Guide For Calculation of Fault Currents For Application of Ac High-Voltage Circuit Breakers Rated On A Total Current Basis
Guide For Calculation of Fault Currents For Application of Ac High-Voltage Circuit Breakers Rated On A Total Current Basis
5-1979
O'l
r-...
....
O'l
o
Lq
r-...
M
U
-
W
W
W
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE C37.5-1979
(Revision o f ANSI C37.5-1969)
Sponsor
Switchgear Committee of the
IEEE Power Engineering Society
Approved June 2 , 1 9 7 7
IEEE Standards Board
Secretariat
Institute of Electrical and Electronics Engineers
National Electrical Manufacturers Association
Approved November 2 9 , 1 9 7 8
American National Standards Institute
Published by
The Institute of Electrical and Electronics Engineers, Inc
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
American National Standard
Copyright © 1 9 7 9 b y
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
Foreword
( T h i s F o r e w o r d is n o t a part o f A N S I / I E E E C 3 7 . 5 - 1 9 7 9 , G u i d e f o r C a l c u l a t i o n o f Fault Currents f o r A p p l i c a t i o n o f
A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a T o t a l Current Basis.)
The Standards Committee on Power Switchgear, C 3 7 , which reviewed and approved this standard,
had the following personnel at the time of approval:
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
Institute o f Electrical a n d E l e c t r o n i c s Engineers M . J. B e a c h y (Alt)
Η. H. F a h n o e
R . E . Friedrich
Μ . J. Maier
C. A . M a t h e w s (Alt)
R . A . M c M a s t e r (Alt)
D . C . Musgrave
G . W . Walsh
H. F. White
National Electrical Manufacturers A s s o c i a t i o n A . P. C o l a i a c o
R. W. Dunham
D . G. Portman
G. A . Wilson
W. R . W i l s o n
Tennessee Valley Authority R o b e r t C. St. Clair
Testing L a b o r a t o r y G r o u p E. J. H u b e r
R . W . Seelbach (Alt)
R . A . Naysmith
U.S. Department o f the A r m y R o b e r t H. Bruck
U.S. Department o f t h e Interior, Bureau o f R e c l a m a t i o n Edward M. T o m s i c
U.S. Department o f Defense, Defense Communications A g e n c y Vacant
U.S. Department o f t h e N a v y , Naval Facilities Engineering C o m m a n d D. M. Hannemann
The Working G r o u p members of the I E E E Power Circuit Breaker Subcommittee who developed
these changes were:
P. L . Kolarik, Chairman
H. W . A n d e r l H. O . S i m m o n s , Jr
W. C Huening, Jr C. L. Wagner
G . L . Nuss C. J. T r u a x
The personnel of the I E E E Power Circuit Breaker Subcommittee w h o reviewed and approved this
standard were:
G. N . Lester, Chairman
H. W . A n d e r l G . P. G u a g l i o n e Η. K . R e i d
J. E. Beehler R. D . Hambrick A . B. Rishworth
D. M. Benenson G . R . Hanks W. N. Rothenbuhler
L. E. Brothers W . C. Huening, Jr F. G . Schaufelberger
R . G . Colclaser P. L. K o l a r i k Η. N . S c h n e i d e r
J. C . C o o n S. R . L a m b e r t E. F. S o l o r z a n o
C. F. C r o m e r D . M . Larson C. J. T r u a x
C. R . C u s i c k W . E. L a u b a c h E. F. V e v e r k a
A. Dupont M . J. Maier C. L. Wagner
C. J. D v o r a k J. A . Maneatis D . R . Webster
J. D . F i n l e y R . A . McMaster A . C. Wert
R . E. Friedrich G. L. Meinders G. A . Wilson
Τ . F . Garrity G . L. Nuss, Jr W. R . Wilson
W . F. Giles I. E. Oliver B. F. Wirtz
Κ . I. G r a y G . O . Perkins C. E. Z a n z i e
J. G . R e c k l e f f
When this standard was approved on June 2 , 1 9 7 7 the I E E E Standards Board had the following
membership:
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
Contents
SECTION PAGE
1. Scope 7
2. Purpose 7
3. Fault Current Calculations 7
3 . 1 General 7
3 . 2 Procedure 7
4. Revision of American National Standards
Referred to in This Standard 11
FIGURES
TABLES
APPENDIX TABLES
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
APPENDIX FIGURES PAGE
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
An American National Standard
solidated edition), Application Guide for A C Step 2: Determine the system X/R ratio
High-Voltage Circuit Breakers Rated on a Sym viewed from the fault point from Xi/Ri for
metrical Current Basis, to compute interrupt three-phase faults or (2-ΧΊ Xq) for single
+
construction
'See References, Appendix, Section A 3 . S e e list o f related standards o n b a c k c o v e r .
3
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE F O R CALCULATION OF FAULT CURRENTS F O R
accurate way of combining parallel circuits interrupting capability of the total current-rated
with different values of X/R into a single cir circuit breaker being considered.
cuit with one value of X/R since the current
from the several circuits will be the sum of 3 . 2 . 2 Momentary Current. For this calcula
several exponentially decaying terms, usually tion, the E/X current should be calculated using
with different exponents, while that from a the reactances given in 3 . 2 . 4 .
single circuit contains just one such term. T h e application will be proper if the E/X
Investigation has shown that for practical pur current times a factor of 1.6 does not exceed
poses the procedure of reducing the reactance the momentary (or making) current of the
t o a single value with the resistance assumed to circuit breaker.
be zero, and reducing the resistance to a single
value with the reactance assumed t o be zero, 3 . 2 . 3 Electrical Quantities Used
gives, in general, better accuracy than any Ε Line-to-neutral voltage corresponding
other reasonably simple procedure (including to the highest typical operating voltage
the phasor representation used at system which occurs at the circuit breaker
frequency). In addition, the error for practical location.
cases is on the conservative side.
