2022 12 05#ReleaseNotes - 750 8x0x
2022 12 05#ReleaseNotes - 750 8x0x
RELEASE NOTES
CONTROLLER PFC100, PFC200, 1. GENERATION - 750-810X , 820X
Content
1. Firmware Release 03.10.10 (22) ..................................................................................................................................... 2
2. Firmware Release 03.10.08 (22) ..................................................................................................................................... 5
3. Firmware Release 03.09.04 (21) ..................................................................................................................................... 8
4. Firmware Release 03.08.08 (20) ....................................................................................................................................11
5. Firmware Release 03.08.07 (20) ....................................................................................................................................11
6. Firmware Release 03.07.14 (19) ....................................................................................................................................15
7. Firmware Release 03.06.19 (18) ....................................................................................................................................18
8. Firmware Release 03.06.11 (18) ....................................................................................................................................19
9. Firmware Release 03.06.09 (18) ....................................................................................................................................20
10. Firmware Release 03.05.10 (17) ....................................................................................................................................23
11. Firmware Release 03.04.10 (16) ....................................................................................................................................26
12. Firmware Release 03.03.11 (15) ....................................................................................................................................28
13. Firmware Release 03.03.10 (15) ....................................................................................................................................28
14. Firmware Release 03.02.02 (14) ....................................................................................................................................31
15. Firmware Release 03.01.07 (13) ....................................................................................................................................32
16. Firmware Release 03.00.39 (12) ....................................................................................................................................34
17. Firmware Release 03.00.35 (12) ....................................................................................................................................36
18. Firmware Release 02.08.35 (11) ....................................................................................................................................38
19. Firmware Release 02.08.31 (11) ....................................................................................................................................38
20. Firmware Release 02.08.26 (11) ....................................................................................................................................39
21. Firmware Release 02.08.25 (11) ....................................................................................................................................39
22. Firmware Release 02.07.07 (10) ....................................................................................................................................41
23. Firmware Release 02.06.20 (09) ....................................................................................................................................43
24. Firmware Release 02.05.23 (08) ....................................................................................................................................46
25. Firmware Release 02.04.24 (07) ....................................................................................................................................47
26. Firmware Release 02.04.22 (06) ....................................................................................................................................48
27. Firmware Release 02.04.21 (05) ....................................................................................................................................51
28. Firmware Release 02.03.23 (04) ....................................................................................................................................52
29. Firmware Release 02.02.20 (03) ....................................................................................................................................55
30. Firmware Release 02.01.10 (02) ....................................................................................................................................57
31. Firmware Release 02.01.04 (01) ....................................................................................................................................58
Compatible from e!COCKPIT Version 1.11 Compatible from WAGO I/O PRO Version 2.3.9.61
Starting with firmware 19, the PFC200 of the second generation has its own image
and release notes.
Affected articles/Available for Supported PLC
Article Number Designation CDS2.3 e!Runtime
750-8100 PFC100 2ETH ECO 4 X
750-8101 PFC100 2ETH 4 X
750-8101/025-000 PFC100 2ETH T 4 X
750-8102 PFC100 2ETH RS 4 X
750-8102/025-000 PFC100 2ETH RS T 4 X
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued
4
No further development of the functional scope
1.1 System
[FIXED] WAT-34925 Extended HTTP security header options in lighttpd (X-Content-Type-
Options, Referrer-Policy).
[FIXED] WAT-34893 Fixed CVE-2022-0529 , CVE-2022-0530
For the transition, it will be included for now. In the next release, the
servers will still be part of the firmware.
[REMOVED] No more unauthenticated guest access possible in WBM.
No more unauthenticated configtool call possible via WBM
HTTP/HTTPS interface.
Compatible from e!COCKPIT Version 1.11 Compatible from WAGO I/O PRO Version 2.3.9.61
Starting with firmware 19, the PFC200 of the second generation has its own image
and release notes.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued
4
No further development of the functional scope
2.1 System
[NEW] WAT-34301 Uptdated lighttpd to version 1.4.64
Updated PHP to version 7.4.28
[NEW] WAT-34555 Allow to specify NTP server via hostname (additonal to IP address)
[NEW] WAT-34471 Updated ca-certificates to version NSS_3_78_RTM
[NEW] WAT-26465 Allow to configure NTP servers by hostname also (previously only IP
addresses were allowed).
[FIXED] WAT-34341 OpenSSL updated to 1.1.1n
[FIXED] WAT-34439 Fixed CVE-2021-29155
[FIXED] WAT-34387 Fixed data race during restore (WAGOupload failed to complete restore
during controller reboot).
[FIXED] WAT-34291 Updated libxml2 to 2.9.13 (fixes CVE-2022-23308)
[FIXED] WAT-34290 Updated expat to 2.4.7 (fixes CVE-2022-25235, CVE-2022-
25236, CVE-2022-25313, CVE-2022-25314, CVE-2022-25315)
[FIXED] WAT-34185 Fixed integer in XML_GetBuffer
For security reasons, only users which are part of a WBM user group
are able to access WBM. All other users will rejected at WBM login.
[NEW] WBM provides information about the used trademarks.
[NEW] Force booting from the internal flash only and prohibit booting from SD
card.
Notice: if you force booting from internal flash, an update is only possi-
ble via ETHERNET. There is a risk that you will no longer be able to
connect to the device if there are any problems.
[FIXED] WAT-34138 No Cross-site Scripting via wrong configtool name.
[FIXED] WAT-32553 Enhanced user guidance and error message in case of wrong/missing
label text while creating new filesystem on memory card.
