0% found this document useful (0 votes)
17 views11 pages

Hydraulic Calculation

The document contains information about pipe segments of various sizes used in a sprinkler system including pipe diameter, flow rate, length, and friction loss calculations. It shows the flow rate in gallons per minute for segments between 1 to 16, lists the pipe sizes for each segment in inches, and includes the friction loss per foot and total friction loss for each segment in psi. Pressure summaries provide the total pressure in psi at each node point when accounting for friction losses.

Uploaded by

Fasil E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views11 pages

Hydraulic Calculation

The document contains information about pipe segments of various sizes used in a sprinkler system including pipe diameter, flow rate, length, and friction loss calculations. It shows the flow rate in gallons per minute for segments between 1 to 16, lists the pipe sizes for each segment in inches, and includes the friction loss per foot and total friction loss for each segment in psi. Pressure summaries provide the total pressure in psi at each node point when accounting for friction losses.

Uploaded by

Fasil E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 11

PIPE SEGMENT FLOW (GPM) PIPE SIZE (INCH) FITTINGS AND DEVICES

1 TO 2 19.5 1

20.868666515
2 TO 3 1
40.368666515
24.994077626
3 TO 4 1.25
65.362744141
27.934849153
4 TO 5 1.5
93.297593294

5 TO 10 2
93.297593294
95.241413539
10 TO 15 1.5
188.53900683
188.54261352
15 TO 16 2.5
377.08162035
0
16 TO PUMP 3
377.08162035

note 1
flow of sprinkler at node 1 :
density = 0.15 gpm/ft2
area of sprinkler = 130 ft2
flow of sprinkler at node 1 = 0.15 * 130 = 19.5 gpm

Pt for sprinkler at node 1 :


Q=KP 0.5

P0.5 = 19.5/5.65 12.1 psi


PIPE LENGTH AND EQUIVALENT LENGTH (FT) FRICTION LOSS (psi/ft) FRICTION LOSS (psi)

9.84 0.156753468989622 1.54245413485788

9.84 0.602331084721222 5.92693787365683

9.84 0.495521358592801 4.87593016855316

14.76 0.393866472557684 5.81346913495141

13.12 0.0970280640614598 1.27300820048635

14.76 1.44737459629982 21.3632490413854

13.12 0.4336014360969 5.68885084159133

328 0.178434177652202 58.5264102699222


PRESSURE SUMMARY (psi) NOTES Q1.85 C1.85 d4.87
Pt 12.1 1
Pe 243.5365 7022.396 1
Pf 1.54245413485788
Pt 13.6424541348579
Pe 935.7981 7022.396 1
Pf 5.92693787365683
Pt 19.5693920085147
Pe 2282.238 7022.396 2.964502
Pf 4.87593016855316
Pt 24.4453221770679
Pe 4408.19 7022.396 7.203846
Pf 5.81346913495141
Pt 30.2587913120193
Pe 4408.19 7022.396 29.24261
Pf 1.27300820048635
Pt 31.5317995125056
Pe 16199.15 7022.396 7.203846
Pf 21.3632490413854
Pt 52.895048553891
Pe 58399 7022.396 86.68977
Pf 5.68885084159133
Pt 58.5838993954823
Pe 58399 7022.396 210.6592
Pf 58.5264102699222
Pt 117.110309665405

7.96668773234044 bar
q K factor P P0.5

20.86867 5.65 13.64245 3.693569

24.99408 5.65 19.56939 4.423731

27.93485 5.65 24.44532 4.944221

93.29759 16.96073 30.25879 5.500799

95.24141 16.961 31.5318 5.615318 188.539 25.9235 52.89505 7.272898

188.5426 25.924 52.89505 7.272898