X Corresponding lowest value of system
In cases where an E/Z calculation is made, it reactance (determined with R assumed
is acceptable to substitute Z/R for X/R pro 0 ) as viewed from fault point with all
vided that the R is obtained from a separate rotating machines represented b y appro
reduction of resistance with the reactance priate reactances as specified in 3 . 2 . 4 .
assumed to be zero. It may be either X or 2 X , + X accord
x 0
Step 3: T h e factors taken from the appro ing t o whether three-phase or single
priate figure (Fig 1 , Fig 2, or Fig 3 ) should be line-to-ground currents are being calcu
applied to the E/X calculation so that the dc lated.
and ac decrements are properly included in the
final result. X x Positive sequence reactance.
T h e following procedure is usually conserva X 2 Negative sequence reactance.
tive: X Zero sequence reactance — may be ob
0
( 1 ) T h e factors of Figs 1 and 2 include the tained from design data, b y calculation,
effects of both ac and dc decay. The E/X cur or b y test.
rent should be multiplied b y a factor from Fig
X¿ Subtransient — direct axis reactance of
1 for a three-phase fault and b y a factor from
a synchronous machine or locked rotor
Fig 2 for a line-to-ground fault if the short-
reactance of an induction machine.
circuit current is fed predominantly from
This is always a positive sequence
generators through:
reactance.
(a) N o t more than one transformation, or
(b) A per-unit reactance external t o the X¿ Transient — direct axis reactance of a
generator which is less than 1.5 times synchronous machine. This is always a
generator per-unit subtransient react positive sequence reactance.
ance on a c o m m o n system M V A base. R Corresponding lowest value of system
( 2 ) The factors of Fig 3 include only the resistance as viewed from the fault
effects of dc decay. The E/X current should be point (determined with X assumed 0)
multiplied b y a factor from Fig 3 for a three- with the resistances of the system
phase or a line-to-ground fault if the short- components determined as specified
circuit current is fed predominantly from under 3 . 2 . 5 . Instead of calculating R,
generators through: an estimate of the system X/R ratio
(a) T w o or more transformations, or may be determined from Table 4. R
(b) A per-unit reactance external to the may be either R or 2R + R according
x X 0
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF A C HIGH-VOLTAGE CIRCUIT BREAKERS C37.5-1979
Fig 2 Fig 3
Line-to-Ground Fault Multiplying Three-Phase and Line-to-Ground
Factors Which Include Effects Fault Multiplying Factors Which
of A C and D C Decrement Include Effects of D C Decrement Only
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE F O R CALCULATION OF FAULT CURRENTS FOR
Table 1
Rotating Machine Reactances for
Short-Circuit Current Calculation
Positive S e q u e n c e R e a c t a n c e s
f o r Calculating
Interrupting Momentary
Duty Duty
T y p e o f Rotating Machine (Per U n i t ) (Per U n i t )
F r o m 5 0 t o 1 0 0 0 h p at 1 8 0 0 r / m i n o r less
3.0X'd 1.2X'd
F r o m 5 0 t o 2 5 0 h p at 3 6 0 0 r / m i n
N e g l e c t all three-phase i n d u c t i o n m o t o r s b e l o w
5 0 h p a n d all single-phase m o t o r s .
NOTES:
this result must n o t e x c e e d t h e m o m e n t a r y capability
( 1 ) X'd o f s y n c h r o n o u s rotating m a c h i n e s is the " r a t e d
o f t h e circuit breaker b e i n g used.
v o l t a g e " (saturated) direct axis subtransient r e a c t a n c e .
( 5 ) W h e n t h e c o n t r i b u t i o n o f large individual induc-
( 2 ) X¿ o f s y n c h r o n o u s rotating m a c h i n e s is the " r a t e d
t i o n m o t o r s is an a p p r e c i a b l e p o r t i o n o f t h e short-
voltage (saturated) d i r e c t axis transient r e a c t a n c e .
circuit current, substitution f o r t h e tabulated multiply-
( 3 ) X'J o f i n d u c t i o n m o t o r s equals 1 . 0 0 divided b y ing factors o f m o r e accurate multipliers based o n man-
per-unit l o c k e d r o t o r current at rated v o l t a g e . ufacturer's time c o n s t a n t data is appropriate. Using
( 4 ) T h e current c o n t r i b u t e d t o a short circuit b y / = (E/X'd)i-tlT'\ as t h e e x p r e s s i o n f o r t h e e x p o n e n t i a l
i n d u c t i o n m o t o r s a n d small s y n c h r o n o u s m o t o r s m a y d e c a y o f i n d u c t i o n m o t o r s y m m e t r i c a l current t o a
usually b e i g n o r e d o n utility systems e x c e p t station terminal short circuit, t h e reactance m u l t i p l y i n g f a c t o r
service s u p p l y systems a n d at substations s u p p l y i n g is i tlT"
+
t w h e r e t is t h e p r o p e r time after initiation o f
large industrial l o a d s . A t these l o c a t i o n s , as w e l l as in the short circuit a n d T" is t h e m o t o r short-circuit time
industrial distribution s y s t e m s o r l o c a t i o n s c l o s e t o c o n s t a n t . ( B o t h s h o u l d b e in t h e same t i m e units.) F o r
large m o t o r s , o r b o t h the c u r r e n t at V4 c y c l e will b e e x a m p l e , using manufacturer's m o t o r data f o r T " , the
increased b y t h e m o t o r c o n t r i b u t i o n t o a greater reactance m u l t i p l y i n g f a c t o r f o r determining the inter-
d e g r e e , p r o p o r t i o n a t e l y , than t h e total current will b e rupting d u t y m a y b e f o u n d using t equal t o t h e circuit
increased at m i n i m u m parting t i m e . I n these cases, an breaker m i n i m u m c o n t a c t parting time. F o r a circuit
additional c a l c u l a t i o n o f t h e Vá c y c l e c u r r e n t s h o u l d b e breaker w i t h a five-cycle rated interrupting t i m e , t = 3
m a d e using t h e a p p r o p r i a t e r e a c t a n c e values given in cycles ( 0 . 0 5 s). F o r determining the momentary duty,
T a b l e 1 u n d e r t h e h e a d i n g " M o m e n t a r y D u t y . " A 1.6 use t = 0 . 5 c y c l e s ( 0 . 0 0 8 3 3 s ) in the reactance multiply-
m u l t i p l y i n g f a c t o r s h o u l d b e used f o r a s y m m e t r y , a n d ing f a c t o r calculations.