For the transition, it will be included for now. In the next release, the
servers will still be part of the firmware.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.10* Compatible from WAGO I/O PRO Version 2.3.9.61
* Service Pack 1 (2021-12) required
Starting with firmware 19, the PFC200 of the second generation has its own image
and release notes.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued
4
No further development of the functional scope
3.1 System
[NEW] WAT32833 Improved robustness of application control with operating mode switch
and additional detection of invalid states.
[NEW] WAT34079 Libcurl update to version 7.81.0
[NEW] Bootloader update to version 2021.10.0
[FIXED] WAT33827 Sender of SNMP "Informs" could be changed
[FIXED] WAT33547 deactivate Multicast Snooping by default
[FIXED] WAT34053 Security-Fix in config-tool print_log.
[FIXED] WAT34123 Network bridges discard their IP address when all associated network
ports are disconnected.
[FIXED] WAT34284 “Dirty Pipe" enables root privileges
CVE-2022-0847
Cloud Connectivity
[NEW] Proxy configuration for MS Azure + Wago Cloud in WBM configurable
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.10* Compatible from WAGO I/O PRO Version 2.3.9.61
* Service Pack 1 (2021-12) required
4.1 System
[FIXED] WAT33793 IPsec: SHA512 based ESP algorithms not available.
[FIXED] WAT33796 Kernel does not boot correctly during FW update.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.10* Compatible from WAGO I/O PRO Version 2.3.9.61
* Service Pack 1 (2021-12) required
Starting with firmware 19, the PFC200 of the second generation has its own image
and release notes.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued
4
No further development of the functional scope
5.1 System
User "user" and "admin" can still be used for authorization in WBM as
default, but they are no longer exclusive for WBM.
Every WBM user can only change his own password now.
Note:
CAN
[NEW] It is now possible to use extended CAN configuration in e!COCKPIT
Cloud Connectivity
[NEW] Cloud Connectivity: Update Azure SDK to 1.6.0
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.9* Compatible from WAGO I/O PRO Version 2.3.9.61
* Service Pack 1 (2021-08) required
Starting with firmware 19, the PFC200 of the second generation has its own image
and release notes.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued
4
No further development of the functional scope
6.1 System
[NEW] Extend routing functionality: routing over an interface.
[NEW] WAT25306 The configuration of a default gateway can now be set on the TCP/IP
configuration page in the WBM together with the IP configuration.
[NEW] Extend the Fix-IP-Feature to address all configured bridges. (Not only
WAT32943 bridge 0)
[NEW] Updated kernel to version 5.10
[FIXED] WAT22710 SEC: Disabled local and remote port forwarding for SSH server by de-
fault (conforming to in BDEW whitepaper)
[FIXED] WAT27285 Fixed invalid progress of 30% during firmware update.
[FIXED] WAT32419 Prevent dropbear from logging "no such file or directory"
[FIXED] WAT32412 PFC 3G: Show correct connection state and signal strength with spe-
cific SIM cards for data service only
[FIXED] WAT33149 Allow PN connection up to 64 modules.
WAT30279
[FIXED] WAT32675 Fix synchronization error while using WagoLibNetSnmpManager and
WagoLibNetSnmp.
[FIXED] WAT28783 PFC is not sending coldstart trap via SNMP
[FIXED] WAT27060 WagoConfigToolLib could not be used to read DHCP assigned DNS
server and default gateway
[FIXED] WAT32606 Fix port mirroring visualization error in WBM.
WAT32832
[FIXED] SEC: Updated dnsmasq to 2.83; Fixed CVE-2020-25684, CVE-2020-
25685, CVE-2020-25686
[FIXED] SEC: Updated sudo to 1.9.5p2; Addresses CVE-2021-3156
[FIXED] WAT32065 Fixed issue displaying the wrong time zone after select time zone CET
via WBM.
[FIXED] WAT32817 Fix SNMP v2c Inform Notification function (extend FB)
[FIXED] Updated ca-certificates to NSS.3.60.1.RTM
[FIXED] WAT33002 Updated webserver lighttpd to version 1.4.59
[FIXED] WAT32855 PFC 3G: Modem Management: Unexpected network traffic with deac-
tivated wireless data service
[FIXED] WAT33412 Fix temporary network loop/network bridge within the FW update pro-
cess, if the network is separated and connected to more than one net-
work
Modbus
[NEW] Bidirectional access to address ranges adjustable
[FIXED] WAT33049 Fix Modbus Master (Client) mode OnValueChange to write data in Modbus
WAT33166 Slave (Server) registers.
CAN
[FIXED] WAT-32262 PFC sends unexpected CAN emergency telegram.
[FIXED] WAT-32399 CAN layer2 receive does not work when calling FbCanL2Open in each
SPS cycle.
[FIXED] WAT-32995 CAN layer2 keeps sockets open / memory leak
[FIXED] WAT-32771 CAN layer2 memory leak when opening CAN socket in disconnected state
Cloud Connectivity
[NEW] Add support for cache mode SD-Card for NativeMQTT
[NEW] IEC retain data is not deleted during transfer of boot application. Retain data
may be reused if it is still compatible to boot application.
[FIXED] Use exponential backoff for retry interval if connection fails due to failing
certificate validation
6.4 Libraries
[FIXED] WAT-33313 Set path to standard certificate store (/etc/ssl/certs) for curl library.
