EE3411 EM-II Lab Manual Final
EE3411 EM-II Lab Manual Final
PRACTICAL RECORD
Register Number
Name
Year / Sem
Degree / Branch
Certified that this is a bonafide record of work done by the above student
during the year 20 - 20
AIM:
To predetermine the regulation of three phase alternator by EMF and MMF method and also to
draw the vector diagrams.
APPARATUS REQUIRED:
1 Voltmeter MI (0-300) V 1
2 Voltmeter MI (0-300) V 1
3 Ammeter MI (0-10) A 1
4 Ammeter MC (0-2) A 1
5 Rheostat - 700, 2A 1
6 Rheostat - 350, 2A 1
7 Tachometer - - 1
8 TPST Switch - - 1
9 Wires - - Req.
FORUMULAE USED:
EMF METHOD:
Let,
Reff =1.6*Ra
3
TABULAR COLUMNS
4
Xs=Zs2- Reff2 ohms
Vph=VL/3 volts
MMF Method
Where,
V1 = V+I*Re*Cos
PRECAUTIONS:
Ensure that the Motor Side field Rheostat at minimum position and Generator side field
rheostat at Maximum position
PROCEDURE:
Switch on dc supply and start the motor using 3 point delta starter.
By adjusting the motor side field rheostat bring DC shunt motor to rated speed.
5
TABULAR COLUMN
EMF METHOD:
MMF METHOD:
6
By varying the alternator side rheostat note down the field current If and open circuit
voltage VOL until the voltage reached the rated value
Switch on dc supply and start the motor using 3 point delta starter.
By adjusting the motor side field rheostat bring DC shunt motor to rated speed.
Repeat the above step for different values of excitations (field current). Take readings up to rated
armature current. Maintain constant speed for all readings
7
MODEL GRAPH
MODEL CALCULATIONS
8
RESULT:
Thus the predetermination of regulation of 3 alternator by EMF & MMF method was
Calculated.
9
CIRCUIT DIAGRAM FOR ZPF AND ASA METHOD
10
EX.NO.2: REGULATION OF ALTERNATOR BY ZPF AND ASA METHOD
DATE :
AIM
To conduct the open circuit, short circuit and ZPF (Zero Power Factor) tests on the given three
phase alternator and pre-determine its regulation.
APPARATUS REQUIRED
1. Ammeter MC (0-2)A 1
2. Ammeter MI (0-10)A 1
3. Voltmeter MI (0-600)V 1
PRECAUTIONS:
Ensure that the Motor Side field Rheostat at minimum position and Generator side field
rheostat at Maximum position.
PROCEDURE
11
TABULATION
DETERMINATION OF REGULATION
12
FOR SHORT CIRCUIT TEST:
13
MODEL GRAPH
MODEL CALCULATION
14
RESULT
Thus the open circuit, short circuit and ZPF (Zero Power Factor) tests on the given
three phase alternator is conducted and to pre-determine its regulation curve
15
CIRCIUT DIAGRAM FOR THREE PHASE ALTERNATOR
16
EX.NO.3 REGULATION OF THREE PHASE SALIENT POLE
ALTERNATOR BY SLIP TEST
DATE:
A1IM
To conduct the slip test on three phase alternator and to predetermine the regulation through
vector diagram.
APPARATUS REQUIRED
1. Ammeter MI (0-10)A 1
2. Voltmeter MI (0-600)V 1
5. Tachometer Digital - 1
FORMULA USED
PRECAUTIONS
The motor field rheostat should be kept in the minimum resistance position.
The alternator field should be kept open throughout the experiment.
17
TABULATION:
Minimum voltage applied to the stator: (Nearly 20% to 30% of rated voltage)
18
PROCEDURE
Note down the name plate details of the motor and alternator.
Connections are made as per the circuit diagram.
Give the supply by closing the DPST switch .Using the three point starter start the
motor to run at the synchronous speed by varying the motor field rheostat at the
same time check whether the alternator field has been opened or not.
Apply 20% to 30% of the rated voltage to the alternator by adjusting the auto
transformer.
To obtain the slip and the maximum oscillation of pointer the speed is reduced
slightly lower than the synchronous speed.
Maximum current, voltage and minimum current voltage are noted. Find out the
direct and quadrature axis impedance.
Draw the line OA vector that represents the rated voltage. Draw the line OB vector
to represent the rated current I which makes an angle of the voltage.
Draw the line AC vector to represent the IaRa drop which parallel to OB vector.
Draw the perpendicular line CD vector to the line.AC (IaRa) drop that represents
IXq drop.
Draw line from the origin through the point D which consists of no load
voltage(Eo).
Draw the pole axis through origin which should be perpendicular to vector OP.