3.2.5 Resistance of System and Typical X/R of the equivalent X/R ratio of any system,
Ratio. For the purpose of determining the rotating machine resistance values obtained
equivalent X/R ratio, it is recommended that from the manufacturer or through use of the
the manufacturer's advice be obtained concern- following table should be adjusted b y the ap-
ing the resistance value to be used for important plicable rotating machine reactance multipliers
electrical devices. In the absence of such recom- from Table 1.
mendations, the approximate resistance is sug- The ranges and typical values of the X/R
gested in Table 2. In both cases, measured ratios of system components may be obtained
values on rotating machines should be converted from Table 3 . A n estimate of the total system
to normal operating temperature. equivalent X/R ratio to the point of fault may
In setting up the R network for the calculation be obtained from Table 4 .
10
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF A C HIGH-VOLTAGE CIRCUIT BREAKERS C37.5-1979
Table 2
Approximate Resistance of System Components
A p p r o x i m a t e Measure
System Componente o f Resistance
T u r b i n e generators a n d
condensers E f f e c t i v e resistance*
Salient p o l e generators
and m o t o r s E f f e c t i v e resistance*
v o l t a g e generator armature t i m e c o n s t a n t in s e c o n d s .
It is usually a b o u t 1.2 times t h e d c resistance.
Table 3
Range and Typical Values of X/R Ratios of System Components
Range Typical
N O T E : A c t u a l values s h o u l d b e o b t a i n e d if practical.
4. Revision of
American National Standards Standards Institute, Inc, the revision shall
Referred to in this Standard apply:
A N S I / I E E E C 3 7 . 0 1 0 - 1 9 7 9 (Consolidated edi
When the following ANSI/IEEE standard t i o n ) , Application Guide for A C High-Voltage
referred to in this standard is superseded b y a Circuit Breakers Rated o n a Symmetrical Cur
revision approved b y the American National rent Basis.
11
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE FOR CALCULATION OF FAULT CURRENTS FOR
Class R a t i n g in M V A Factor
Fig 4
X/R Range for Power Transformers
12
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF A C HIGH-VOLTAGE CIRCUIT BREAKERS C37.5-1979
Table 4
Equivalent System X/R Ratio at Typical Locations
(For Quick Approximations)
T y p e o f Circuit X/R
13
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE F O R CALCULATION OF F A U L T CURRENTS F O R
Appendix
Fault Current Calculation Examples
guide.
R
| ( o e ) ' 0.0017
Since it is apparent that faults on the line
side of breakers A and Β produce higher fault X, • 0.1 20
current through the breaker than does a fault R | ( o c ) -0.0120
EQUIVALENT
( 0 0 0 1 7 + 0 0 0 1 5 + 0
KD-*- Base k V = 6 9
Base A = 8 3 7
GENERATOR T h e value o f v o l t a g e c o r r e s p o n d i n g t o the highest
o p e r a t i n g v o l t a g e at t h e fault p o i n t is 7 0 . 5 k V line t o
line.
r, _70.5
1.022
^ P i -
69
F o r a three-phase fault,
K >
1.022
X 837 = 9990 A
φ i 34 kV s c
0.0856
70.5 kV
Fig A l Fig A 2
System for Fault Current Calculation System for Three-Phase Fault Calculation for
Bieaker A
Ri 0.00255 ΰ ύ Λ
2Ä, + X 0 2 X 0.00255 + 0.00143
14
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF AC HIGH-VOLTAGE CIRCUIT BREAKERS C37.5-1979
7 S C = 11 2 0 0 A
T
° t a l =
(0.0015 + 0.0010 + 0.0300) = 0 0 0 1 4 3
Table A l
Short-Circuit Currents and Breaker A Capability
15
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE F O R CALCULATION OF FAULT CURRENTS FOR
X - 0 030
X„ • 0 5 0 0 0
"Kocl- 0 . 0 0 0 5 R- • O 0 0 1 0
R. · 0 0 3 0
A V v Q
X I · O 0 70 X -O 070
0
R
l ( « ) • 0 001 5 Ro- O 0 0 1 5
X d · 0 150
"lloel" 0 . 0 0 1 7
X„ • 0 3 0 0
R o • 0 0 30
χ,· o. zoo i i X • 0
0 200
«I( O C |-00040 R = 0 004
0
2
2
(0.0015 + 0.0300) (0.0010)
(0.0017+0.0015+0.0120)(0.0005)
_ 2
2 R + 0.0040 = 0.00494
+0.0040=0.00447 0
(0.0015 + 0.0300 + 0.0010)
1
(0.0017+0.0015+0.0120+0.0005)
2
2
Base k V = 3 4 . 5 F o r a single line-to-ground fault,
Base A = 1 6 7 0 3 X 0.986
T h e value o f v o l t a g e c o r r e s p o n d i n g t o the highest X 1670 = 7440 A
i s c
2 (0.219) + 0.226
o p e r a t i n g v o l t a g e at t h e fault p o i n t is 3 4 k V line t o
line.