[FIXED] WAT-32886 Restore behavior of WagoSysProcess library for PFC firmware release 17
and older.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.8 Compatible from WAGO I/O PRO Version 2.3.9.61
7.1 System
[NEW] PFC200 with 4G: Send and receive SMS via e!COCKPIT IEC-Library
PFC200 with 4G: Modem configuration can now be prepared in WBM even when
[NEW]
SIM is not inserted or locked
[NEW] PFC200 with 4G: Manual configuration of net type and provider via WBM
[NEW] PFC200 with 4G: Networkscan of available mobile radio networks via WBM
[NEW] PFC200 with 4G: CID/LAC to determine the location of the cell tower
[FIXED] PFC200 with 4G: Stabilization for applications with massive cell changes
PFC200 with 4G: Authentication type "PAP or CHAP" can now be configured cor-
[FIXED] WAT-32751
rectly
[KNOWN] PFC200 with 4G: 2kB Memoryleak for each Modem-Reset.
Attention!
To be able to use the new features for the PFC200 with 4G, e!COCKPIT v1.9 is required. In addition, a small
change must be made in the Library Manager of the e!COCKPIT project. The placeholder WagoSysModem_Inter-
nal must be set to WagoSysModem_Internal_PFC_1.1.4.0.
Compatible from e!COCKPIT Version 1.8 Compatible from WAGO I/O PRO Version 2.3.9.61
8.1 System
[FIXED] WAT32767 Fixed system freeze on frequent access to retain memory.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Compatible from e!COCKPIT Version 1.8 Compatible from WAGO I/O PRO Version 2.3.9.61
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued, last call on 31.12.2020
3
Firmware is guaranteed to be maintained until the last FW release 2021
4
New features not guaranteed for next firmware versions
9.1 System
[NEW] PFC200 with 4G: Modem reset possible
[NEW] The invalid IP adress 0.0.0.0 is not accepted by the system.
In case of IP missconfguration a corresponding error message
[NEW]
is displayed in the WBM dialog.
[NEW] Compiler Update to Linaro GCC 9.2
[FIXED] WAT31972 WBM: Not all TZ strings can be set and displayed
WAT32325
[FIXED] WAT32141 Communication over service port could not established.
[FIXED] WAT31951 750-8207: Connection problems with roaming SIM cards
[FIXED] WAT32108 750-8212: Config tool bootproject argument not available
[FIXED] WAT32262 PFC sends undocumented emergency telegram
[REMOVED] Removed deprecated function ct_liblog_reportError
OPC UA
[NEW] Integration of the WAGO OPC UA server into the Firmware.
[NEW] Import of a customer-specific information model possible.
(WAGO Mapping Editor is required.)
[REMOVED] Discontinue 3S OPC UA Server in the firmware. (Can be installed
for firmware 19, available via support: [email protected]).
CAN
[FIXED] WAT32038 CAN continues to run even if the Runtime crashes
[FIXED] WAT31936 750-8215: Missing EDS file for CAN
BACnet
[NEW] BACnet S license added to the BACnet Stack.
[NEW] BACnet: Added further error code information on incorrect user
input.
Cloud Connectivity
[NEW] Cloud Connectivity: Use Azure specific system properties to pro-
vide content type and content encoding of device2cloud mes-
sages for message routing
[FIXED] Cloud Connectivity: WBM: Minor usability issues
[FIXED] Cloud Connectivity: Improve robustness in scenarios with high
transmission rate and high data volume
[FIXED] Cloud Connectivity: Resend DeviceHello message with interval
of 30 seconds if corresponding CloudHello message is not re-
ceived
[REMOVED] Cloud Connectivity: Discontinue support of WAGO Protocol 1.0
[REMOVED] Cloud Connectivity: Discontinue support of Cloud Connectivity
with WagoLibCloud_02.lib for Codesys 2.3
SFTP
[FIXED] WAT31270 SFTP Client freezes
9.4 Libraries
[NEW] WAT31930 Updated libssh (1.8.0 -> 1.9.0)
[NEW] Library for monitoring and controlling the modem.
[FIXED] WAT32098 CDS2 configToolFb is blocking while error handling.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued, last call on 31.12.2020
3
Firmware is guaranteed to be maintained until the last FW release 2021
4
New features not guaranteed for next firmware
10.1 System
[NEW] Each bridge contains its own MAC address for 2nd generation
PFC200(750-821X)
[NEW] PFC 4G: Configurable data service
[NEW] PFC 4G: Activate SIM card with PIN/PUK
[NEW] PFC 4G: Determine signal strength from the mobile network
[NEW] WBM-NG: Extension by the area "Package Server”
[NEW] WBM-NG: Password length increased to maximum 100 characters
[NEW] WBM: Discontinuation of the legacy WBM
[NEW] Config-tool no longer uses /etc/specific/network-interfaces.xml (do not
use this file anymore - it will be removed in future versions)
[NEW] config-tool ipdatacheck option --subnet-check is removed
[NEW] CBM: TCP/IP settings show bridge names instead of ethernet interface
labels
[NEW] CBM: Ethernet port physical settings now support 4-port PFCs (X1, X2,
X11, X12)
[NEW] Cloud Connectivity: Add support for two parallel cloud connections
[NEW] Cloud Connectivity: Add statically configuration of protocol version
[NEW] Cloud Connectivity: Add support for certificate based authentification for
Azure IoT Hub connections
[NEW] Cloud Connectivity: Add option for application specific property for Az-
ure IoT Hub connections
[FIXED] CC-1900 Cloud Connectivity: Improve robustness of Azure IoT hub connection
when using an unreliable network connection
[FIXED] WAT31159 SEC: WBM-NG: Cookies can no longer be deleted or modified over an
insecure connection
[FIXED] WAT26409 PFC 3G: The options PREFER_GSM and PREFER_UMTS for mobile
networks are no longer supported because they are not correctly con-
sidered by the modem
[FIXED] WAT31612 PFC 3G: Visibility of the signal strength restored
[FIXED] WAT31625 PFC 3G: Provider list for manual selection is also displayed if a SIM
card without PIN is used
[FIXED] WAT31910 Fixed restore of NTP server settings
[FIXED] WAT31537 SEC: PPPD update
[KNOWN] WAT31818 Under Firefox, the old WBM allowed to accept passwords of any length
but only the first 32 characters were saved. In order to use these pass-
words in WBM-NG, only the first 32 characters of these passwords
must be entered.
