6314 2tdhhpu-052

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Product Data Sheet 9295420052

VWS0148XULDS
6314/2TDHHPU The engineer's choice
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

6314/2TDHHPU

INDEX

1 General ............................................................................................................................................................... 3
2 Mechanics .......................................................................................................................................................... 3
2.1 General......................................................................................................................................................... 3
2.2 Connections.................................................................................................................................................. 3
3 Operating Data ................................................................................................................................................... 4
3.1 Electrical Interface - Input.............................................................................................................................. 4
3.2 Electrical Operating Data .............................................................................................................................. 5
3.3 Electrical Interface - Output ........................................................................................................................... 6
3.4 Electrical Features ........................................................................................................................................ 7
3.5 Aerodynamics ............................................................................................................................................... 8
3.6 Sound Data................................................................................................................................................... 9
4 Environment....................................................................................................................................................... 9
4.1 General......................................................................................................................................................... 9
4.2 Climatic Requirements ................................................................................................................................ 10
4.3 EMC ........................................................................................................................................................... 10
5 Safety................................................................................................................................................................ 12
5.1 Electrical Safety .......................................................................................................................................... 12
5.2 Approval Tests............................................................................................................................................ 12
6 Reliability.......................................................................................................................................................... 12
6.1 General....................................................................................................................................................... 12

04/06/2019 page 2 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

1 General

Fan type Fan


Rotating direction looking at rotor Counterclockwise
Airflow direction Air outlet over struts
Bearing system Ball bearing
Mounting position - shaft Any

2 Mechanics

2.1 General
Depth 51,0 mm
Diameter 172,0 mm
Mass 0,875 kg
Housing material Metal
Impeller material Plastic
Max. torque when mounted across both mounting Wire outlet corner: 600 Ncm
flanges Remaining corners: 600 Ncm
Screw size ISO 4762 - M4 degreased, without an additional
brace and without washer

2.2 Connections

Electrical connection Wires


Lead wire length L = 365 mm
+- 10,0 mm
Tolerance
Tube length S = 10 mm
+- 2,0 mm
Tolerance

Wire Color Operation Wire size Insulation diameter


1 red + UB AWG 18 2,2 mm
2 blue - GND AWG 18 2,2 mm
3 violet PWM AWG 22 1,7 mm
4 white Tacho AWG 22 1,7 mm

The auxilliaries shown on the schematic diagram (which are required for the intended use) are not part of our delivery.

04/06/2019 page 3 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

3 Operating Data

3.1 Electrical Interface - Input

Control input PWM

Features

Inpute type Open collector


PWM - Frequency
typical: 2 kHz
Input frequency range 1 kHz - 20 kHz

Characteristics

Schematics

The shown pull-up resistor R1 to the internal reference voltage (+5V) has 4.7kOhm.

Information to the curve:

04/06/2019 page 4 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

0% - <=7% PWM: 0 1/min


7% - 10% PWM: 1.000 1/min (corresponding to min. speed)
10% - 90% PWM: linear increasing curve
90% - 100% PWM: 7.000 1/min (corresponding to max. speed)
7% PWM: 1.000 1/min (Fan on, comming from 0% PWM)
7% - 5% PWM: linear decreasing curve (von 100% PWM kommend)
5% PWM: 800 1/min or 0 1/min (Fan off, comming from 100% PWM)

Transistor requirements:
Vce max. >= 12V; Isink max. >=5mA; Vce sat. <= 0,15V

3.2 Electrical Operating Data

Measurement Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
conditions: time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.