Fig A 5
System for Single Line-to-Ground Fault
F o r a three-phase fault, Calculation for Breaker Β
/ S C =
A L F | X
1670 = 7520 A
16
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF A C HIGH-VOLTAGE CIRCUIT BREAKERS C37.5-1979
= 7520 A.
A 2 . 1 General. The system in Fig A 6 can be
A multiplier of 1.6 gives the momentary total used t o illustrate the use of rotating machine
rms current duty for the breaker. Thus, a cal reactance multipliers in fault current calculat
culated current of 1.6 X 7 5 2 0 = 1 2 0 3 0 A must ing procedures described in this guide.
be within the breaker momentary rating for Since it is apparent that a fault on the line
proper application. side of Breaker C produces higher fault current
A l . 3 . 5 Selection of Breaker B. A s in A l . 2 . 5 through the breaker than does a fault on the
an outdoor oil circuit breaker is selected from bus side, currents have been calculated on the
American National Standard C37.6-1971, line side of the breaker only. In case of doubt,
Schedules of Preferred Ratings for A C High- currents for faults on both sides of the breaker
Voltage Circuit Breakers Rated on a Total should be determined.
Current Basis. The only interrupting rating
listed for a 3 4 . 5 k V outdoor breaker is 2 5 0 0 A 2 . 2 Short-Circuit Current Calculations, Break
M V A . The maximum design voltage is 3 8 k V , er C
the minimum voltage for rated interrupting A 2 . 2 . 1 Three-Phase Fault. In Fig A 7 positive
M V A is 2 4 k V , and the interrupting time is sequence reactances and resistances in per unit
8 c. The continuous current is 2 0 0 0 A . on a 1 0 0 M V A base are indicated adjacent to
The breaker has an interrupting rating in generators, motors, and transformers. The
amperes at rated voltage of 4 2 k A . The maxi resistances were determined by dividing each
mum interrupting rating at 2 4 k V is 6 0 k A . The reactance by the corresponding X/R ratio.
interrupting capability at the operating voltage Normal voltage is used as base at all levels.
of 3 4 k V is 4 2 X 3 4 . 5 / 3 4 = 4 2 . 6 k A . For short-circuit current calculations, rotat
Table A 2 shows the comparison of calculated ing machine reactances are adjusted using the
short-circuit current with the capability of the multipliers from Table 1. N o t e that different
breaker and shows that the interrupting cap factors apply for interrupting and momentary
ability of the breaker is much larger than the duties. (The factors are listed in Fig A 7 also).
calculated system fault currents. For a fault on the line side of Breaker C, the
The momentary current capability of the fault point reactance Χχ for determining the
breaker is 9 6 k A which is also much larger than short-circuit current which the breaker must
the calculated maximum momentary current of interrupt is calculated as follows:
12.03 kA.
Table A 2
Short-Circuit Currents and Breaker Β Capability
17
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
GUIDE F O R CALCULATION OF F A U L T CURRENTS F O R
POWER SYSTEM
EQUIVALENT
X, = 0.5
X/R = 25
Δ X, = I-87
69/4.16 kV X/R = 15
, 4.16/2.4 kV
Δ Χ ι = 7.7
R = I2 2< r r r n
6 / 4 8 kv
4 16/48
-T( x / R = 10
1
COMPOSITE COMPOSITE
X(j = 3 45 EQUIVALENT X¡j = 4.75
X / R = 30
X(J = 16 8
1000 HP OF
INDUCTION MOTOR
SYNCHRONOUS LOAD INDUCTION
MOTORS INDIVIDUAL SIZES MOTORS
O O
50 TO 250 HP
Ó Ó
2000 HP 2000 HP 2000 HP 2000 HP
Fig A 6
System Illustrating Large Short-Circuit
Current Contribution from Motors
POWER SYSTEM
EQUIVALENT
= n Δ I^JUU Δ X | = 7.7
= 00917 j( r r r < - \ j{ Ri = 0.77
COMPOSITE COMPOSITE
X'¿ = 3. 45 EQUIVALENT xjj = 4.75
R i = 0.115 R| = 0.158
X'¿ - 16.8
R ι = I 68
1000 HP OF
INDUCTION MOTOR
SYNCHRONOUS LOAD INDUCTION
MOTORS INDIVIDUAL SIZES MOTORS
0 0
2000 HP
50 TO 250 HP
Ó
2000 HP
Ó
FigA7
Positive Sequence Impedance for System
Shown in Fig A 6
18
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
APPLICATION OF A C HIGH V O L T A G E CIRCUIT BREAKERS C37.5-1979
voltage is:
10 1 2 5 X 1.08 = 1 0 9 4 0 A
X, 1.87 + 0.5 ( 3 . 4 5 ) ( 1 . 5 ) + 1.1
For the Breaker C location, the short-circuit
+ I + I current for a fault exceeds the circuit breaker
( 1 6 . 8 ) ( 3 . 0 ) + 7.7 (4.75) (1.5)
interrupting capability.
Total X , = 1 . 3 5 3 A2.2.3 Momentary Calculation. Using Fig A 7 ,
The corresponding fault point resistance i 2 t
the fault point reactance X for determining
is calculated as follows: momentary duty (at one-half cycle) is calculated
as follows: (Multipliers are from Table 1 and
1 1 . 1
are listed in Fig A 7 ) .