The Release Note(s) and the corresponding update(s) are provided free of charge. The stat-
utory warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the
Release Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are)
intended to further enhance and / or to enrich our product(s), but does not mean that the
previous software version was defective. In order to benefit from the improvements, we
generally recommend the implementation of the update(s), but we cannot assume the final
responsibility for the installation of the update(s) or their costs. Since we know neither the
concrete application nor the individual conditions of use.
Important:
1
e!RUNTIME available for devices produced 07/2017 or later
2
Product discontinued, last call on 31.12.2020
3
Firmware is guaranteed to be maintained until the last FW release 202
11.1 System
[NEW] New Web Based Management integrated. WBM has a contemporary look
and feel such as an improved handling.
[NEW] WBM-NG: network configuration adopted to support 4 ports
[NEW] WBM-NG: configuration is based on bridges, instead of interfaces
[NEW] WBM-NG: Improved DIP switch logic
[NEW] SSH host keys are taken over during firmware update
[NEW] Custom OpenVPN data is regarded during backup
[NEW] Added curl command line tool
[NEW] Updated tcpdump (4.9.2 -> 4.9.3)
[NEW] Updated dropbear (2018.76 -> 2019.78)
[NEW] Updated libcurl/curl (7.65.0 -> 7.67.0)
[NEW] Updated net-snmp (5.7.3 -> 5.8)
[NEW] Updated sudo (1.8.28 -> 1.8.31)
[NEW] Updated PHP (7.3.5 -> 7.3.15)
[NEW] Updated mdmd (0.5.3 -> 0.7.6)
Several and improvements for configuration of internal 3G modem and ad-
ditional failure diagnostics (see new version of 750-8207 manual)
[NEW] WAT31394 Added EXT4 filesystem as SD card formatting option.
[NEW] WAT29230 Enlargement of the CANopen master configuration memory now enables
more complex CANopen project planning.
[FIXED] WAT30870 Internal MAC address translation.
[FIXED] WAT29930 Conflicted IP configurations.
WAT31094
[FIXED] WAT31179 Missing routing table update.
WAT31114
[FIXED] WAT30885 Changing third DIP switch octetts is not possible.
[FIXED] WAT30573 Modem cannot be addressed after several resets.
WAT30910
[FIXED] WAT31166 Modem swichtover to GSM not possible.
[FIXED] WAT31218 Possible loss of internal 3G modem parameter on power cycle.
[FIXED] WAT31543 IP remains on bridge after link loss on interfaces
[FIXED] WAT31072 Fixed CVE-2019-5134, 5135, -5155, -5156. 5157, -5166, -5167, -5168,
WAT31071 -5169, -5170, -5171, -5172, -5173, -5174, -5175, -5176, -5177, 5178,
WAT31068 -5179, -5180, -5181, -5182, -5185, -5186
More information: www.wago.com/security
BACnet
[NEW] Add BACnet Support for PFC200 G2 (750-8212, 750-8212/025-00X, 750-
8213) and Control Panel Devices (762-430X/8000-002, 762-530X/8000-
002)
CAN
[FIXED] WAT31136 Added method CAN_RX_ALL in Codesys2 CANLayer2 library. This method
allows processing of CAN telegrams in order of their receiption. New ver-
sion of WagoCANLayer2_03.lib is required.
MQTT
[FIXED] Fixed timestamp creation for Sparkplug NDATA messages: Use data crea-
tion time instead of transmission time
[FIXED] Increased handshake timeout for WAGO protocol
[FIXED] Try to reconnect automatically if MQTT broker denies connection
[KNOWN] 31190 Limit for maximum number of Trend Log (Multiple) Objects is set to 300
Compatible from e!COCKPIT Version 1.6.1 Compatible from WAGO I/O PRO Version 2.3.9.55
Important:
(X)1 e!RUNTIME available for devices produced 07/2017 or later
12.1 System
[FIXED] WAT31102 Improved robustness by heavy ethernet traffic.
Compatible from e!COCKPIT Version 1.6.1 Compatible from WAGO I/O PRO Version 2.3.9.55
Important:
(X)1 e!RUNTIME available for devices produced 07/2017 or later
13.1 System
[NEW] The switch mode on 4-port PFC devices (750-8215) may now be config-
ured like 2-port devices for ports X1 & X2 via WBM.
The default switch configuration on 750-8215 has changed from a fixed
separated to an all switched setting.
It is now possible to configure all 4 ports, as you like via config-tool. Our
next release will make this feature available via WBM.
[NEW] By download of the CDS3 PROFINET i-Device functionality, the
PROFINET-designated ports X11 & X12 are automatically combined in
one bridge.
[FIXED] WAT30375 Cloud-Connectivity: Improve robustness of Azure IoT hub connection when
using an unreliable network connection.
[FIXED] WAT30253 Correct impact of SMS method calls and modem status requests from
Codesys IEC application to modem data service for PFC 750-8207.
