0% found this document useful (0 votes)
44 views3 pages

Fc-Sdi-1624 - Tab Esd

The SDI-1624 module has the following specifications: - It is a safe digital input module that comes in conformal coated (FC) and non-conformal coated (FS) versions. - It has 16 input channels, requires 5Vdc or 24Vdc power, and can handle input signals up to 36Vdc. - The outputs are 24Vdc solid state and can supply up to 450mA of current.

Uploaded by

Andres Boscan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views3 pages

Fc-Sdi-1624 - Tab Esd

The SDI-1624 module has the following specifications: - It is a safe digital input module that comes in conformal coated (FC) and non-conformal coated (FS) versions. - It has 16 input channels, requires 5Vdc or 24Vdc power, and can handle input signals up to 36Vdc. - The outputs are 24Vdc solid state and can supply up to 450mA of current.

Uploaded by

Andres Boscan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

SDI-1624

Technical data
The SDI-1624 module has the following specifications:

General Type numbers1: FS-SDI-1624 V1.0


FC-SDI-1624 CCV1.0
Approvals: CE, TUV, UL, CSA, FM
Space requirements: 4 TE, 3 HE (= 4 HP, 3U)
Power Power requirements: 5 Vdc, 8 mA
24 Vdc int., 110 mA
24 Vdc ext., 110 mA (input currents)
Ripple content (on 5 Vdc): < 0.5 Vp-p (0—360 Hz)
Input Number of input channels: 16
Maximum input voltage: 36 Vdc
Input current: 7 mA at 24 Vdc
Input HIGH: > 15 Vdc
Input LOW: < 9 Vdc (I < 2 mA)
Input delay: Typically 10 ms
Output Type 24 Vdc solid state, short circuit proof
Maximum current 450 mA (see Figure 174 on page 296)
Max. load capacitance 32 μF
Voltage drop < 1.5 V at 450 mA
Key coding (See section “Key coding” on page 17)
Module connector code:
• Holes A5, C5
Chassis connector code:
• Large pins A5, C5

1 FS-type modules are non conformal coated modules.


FC-type modules are conformal coated modules. Conformal coated modules have the letters
“CC” preceding the version number.

Safety Manager Hardware Reference 297


Safety Manager Glossary

Fault Tolerant Ethernet (FTE)


An Ethernet based control network of Experion PKS.
FC
Prefix used to identify conformal-coated module from non conformal coated
modules. See also: FS.
• FC-SDI-1624 is a safe digital input module with conformal coating
• FS-SDI-1624 is a safe digital input module without conformal coating
Field Termination Assembly (FTA)
Assembly to connect field wiring to the SM chassis IO modules.
Field value
The value of a process point as present at the interface of the system with the
EUC.
Fieldbus
Wiring solution and communication protocol in which multiple sensors and
actuators are connected to a DCS or SIS, using a single cable.
Fire and Gas system
Independent protective system which continuously monitors certain process
points (e.g. combustible gas levels) and environmental points (e.g. heat, smoke,
temperature and toxic gas levels). If any of these points exceed a predetermined
level, the system will raise an alarm and take automatic action to close operating
valves and damper doors, activate extinguishers, cut off electrical power and vent
dangerous gases.
Force
A signal override of some sort that is applied on a system level.
A force applied to an input affects the input application state as it overrides the
actual field value and diagnostic state of the forced input.
A force applied to an output affects the output field state as it overrides the
application value or diagnostic value with the forced value.

Caution
Forcing introduces a potentially dangerous situation as the corresponding point
could go unnoticed to the unsafe state while the force is active.

860 Release 151, Issue 1.0


Safety Manager Glossary

FS
Prefix used to identify non conformal-coated module from conformal coated
modules. See also: FC.
• FS-SDI-1624 is a safe digital input module without conformal coating
• FC-SDI-1624 is a safe digital input module with conformal coating
Function block
Element in a functional logic diagram (FLD) which performs a user defined logic
function. Function blocks are designed to implement & re-use complex functions
via a single (user defined) element.
Functional Logic Diagram (FLD)
Diagrammatic representation of the application (conform the IEC 61131-3
standard) which is used to program Safety Manager. FLDs are directly translated
into code that can be executed by Safety Manager, thus eliminating the need for
manual programming. See also: Application Editor.
Functional safety
Part of the overall safety relating to the EUC and the EUC control system which
depends on the correct functioning of the E/E/PE safety-related systems, other
technology safety-related systems and external risk reduction facilities.

Figure 539 Failure model

L (i-1) FU Level(i) Level(i-1)


L (i FU L (i FU
"F" state
L (i+1) FU L (i+1) FU L (i+1) FU L (i+1) FU failure
"Entity X"
L (i+1) FU L (i+1) FU L (i+1) FU L (i+1) FU "F" state
failure cause

cause
L= level, i=1,2,3, etc.; FU=Functional Unit
A) Configuration of a Functional Unit B) Generalized view

Level(i) Level(i-1) Level(i) Level(i-1)


fault
failure failure
"Entity X" "Entity X"
fault
failure fault failure failure cause

fault failure cause

C) IEC 61508's and ISO/IEC 2382-14's view D) IEC 50(191)'s view

Safety Manager Hardware Reference 861