Ä, 0.125 + 0.02 (0.115) (1.5) + 0.0917
+ 1 + I X 1 . 8 7 + 0 . 5 ' ( 3 . 4 5 ) ( 1 . 0 ) + 1.1
(1.68) (3.0) + 0.77 (0.158) (1.5)
Total R l = 0.0663 + I + I
(16.8) (1.2) + 7.7 4.75(1.0)
Base voltage = 4 . 1 6 k V
X = 1.125
Base current = 1 3 9 0 0 A
The value of operating voltage corresponding The total current short-circuit duty at one-
to the highest operating voltage at the fault half cycle, calculated in accordance with 3 . 2 . 2 ,
point is 4.1 k V line-to-line. is:
p iiV -
£ u= 0 986 0.986
X 1 3 9 0 0 X 1.6 = 1 9 5 0 0 A
1.125
19
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
C37.5-1979 GUIDE FOR CALCULATION OF FAULT CURRENTS FOR
20
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
C 3 7 . 2 0 - 1 9 7 4 Switchgear A s s e m b l i e s , Including Metal- C 3 7 . 4 5 - 1 9 6 9 ( R 1 9 7 4 ) Specifications for Distribution
E n c l o s e d Bus (includes s u p p l e m e n t C 3 7 . 2 0 a - 1 9 7 0 , E n c l o s e d Single-Pole Air S w i t c h e s ( A N S I )
C37.20b-1972, C37.20c-1974, C37.20d-1978) (Con
solidated e d i t i o n , A N S I / I E E E ) C 3 7 . 4 6 - 1 9 6 9 ( R 1 9 7 4 ) Specifications for P o w e r Fuses
and Fuse D i s c o n n e c t i n g Switches ( A N S I )
C 3 7 . 2 3 - 1 9 7 0 ( R 1 9 7 7 ) G u i d e for Calculating Losses in
Isolated-Phase Bus ( A N S I / I E E E ) C 3 7 . 4 7 - 1 9 6 9 ( R 1 9 7 4 ) S p e c i f i c a t i o n s for Distribution
C 3 7 . 2 4 - 1 9 7 1 ( R 1 9 7 6 ) G u i d e for Evaluating the Effect Fuse D i s c o n n e c t i n g S w i t c h e s , Fuse S u p p o r t s , and Cur
o f Solar R a d i a t i o n o n O u t d o o r Metal-Clad Switchgear rent-Limiting Fuses ( A N S I )
(ANSI/IEEE)
C 3 7 . 4 8 - 1 9 6 9 ( R 1 9 7 4 ) G u i d e for A p p l i c a t i o n , Opera
C 3 7 . 2 6 - 1 9 7 2 ( R 1 9 7 7 ) G u i d e for M e t h o d s o f P o w e r t i o n , and Maintenance o f Distribution C u t o u t s and
F a c t o r Measurement f o r L o w - V o l t a g e Inductive Test Fuse Links, S e c o n d a r y Fuses, Distribution E n c l o s e d
Circuits ( A N S I / I E E E ) Single-Pole Air S w i t c h e s , P o w e r Fuses, Fuse D i s c o n
C 3 7 . 2 7 - 1 9 7 2 Application Guide for Low-Voltage A C necting S w i t c h e s , and A c c e s s o r i e s ( A N S I )
Non-Integrally F u s e d P o w e r Circuit Breakers (Using
Separately M o u n t e d Current-Limiting F u s e s ) ( A N S I / C 3 7 . 5 0 - 1 9 7 3 Test Procedures f o r L o w - V o l t a g e A C
IEEE) P o w e r Circuit Breakers Used in Enclosures, (includes
s u p p l e m e n t s C 3 7 . 5 0 a - 1 9 7 5 and C 5 7 . 5 0 b - 1 9 7 5 ) ( A N S I )
C 3 7 . 2 9 - 1 9 7 4 Standard for Low-Voltage A C Power
Circuit P r o t e c t o r s Used in Enclosures ( A N S I / I E E E ) C 3 7 . 5 1 - 1 9 7 9 C o n f o r m a n c e Testing o f Metal-Enclosed
L o w - V o l t a g e A C P o w e r Circuit Breaker Switchgear A s
C 3 7 . 3 0 - 1 9 7 1 D e f i n i t i o n s and R e q u i r e m e n t s for High- semblies ( A N S I )
V o l t a g e A i r S w i t c h e s , Insulators, and Bus S u p p o r t s
(ANSI/IEEE) C 3 7 . 5 2 - 1 9 7 4 Test P r o c e d u r e s f o r L o w - V o l t a g e A C
P o w e r Circuit P r o t e c t o r s Used in Enclosures
C37.30a-1975 Supplement to C37.30-1971, (ANSI/
I E E E ) ( s o l d separately) C37.60-1974 Requirements for A u t o m a t i c Circuit
R e c l o s e r s f o r Alternating Current Systems (ANSI/
C 3 7 . 3 0 g - 1 9 8 0 Definitions and R e q u i r e m e n t s f o r High- IEEE)
V o t l a g e Air (partial revision o f A N S I / I E E E C 3 7 . 3 0 -
1971) (ANSI/IEEE) C 3 7 . 6 1 - 1 9 7 3 G u i d e f o r the A p p l i c a t i o n , O p e r a t i o n ,
and Maintenance o f A u t o m a t i c Circuit Reclosers
C 3 7 . 3 1 - 1 9 6 2 ( R 1 9 6 9 ) Electrical and Mechanical Char (ANSI/IEEE)
acteristics o f I n d o o r Apparatus Insulators ( A N S I )
C 3 7 . 6 3 - 1 9 6 9 ( R 1 9 7 4 ) Requirements for Automatic