The Release Note(s) and the corresponding update(s) are provided free of charge. The statutory
warranty and liability regulations of §§ 521, 523 BGB apply to possible errors in the Release
Note(s) or possible defects in the update (CISG is excluded). The update(s) is (are) intended to
further enhance and / or to enrich our product(s), but does not mean that the previous software
version was defective. In order to benefit from the improvements, we generally recommend the
implementation of the update(s), but we cannot assume the final responsibility for the installation
of the update(s) or their costs. Since we know neither the concrete application nor the individual
conditions of use.
Compatible from e!COCKPIT Version 1.6 Compatible from WAGO I/O PRO Version 2.3.9.55
Important:
14.1 System
[FIXED] WAT29498 e!COCKPIT BlkDrvTcp Exception
[FIXED] WAT30282 "force" on the Software Uploads page in the Web based Management does
not work
Cloud Connectivity
[NEW] Compression method integrated
[NEW] WAGO protocol extended by data type String
[NEW] Recovery of an application backup via WAGO Cloud (application update)
[NEW] Restoring an application backup via WAGO Cloud in the context of a firm-
ware update (device update)
OPC UA
[FIXED] WAT29993 OPC UA inactive after firewall activation.
Profibus
[FIXED] WAT30087 e!COCKPIT: Profibus Slave: wrong input data when mapping to existing
variables
[FIXED] WAT30170 Profibus slave: no correct data transmission of array slots when accessing
via addresses / existing variables
14.4 Libraries
[FIXED] WAT30132 WagoSysCurl does not consider the udiStringLength of the method
curl_easy_setopt_STRING2
Compatible from e!COCKPIT Version 1.5.1 Compatible from WAGO I/O PRO Version 2.3.9.55
Important:
(X)1 e!RUNTIME available for devices produced 07/2017 or later
Firmware 03.01.07 (13) is not permitted to be used for Profibus Slave Devices. (750-8206,
750-8216, and variants; see above)
15.1 System
[NEW] New Device: PFC200 with BACnet (750-8212/000-100)
[NEW] Backups can be encrypted via password.
[NEW] PHP updated to 7.3
[NEW] OpenSSL updated to 1.0.2q
15.4 Libraries
[FIXED] WAT29373 WagoAppHttp: Data sporadically in header.
[FIXED] WAT29513 WagoAppFTP: FTP/FTPS client freezes during processing.
Compatible from e!COCKPIT Version 1.5 Compatible from WAGO I/O PRO Version 2.3.9.55
16.1 System
[FIXED] WAT28151 Unreliable behavior of the mobile connection (750-8207)
WAT28953
WAT28822
WAT28853
[FIXED] WAT29247 Directory structure of /home folder was destroyed after system backup
[NEW] WAT29453 Checksum of CODESYS 2.3 project is shown in WBM
[NEW] WAT29454 Advanced Intrusion Detection Environment (AIDE) can be used to identify
changes of filesystem
Profibus
[FIXED] WAT29313 Using Bool and Real variables under Profibus does not work properly.
WAT28790
Compatible from e!COCKPIT Version 1.5 Compatible from WAGO I/O PRO Version 2.3.9.55
Important:
(X)1 e!RUNTIME available for devices produced 07/2017 or later
17.1 System
[FIXED] WAT29498 Net-LED shows wrong connection state
[FIXED] WAT25828 Restricted remote connectivity between e!Cockpit and 750-8207 via 3G mo-
dem and VPN
[FIXED] WAT26533 WebVisu may open too many sockets
[FIXED] WAT27038 /va/log/access.log may grow up to 4 MBytes
[KNOWN] WAT27110 SNMP exceptions while sending Messages from different Tasks
[KNOWN] WAT27216 Ethernet Broadcast and Bandwidth limitation does not work properly.
Cloud Connectivity
[NEW] Handshake between WAGO Cloud and PFCx00 (Cloud Connecitvity)
[NEW] Event-based publishing of data via the Wago protocol
[NEW] Integration of native MQTT
[NEW] Support of Sparkplug protocol (can only be used with license)
OPC UA
[FIXED] WAT23100 OPC UA low update rate in case of more than 1000 variables
Profibus
[KNOWN] WAT29313 Using BOOL variables under Profibus does not work properly.
17.5 Libraries
[NEW] SQlite Databas Management System (including IEC Library)
[KNOWN] WAT26085 WagoAppProcessorLoad returns invalid cpu load value, calculation in-
cludes not all system processes
[KNOWN] WAT27060 WagoConfigToolLIB.lib cannot read some networking settings when con-
figured with DHCP
18.4 Libraries
[FIXED] WAT26587 WagoLibNetSNMP: Register of custom IDs does not work
[FIXED] WAT24127 WagoLibNetSNMP: Excessive settings of OIDs could cause connection
aborts in debug mode.
[FIXED] WAT25792 NMT-Master doesn’t start the slaves correctly after “Bus Off”.
[FIXED] WAT25815 Slave does not work properly when Runtime is in Stop.
[FIXED] WAT24216 High jitter of the sync telegram.
[FIXED] WAT25418 CAN task stops after some time.
[FIXED] WAT25204 CAN transmission error when using Heartbeat.
OPC-UA
[FIXED] WAT25214 Object "Service Level" is set to "0". (now “200”)
Important:
(X)1 In this version the Telecontrol feature is not available in e!RUNTIME.