∆p = 0: corresp. to free air flow (see chapter aerodynamics)


I: corresp. to arithm. mean current value

Name Condition
PWM 0001 PWM: 95 %; f: 2 kHz
>90% PWM; f = 2 kHz or broken lead wire (open control input)

Features Condition Symbol Values


Voltage range U 16 V 36 V
Nominal voltage UN 24,0 V
Power consumption ∆p = 0 37 W 70 W 70 W
P +- 10 % +- 10 % +- 10 %
Tolerance
PWM 0010
Current consumption ∆p = 0 2.300 mA 2.800 mA 1.850 mA
I +- 10 % +- 10 % +- 10 %
Tolerance
PWM 0010
Speed ∆p = 0 5.750 1/min 7.000 1/min 7.000 1/min
n +- 7,5 % +- 5 % +- 5 %
Tolerance
PWM 0010

04/06/2019 page 5 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

3.3 Electrical Interface - Output

Tacho type /2 (open collector)

Features Note Values


Tacho operating voltage UBS <= 32 V
Tacho signal Low US low I sink: 2 mA <= 0,4 V
Tacho signal High US high I source: 0 mA <=32 V
Maximum sink current Isink <= 20 mA
External resistor Ra from UBS to US required. All voltages measured
External resistor
to GND.
Tacho frequency (6 x n) / 60
Tacho isolated from motor No
Slew rate => 0,5 V/us

n = revolutions per minute (1/min)

Please note:
At zero speed the tacho signal is at a static HIGH. It will be also HIGH when the fan is still spinning, but the speed
control signal is set to zero speed already.
The tacho signal is only activated after the start-up is completed.

04/06/2019 page 6 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

3.4 Electrical Features

Electronic function Speed-Controlled


Reversed polarity protection P-CH FET
Max. residual current at UN IF <= 5 mA
Locked rotor protection Auto restart
Locked rotor current at UN Iblock approx. 2.000 mA
Clock signal at locked rotor t3 / t4 typical: 4 s / 11,0 s
Internal fuse Littelfuse NANO2 > Very Fast-Acting > 451/453 Series
10A / 125V (Art.No.: 0451010.MRL)

After 4 unsuccessful start up trys the fan will be turned off for 40 seconds. .

This fan has a startup delay of 2 seconds after applying supply voltage.

04/06/2019 page 7 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

3.5 Aerodynamics

Measurement Measured with a double chamber intake rig acc. to DIN EN ISO 5801.
conditions: Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C;
In the intake and outlet area should not be any solid obstruction within 0,5 m. Motor shaft
horizontal.
The information is only valid under the specified test conditions and may be changed by the
installation conditions. If there are deviations from the standard test conditions, the
characteristic values must be checked under the installed conditions. Power consumption of
the fan motor when operating at normal voltage is shown. Depending on the operating
conditions of the application, the power input may be higher.

a.) Operation condition:

7.000 1/min at free air PWM 95 %; f: 2 kHz


flow

Max. free-air flow (∆p = 0 / = max.) 697 m3/h


Max. static pressure (∆p = max. / =0) 860 Pa

04/06/2019 page 8 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

3.6 Sound Data

Measurement Sound pressure level: 1 meter distance between microphone and the air intake.
conditions: Sound power level: Acc. to DIN 45635 part 38 (ISO 10302)
Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A)
For further measurement conditions see chapter aerodynamics.

a.) Operation condition:

7.000 1/min at free air PWM 95 %; f: 2 kHz


flow

Optimal operating point 680 m3/h @ 35 Pa

Sound power level at the optimal operating 8 bel(A)


point
Sound pressure level at free air flow, 68 dB(A)
measured in rubber bands

4 Environment

4.1 General

Min. permitted ambient temperature TU min. -20 °C


Max. permitted ambient temperature TU max. 65 °C
Min. permitted storage temperature TL min. -40 °C
Max. permitted storage temperature TL max. 80 °C

04/06/2019 page 9 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

4.2 Climatic Requirements

IP-protection type (certified) IP 68 (for fan only, not for connector if applicable) **)
Humidity requirements humid temperature, cyclic; according to DIN EN 60068-2-38, 10
cycle and condensation water check; according to DIN EN ISO
6270-2, 14 days

Salt fog requirements None

Permitted application area:


The product is for the use in partial sheltered rooms or open, roofed areas. Direct exposure to water is allowed
provided that this does not prevent the normal operation. Saline ambient conditions must be avoided.

Pollution degree 3 (according DIN EN 60664-1)


It occurs conductive pollution or dry non-conductive pollution which becomes conductive due to condensation.