C 3 7 . 3 2 - 1 9 7 2 S c h e d u l e s o f Preferred Ratings, Manu Line Sectionalizers for Alternating-Current Systems,
facturing S p e c i f i c a t i o n s , a n d A p p l i c a t i o n G u i d e for (includes supplement C 3 7 . 6 3 a - 1 9 7 3 ) ( A N S I )
H i g h - V o l t a g e Air S w i t c h e s , Bus S u p p o r t s , and S w i t c h
Accessories ( A N S I ) C 3 7 . 6 6 - 1 9 6 9 ( R 1 9 7 4 ) R e q u i r e m e n t s for Oil-Filled
Capacitor Switches for Alternating-Current Systems
C37.33-1970 ( R 1 9 7 6 ) R a t e d C o n t r o l V o l t a g e s and
(ANSI)
their Ranges for H i g h - V o l t a g e Air Switches ( A N S I )
C 3 7 . 8 5 - 1 9 7 2 ( R 1 9 7 8 ) Safety R e q u i r e m e n t s for X -
C 3 7 . 3 4 - 1 9 7 1 ( R 1 9 7 7 ) Test C o d e for H i g h - V o l t a g e Air R a d i a t i o n Limits f o r A C H i g h - V o l t a g e P o w e r V a c u u m
Switches ( A N S I / I E E E ) Interrupters Used in P o w e r Switchgear (includes sup
C37.34a-1975 supplement to C37.34-1971, sold plement C37.85a-1972) ( A N S I )
separately
C 3 7 . 9 0 - 1 9 7 8 R e l a y s and Relay Systems Associated
C 3 7 . 3 5 - 1 9 7 6 G u i d e for the A p p l i c a t i o n , Installation, with Electric P o w e r Apparatus ( A N S I / I E E E )
O p e r a t i o n , and M a i n t e n a n c e o f H i g h - V o l t a g e Air Dis
c o n n e c t i n g and L o a d Interrupter S w i t c h e s ( A N S I ) C 3 7 . 9 0 a - 1 9 7 4 ( R 1 9 7 9 ) G u i d e f o r Surge Withstand Ca
pability ( S W C ) Tests ( S u p p l e m e n t t o A N S I / I E E E
C 3 7 . 3 7 - 1 9 7 9 L o a d i n g G u i d e for A C H i g h - V o l t a g e Air C37.90-1978) (ANSI/IEEE)
Switches (In E x c e s s o f 1 0 0 0 V o l t s ) (revision o f C 3 7 . 3 7 -
1971) (ANSI/IEEE) C 3 7 . 9 1 - 1 9 7 2 ( R 1 9 7 9 ) G u i d e f o r Protective Relay A p
plications t o P o w e r Transformers ( A N S I / I E E E )
C 3 7 . 4 0 - 1 9 6 9 ( R 1 9 7 4 ) Service C o n d i t i o n s a n d Defini
tions for Distribution C u t o u t s a n d Fuse L i n k s , Sec C 3 7 . 9 3 - 1 9 7 6 G u i d e for P r o t e c t i v e R e l a y A p p l i c a t i o n s
o n d a r y Fuses, Distribution E n c l o s e d Single-Pole Air o f A u d i o T o n e s o v e r T e l e p h o n e Channels ( A N S I /
S w i t c h e s , P o w e r Fuses, Fuse D i s c o n n e c t i n g S w i t c h e s , IEEE)
and A c c e s s o r i e s ( A N S I )
C 3 7 . 9 5 - 1 9 7 4 ( R 1 9 7 9 ) G u i d e for Protective Relaying
C 3 7 . 4 1 - 1 9 6 9 ( R 1 9 7 4 ) Design Tests for Distribution o f Utility-Consumer I n t e r c o n n e c t i o n s ( A N S I / I E E E )
C u t o u t s and Fuse Links, S e c o n d a r y Fuses, Distribu
tion E n c l o s e d Single-Pole Air S w i t c h e s , P o w e r Fuses, C 3 7 . 9 6 - 1 9 7 5 G u i d e for A C M o t o r P r o t e c t i o n (super
Fuse D i s c o n n e c t i n g S w i t c h e s , and A c c e s s o r i e s ( A N S I ) sedes C 3 7 . 9 2 - 1 9 7 2 and C 3 7 . 9 4 - 1 9 7 2 ) ( A N S I / I E E E )
C37.41a-1979 (supplement to C 3 7 . 4 1 - 1 9 6 9 ) (ANSI/ C 3 7 . 9 7 - 1 9 7 9 G u i d e for Protective Relay A p p l i c a t i o n s
IEEE) t o P o w e r S y s t e m Buses ( A N S I / I E E E )
C 3 7 . 4 2 - 1 9 6 9 ( R 1 9 7 4 ) S p e c i f i c a t i o n s for Distribution C 3 7 . 9 8 - 1 9 7 8 Standard for Seismic Testing o f Relays
E n c l o s e d , O p e n , and O p e n - L i n k C u t o u t s ( A N S I ) (This standard c o m p l e m e n t s A N S I / I E E E 3 4 4 - 1 9 7 5 )
(ANSI/IEEE)
C 3 7 . 4 3 - 1 9 6 9 ( R 1 9 7 4 ) S p e c i f i c a t i o n s for Distribution
Fuse Links for Use in Distribution E n c l o s e d , O p e n , C 3 7 . 9 9 - 1 9 8 0 G u i d e for the P r o t e c t i o n o f Shunt Capa
and Open-Link C u t o u t s ( A N S I ) c i t o r Banks ( A N S I / I E E E )
C37.44-1969 ( R 1 9 7 4 ) Specifications for Distribution C37.100-1972 Definitions for Power Switchgear
Oil C u t o u t s and Fuse Links ( A N S I ) (ANSI)
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.