21.1 System
[NEW] WAT MQTT support is part of the standard firmware package
[FIXED] WAT22634 Memory leak in the mdmd
[FIXED] WAT24268 GSM-Modem reports "Error while Reading SIM-Data" when automatic
switch from UMTS to GSM is performed
[FIXED] WAT23086 Controller may crash while scanning with e!COCKPIT
[FIXED] WAT21999 Memory leak in the LED server daemon
[FIXED] WAT Several security leaks, see also WAGO homepage for further details on
known security vulnerabilities
[KNOWN] WAT25270 The LED stops blinking after long term at times
[KNOWN] WAT24264 Ethernet broadcast and bandwidth limitation does not work properly
[KNOWN] WAT25246 IPsec implementation is not conform according to the RFC
[KNOWN] WAT22573 SNMP exceptions while sending messages from different tasks
[KNOWN] WAT22155 Installation of IPK packages may fail because of timeouts
CAN/CANopen
[FIXED] WAT25204 CAN transmission error when using Heartbeat telegrams
[KNOWN] WAT24358 CANopen Baudrate 800 kB not supported on new controllers 750-821x
Profibus
[FIXED] WAT23591 PROFIBUS: timing problems with 12 MBaud
[FIXED] WAT23828 750-8206 PROFIBUS Slave Array of Bool Mapping Master Slave not com-
plete
[KNOWN] WAT25074 750-8208: Problems with recalculation of PROFIBUS addresses while add-
ing new modules inside PROFIBUS Master configurator
[KNOWN] WAT25529 750-8208: A Project download fails if profibus I/O data size is greater than
3528 byte. (The documented I/O data size of the Profibus master is reduced
in this firmware)
[KNOWN] WAT25517 The use of BusDiag.lib is limited to older hardware according to buffer size
limitation. Strictly recommended is the use of the wago library
WAGO_BusDiag_01.lib.
21.6 Libraries
22.1 System
[FIXED] WAT22022 Sometimes NTP settings were overwritten after reboot.
[FIXED] WAT23465 Permanent debugging with IO-Check or e!COCKPIT over several days
could result into a system crash.
None
CAN/CANopen
[FIXED] WAT22728 Error message “PDO-Mapping 1601-1 Failed” after download of an e!Cock-
pit project
[FIXED] WAT21010 Library CIA405_NMT showed a wrong error message “0x25” for a non-ex-
isting device
[FIXED] WAT20942 Bus OFF LED was switching back to green also if there is no physical con-
nection
[FIXED] WAT20890 Function block CANOPEN_DIAG showed STATE UNKNOWN if a de-
vice(node guarding) was stopped
Profibus
None
22.6 Libraries
23.1 System
[FIXED] WAT22713 Tcpdump Packages updated to 4.9.0
[FIXED] WAT22505 OpenVPN – After time x no communication possible despite established
connection
[FIXED] WAT22021 PFC200 loses NTP client settings
[FIXED] WAT22219 Failure to execute the PING via FBPing can result in connection problems
via Ethernet
[FIXED] WAT22158 Insecure encryption algorithms in FTPS server
[FIXED] WAT22021 PFC200 loses NTP client settings
[FIXED] WAT21503 The firewall does not allow the IEC60870-5-104 and IEC61850 protocols
[FIXED] WAT21487 Malfunction with RS485 and parity none on onboard serial interface
[FIXED] WAT21457 Syslog server accessible from outside
[FIXED] WAT21407 Various security problems in the configtools scripts
[FIXED] WAT21313 PFC100 : Inaccuracy of the real-time clock
[FIXED] WAT20915 PFC100: Data corruption when reading the retentive data
[FIXED] WAT16121 PHP Version is sent inside HTTP header
[FIXED] WAT15970 Reflected cross site scripting
[FIXED] WAT21999 The LED server daemon has a memory leak.
[KNOWN] -/- MySQL is not compatible with PHP server version 5.6.27 update
CAN/CANopen
[FIXED] WAT20635 The PFC200 as a CANopen master sends reset node to all nodes after a
break.
Profibus
None
23.6 Libraries
[KNOWN] WAT22595 By updating the OpenSSL with the CoDeSys V2.3 library WagoLibSSL it is
no longer possible to use the methods of the SSLv2.
Instead, use SSLv23 or higher. The default is TLS V1.2
24.1 System
[FIXED] WAT20045 Tool “Ethernet Settings” failed to finish the write command
[FIXED] WAT19844 750-8207: Signal strength LED didn’t work
[FIXED] WAT18914 Mounting the SD card after pull out/in during file access
[NEW] WAT18216 IO-Check: Setting of module parameters
[FIXED] WAT18494 Not accessible caused by alternating the switch mode to separated
[NEW] WAT16609 Firewall user filter allow white and black listing
[FIXED] WAT15953 Firewall VPN interface not selectable
[NEW] WAT14096 New error code for number of modules to high (1 + 16)
CAN/CANopen
[NEW] WAT16803 Supports CANopen device profile DS405
Profibus
None
24.6 Libraries
[FIXED] WAT20227 Sercom.lib: ACCESS VIOLATION if used COM port number >=2
[FIXED] WAT20022 e!Runtime WagoAppSocket: FbUdpPcketClient didn’t reset the trigger input
[FIXED] WAT19383 e!Runtime WagoSysFileDir: Folder creation on a not existing media caused
system crash
[FIXED] WAT18322 e!Runtime WagoAppTime: Caused segmentation faults
26.1 System
[NEW] WAT12376 Add localdomain.lan as default domain
[NEW] WAT13150 Use the NTP server address from DHCP request answer
[NEW] WAT13933 Target memory size is selectable if Create Boot Image is used
[NEW] WAT13970 Change default assignment of the serial Interface to unassigned
[NEW] WAT13980 Extend the service interface with Linux console
[NEW] openVPN/ipsec configuration via web page of web based management
[NEW] starting phases of the device are better signalled by LEDs, boot phase is
represented by flashing SYS LED
[FIXED] WAT9839 Create Boot Image does not work with SD Cards greater or equal than 16
GB with FAT formatting cards
[FIXED] WAT11931 Error in flow control of the serial interface avoid the reconfiguration
[FIXED] WAT14196 Updated SSH-Daemon dropbear to latest release version 2015-67.