**) The specification of the IP protection refers to the conditions mentioned in certification of the fan. The above
mentioned short description of the protection scope is not final. For detailed information of the respective protection
scope and definitions, see certification as well as DIN EN 60529 (protection by housings) and ISO 20653 (for vehicles)
with the letter K.

Short description of the IP-protection type:


Solid particle Protection: Dust tight.
Protection against deliberate contact: Protected against contact to hazardous parts with a wire.
Protection against water: The fan test according to IP68 (Based on IEC 60529), is conducted in non-operating mode.
The fan is tested by a complete immersion in water for a period of 2h at a water-level of 1,2m. Electrical connections
are not immersed since they are customer specific.

Please require severity levels and specification parameters from the responsible development departments.

4.3 EMC

Kind Radiated Emission; 30 MHz - 1000 MHz


According DIN EN 55032:2016-02
Ceck accuracy / Limit Class A
Result Below limit Class B

Kind Electrostatic Discharge Immunity Test


According DIN EN 61000-4-2:2001-12
Ceck accuracy / Limit Contact Discharge +/- 4 kV; Air Discharge +/- 8 kV
Result A: The monitored function operates as designed during and after exposure
to a disturbance.

Kind Electromagnetic Field Immunity Test


According DIN EN 61000-4-3:2006-12
Ceck accuracy / Limit 10 V/m; 80 - 1000 MHz; AM; m = 0,8; f = 1 kHz; 1%; t = 3 s
Result A: The monitored function operates as designed during and after exposure
to a disturbance.

04/06/2019 page 10 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

Kind Electrical Fast Transient / Burst Immunity Test


According DIN EN 61000-4-4:2005-07
Ceck accuracy / Limit +/- 2 kV on Power Lines; Coupling: POS, NEG, {PE}, ALL, 5 kHz and 100
kHz; 1 min
Result A: The monitored function operates as designed during and after exposure
to a disturbance.

Kind Immunity to Conducted Disturbances, Induced by RF-Fields


According DIN EN 61000-4-6:2001-12
Ceck accuracy / Limit 10 Vrms; 150 kHz - 80 MHz; m = 0,8; f = 1 kHz; 1%; t = 3 s
Result A: The monitored function operates as designed during and after exposure
to a disturbance.

04/06/2019 page 11 of 13
Product Data Sheet 9295420052
VWS0148XULDS
6314/2TDHHPU

5 Safety

5.1 Electrical Safety

Dielectric strength
DIN EN 60950 (VDE 0805) and DIN EN 60335 (VDE 0700)
A.) Type test 500 VAC / 1 Min.
Measuring conditions: After 48h of storage at 95% R.H. and
25°C.
No arcing or breakdown is allowed!
All connections together to ground.
B.) Routine test 850 VDC / 1 Sec.
Measuring conditions: At indoor climate.
No arcing or breakdown is allowed!
All connections together to ground.
Isolation resistance RI > 10 MOhm
Measuring conditions: After 48h of storage at 95% R.H. and
25°C measured with U=500 VDC for 1 min.
Clearance / creepage distance 1,0 mm / 1,2 mm
Protection class III

5.2 Approval Tests

CE EC Declaration of Conformity Yes


EAC Eurasian Conformity Yes
UL Underwriters Laboratories Yes / UL507, Electric Fans E38324
VDE Association for Electrical, Electronic and Information Yes / Approval acc. to EN 60950 (VDE 0805) - Information
Technologies technology equipment
CSA Canadian Standards Association Yes / C22.2 No. 113 Fans and Ventilators
CCC China Compulsory Certification Not applicable

The approval tests are observed to:


U approval max.:36,0 V @ TU approval max.: 65 °C

6 Reliability

6.1 General
Life expectancy L10 at TU = 40 °C 62.500 h
Life expectancy L10 at TU max. 35.000 h
Life expectancy L10 acc. to IPC 9591 at TU = 40 °C 105. 000 h

04/06/2019 page 12 of 13