19
DETERMINATION OF REGULATION
VECTOR DIAGRAM
20
21
MODEL CALCULATION
22
RESULT
Thus the slip test on three phase alternator is conducted and regulation of alternator is found
using two reaction theory.
23
CIRCUIT DIAGRAM FOR NEGATIVE SEQUENCE
24
EX.NO.4 DETERMINATION OF NEGATIVE SEQUANCE AND ZERO SEQUENCE
REACTANCE OF A SYNCHRONOUS GENERATOR.
DATE:
APPARATUS REQUIRED
1. Ammeter MI (0-10)A 1
2. Voltmeter MI (0-150)V 1
5. Tachometer Digital - 1
THEORY:-
FORMULA USED
25
TABULATION
26
PRECAUTIONS
The motor field rheostat should be kept in the minimum resistance position.
The alternator field should be kept open throughout the experiment.
PROCEDURE
It is a reactance of a synchronous machine under steady state condition in the direct axis.
The positive sequence impedance can also be defined as the impedance offered by the machine
to the flow of positive sequence currents in the armature windings create a magnetic field that
rotates in the normal direction in the air gap.
27
MODEL CALCULATION
28
RESULT
29
CIRCUIT DIAGRAM FOR V AND INVERTED V CURVES OF THREE PHASE
SYNCHRONOUS MOTOR
30
EX.NO.5 V AND INVERTED V CURVES OF THREE PHASE
DATE: SYNCHRONOUS MOTOR
AIM
To draw the V and inverted V curves of the three phase synchronous motor
APPARATUS REQUIRED
1. Ammeter MC (0-2)A 1
2. Ammeter MI (0-10)A 1
3. Voltmeter MI (0-600)V 1
PRECAUTIONS
PROCEDURE
31
TABULATION
WITHOUT LOAD CONDITION
MODEL GRAPH
32
RESULT
Thus the V and inverted V curves of the three phase synchronous motor were drawn.
33
CIRCUIT DIAGRAM FOR LOAD TEST ON THREE PHASE INDUCTION MOTOR
34
EX.NO.6 LOAD TEST ON THREE PHASE INDUCTION MOTOR
DATE:
AIM:
To conduct load test on three phase squirrel cage Induction motor and to obtain the load
characteristics of
APPARATUS REQUIRED:
1. Voltmeter (0-600) V MI 1
2. Ammeter (0-10) A MI 1
4. Tachometer Digital 1
PRECAUTIONS:
35
TABULATION
Spring balance
Line Input Speed readings PF
Line Voltage Torque Output η Slip
Current Power N S1 -
S.No. (VL) S1 S2 T Power % %
IL PL Rpm S2
volt N-m watt
Ampere watt Kg Kg
Kg
MODEL GRAPH
MODEL CALCULATION
36
PROCEDURE:
RESULT
Thus the load test on three phase squirrel cage induction motor is conducted and its performance
characteristics curves are drawn.
37
CIRCUIT DIAGRAM FOR NO LOAD TEST
38
EX.NO.7 NO LOAD AND BLOCKED ROTOR TEST ON THREE PHASE
INDUCTION MOTOR
DATE:
AIM
To conduct the no load and blocked rotor test on three phase squirrel cage induction
motor and to predetermine the performance using circle diagram.
APPARATUS REQUIRED
1. Ammeter MI (0-10)A 1
2. Voltmeter MI (0-600)V 1
5. Tachometer Digital - 1
PRECAUTIONS:
1. The autotransformer should be kept at minimum voltage position.
2. Blocking of the rotor should be done properly.
3. Making sure that only a small voltage is applied across the stator terminal when the rotor is
blocked.
PROCEDURE:
NO LOAD TEST:
39
CIRCUIRT DIAGRAM FOR BLOCKED ROTOR TEST
40
CONSTRUCTION OF CIRCLE DIAGRAM:
1. Draw the lines by taking the current (I) in X-axis, voltage (V) in Y axis.
2. From the no load test find out the current I0 and draw the vector OA with the magnitude of
I0 from the origin by suitable current scale, which lags the voltage(Y-axis) V by an angle Ф0
where Ф0 =cos-1(W0/3V0I0).
3. From the current ISC find out ISN(short circuit current corresponding to the normal voltage)
by the formula ISN= ISC(V(rated)/VSC),draw the OB vector with the magnitude of ISN from
the origin by the same current scale, which lags the voltage (Y-axis) V by an angle ФSC
where ФSC =cos-1(WSC/3VSCISC).
4. Join the points B and A to get the output line.
5. Draw the parallel line for the X-axis from the point A and for the Y-axis from point B up to
X-axis ( at point E), let both the lines intersect at the point D.
6. Then draw the bisector of the output line and extend it to the line AD, let the point of
intersection be C.