[FIXED] WAT14473 Switching terminal bus extension does not work
[FIXED] WAT15752 Correction of the SYS-LED blink codes
[FIXED] WAT15896 Security: to many internal or detailed information in error messages
[FIXED] WAT16500 DHCP Settings override static parameter
[FIXED] WAT16515 Missing data file synchronization by FTP put command
PROGRAM POU
VAR RETAIN
myString1: STRING; (* with error *)
myString2: STRING(79); (* working *)
END_VAR
All variables in structures must be declared with a 4-byte alignment and
string variables in structures must use an odd length.
[KNOWN] The Telecontrol functionality is only available together with CODESYS V2.3
on the devices.
CAN/CANopen
[FIXED] WAT13692 Master does not start guarding with setting “No initialization”
[FIXED] WAT14076 Master does not restart slave after guarding error
[FIXED] WAT14359 No automatic restart at bus error
WAT16298
[FIXED] WAT14373 Master does not assume sync consuming parameters
[FIXED] WAT14570 CODESYS V2.3: PFC200 as CAN-Layer2 device can't receive telegrams af-
ter program download
[FIXED] WAT15121 Master treated slaves without static configuration in the IDE wrong
[FIXED] WA15648 The blink code of the CAN LED is incorrect when Guarding Error
Profibus
[] None
26.6 Libraries
[NEW] WAT10385 e!RUNTIME: Implementation of the dynamic K-Bus configuration
[NEW] WAT10539 CODESYS V2.3: SMS transfer via IEC Library SMS_01.lib and
e!RUNTIME: WagoAppSerial_Sms.lib supported
[NEW] WAT12372 e!RUNTIME: WagoAppSNMP.Lib.was added
[NEW] WAT12373 e!RUNTIME: WagoAppFTP.Lib was added
[NEW] WAT13928 Using the new toolchain for documentation creation of e!RUNTIME
libraries leading to better content presentation
[NEW] WAT16393 CODESYS V2.3: BusDiag.lib: New implementation of the error codes for
Bus fault → PreOp and Stopped
Bus not communicating → Bus off
[FIXED] WAT10772 Compatible implementation of the interface RS232 at Online Change
[FIXED] WAT11484 e!RUNTIME: WagoSysAtomic Interface compatible newly created
[FIXED] WAT11780 CODESYS V2.3: WagoConfigTool.Lib function IP_TO_STRING provides
false return value
[FIXED] WAT13882 CODESYS V2.3: Expansion of the WagoLibSSL.lib result of new TLS1.2
[FIXED] WAT14610 Error process data access in WagoLibKBus.lib after online change
[FIXED] WAT14718 Incorrect handling of parity errors in WagoSysCom.
[FIXED] WAT14899 CODESYS V2.3: Function SysDirRead treats the file pointer wrong
[FIXED] WAT15665 Frame Error or Parity Error in the on board serial interface
[FIXED] WAT16103 CODESYS V2.3: SNMP when sending a trap with version v2c via a host
name the Runtime may crash
[FIXED] WAT16627 CODESYS V2.3: WagoLibSSL.lib After online change a connection is not
possible
[FIXED] WAT16734 CODESYS V2.3: Functions of the SyslibSocketsAsync.lib return error
[FIXED] WAT16746 CODESYS V2.3: WagoLibLed.lib: Function LED_GET_STATE always pro-
vides the value 0 for the LED color
[FIXED] WAT17161 CODESYS V2.3: SysSockSetOptions() supports no Multicast groups
[KNOWN] WAT18533 Requesting the signal strength form the 750-8207 modem may hold the call-
ing CODESYS task.
28.1 System
[NEW] WAT10540 Firewall IP / Ports
[NEW] WAT9785 Broadcast Protection / ICMP Protection
[NEW] WAT10549 Traffic Limitation, Port Mirroring
[NEW] WAT10538 MAC Address Filter
[NEW] WAT10462 Local DHCP Server (not activated by default)
[NEW] WAT10462 Local DNS Server (not activated by default)
[NEW] WAT10463 NTP-Client supports up to 4 NTP-Servers
[NEW] WAT Domain name und gateway are taken from the DHCP Request
[FIXED] WAT9204 CpuUsage: monitoring requires excessive CPU load
[FIXED] WAT9972 WAGO Ethernet-Settings / IO-Check: communication speed is low
[FIXED] WAT10504 IO-Update: communication speed is low
[FIXED] WAT11377 Security improvement: Port of WAGO tools can be deactivated by user
[FIXED] WAT11799 Local bus with only end module leads to usage of 100% cpu load
[FIXED] WAT11912 WAGO-Ethernet-Settings communication with controller temporary stops
[FIXED] WAT11939 Factory Reset does not reset all parameters
[FIXED] WAT12452 Security improvement: bash code injection vulnerability (shellshock)
[FIXED] WAT12819 Security improvement: OpenSSL update to 1.0.0o
[FIXED] WAT13289 WAGO-Ethernet-Settings: COM port is disabled after writing the settings.