Related Standards in the C37 Series
C 3 7 . 0 4 - 1 9 7 9 Rating Structure for A C H i g h - V o l t a g e C 3 7 . 0 9 - 1 9 7 9 Test P r o c e d u r e for A C High-Voltage
Circuit Breakers R a t e d o n a S y m m e t r i c a l Current Basis Circuit Breakers R a t e d o n a S y m m e t r i c a l Current
( C o n s o l i d a t e d e d i t i o n , Including s u p p l e m e n t s C 3 7 . 0 4 a , Basis ( C o n s o l i d a t e d e d i t i o n , A N S I / I E E E )
C 3 7 . 0 4 b , and C 3 7 . 0 4 c ) , ( A N S I / I E E E )
C 3 7 . 0 1 0 - 1 9 7 9 A p p l i c a t i o n G u i d e for A C High-Voltage
C 3 7 . 0 5 - 1 9 6 4 ( R 1 9 7 6 ) M e t h o d s f o r D e t e r m i n i n g the Circuit Breakers R a t e d o n a S y m m e t r i c a l Current
Values o f a Sinusoidal Current Wave and a N o r m a l - Basis ( C o n s o l i d a t e d e d i t i o n , A N S I / I E E E )
F r e q u e n c y R e c o v e r y V o l t a g e for A C H i g h - V o l t a g e
C 3 7 . 0 1 1 - 1 9 7 9 A p p l i c a t i o n G u i d e for Transient R e
Circuit Breakers ( A N S I )
c o v e r y V o l t a g e f o r A C H i g h - V o l t a g e Circuit Breakers
C 3 7 . 0 6 - 1 9 7 9 Preferred Ratings and R e l a t e d R e q u i r e d R a t e d o n a S y m m e t r i c a l Current Basis ( C o n s o l i d a t e d
Capabilities for A C H i g h - V o l t a g e Circuit Breakers edition, ANSI/IEEE)
R a t e d o n a S y m m e t r i c a l Current Basis ( C o n s o l i d a t e d C 3 7 . 0 1 2 - 1 9 7 9 A p p l i c a t i o n G u i d e for Capacitance Cur
edition, ANSI) rent S w i t c h i n g o f A C H i g h - V o l t a g e Circuit Breakers
C 3 7 . 0 7 - 1 9 6 9 ( R 1 9 7 6 ) Interrupting Capability F a c t o r s R a t e d o n a S y m m e t r i c a l Current Basis, ( C o n s o l i d a t e d
f o r R e c l o s i n g Service for A C H i g h - V o l t a g e Circuit edition) (ANSI/IEEE)
Breakers ( A N S I ) C 3 7 . 1 - 1 9 7 9 Standard D e f i n i t i o n , Specification and
Analysis o f Manual, A u t o m a t i c , and Supervisory Sta
C 3 7 . 0 7 1 - 1 9 6 9 ( R 1 9 7 6 ) R e q u i r e m e n t s for L i n e Closing
t i o n C o n t r o l and Data A c q u i s i t i o n ( A N S I / I E E E )
S w i t c h i n g Surge V o l t a g e C o n t r o l f o r A C H i g h - V o l t a g e
Circuit Breakers R a t e d o n a S y m m e t r i c a l Current Basis, C 3 7 . 2 - 1 9 7 9 Standard Electrical P o w e r System Device
3 6 2 k V and A b o v e , R a t e d M a x i m u m V o l t a g e , includes Function Numbers (ANSI/IEEE)
supplement C 3 7 . 0 7 1 a - 1 9 7 4 ) , (ANSI)
C 3 7 . 4 - 1 9 5 3 ( R 1 9 7 6 ) Definitions and Rating Struc
ture for A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a
C 3 7 . 0 7 2 - 1 9 7 1 ( R 1 9 7 6 ) R e q u i r e m e n t s for Transient R e
T o t a l Current Basis [ i n c l u d e s supplements C 3 7 . 4 a -
c o v e r y V o l t a g e for A C H i g h - V o l t a g e Circuit Breakers
1 9 5 8 ( R 1 9 6 6 ) and C 3 7 . 4 b - 1 9 7 0 ( R 1 9 7 1 ) (reaffirmed
R a t e d o n a S y m m e t r i c a l Current Basis ( A N S I / I E E E )
with c h a n g e in t i t l e ) ] ( A N S I ) and C 3 7 . 4 c - 1 9 8 0 ( A N S I /
C 3 7 . 0 7 2 1 - 1 9 7 1 ( R 1 9 7 7 ) A p p l i c a t i o n G u i d e f o r Tran IEEE)
sient R e c o v e r y V o l t a g e for A C H i g h - V o l t a g e Circuit
C 3 7 . 5 - 1 9 7 9 G u i d e for Calculation o f Fault Currents
Breakers R a t e d o n a S y m m e t r i c a l Current Basis ( A N S I /
for A p p l i c a t i o n o f A C H i g h - V o l t a g e Circuit Breakers
IEEE)
R a t e d o n a T o t a l Current Basis ( A N S I / I E E E )
C 3 7 . 0 7 2 2 - 1 9 7 1 ( R 1 9 7 6 ) S c h e d u l e s o f Preferred Tran
C 3 7 . 6 - 1 9 7 1 ( R 1 9 7 6 ) Schedules o f Preferred Ratings
sient R e c o v e r y V o l t a g e Ratings and Related R e q u i r e d
for A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a T o t a l
Capabilities f o r A C H i g h - V o l t a g e Circuit Breakers
Current Basis ( A N S I )