7. By keeping the point C as centre draw a semicircle with the radius CA.
8. Let EB be the line of total loss[ED (constant loss)=DB(variable loss)].
9. In the line DB locate the point G to separate the stator and rotor copper loss by using the
formula,
Rotor copper loss WSC-3ISC2RS
11. Draw the tangent to the semicircle in such a way that it should be parallel to the output line.
Let the point of tangent be H.
12. Draw the line parallel to Y-axis so that the line will meet the output line, which is named as
H’.
13. Here the HH’ will be the maximum output power.
14. Draw the tangent to the semicircle in such a way that it should be parallel to the torque line.
Let the point of tangent be I.
15. Draw the line parallel to Y-axis so the that line will meet the output line, which is named as
I’.
16. Here the I I’ will be the maximum torque.
17. Draw the tangent to the semicircle in such a way that it should be parallel to the X-axis. Let
the point of tangent be J.
18. Draw the line parallel to Y-axis such that line will meet the output line is named as J’.
19. Here the JJ’ will be the maximum input power.
20. From the circle diagram, find the maximum input power, maximum torque, maximum
output power, rotor copper loss, stator copper loss and slip.
41
TABULATION
NO LOAD TEST
42
TO FIND THE FULL LOAD QUANTITIES:
22. Draw the parallel line to output line AB, which cuts the semicircle at point L (near by
Y-axis).
23. Draw the parallel line for Y-axis from point L to X-axis (point Q). Then join O and L.
43
EQUIVALENT CIRCUIT
CIRCLE DIAGRAM
MODEL CALCULATION
44
RESULT
Thus the no load and blocked rotor test on three phase squirrel cage induction motor is
conducted and also to predetermine the performance using the circle diagram is drawn.
45
CIRCUIT DIAGRAM FOR SEPARATION OF NO LOAD LOSSES OF 3 PHASE
INDUCTION MOTOR
46
EX.NO.8 SEPERATION OF NO LOAD LOSSES IN A THREE PHASE
INDUCTION MOTOR
DATE:
AIM
APPARATUS REQUIRED
1. Ammeter MI (0-10)A 1
2. Voltmeter MI (0-600)V 1
5. Tachometer Digital - 1
FORMULAE USED:
1. Stator copper loss = 3I02 RS in watt.
2. Constant loss/phase (WC) = (W-3I02 RS) /3 in watt.
3. Core loss / phase (Wi) = WC – Mechanical loss (Wm) in watt.
where, W =Total input power in watt.
here the mechanical loss (Wm) will be the distance from the origin to the point at where
the Constant loss/phase (WC) Vs voltage curve cuts the Y-axis.
PRECAUTIONS:
1. The autotransformer should be kept at minimum voltage position.
2. The motor should not be loaded through out the experiment.
PROCEDURE:
2. By closing the TPST supply three-phase supply switch energies the autotransformer.
3. Start the motor using auto-transformer starter.
4. The autotransformer should be varied till the motor attains its rated speed and note down
the input power, voltage and current.
5. Repeat the same procedure for lower values of the voltage and tabulate the readings.
47
TABULATION
MODEL GRAPH
MODEL CALCULATION
48
RESULT:
Thus the separation of no load losses of 3 phase induction motor is successfully verified
49
CIRCUIT DIAGRAM FOR SINGLE PHASE INDUCTION MOTOR
50
EX.NO.9 LOAD TEST ON SINGLE PHASE INDUCTION MOTOR
DATE:
AIM
To conduct the load test on single phase induction motor and to draw the performance
characteristics curves.
APPARATUS REQUIRED
1. Voltmeter (0-300) V MI 1
2. Ammeter (0-10) A MI 1
4. Tachometer Digital - 1
FORMULAE USED:
1. Torque,T=9.81*Reff*(S1-S2) N-m
Where,
Reff =Effective radius of the brake drum in m.
S1,S2=Spring balance readings in Kg.
2. Output power,Po = 2πNT/60 watts
Where,
N=speed of the motor in rpm
51
TABULATION
Sl. Line Line Input Speed Spring balance Torque Output η Slip PF
No. Voltage Current Power N readings T Power % %
VL IL PL Rpm N-m watt
(volt) (Ampere) (watt)
S1 S2 S1 - S2
Kg Kg in Kg
MODEL GRAPH
MECHANICAL CHARACTERISTICS
52
PROCEDURE
1. Connections are made as per the circuit diagram.
2. The DPST switch is closed and the motor is started using on the line started to run at
rated speed.
3. At no load the speed, current, voltage and power can be noted.
4. By applying the load for various values of current the above mentioned readings are
noted.