[FIXED] WAT13291 WAGO-Ethernet-Settings: IP settings are activated in sequence. This makes
it possible that devices lose their connection to the network.
[FIXED] WAT13839 SNMP: Traps in SNMP V3 are transmitted twice.
[FIXED] WAT13911 IO-LED: When booting the error code “Recoverable Error” is blinking.
[FIXED] WAT14079 Internal flash file system saves changes too late (data security in case of
unforeseen shut down)
[KNOWN] WAT13366 Ethernet-Settings: Cannot setup the second default gateway.
[KNOWN] WAT13838 Please use WAGO-Ethernet-Settings with at least version 06.03.01 (01).
[KNOWN] WAT13195 CODESYS V2.3: the use of CODESYS 2.3.9.47 is recommended in order to
resolve compiler-related problems with CONCAT string functions and nested
functions.
[KNOWN] CODESYS V2.3: various known issues in the 3S visualization.
WAT13208
[FIXED] WAT Several security leaks
[FIXED] WAT9784 Package Server does not work if system boot from SD card
[FIXED] WAT11386 Security improvement: Login within WBM websites
[FIXED] WAT12000 Security improvement: Command injection in WBM
[FIXED] WAT12200 Page Diagnostics: list items not sorted by date
[FIXED] WAT12459 Diagnostic: time stamp ignores time zone settings
[FIXED] WAT12748 Page areas were shown twice occasionally
[FIXED] WAT14121 Cannot remove all DNS Servers from list. Last item remains.
[KNOWN] WAT14073 SNMP: Authentication Key is displayed in WBM in plain text.
CAN/CANopen
[NEW] WAT10982 CODESYS V2.3: CAN Layer2 as device in dialog “PLC configuration”
[FIXED] WAT9475 CANopen Slave Sync monitoring does not work with Object 0x1006
[FIXED] WAT WagoCANopen_02.lib – several bugs
[FIXED] WAT12770 WagoCANLayer2_01.lib – several bugs
[FIXED] WAT9535 BusDiag.lib – STATE variable delivers wrong values
[FIXED] WAT9556 CANopen Master starts the slaves not reliable
[FIXED] WAT11359 Memory leak while project download
[FIXED] WAT12120 PFC200 sends message START_ALL_NODES instead of START_NODE to
projected slaves
[FIXED] WAT12744 CANopen Master start of slaves after short BusOff not reliable
[FIXED] WAT14128 CAN Bus Startup is unstable with many slaves.
[FIXED] WAT14161 In case of short-term bus errors, the slave startup again unreliable.
Profibus
[FIXED] WAT12975 GSD settings use wrong byte order (Motorola/Intel)
[FIXED] WAT14148 Modul parameter uses wrong byte orientation (motorola/intel format) in gsd
file for third party plcs (Siemens S7).
28.6 Libraries
[NEW] WAT10837 CODESYS V2.3: WagoLibNetSnmpManager.lib with support of Traps, Noti-
fication and Inform.
[FIXED] WAT Kbus Lib
[FIXED] WAT9332 SerComm.lib: support new feature in 750-652 (SW04, DMX data transfer)
[FIXED] WAT9992 SerComm.lib: communication via onboard interface cannot transmit data if
more than 512 bytes should send
[FIXED] WAT11765 SysLibFile.lib: Function SysFileDelete does not release file handles
[FIXED] WAT12128 IEC61850: Goose communication as publisher not possible
[FIXED] WAT12157 WagoLibKbus.lib: crash after multiple registration of data
[FIXED] WAT13353 CODESYS V2.3: Wrong digital offset calculation in system libraries mod-
com.lib and
WagoLibKBus.lib.
[FIXED] WAT13993 CODESYS V2.3: WagoLibNetSnmpManager.lib SNMPM_NULL_TO_TLV
can not be used.
[FIXED] WAT13999 CODESYS V2.3: Serial_Interface_01.lib FB_Serial_Interface does not work
after online change.
[FIXED] WAT14085 CODESYS V2.3 Sercomm.lib: wrong configuration handling of unconfigura-
ble serial module (750-653)
[FIXED] WAT14728 CODESYS V2.3 BusDiag.lib: DiagGetBusState does not return an error if
WAT14729 DEVICENUMBER is invalid.
[FIXED] WAT14731 CODESYS V2.3 BusDiag.lib: DiagGetState does not return an error if
BUSMEMBERID is invalid.
[FIXED] WAT15418 CODESYS V2.3 modb_l05.lib with Modbus RS485: After program download,
the interface cannot be opened sporadically.
29.1 System
[NEW] WAT10466 SSL3.0 and TLS1.1 is provided (RFC6101, RFC5246) (openssl) for use in
other library services
[NEW] WAT10465 SNMP extension in WagoLibNetSnmpManager library.
[NEW] WAT10461 Dual-LAN is configurable / activated by WBM
[NEW] WAT9679 LED signals an error even though CANopen is not configured/used.
29.6 Libraries
[NEW] WagoLibKBus.lib
This library supports the reading and writing of data points in synchronism
with the task K-Bus
[NEW] WagoCANLayer2_02.lib
This library supports the reading and writing of data on Layer 2 level
[FIXED] WAT9677 WagoCANopen_02.lib changes the behavior to meet the documentation
[FIXED] WAT10106 SysLibCom: SysComWrite does not send all data on the line
30.1 System
No updates
30.6 Libraries
No updates
31.1 System
[NEW] Firmware released first time
CODESYS Version: 2.4.7.x
LINUX Version: 3.6.11