R a t e d o n a S y m m e t r i c a l Current Basts ( i n c l u d e s sup
plement C37.0722a-1976, ANSI) C 3 7 . 7 - 1 9 6 0 ( R 1 9 7 6 ) (reaffirmed with change in title)
Interrupting Rating Factors for R e c l o s i n g Service
C 3 7 . 0 7 3 - 1 9 7 2 ( R 1 9 7 8 ) R e q u i r e m e n t s for Capacitance for A C H i g h - V o l t a g e Circuit Breakers R a t e d o n a T o t a l
Current S w i t c h i n g f o r A C H i g h - V o l t a g e Circuit Break Current Basis ( A N S I )
ers R a t e d o n a S y m m e t r i c a l Current Basis ( i n c l u d e s
C 3 7 . 9 - 1 9 5 3 ( R 1 9 7 6 ) (reaffirmed with change in title)
C37.073a-1978), (ANSI/IEEE)
Test C o d e f o r A C H i g h - V o l t a g e Circuit Breakers Rated
C 3 7 . 0 7 3 1 - 1 9 7 3 A p p l i c a t i o n G u i d e for Capacitance o n a T o t a l Current Basis [ i n c l u d e s s u p p l e m e n t C 3 7 . 9 a -
Current S w i t c h i n g f o r A C H i g h - V o l t a g e Circuit Break 1970 (R 1971)] (ANSI)
ers R a t e d o n a S y m m e t r i c a l Current Basis ( i n c l u d e s
C 3 7 . 1 1 - 1 9 7 5 R e q u i r e m e n t s f o r Electrical C o n t r o l for
supplement C 3 7 . 0 7 3 1 a - 1 9 7 6 ) (ANSI/IEEE)
A C High V o l t a g e Circuit Breakers Rated o n a S y m
C 3 7 . 0 7 3 2 - 1 9 7 2 S c h e d u l e o f Preferred Ratings for metrical Current Basis and a Total Current Basis
C a p a c i t a n c e Current S w i t c h i n g for A C H i g h - V o l t a g e (ANSI)
Circuit Breakers R a t e d o n a S y m m e t r i c a l Current
C 3 7 . 1 2 - 1 9 6 9 ( R 1 9 7 4 ) G u i d e Specifications for A C
Basis ( A N S I )
High-Voltage Circuit Breakers R a t e d o n a Symmetrical
C 3 7 . 0 7 4 - 1 9 7 2 ( R 1 9 7 8 ) R e q u i r e m e n t s for Switching- Current Basis and a T o t a l Current Basis ( A N S I )
I m p u l s e V o l t a g e Insulation Strength for A C High-
C 3 7 . 1 3 - 1 9 7 3 L o w - V o l t a g e A C P o w e r Circuit Breakers
V o l t a g e Circuit Breakers R a t e d o n a S y m m e t r i c a l Cur
Used in Enclosures ( A N S I / I E E E )
rent Basis ( 3 6 2 k V and A b o v e ) ( A N S I / I E E E )
C 3 7 . 1 3 a - 1 9 7 6 L o w - V o l t a g e A C Integrally Fused P o w e r
C 3 7 . 0 7 6 - 1 9 7 2 ( R 1 9 7 8 ) R e q u i r e m e n t s f o r Pressurized Circuit Breakers ( s u p p l e m e n t t o C 3 7 . 1 3 - 1 9 7 3 ) ( A N S I /
C o m p o n e n t s o f A C H i g h - V o l t a g e Circuit Breakers IEEE)
R a t e d o n a S y m m e t r i c a l Current Basis ( A N S I / I E E E )
C 3 7 . 1 4 - 1 9 7 9 L o w - V o l t a g e D C P o w e r Circuit Breakers
C 3 7 . 0 7 8 - 1 9 7 2 ( R 1 9 7 8 ) R e q u i r e m e n t s for External In Used in Enclosures ( A N S I / I E E E )
sulation for O u t d o o r A C H i g h - V o l t a g e Circuit Breakers
C 3 7 . 1 6 - 1 9 7 9 Preferred Ratings, Related R e q u i r e m e n t s
R a t e d o n a S y m m e t r i c a l Current Basis ( A N S I / I E E E )
for and A p p l i c a t i o n R e c o m m e n d a t i o n s for L o w -
V o l t a g e P o w e r Circuit Breakers and A C P o w e r Cir
C 3 7 . 0 7 8 1 - 1 9 7 2 S c h e d u l e o f Dielectric Test Values for cuit P r o t e c t o r s (revision o f C 3 7 . 1 6 - 1 9 7 3 ) ( A N S I )
O u t d o o r A C H i g h - V o l t a g e Circuit Breaker External
Insulation R a t e d o n a S y m m e t r i c a l Current Basis C 3 7 . 1 7 - 1 9 7 9 T r i p Devices for A C and General Purpose
(ANSI) D C L o w - V o l t a g e P o w e r Circuit Breakers ( A N S I )
C 3 7 . 0 7 9 - 1 9 7 3 ( R 1 9 7 8 ) Test for A C H i g h - V o l t a g e Cir C 3 7 . 1 8 - 1 9 7 9 Standard Field Discharge Circuit Breakers
cuit Breakers R a t e d o n a S y m m e t r i c a l Basis W h e n Used in Enclosures for R o t a t i n g Electric Machinery
R a t e d for Out-of-Phase S w i t c h i n g ( A N S I / I E E E ) (ANSI/IEEE)
Authorized licensed use limited to: La Trobe University. Downloaded on June 20,2016 at 02:48:21 UTC from IEEE Xplore. Restrictions apply.