire alarm
systems and elevators are also sometimes linked to a BMS, for monitoring. in case a fire is
detected then the only the fire alarm panel could shut off dampers in the ventilation system
to stop smoke spreading and send all the elevators to the ground floor and park them to
prevent people from using them in the event of a fire .
143
6.2.3 Maintenance Companies
Ease of information availability problem
Computerized maintenance scheduling
Effective use of maintenance staff
Early detection of problems
More satisfied occupants
The controllers typically have analog and digital inputs, that allow measurement of
the variable (temperature, humidity, or pressure) and analog and digital outputs
for control of the medium (hot/cold water and/or steam). Digital inputs are
typically (dry) contacts from a control device, and analog inputs are typically a
voltage or current measurement from a variable (temperature, humidity, velocity, or
pressure) sensing device. Digital outputs are typically relay contacts used to start
and stop equipment, and analog outputs are typically voltage or current signals to
control the movement of the medium (air/water/steam) control devices.
144
6.3.2 Integration
When different DDC data networks are linked together they can be controlled
from a shared platform. This platform can then share information from one language
to another. For example, a LON controller could share a temperature value with a
BACnet controller. The integration platform can not only make information
shareable, but can interact with all the devices.
6.3.3 In HVAC
DDC is often used to control HVAC (heating, ventilating, and air conditioning) devices such
as valves via microprocessors using software to perform the control logic. Such systems
receive analog and digital inputs from the sensors and devices installed in the HVAC system
and, according to the control logic, provide analog or digital outputs to control the HVAC
system devices.
These systems may be mated with a software package that graphically allows operators to
monitor, control, alarm and diagnose building equipment remotely.
145
Table 6.1: Logic Table for Air Handling Unit
146