5. The load is later released and the motor is switched off the graph is drawn.
53
ELECTRICAL CHARACTERISTICS
MODEL CALCULATION
54
RESULT
Thus the load test on single phase induction motor is conducted and the performance curves
are drawn
55
CIRCUIT DIAGRAM FOR NO LOAD TEST
56
EX.NO.10 NO LOAD AND BLOCKED ROTOR TEST ON SINGLE PHASE
INDUCTION MOTOR
DATE:
AIM
To conduct the no load and blocked rotor test on single phase squirrel cage induction
motor and to predetermine the performance using circle diagram.
APPARATUS REQUIRED
1. Ammeter MI (0-10)A 1
2. Voltmeter MI (0-600)V 1
5. Tachometer Digital - 1
FORMULAE USED:
NO LOAD TEST:
Where,
W0=No load power in watt
V0=No load voltage in volt
57
CIRCUIRT DIAGRAM FOR BLOCKED ROTOR TEST
58
4. Rotor resistance referred to stator side R2’=R01-R1
5. Stator resistance/phase AC value, R1= Ra (ac) =1.3 x Rdc
PROCEDURE:
NO - LOAD TEST
2. Apply the rated voltage to the induction motor by varying auto transformer, so that the
machine runs
at rated speed.
4. Restore the autotransformer to its initial position, and switch off the supply.
3. Vary the supply voltage with the help of autotransformer so that the ammeter reads rated
current
and note down the corresponding Ammeter, Voltmeter and Wattmeter readings.
4. Reduce voltage to zero with auto transformer and switch off the supply
59
TABULATION
NO LOAD TEST
EQUIVALENT CIRCUIT
MODEL CALCULATION
60
RESULT
Thus the no load and blocked rotor test on single phase squirrel cage induction motor is
conducted and also the equivalent circuit diagram is drawn
61
Fig-1 DIRECT ON-LINE STARTER (DOL)
62
EX.NO.11 STUDY OF INDUCTION MOTOR STARTERS
DATE:
AIM:
Therefore, 3-phase induction motors employ a starting method not to provide a starting
torque at the rotor, but because of the following reasons;
There are many methods in use to start 3-phase induction motors. Some of the common methods
are
The Direct On-Line (DOL) starter is the simplest and the most inexpensive of all starting
methods and is usually used for squirrel cage induction motors. It directly connects the contacts
of the motor to the full supply voltage. The starting current is very large, normally 6 to 8 times
the rated current. The starting torque is likely to be 0.75 to 2 times the full load torque. In order
to avoid excessive voltage drops in the supply line due to high starting currents, the DOL starter
is used only for motors with a rating of less than 5KW There are safety mechanisms inside the
DOL starter which provides protection to the motor as well as the operator of the motor.The
power and control circuits of induction motor with DOL starter are shown in figure(1).
63
FIG.2 STAR-DELTA STARTER
64
STAR-DELTA STARTER
The star delta starting is a very common type of starter and extensively used, compared to
the other types of the starters. This method used reduced supply voltage in starting. Figure(2)
shows the connection of a 3phase induction motor with a star – delta starter. The method
achieved low starting current by first connecting the stator winding in star configuration, and
then after the motor reaches a certain speed, throw switch changes the winding arrangements
from star to delta configuration. By connecting the stator windings, first in star and then in delta,
the line current drawn by the motor at starting is reduced
to one-third as compared to starting current with the windings connected in delta. At the
time of starting when the stator windings are start connected, each stator phase gets voltage ,
where VL//3 is the line voltage. Since the torque developed by an induction motor is proportional
to the square of the applied voltage, star- delta starting reduced the starting torque to one – third
that obtainable by direct delta starting.
The operation principle of auto transformer method is similar to the star delta starter
method. The starting current is limited by (using a three phase auto Transformer) reduce the
initial stator applied voltage.
The auto transformer starter is more expensive, more complicated in operation and
bulkier in construction when compared with the star – delta starter method. But an auto
transformer starter is suitable for both star and delta connected motors, and the starting current
and torque can be adjusted to a desired value by taking the correct tapping from the auto
transformer. When the star delta method is considered, voltage can be adjusted only by factor of
1//3 Figure (3) shows the connection of a 3phase induction motor with auto transformer starter.
65
FIG.(3) SHOWS I.M WITH AUTO TRANSFORMER STARTER.
66
ROTOR IMPEDANCE STARTER:
This method allows external resistance to be connected to the rotor through slip rings and
brushes. Initially, the rotor resistance is set to maximum and is then gradually decreased as the
motor speed increases, until it becomes zero.
The rotor impedance starting mechanism is usually very bulky and expensive when
compared with other methods. It also has very high maintenance costs. Also, a considerable
amount of heat is generated through the resistors when current runs through them. The starting
frequency is also limited in this method. However, the rotor impedance method allows the motor
to be started while on load. Figure (4) hows the connection of a 3phase induction motor with
rotor resistance starter
RESULT:
67